ML050670045

From kanterella
Jump to navigation Jump to search
Inservice Inspection Summary Reports
ML050670045
Person / Time
Site: Turkey Point 
Issue date: 02/28/2005
From: Jones T
Florida Power & Light Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
L-2005-046
Download: ML050670045 (165)


Text

~EB 22005 FPL L-2005-046 10 CFR 50.55a U. S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D. C. 20555 Re:

Turkey Point Unit 3 Docket No. 50-250 Inservice Inspection Reoort Attached are the Executive Summary and the following reports for Turkey Point Unit 3 in accordance with the provisions of the ASME Code, Section XI:

Form NIS-1 Owners' Report for Inservice Inspections.

Form N IS-2 Owners' Report for Repairs or Replacements.

Form NIS-BB Owners' Data Report for Eddy Current Examination Results.

Summary of Visual Examinations and Functional Testing of Snubbers.

Summary of Inservice Inspection Examinations.

Summary of System Pressure Testing.

Should there be any questions concerning this report, please contact Walter Parker at 305-246-6632.

Very truly yours Terry 0. Jones Vice President Turkey Point Nuclear Plant SM Attachments NRC Regulatory Issue Summary 2001-05 waived the requirements that multiple copies of documents be submitted to the NRC an FPL Group company

TURKEY POINT PLANT UNIT 3 2004 REFUELING OUTAGE INSERVICE INSPECTION REPORT Executive Summary This Inservice Inspection report is for the 2004 Turkey Point Unit 3 refueling outage. This was the first outage of the first period of the fourth 10-year interval. Additionally, a limited number of examinations, specifically RPV examinations, were examined and credited in accordance with the requirements of the third 10-year interval. The third 10-year interval was extended by eight months by implementing paragraph IWA-2430(d) of ASME Section XI. This extension was necessary to meet the station's goals and to schedule work in an effective manner consistent with ALARA principles. Turkey Point licensing group requested a phone conversation with the Nuclear Regulatory Commission on June 13, 2002 to discuss this matter and followed-up with a letter, L-2002-125, on June 26, 2002.

Inservice examinations consisted of augmented Feedwater ultrasonic examinations on the A, B and C Steam Generator Feedwater nozzles, adjacent piping, and fittings. Also examined were selected components from the Reactor Pressure Vessel, Reactor Coolant, Pressurizer, Residual Heat Removal, Safety Injection, Main Feedwater, Auxiliary Feedwater, Steam Generator Blowdown, Steam Generator B and C Primary Side, Steam Generator B and C Secondary Side, Chemical and Volume Control, Component Cooling Water and Intake Cooling Water System. The attached Inservice Inspection summary tables detail the examinations performed during the outage. Examinations credited to the Third Interval are detailed in Attachment 1 and examinations credited to the Fourth Interval are detailed in Attachment 2.

The attached NIS-2 forms document the repair and replacement activities that have taken place since the previous Unit 3 submittal, and those performed during the 2004 refueling outage.

There were no IWE examinations scheduled for this outage. However, a preservice examination was performed on the containment liner where a hole was cut for the passage of the new reactor head.

There were no IWL examinations scheduled for this outage. However, a preservice examination was performed on the tendons and concrete surfaces where a hole was cut for the passage of the new reactor head.

Snubber visual examinations and functional tests were conducted in accordance with ASME Section XI and Turkey Point Plant Technical Specifications. Reference Attachment 4, Sunmmary of Visual Examinations and Functional Testing of Snubbers, for examination scope and results.

System pressure testing was conducted in accordance with the requirements of ASME Section XI and Turkey Point Technical Specifications. Reference Attachment 3, Summnary of System Pressure Testing, for test boundaries and results.

Steam Generator eddy current examinations were conducted in steam generators 3A, 3B and 3C. The number and extent of tubes examined was 100% of all inservice tubes, in row 3 and higher, in S/G's 3A, 3B and 3C from tube end to tube end using the bobbin coil technique. The bobbin coil technique was also used to examine the hot let and cold leg straight sections of rows I and 2 in all three S/G's. The motorized rotating pancake coil technique (Plus Point) was used to examine 100% of the hot leg tube expansion transitions in S/G's 3A, 3B and 3C from 3" above to 2" below the secondary face of the hot leg tubesheet. Additional Plus Point examinations were performed in approximately 50% of the Row 1 and Row 2 U-bends and approximately 50% of the hot leg straight section dings/dents (>= 5 volts) and approximately 50% of the U-bend region dings/dents (>= 3 volts). This is shown under "Total Tubes Inspected" on the attached "FORM NIS-BB OWNERS' DATA REPORT FOR EDDY CURRENT EXAMINATION RESULTS". Reference for examination results.

TURKEY POINT UNIT 3 2004 REFUELING OUTAGE FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS

FORM NIS-1 Page 1 of 13 Owner:

Florida Power & Light Company, 700 Universe Blvd. Juno Beach, Florida 33408 Plant:

Turkey Point Nuclear Power Plant, 9760 SW 344 Street, Florida City, Florida 33035 Plant Unit: 3 Owner Certificate of Authorization (if required)

N!/A Commercial Service Date: December 14. 1972 National Board Number for Unit: N/A

1.

Owner: Florida Power and Light Company 700 Universe Blvd.

Juno Beach, Florida 33408

2.

Plant:

Florida Power & Light Company Turkey Point Nuclear Power Plant 9760 SW 344 Street Florida City, Florida 33035

3.

Plant Unit: 3

4.

Owner Certificate of Authorization (if required): N/A

5.

Commercial Service Date: December 14. 1972 6.

National Board Number for Unit:

N/A

7.

Components Inspected:

Component or Manufacturer Manufacturer State or or Installer Province National Board No.

Appurtenance or Installer Serial No.

No.

Reactor Reactor Babcock and 6 0 0 1

/

Pressure Wilcox 610-0116 N/AN-160 Vessel Pressurizer Westinghouse 3T200 N/A N-720 Regenerative Heat Westinghouse 3E200 N/A N/A Exchanger Reactor Coolant Bechtel N/A N/A N/A System Reactor Coolant Pump Westinghouse 3P-200C N/A N/A C

Chemical and Volume Bechtel N/A N/A N/A Control Safety Injection Bechtel N/A N/A N/A System

FORM NIS-1 Page 2 of 11 Owner:

Florida Power & Light Company, 700 Universe Blvd. Juno Beach, Florida 33408 Plant:

Turkey Point Nuclear Power Plant, 9760 SW 344 Street, Florida City, Florida 33035 Plant Unit: a Owner Certificate of Authorization (if required)

NIA Commercial Service Date: December 14.1972 Component or Manufacturer Manufacturer State or or Installer Province National Board No.

Appurtenance or Installer Serial No.

No.

RHR System Bechtel N/A N/A N/A Steam Westinghouse 16A-5885-1 N/A N/A Generator A Wetnhue FSGT-300 1 Steam Westinghouse 16A-5885-2 N/A N/A Generator B Wetnhue FSGT-3002 Steam Westinghouse 16A-5885-3 N/A N/A Generator C Wetnhue FSGT-3003 Steam Generator Bechtel N/A N/A N/A Blowdown A Steam Generator Bechtel N/A N/A N/A Blowdown C Auxiliary Bechtel N/A N/A N/A Feedwater Main Feedwater Bechtel N/A N/A N/A System Component Bechtel N/A N/A N/A Cooling Intake Cooling Bechtel N/A N/A N/A Water System

8.

Examination Dates: from 3/28/03 to 12/02/04

9.

Inspection Period Identification: First Period, from 2/22/2004 to 2/21/2007.

10. Inspection Interval Identification: Fourth Interval, from 2/22/2004 to 2/21/2014.
11. Applicable Edition of Section XI: 1998, 2000 Addenda, (IWE) 1992/1992 Addenda
12. Date/Revision of Inspection Plan: February 22, 2004/ Revision 0.
13. Abstract of examinations and test. Include a list of examinations and tests and a statement concerning status of work required for the inspection plan.

FORM NIS-1 Page 3 of 11 Owner:

Florida Power & Light Company, 700 Universe Blvd. Juno Beach, Florida 33408 Plant:

Turkey Point Nuclear Power Plant, 9760 SW 344 Street, Florida City, Florida 33035 Plant Unit: 3 Owner Certificate of Authorization (if required)

NWA Commercial Service Date: December 14.1972 Inservice Examination of selected Class 1, 2 and 3 components and piping systems of Florida Power and Light's (FPL) Turkey Point Unit 3 were performed during the 2004 Refueling Outage. This cycle began on 3/28/2003 and ended 12/2/2004. This was the first outage of the first period of the fourth 10-year interval. Additionally, a limited number of examinations specifically RPV examinations, were examined and credited in accordance with the requirements of the third 10-year interval.

The third 10-year interval was extended by eight months by implementing paragraph IWA-2430(d) of the 1989 Edition, No Addenda of ASME Section XI. This extension was necessary to meet the station's goals and to schedule work in an effective manner consistent with ALARAprinciples. Turkey Point licensing group requested a phone conversation with the Nuclear Regulatory Commission June 13, 2002 to discuss this matter and followed-up with a letter, L-2002-125, on June 26, 2002. This is also the first outage of the first period in the fourth 10-year interval.

The components and piping systems examined were selected in accordance with the Third ten-year interval program or Fourth Ten-Year Inservice Inspection Program.

The inspection plans include an alternative to the examination and Pressure Test requirements of Table IWB-2500-1, Category B-F and B-J piping welds, as defined in American Society of Mechanical Engineers (ASME)Section XI, 1989, No Addenda and the 1998 Edition with Addenda through 2000. This alternative implements a risk informed inspection program for the examination selection for the Class 1, Category B-F and B-J piping welds in lieu of the requirements of Table IWB-2500-1.

The alternative Plan allows examination selection for Unit 3 to be in accordance with "Florida Power & Light Turkey Point Unit 3 Risk-Informed Inservice Inspection Program.

Manual ultrasonic, radiography, visual, magnetic particle, and liquid penetrant non-destructive methods were used to examine components, piping, and their supports.

FPL personnel supported by Washington Group International personnel performed the examinations. See the attached report, Turkey Point Unit 3 Inservice Inspection, for examination scope and results.

Framatome personnel performed automated ultrasonic and remote visual on the girth welds, inside surfaces, and internals of the reactor pressure vessel that were credited to the third 10-year inservice inspection examination.

FPL personnel supported by Framatome personnel conducted Eddy Current examinations on Steam Generators A, B, and C from 10/5/2004 through 10/14/2004.

No tubes were plugged during this outage. See the attached NIS-BB report for the summary of examination results.

FORM NIS-1 Page 4 of 11 Owner:

Florida Power & Light Company, 700 Universe Blvd. Juno Beach, Florida 33408 Plant:

Turkey Point Nuclear Power Plant, 9760 SW 344 Street, Florida City, Florida 33035 Plant Unit: a Owner Certificate of Authorization (if required)

Nl16 Commercial Service Date: December 14. 1972 Snubber visual examinations and functional testing were conducted in accordance with ASME Section XI and Turkey Point Technical Specifications. Basic-PSA, Inc supplied examination and testing services. See the attached report, Summary of Visual Examinations and Functional Testing of Snubbers, for examination scope and results.

FPL visual examiners conducted system pressure testing in accordance with the requirements of ASME Section XI and Turkey Point Technical Specifications. See the attached report, Summnuary of System Pressure Testing, for test boundaries and results.

No scheduled IWE examinations were required this outage. Preservice examinations were performed in areas of coating repairs to the containment metallic liner and moisture barrier seal. A preservice examination was also performed on the containment liner where the hole was cut for the passage of the new reactor head.

There were no IWL examinations scheduled for this outage. However, a preservice examination was performed on the tendons and concrete surfaces where a hole was cut for the passage of the new reactor head.

14. Abstract of Results of Examinations and Tests. (FONT)

Class 1 Reactor Pressure Vessel Reactor Pressure Vessel ligaments around stud holes were examined by the ultrasonic method. No reportable indications were identified.

Reactor Pressure Vessel circumferential welds, vessel internals, and internal surfaces were examined by the remote visual and volumetric methods. Two components were found to have indications. Reactor Radial Support Kevwav was found to have recordable indications on the Radial Support Keyway at 270 degrees. Several scratches and small gouges were observed on the I.D. edge of the mating surfaces and Core Support Barrel Support Flange was found to have a recordable indication on an Irradiation Plug at 40 degrees. The Irradiation plug was compressed/crushed and bent. The outer edge was also deformed in the access hole (Refer to section 15, "Abstract of Corrective Measures"). No additional reportable indications were identified.

A Reactor Pressure Vessel nozzle support was examined by the remote visual method. No reportable indications were identified.

FORM NIS-1 Page S of 11 Owner:

Florida Power & Light Company, 700 Universe Blvd. Juno Beach, Florida 33408 Plant:

Turkey Point Nuclear Power Plant, 9760 SW 344 Street, Florida City, Florida 33035 Plant Unit: 3 Owner Certificate of Authorization (if required)

NIAl Commercial Service Date: December 14. 1972 Preservice examination was performed on the replacement reactor head's CRDM's P-55, 68, 38, 29, 57, 67, 61, 69, 58, 62, 30, 26, 51, 63, 59, 64, 32, 27, 53, 65, 60, 66, 34, and 28 with the surface method. No reportable indications were identified.

Preservice examination was performed on the replacement reactor head's three lifting lugs at 750, 180°, and 3000 and three support lugs at 00, 1200, and 2400 with the surface method. No reportable indications were identified.

Pressurizer A Pressurizer girth weld and long seam weld were examined with the ultrasonic method. No reportable indications were identified.

Reactor Coolant System Reactor Coolant piping welds were examined with the volumetric method and supports were examined with the visual method. No reportable indications were identified.

Reactor Coolant Pump C The Reactor Coolant Pump C meridian welds were examined by the visual method.

No reportable indications were identified.

Chemical and Volume Control Chemical and Volume Control piping welds were examined with the surface method and supports were examined the visual method. Two supports were found to have indications. Support 3-VCH-1 15 was found to have a bent stanchion and the stanchion was toed at the guide plate and Support 3-VCH-1 14 was found to have the spring setting out of tolerance (Refer to section 15, "Abstract of Corrective Measures"). No additional reportable indications were identified.

Steam Generators (Eddy Current)

Eddy Current examinations were performed of the tubing of the three Steam Generators. The results of the examinations are detailed in the NIS-BB report.

FORM NIS-1 Page 6 of 11 Owner:

Florida Power & Ught Company, 700 Universe Blvd. Juno Beach, Florida 33408 Plant:

Turkey Point Nuclear Power Plant, 9760 SW 344 Street, Florida City, Florida 33035 Plant Unit: a Owner Certificate of Authorization (if required)

N/A Commercial Service Date: December 14.1972 Steam Generator B Steam Generator B inlet and outlet nozzle inner radii and inlet and outlet manway bolting were examined with the visual method and tubesheet to head weld were examined with the volumetric method. No reportable indications were identified.

Steam Generator C Steam Generator C inlet and outlet nozzle inner radii were examined with the visual method. Two reportable indications were identified in the channel head cladding in the area of the cold leg primary nozzle inside radius. (Refer to section 15, "Abstract of Corrective Measures"). No additional reportable indications were identified.

Regenerative Heat Exchanger Per Relief Request #1, a VT-2 visual examination was performed at the beginning of the outage to look for accumulated boric acid crystals and evidence of leakage and during the system leakage test to look for evidence of leakage. No reportable indications were identified.

Residual Heat Removal System Residual Heat Removal piping welds were examined with the surface and volumetric methods. No reportable indications were identified.

Safety Injection Svstem Safety Injection supports were examined with the visual method. One support was found to have a clearance gap outside the specified dimension of the support drawing (Refer to section 15, "Abstract of Corrective Measures"). No additional reportable indications were identified.

Preservice liquid penetrant examinations were performed on replacement welds for Valve 3-873A and 3-873B. No reportable indications were identified.

Class 2 Steam Generators B Steam Generator B girth welds were examined with the volumetric method. No reportable indications were identified.

FORM NIS-1 Page 7 of 11 Owner:

Florida Power & Light Company, 700 Universe Blvd. Juno Beach, Florida 33408 Plant:

Turkey Point Nuclear Power Plant, 9760 SW 344 Street, Florida City, Florida 33035 Plant Unit: 3 Owner Certificate of Authorization (if required)

NA Commercial Service Date: December 14. 1972 Also, an augmented examination was performed on the secondary side of Steam Generator C for debris and damage. No reportable indications were identified.

Safety Iniection Piping Safety Injection piping welds were examined with the surface and volumetric methods and the piping supports were examined with the visual method. Two supports were found to have indications. Support C had two drawing discrepancies and support 8080-R-006-01 had clearance gaps outside the specified dimensions of the support drawing (Refer to section 15, "Abstract of Corrective Measures"). No additional reportable indications were identified.

Preservice liquid penetrant examinations were performed on replacement welds for Valve 3-873A and 3-873B. No reportable indications were identified.

Residual Heat Removal Piping Residual Heat Removal piping welds were examined with the surface and volumetric methods and the piping supports were examined with the visual method.

One support was found with the cold setting out of tolerance with the drawing specified acceptable range. (Refer to section 15, "Abstract of Corrective Measures"). No additional reportable indications were identified.

Main Feedwater Piping Augmented examinations were conducted of all three Steam Generator Feedwater nozzle ramps to a distance one-pipe diameter on the upstream elbow weld with the ultrasonic method. Acceptable geometric indications were identified. No reportable indications were identified.

Steam Generator A and C Blowdown Piping Steam Generator Blowdown A and C piping welds were examined with the surface and volumetric methods and supports were examined with the visual method. No reportable indications were identified.

Class 3 Auxiliary Feedwater Pipin2 Auxiliary Feedwater piping supports were examined with the visual method. No reportable indications were identified.

FORM NIS-1 Page 8 of 11 Owner:

Florida Power & Ught Company, 700 Universe Blvd. Juno Beach, Florida 33408 Plant:

Turkey Point Nuclear Power Plant, 9760 SW 344 Street, Florida City, Florida 33035 Plant Unit: 3 Owner Certificate of Authorization (if required)

NIA Commercial Service Date: December 14. 1972 Component Cooling Water Pining Component Cooling Water piping supports were examined with the visual method.

Support SR-142 had clearance gaps outside the specified dimensions of the support drawing. (Refer to section 15, "Abstract of Corrective Measures"). No additional reportable indications were identified.

Intake Cooling Water Intake Cooling Water piping supports were examined with the visual method.

(Strainer B) was found to have a crack in the concrete approximately eight inches long that extends from the base plate along the edge of the concrete floor pad at the southwest support base location (Refer to section 15, "Abstract of Corrective Measures"). No additional reportable indications were identified.

15. Abstract of Corrective Measures Reactor Radial Support Keyway was found to have recordable indications on the Radial Support Keyway at 270 degrees. Several scratches and small gouges were observed on the I.D. edge of the mating surfaces. Engineering Disposition: The tool marks do not affect internals of the reactor vessel radial support from performing their intended function, therefore this condition is not a non-conformance. The condition is acceptable. Reference CR 2004-11911.

Core Support Barrel Support Flange was found to have a recordable indication on an Irradiation Plug at 40 degrees. The Irradiation plug was compressed/crushed and bent. The outer edge was also deformed in the access hole. Engineering Disposition: Use as-is. The capsule is tight in place and performing its core bypass function, with minimal contact damage with the corresponding surface of the reactor vessel. Westinghouse completed a final evaluation. Reference CR 2004-11474.

Steam Generator "C" Cold Leg primary side inside radius (3-SGC-O-IRS) was found to have two indications identified in the first clad bead on nozzle side at approximately 3:00 to 4:00 o'clock facing nozzle from the inside diameter. Both indications cross the clad weld bead, approximately.75 inch long. The weld bead total width is approximately 0.75 inches. For further evaluation of the indications, an outside diameter ultrasonic examination of the 3C SG cold leg was performed which confirmed that the cladding indications do not penetrate into the carbon steel base material (pressure boundary). Based on discussions with Westinghouse, the OEM, and their experience with over 7 other cases of similar flaws at other plants, the flaws were most likely caused during initial fabrication, or subsequent maintenance. Engineering disposition found that since the flaws did not penetrate

FORM NIS-1 Page 9 of 11 Owner:

Florida Power & Ught Company, 700 Universe Blvd. Juno Beach, Florida 33408 Plant:

Turkey Point Nuclear Power Plant, 9760 SW 344 Street, Florida City, Florida 33035 Plant Unit: a Owner Certificate of Authorization (if required) 1A!

Commercial Service Date: December 14.1972 into the carbon steel base material and the observed flaws were not likely caused by environmental factors, these flaws can be accepted without further evaluation and no change in inspection scope or frequency is required. Reference CR No. 2004-11026.

Chemical and Volume Control piping support (VCH-3-115) was found to have a bent stanchion approximately 3 inches down from the integral attachment. The stanchion is also toed at the guide plate rendering the support unable to slide. The cause of the failure was determined to be excessive thermal forces exerted on the support resulting in bending stresses on the support stanchion, beyond yield, causing the identified permanent deformation. A satisfactory liquid penetrant examination was performed on the integral attachment as part of the scheduled inservice inspection outage work. Engineering disposition required examination on similar supports, and adjacent supports, per the requirements of Code Case N-491-1. This required examination of three additional supports. After the above information was compiled, a final engineering disposition was added to restore the support per the instructions and details provided in MRA 04-9153-01 to SPEC-C-024 and WO 34017723. A VT-3 of the as-built support configuration was performed and the results were forwarded to Engineering. CRN C-1 1367 was generated to document the new support. Reference CR No. 2004-9153.

Chemical and Volume Control piping support (VCH-3-114) was found to have the cold setting out of tolerance with the design drawing. A review of the Bergen-Paterson catalog 1990 Edition, indicates that with the reported as-found cold setting and with a pipe thermal movement of Y= +5/16 inch, the resulting operating loads and displacements on the spring can are still within the working range of the spring.

It also confirmed that no bottoming-out had occurred. Engineering disposition directed to have the spring hanger adjusted to the design drawing cold setting of 175 lbs. after the modification of VCH-3-115. A VT-3 visual examination was performed to verify the final setting. Work was performed under WO No.

34017723. Reference CR No. 2004-11013.

Safety Injection piping support (8080-H-010-12) was found to have the clearances not within tolerances of the drawing. Engineering disposition found that the 34" dimension shown in the drawing is not a gap for support function. The dimension is a reference dimension intended to show the location of an adjacent interference in the gang-type support. The reported existing gap in the X-direction of.60 inch is more than adequate to accommodate the maximum pipe X-movement of.0107" at the support location. The support is acceptable as-is. Reference CR No. 2004-10682.

Residual Heat Removal piping support (SR-251) was found to have the cold setting out of tolerance with the design drawing. Engineering disposition directed to have

FORM NIS-1 Page 10 of 11 Owner:

Florida Power & Light Company, 700 Universe Blvd. Juno Beach, Florida 33408 Plant:

Turkey Point Nuclear Power Plant, 9760 SW 344 Street, Florida City, Florida 33035 Plant Unit: a Owner Certificate of Authorization (if required)

NWA Commercial Service Date: December 14. 1972 the spring hanger adjusted to the design drawing cold setting of 3/8-inches or 692 lbs. The field adjustment was unable to engage (not carry the load) as stated in Interim Disposition #1 of CR 2004-10252. With further direction from engineering, the spring hanger was adjusted until it became tight, able to carry a load at the 5/8-inch setting or approximately 769 lbs. A VT-3 was performed to document the as-left condition. A visual examination of the spring hanger will be performed during the upcoming Unit 3 cycle 22 refueling outage. Based on the results of that inspection, Engineering will determine if any additional fieldwork is required or if a drawing change is necessary. Work was performed under WO No. 33021794.

Reference CR No. 2004-10252.

Safety Injection piping support (C) was found to have a drawing discrepancy. There is one nut on the top of the turnbuckle while the drawing shows two and there is no nut on the bottom of the turnbuckle, while the drawing shows one. Engineering disposition found that the condition is in accordance with correct design standard.

The support design drawing will be corrected per CRN-C-1 1336 (PC/M No,03-106). Issued MRA CR-04-10091-01 for SPEC C-024. Reference CR No. 2004-10091.

Safety Injection piping support (8080-R-006-01) was found to have the clearances not within tolerances of the drawing. Engineering disposition found that the as-found condition with zero gaps will not cause failure or malfunction of SSC and is not a deficiency or deviation in material of SSC. The support design drawing will be corrected per CRN-C-1 1333 (PC/M No,03-106 & ITOP No. 04-10-017). Issued MRA CR-04-10094-01 for SPEC C-017. Reference CR No. 2004-10094.

Component Cooling Water piping support (SR-142) was found to have the clearances not within tolerances of the drawing. Engineering disposition found that the combined maximum gap was within tolerance of Engineering Standard, STD-C-011. Therefore, no adverse condition exists and no drawing update or corrective actions are required. Reference CR No. 2004-10092 Intake Cooling Water piping support (Strainer B) was found to have a crack in the concrete approximately eight inches long that extends from the base plate along the edge of the concrete floor pad at the southwest support base location. Engineering disposition found that the condition does not adversely affect the anchor bolts and their ability to perform their intended function in providing anchorage and seismic restraint for the support structure. There are no operability concerns and support is acceptable. Refer to CR No. 2004-10090.

FORM NIS-1 (Continued)

Page 11 of 11 Owner:

Florida Power & Light Company, 700 Universe Blvd. Juno Beach, Florida 33408 Plant:

Turkey Point Nuclear Power Plant, 9760 SW 344 Street, Florida City, Florida 33035 Plant Unit: 3 Owner Certificate of Authorization (if required)

N/A Commercial ServiceDate: December 14, 1972 National Board Number for Unit: N/A We certify that a) the statements made in this report are correct, b) the examinations and tests meet the Inspection Plan as required by the ASME Code,Section XI, and c) corrective measures taken conform to the rules of the ASME Code,Section XI.

Certificate of Authorization No.

N/A Expiration Date Date:

Signed:

By Xo CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Florida, and employed by The Hartford Steam Boiler Inspection and Insurance Company of Connecticut of Hartford, CT have inspected the components described in this Owner's Report during the period L-21-o4 to 2-11-0 5

, and stat'e that to the best of my knowledge and belief, the Owner has performed examinations and tests and taken corrective measures described in the Owner's Report in accordance with the Inspection Plan and as required by the ASME Code,Section XI.

By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations, tests, and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

G FL 177 CA.c.,. T )

Inspector's Signature National Board, State, Province, and Endorsements Date:

2-17-o!5

NIS-2 Reports

Abstract The attached NIS-2 reports detail the repair/replacement of Class 1, 2 and 3 piping and components for Florida Power and Light Company, Turkey Point Unit 3. These repairs or replacements were performed prior to and during the Fall 2004 refueling outage, between the dates of March 28, 2003, December 2, 2004.

Piping and components were inspected/tested in accordance with Section XI of the American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel code "Rules for Inservice Inspection of Nuclear Power Components, "1989 Edition, No Addenda up to February 21, 2004 and 1998 Edition up to and including the 2000 Addenda on February 22, 2004.

NIS-2 LOG Report No.

Report Daite Work Order Number- -::ANII Certification Framatome 1/25/2005 33021301 -01 2/1/2005 50-5038798-04 (FANP)

SGT 1/24/2005 34005142-04 1/26/2005 SGT 1/19/2005 34005142-05 1/25/2005 SGT 1/24/2005 34005142-06 1/25/2005 04-001-3 1/15/2004 33015127-01 1/4/2005 04-002-3 10/2/2004 34014914-01 1/3/2005 04-003-3 10/2/2004 33021380-01 1/4/2005 04-004-3 10/2/2004 33020989-01 1/5/2005 04-005-3 10/3/2004 33015160-07 1/4/2005 04-006-3 10/4/2004 32018395-01 1/4/2005 04-007-3 10/17/2004 33022331-01 1/4/2005 04-008-3 10/5/2004 3400637 1-02 1/5/2005 04-009-3 10/5/2004 CR 03-0207 1/4/2005 04-010-3 10/6/2005 34004673-01 1/8/2005 04-011-3 10/6/2004 3406953-01 1/8/2005 04-012-3 10/6/2004 34001271-01 1/8/2005 04-013-3 10/5/2004 34017422-01 1/5/2005 04-014-3 10/14/2004 33012526-01 1/4/2005 04-015-3 10/17/2004 34008530-01 1/4/2005 04-016-3 10/6/2004 34011856-01 1/5/2005 04-017-3 10/7/2004 34012308-01 1/4/2005 04-018-3 10/20/2004 33023668-01 1/4/2005 04-019-3 10/20/2004 33023669-01 1/4/2005 04-020-3 10/21/2004 33009476-01 1/4/2005 04-021-3 11/2/2004 34000102-01 1/4/2005 04-022-3 11/4/2004 34000031-01 1/5/2005

Report No.

Report-Date Work Order Number ANIICertification 04-023-3 11/9/2004 33005126-03 1/5/2005 04-024-3 11/10/2004 33012172-01 1/5/2005 04-025-3 11/10/2004 33022950-01 1/5/2005 04-026-3 11/10/2004 34008570-01 1/5/2005 04-027-3 11/11/2004 34001110-01 1/5/2005 04-028-3 11/12/2004 34018233-01 1/5/2005 04-029-3 11/12/2004 33022904-01 1/5/2005 04-030-3 11/12/2004 33021285-01 1/5/2005 04-031-3 11/12/2004 33016751-01 1/5/2005 04-032-3 11/12/2004 31017889-01 1/5/2005 04-033-3 11/13/2004 33023249-01 1/5/2005 04-034-3 11/19/2004 34011613-01 1/5/2005 04-035-3 11/19/2004 34011614-01 1/5/2005 04-036-3 11/19/2004 33021720-01 1/8/2005 04-037-3 11/20/2004 34004417-01 1/8/2005 04-038-3 11/22/2004 34008671-01 2/1/2005 04-039-3 11/23/2004 31022850-01 1/8/2005 04-040-3 11/23/2004 30006362-01 1/8/2005 04-041-3 11/24/2004 31007526-01 1/8/2005 04-042-3 11/24/2004 31020694-01 1/8/2005 04-043-3 11/24/2004 31020695-01 1/22/2005 04-044-3 11/29/2004 34000317-01 1/22/2005 04-045-3 12/1/2004 33021534-02 1/22/2005 04-046-3 11/29/2004 34000316-01 1/8/2005 04-047-3 11/29/2004 31005377-01 1/22/2005 04-048-3 12/3/2004 31005378-01 1/8/2005 04-049-3 11/29/2004 34000703-01 1/8/2005 04-050-3 11/30/2004 33005126-01 1/8/2005 04-051-3 11/30/2004 31007667-01 1/22/2005

Report No.

Report Date work Order Number ANII Certificaion 04-052-3 11/30/2004 33023667-01 1/8/2005 04-053-3 11/29/2004 34015594-01 1/8/2005 04-054-3 12/2/2004 33010553-01 1/8/2005 04-055-3 12/2/2004 33010541-01 1/8/2005 04-056-3 12/3/2004 32018647-01 2/1/2005 04-057-3 11/29/2004 30009289-01 1/8/2005 04-058-3 12/3/2004 33022084-01 1/8/2005 04-059-3 12/2/2004 34019617-01 1/8/2005 04-060-3 12/3/2004 34018385-01 2/1/2005 04-061-3 12/3/2004 33010523-01 1/8/2005 04-062-3 12/3/2004 33021531-01 1/8/2005 04-063-3 11/29/2004 34017723-01 1/8/2005 04-064-3 12/3/2004 34006019-03 1/8/2005 04-065-3 12/3/2004 33013069-01 1/8/2005 04-066-3 12/3/2004 33000466-02 1/8/2005 04-067-3 12/6/2004 CR 04-10708 1/8/2005 04-068-3 12/7/2004 34000755-01 1/22/2005

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code, Section )a

1. Owner Florida Power & Light Co.

nit.

nlninnnL 4.S vax vvvv Narne 700 Universe Blvd., Juno Beach, Fl 33408 Sheet I

of 4

Address

2. Plant Turkey Point Nuclear Power Plant Name 9760 SW 344th St.. Florida Citv. FL 33035 Unit 3

WO 33021301-01. 50-5038798-04 (FANP)

Address RepairfReplacermmt Organization P.O. Box. Job No.. edC

3. Work Performed by Framatome-ANP. Inc. ______Type Code Symbol Stamp N/A Name Authorization No.

N/A 3315 Old Forest Road Lynchbura, VA 24501 Expiration Date N/A Address

4. Identification of System Reactor Vessel (043)
5. (a) Applicable Construction Code ASME III.

1989 Edition, No

Addenda, N-474-2 Code Case Ye (b) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity _ 1998 a 2000 2142-1 Yew 2143-1 (c) Applicable Section XI Code Cases None N-588 N-461
6. Identification of Comronents:

Name of Name of Manufacturer National Year Corrected, ASMECode component Manufacturer Serial No.

Board No.

Other Identification Built rnsv ed. or Stamrped Reactor Framatome CCITUO01 N/A N/A 2004 Installed Yes Head ANP CRDM Jeumont 2641 N/A K-1 4/62 2004 Installed Yes CRDM Jeumont 2643 N/A P-1 0/63 2004 Installed Yes CRDM Jeumont 2644 N/A J-13/38 2004 Installed Yes CRDM Jeumont 2645 N/A K12/30 2004 Installed Yes CRDM Jeumont 2658 N/A M10/31 2004 Installed Yes CRDM Jeumont 2619 N/A Li 1-26 2004 Installed Yes CRDM Jeumont 2626 N/A N9/39 2004 Installed Yes CRDM Jeumont 2624 N/A H12/22 2004 Installed Yes CRDM Jeumont 2632 N/A G13/45 2004 Installed Yes CRDM Jeurnont 2633 N/A F14/69 2004 Installed Yes CRDM Jeumont 2628 N/A L9/15 2004 Installed Yes CRDM Jeumont 2629 N/A J-11/14 2004 Installed Yes

7.

Description of Work Installed new Reactor Head and Control rod Drive Mechanisms (CRDM).

The UTC numbers for the reolacement CRDMs are. In order of ap

Dearance In table:

UTC 0000459813.

0000459815.000459816. 0000459817.0000459830.0000459791.0000459798.0000459796. 0000459804.

0000459805.0000459800.0000459801.0000459809.0000459814. 0000459812.0000459802. 0000459810.

0000459788.0000459785.0000459822.0000459793.0000459803.0000459824.0000459787.0000459832.

0000459831, 0000459818. 0000459820. 0000459792.0000459794. 0000459799. 0000459797.0000459827.

0000459819. nQ0459r298 0000459821. OQ0459829. 00Q459790.Q0000459789. 000045978. 0000459795.

0000459811. 0000459807.0000459823. and 0000459825.

8.

Tests Conducted:

Hydrostatic 0 Pneumatic 0 Nominal Operating Pressure 0 ExemptO Other El Pressure 2235 psi Test Temp. 247

°F NOTE: Supplemenal sheets hi fornof lists, skcesor drswings moy be used. povied(l) size is K x 11 in.t2) Infrnnb n in itenms I dirough6ofthissrepot is imcluded on each shet. miad (3) ecch dheet is numbered and number ofl' eets is reconred a the top of this ronn r.7,99)

This ronn (EO0030) may be ohained from the Order Dqpt. ASME, 22 LAw Driuc, Box 2300, Fairfield, NJ 07007.2300.

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code, Section )a

1. Owner Florida Power & Uieht Co.

Narn 700 Universe Blvd., Juno Beach, Fl 33408 Address

2. Plant Turkey Point Niiclear Power Plant Narne 9760 SW 344th St.. Florida City, FL 33035 Date 0 125/2005 Sheet 2

of 4

Unit 3

WO 33021301-01. 50-503R798-04 (FANP)

Address Rqufrir/RerI eiemnt Orgilzanion P.O. Box, Job No.. etc.

3. Work Performed by Framatome-ANP, Inc Type Code Symbol Stamp N/A Narm Authorization No.

N/A 3315 Old Forest Road Lynchburg, VA 24501 Expiration Date N/A Address

4. Identification of System Reactor Vessel (043)
5. (a) Applicable Construction Code ASME III

..1989

Edition, No
Addenda, N-474-2 Code Case (b) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 1998 a 2000 2142-1 Y,

2143-1 (c) Applicable Section XI Code Cases None N-588 N-461

6. Identification o Components:

Name of Name of Manufacturer National Year Corrected.

ASME Code component Manufacturer Serial No.

Board No.

Other Identification Built orensvedd (Yes or No)

CRDM Jeumont 2637 N/A P-6/64 2004 Installed Yes CRDM Jeumont 2642 N/A N-7/72 2004 Installed Yes CRDM Jeumont 2640 N/A M-8/23 2004 Installed Yes CRDM Jeumont 2630 N/A F-12/37 2004 Installed Yes CRDM Jeumont 2638 N/A H-1 0/06 2004 Installed Yes CRDM Jeumont 2616 N/A K-8/07 2004 Installed Yes CRDM Jeumont 2613 N/A G-11/21 2004 Installed Yes CRDM Jeumont 2650 N/A M-6/32 2004 Installed Yes CRDM Jeumont 2621 N/A D-10/36 2004 Installed Yes CRDM Jeumont 2631 N/A E-9/20 2004 Installed Yes CRDM Jeumont 2652 N/A E-1 1/29 2004 Installed Yes CRDM Jeumont 2615 N/A H-8/01 2004 Installed Yes CRDM Jeumont 2660 N/A 18/9 2004 Installed Yes CRDM Jeumont 2659 N/A F6/8 2004 Installed Yes CRDM Jeumont 2646 NIA L-5/27 2004 Installed Yes

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code,Section XI

1. Owner Florida Power & 1ie1it Co.

Nasr 700 Universe Blvd.. juno Beach. Fl 33408 Address

2. Plant Turkev Point Nuclear Power Plant Naur 9760 SW 344th St., Florida City. Fl, 33035 Address
3. Work Performed by Framatome-ANP, Inc Narlr 3315 Old Forest Road Lynchburg, VA 24501 Date 0 1/25/2005 Sheet 3

of 4

Unit 3

WO 33021301-01. 50-503R798-04 (FANP)

Repar/Replacernt Orgiaizalion P.O. Box. Job No. etc.

Type Code Symbol Stamp N/A Authorization No.

N/A Expiration Date N/A Address

4. Identification of System Reactor Vessel (043)
5. (a) Applicable Construction Code ASME III 1989 Edition, No
Addenda, N-474-2 Code Case YeN (b) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 1998 a 2000 2142-1 ye-2143-1 (c) Applicable Section XI Code Cases None N-588 N-461
6. Identification o Components:

Name of Name of Manufacturer National Year Corrected.

ASME Code component Manufacturer Serial No.

Board No.

Other Identification Built orIale (Yes or No)

CRDM Jeumont 2648 N/A C-9144 2004 Installed Yes CRDM Jeumont 2620 N/A G-5/18 2004 Installed Yes CRDM Jeumont 2622 N/A K-2/65 2004 Installed Yes CRDM Jeumont 2627 N/A D-8/25 2004 Installed Yes CRDM Jeumont 2625 N/A F-4/34 2004 Installed Yes CRDM Jeumont 2655 N/A F-2/66 2004 Installed Yes CRDM Jeumont 2647 N/A B-6/67 2004 Installed Yes CRDM Jeumont 2656 N/A K-4133 2004 Installed Yes CRDM Jeumont 2649 N/A 1-7/16 2004 Installed Yes CRDM Jeumont 2657 N/A J-5/17 2004 Installed Yes CRDM Jeumont 2618 N/A E-5/28 2004 Installed Yes CRDM Jeumont 2617 N/A G-3/42 2004 Installed Yes CRDM Jeumont 2614 N/A D-6/35 2004 Installed Yes CRDM Jeumont 2623 N/A C-7/43 2004 Installed Yes CRDM Jeumont 2639 N/A J-3/41 2004 Installed Yes CRDM Jeumont 2635 NIA H-4/24 2004 Installed Yes CRDM Jeumont 2651 N/A B-i 0/68 2004 Installed Yes CRDM Jeumont 2653 N/A E-7/19 2004 Installed Yes

Sheet 4 of 4

,Wo 330.ZI 3a-oI FORM NIS-2 (Back)

9.

Remarks: N-2 forms for the reactor head and CRDMs are attached.

Applicable Manufacturer's Data Reports to be attached Other itAms InstaIAd arA as fnllnws RVH Plug. Serial Number JT-27 at H-14158: RVH Plug. Serial Number JT-28 at B-8/71 RVLMS. Serial Number 1430B4YP at P8/59: Serial Number 1430B5YP at H-2160 CETNA. Serial Number 8-0304006 at C-5/55: CETNA. Serial Number B-0304008 at E-13i70:

CETNA. Serial Number B-0304007 at L-3/53: CETNA. Serial Number 8-0304009 at N-1/51.

Complete new reactor head assembly was pressure tested by a system leakage test.

UTC numbers. for each Item in the order listed: 0000459845. 0000459845. 0000459965. 0000459966. 0000459850.

0000459850. 0000459850. and 0000459850 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp ME pa Certificate of Authorization No.

___o_

Signed ISI Supervisor Date 01/26

/ 2005 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Florida and employed by HSB CT of Hartford. CT havo inspected the components described In this Owner's Report during the period I o-iq -oA to 2-01-05

,and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions

c2

'? f,7 c Inspector's Signature National Board, State, Province, and Endorsements Date 2

Z0

_l,

'-I-

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code,Section XI

1. Owner Florida Powver & Lieht Co.

Date Januarv 24. 2005 Narne 700 Universe Blvd., Juno Beach. Fl 33408 Sheet I

of 2

Address

2. Plant Turkey Point Nuclear Power Plant Unit 3

Narn 9760 SIN 3 4 4 h Street. Florida City, FL 33035 WO #34005142. Task 4 Address RcpairRlcipcmnl Organizaion P.O. Box. Job No., etc.

3. Work Performed by -SGT, Inc Typo Code Symbol Stamp ____N/A Naffic Authorization No. _

_N/A

_400 S. Tryon Street, Suite 2 1 00, Charlotte, NC 28285_ Expiration Date NIA Address

4. Identification of System Containment Building-Tendon System (51)
5. (a) Applicable Construction Code ACI 318
Edition, 1963
Addenda, NIA Code Case Yea (b) Applicable Edition of Section X Uilized for Repair/Replacement Activity 1992 a1992 Year (c) Applicable Section XI Code Cases ___N/A
7.

Description of Work:

As part of the Turkey Point Unit 3 and 4 Reactor Vessel Closure Head (RVCH) Replacement Project, a portion of the reactor building containment wall was removed to provide an opening through which the original and replacement RVCH were moved. Existing tendons (40 horizontal, 10 vertical) in the opening were removed and discarded and new tendons installed through new tendon sheaths spliced to the existing sheathing. Additionally, twelve horizontal tendons and two vertical tendons adjacent to the opening were removed and replaced. New anchorheads (stressing washers) were installed on shop ends and anchorheads or bearing plate stiffeners (to match original configuration) were installed on field ends of replaced tendons. For veritical tendons adjacent to the opening that were detensioned, new anchorheads were installed on shop ends.

8.

Tests Conducted:

Hydrostatic 0 Pneumatic 0 Nominal Operating Pressure 0 ExemptO Other ED ILRT Pressure 49.9 psi Test Tcmp. E0 F NOTE Surpncinntal.

sheets in,r nn of lists. s&etIrCs, OtrajOingnraybc useCi provsled (I) size is K. x 1 ln.. () infornsation in keens I Hwough6 of tis repon ts inc.&ad on cOch seem. nd (3) ech shet I mhernei ass nunber of shets Is rm or.1 at th. top of tbis fomn

9.

Remarks:

Olher items installed are as follows:

Applicable Manufacturer's Data Reports to be attached Component.o bAs NuTmCber Other Identification 52 Horizontal See Below Mk# 62H33 thru 62H58 Tendons e

Mk# 15H33 thru 15H58 12 Vertical Mk# 61V10, 12V8 Tendons See Below Mk# 61V12 thru 61V21 116 460709,460500, 461024, Heat Codes Anchorheads 461054 thru 461077, 461305 See Below 461173, 461191,461190, Heat Codes: TE453377, Shim Sets 461189, 461193 CCW64403, TDA31 608, TH453457 Bearing Plate 461274 Heat Codes: TZ12, TZ13, Stiffeners (4)

TZ14,TZ18 Visconorust 460419,461192,461211, Lot # 496919, 475934, Tendon Grease 461212 466228, 450295

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code,Section XI FORM NIS-2 (Back)

9.0 Remarks

Continued Tendon UTC Numbers(in order):

460849. 460849.460849. 460533. 460533. 460533. 460532.460532. 460532. 460532. 460532. 460531. 460849.

460849. 460530. 460533. 460533.460849. 460533. 460533. 460533. 460530. 460530. 460849. 460849. 460849.

460849. 460849. 460849. 460550. 460550. 460549. 460549. 460549. 460543.460539. 460539. 460538. 460538.

460538. 460537. 460538.460536.460537. 460534. 460537. 460537. 460535. 460535.460849. 460849. 460849.

460855.461272.460529.460528.460527.460526.460525.460524.460523.460522.460521.460551 Anchorhead Heat Codes:

TPI. TP2. TP3. TP4. TP5. TP6. TP7. Ti'9. TPri.

TP1I2. TPI3. TP14. TP15. TPI6. TPI7. TP18. TPI97 TP20. TP2I. 11'22. TP23.

TP24. TP25. TP26. TP27. TP28. TP29. TP30. TP31. TP326 TP33.7P35. M6.7P37. TP38. TP39. TP40. TP41. TP42.TP43.

V191.

TWI92. TWVI93. TW194. 7W196. TV197. TW198. TW200. TW201. TW202. TW203. TW205. 7W206. TW207. TW208.

TWV209. TW210.

MO61. TW162. TW163. TV165. TW166. TW167. TW169. TWI70. TW171. 7W172. TW173. TW174.

TW175.

1Vi76.

TW177.

WV178. TWV79.

WMV80 TV181. TWI82. T'V183. TWI84. TWI85. TWI86. TWI87. TWIS8.

TWV89. TWI90. TW211. TW212. 7V213. TW214. TW215.TP104. TP115. TPI16. TP118. TPI21. TP122. TP123. TP124.

TP125. TP127. TPI28. TP129. TP130. TPI31. TP132. TP133. TP135. TP138. TP139. TP141. TP147. TP148. TP150.

TP152. TP163. TD26 CERTIFICATE OF COMPLIANCE I certify that the statements made in the report are correct and that this conforms to the requirements of the ASME Code. Section Xl.

Type Code Symbol Stamp si l Certificate of Authorization No. ___l_

Signed P

I 51 Date -

4LL. 20_.Q5 CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of iorida and employed by HSBCT of Hartford.

have inspected the components described in this Owner's Report during the period o(,-ZI -04 to I -Z4 05

, and state that to the best of my knowiedge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report In accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owner's ReporL Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this inspection.

4le1

< -a Commissions FL 41)7 (A,. C

,J)

Inspector's Signature National Board, State, Province, and Endorsements Date I - Z; -O 5

- O 5 WP*a 320o5f,2-Page 2 of 2

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code,Section XI

1. Owner Florida Power & Lieht Co.

Daite Januarv 19. 2005

0.

A.

Nane 700 Universe Blvd., Juno Beach, Fl 33408 Sheet I

of 2

Address

2. Plant Turkey Point Nuclear Power Plant Unit 3

Name 9760 SW 3 4 4th Street. Florida Citv. FL 33035 WO #34005142. Task 5 Address Repair/Riclaemrnt Organization P.O. Box, Job No., ctc.

3. Work Performed by _SGT, Inc Type Code Symbol Stamp _

N/A Name Authorization No.

___N/A

_400 S. Tryon Street, Suite 2 100, Charlotte, NC 28285_ Expiration Date N/A Address

4. Identification of System Containment Building - Concrete (511)
5. (a) Applicable Construction Code ACI 318
Edition, 1963
Addenda, N/A Code Case Yea (b) Applicable Edition of Section Xl Utilized for Repair/Replacement Activity 1992 a1992 Year (c) Applicable Section Xl Code Cases

_N/A_

6. Identification o Components:

Name of Name of Manufacturer National Year Corecled.

ASME Code component Manufacturer Serial No.

Board No.

Other Identification Built Reorved.

Starsad ed (Yes

[Concret Bechtel N/A N/A Reactor Building Wall 1970 Corrected No Buidin

7.

Description of Work:

As part of the Turkey Point Unit 3 and 4 Reactor Vessel Closure Head (RVCH) Replacement Project, a portion of the reactor building containment wall was removed to provide an opening through which the original and replacement RVCH were moved. Existing concrete was removed by hydro-demolition. The wall was reconstructed by re-installing existing re-inforcing using swage coupler splices and fusion welding.

Both existing reinforcing and new reinforcing was installed. Sheathing was placed in the wall to reconnect the existing tendon sheaths. A new reinforcing mat using #11 Grade 60 steel was installed on the inner (liner plate side) face of the wall to carry tensile forces created upon restoration of the post-tensioning system In the wall.

8.

Tests Conducted:

Hydrostatic 3 Pneumatic 0 Nominal Operating Pressure 0 ExemptO Other 0 ILRT Pressure 49.2 psi Test Temp. Z 0 F NOTE: Suptlnritul hents rn forioftl skchres. or &wings iroy be used, Mrovid d().sze is Si a I I fi. (2) infxnoaiocnv in hens I trugh6ofthisepont is includ don r

bc ugrt. ausi (3) eacah sret is numbered ar number of sheets ix rsied a the 1o010 of form

9.

Remarks:

Other items Installed are as follows:

Applicable Manufacturers Data Reports to be attached Name of Parts Number Other Identification Stock Code 409177-1 Inside Rebar Mat 0459738 Stock Code 409178-1 0458984 Stock Code 408647-2 0458984 Stock Code 408650-2 0459629 Stock Code 408658-2 Concrete 0459138,0460185 Stock Code 408660-2 0460853 0460968 Stock Code 408622-2 0459944 Stock Code 408623-2 Couplers Size 9 0459446 Stock Code 409193-1 43 Rebar Couplers 0459447. 0460995 Stock Code 409194-1 Si e 11_

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code,Section XI FORM NIS-2 (Back)

9.0 Remarks

Conlinued CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp t4l 1 A-Certificate of Authorization No.

hi A-Signed 1S I.

l 5v 0 4soI Date 81X6 20.0^5 CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Florid and employed by HSICT of Hartford, have Inspected the components described in this Owner's Report during the period

(--Zi- 04 to I !5

, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report In accordance with the requirements of the ASME Code.Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this inspection.

/Commissions FL 4 77 4A, C.'H.'I)

Inspector's Signature National Board, State, Province, and Endorsements Date I

2-5

, 22 0 Page 2 of 2 Ebb 13yoo 5/CL -

5

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code,Section XI

1. Owner Florida Power& Light Co.

Date January 24, 2005 Nane 700 Universe Blvd., Juno Beach, Fl 33408 Sheet I

of 2

Address

2. Plant Turkey Point Nuclear Power Plant Unit 3

Name 9760 SW 344th Street. Florida City. FL 33035 WO #34005142, Task 6 Address Repasirfieplacenitnt Organization P.O. Box, Job No.. etc.

3. Work Performed by SGT. Inc Type Code Symbol Stamp __N/A Name Authorization No.

N/A 4400 S. Trvon Street. Suite 2 10. Charlotte, NC 28285 Expiration Date _N/A Address

4. Identification of System Containment Building - Liner Plate (51)
5. (a) Applicable Construction Code ASME Section VIII
Edition, 1965
Addenda, N/A Code Case
Yew, (b) Applicable Edition of SectionXIL lized forRepair/ReplacementActivity 1992 a1992: 5610-C-47 Rev2 (for NDE work)
yea, (c) Applicable Section Xl Code Cases _

N/A_

6. Identification of Components:

Name of Name of Manufacturer National Year Corrected.

ASME Code component Manufacturer Serial No.

Board No.

Other Identification Built or tnltaNed or No)

Liner Plate Bechtel N/A N/A Steel Liner 1970 corrected No J=

7.

Description of Work:

As part of the Turkey Point Unit 3 and 4 Reactor Vessel Closure Head (RVCH) Replacement Project, a portion of the reactor building containment wall was removed to provide an opening through which the original and replacement RVCH were moved. The existing liner plate was taken out of the opening and subsequently re-installed. The channel and angle steel connected to the liner plate for stiffening was re-installed with new material for splices across the liner plate seam welds. Alignment nuts used on the inside of the liner plate remain in place following re-installation of the existing liner plate.

8. Tests Conducted:

Hydrostatic 0 Pneumatic 0 Nominal Operating Pressure 0 ExemptO Other 0 ILRT Pressure 49.9psi TestTermp. 80°F NOTE: Suppiclennal sheets in forn of lihs sketches, or drowings may be ued, pmivided (I) size is K % x I1 in., (2) infsonssion hi ken" I though 6 of this rert is included on each siret. atd (3) each slhet is numbered and number of sheets srecordned at the top of this form

9. Remarks:

Other Items Installed are as follows:

Applicable Manufacturer's Data Reports to be attached Other Identification Stock Code 409211-1 Stock Code 409208-1 Stock Code 409212-1 Stock Code 409213-1 Stock Code 30265-1 Stock Code 409293-1

FORM NIS-2 OWNER'S REPORT FOR REPAIR/REPLACEMENT ACTIVITY As Required by the Provisions of the ASME Code,Section XI FORM NIS-2 (Back)

CERTIFICATE OF COMPLIANCE I certify that the statements made In the report are correct and that this conforms to the requirements of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Signed ISI Supervisor Date 01/26 2005 CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Florid and employed by HSB CT of Hartford. CT have inspected the components described in this Owner's Report during the period oro - v - o4 to I-2 (0 - O 5, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owner's Report In accordance with the requirements of the ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.

~

Commissions AZ w

k 877 Inspector's Signature National Board, State, Province, and Endorsements Date

/-

5

. 2005 WO 34005142-06 Page 2 of 2

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI Nner Florida Power and Light Co.

Date Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet Address Turkey Point Plant 1/15/2004 I

of 2

3 WO#: 33015127-01 CR#:

N/A Unit

2. Plant Name 9760 SW 344 Street Florida City, FL 33035 Address Florida Power and Light Co.

Name

3. Work Performed by Repair Organization, P.O. No, Job No, etc.

Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date NIA 9760 SW 344 Street Florida City, FL 33035 Address CVCS Charging and Letdown

4. Identification of System:

System #:

47 Quality Group B

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1955 Edition, N/A
Addenda, 1998 Edition, 2000
Addenda, NIA N/A Code Case Code Case
6. Identification of Components Repaired or Replaced and Replacement Components A

ASME Corrected.

Code Name of Name of Mfg Mfg Serial National Other Year Removed or Stamp I

Component Number Board Identification Built Installed Yes/No 3C CHARGING PUMP Union Pump N/A N

3P201C N/A Installed N

7. Description of Work:

Installed New Pump

8. Tests Conducted:

Hydrostatic:

N/A 0

Other N/A Pneumatic N/A Nominal Operating Pressure X

Pressure 2300 psig Test Temperature 116 deg F 04-001-3

Sheet 2 of 2 FORM NIS-2 (Back) marks None CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code. Section Xi.

Type Code Symbol Stamp NIA Certificate of Authorization No.

I Signed N/A Expiration D.ate:

N/A Date I 'C' )

'K -vnev- %) i %?I 

s..

ACTS Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described in this Owners Report during the period of IZ 0?,

to 1 o5 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this inspection.

.11 inqnpr4neq Rinnnhm-Commissions F1r 47ZY&4, C,6

)

National Board. State. Providence, and Endorsements ra Jo....

Date

/-4-es 04-001-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl wner Florida Power and Light Co.

Date Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet Address Turkey Point Plant 10/2/2004 1

of 2

3 WO#: 34014914-01 CR#:

N/A Repair OrganiatIon, P.O. No, Job No., etc.

Unit

2. Plant Name 9760 SW 344 Street Florida City, FL 33035 Address
3. Work Performed by Florida Power and Light Co.

Name 9760 SW 344 Street Florida City, FL 33035 Type Code Symbol Stamp Authorization Number Fenir;-ntn nlt N/A N/A N/A Address a

l Intake Cooling Water System #:

19 Quality Group

4. Identification of System:

C

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 19 55 Edition, 1998 Edition, N/A
Addenda, 2000
Addenda, N/A N/A Code Case Code Case
6. Identification of Components Repaired or Replaced and Replacement Components U

ASME Corrected, Code Name of Name of Mfg Mfg Serial National Other Year Removed or Stamp Component Number Board Identification Built Installed Yes/No Drain Valve N/A N/A N/A 3-50-377 N/A Installed N

7. Description of Work:

Install new valve

8. Tests Conducted:

Hydrostatic:

N/A Other N/A Pneumatic NIA Nominal Operating Pressure X

Pressure 11 psig Test Temperature 92.5 deg F 04-002-3

Sheet 2 of 2 FORM NIS-2 (Back)

.marks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Expiration Date:

N/A Signe 3 a-Date Owner or Owners Designet, Title 0

CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described In this Owners Report during the period of 8-A-O4 to

/ oS and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report In accordance with the requirements of ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.

Inspector's Signature Commissions -L 4 77 (

-,A,X )

National Board, State, Providence, and Endorsements Date i-3-of 04-002-3

w ner

2. Plant
3. Work Performec FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi Florida Power and Light Co.

Date 10 Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet I

Address Turkey Point Plant Unit

/2/2004 of 2

3 01 CR#:

N/A I by

-1 Name 9760 SW 344 Street Florida City, FL 33035 WO#: 33021380-Address Florida Power and Light Co.

c Name 9760 SW 344 Street Florida City, FL 33035 Address

4. Identification of System:

CVCS Charging and Letdown System #:

4

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components Repair Organization, P.O. No, Job No., etc.

Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date N/A 7

Quality Group B

19 55 Edition, N/A

Addenda, N/A Code Case 1998 Edition, 2000
Addenda, N/A Code Case Mfg Serial Number Name of Component Name of Mfg National Board Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No 4

4

+

4 3B Charging Pump N/A NMA N/A 13P201B NIA Corrected N

7. Description of Work:

Install new stuffing boxes on pump

8. Tests Conducted:

Hydrostatic:

N/A Other N/A Pneumatic N/A Pressure 2375 psig Nominal Operating Pressure X

Test Temperature 118 deg F 04-003-3

Sheet 2 of 2 FORM NIS-2 (Back)

.emarks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Expiration Date:

NIA Signed

=

) ¶1 Date J

ZQr Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford Connecticut, have inspected the components described in this Owners Report during the period of 42zz-a2 to l-4-f5 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Signature Commissions f-47

'4 C, V, I)

National Board. State, Provide

, and Endorsements Date

/-v-05 04-003-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI wner Florida Power and Light Co.

Date Nare 700 Universe Blvd. Juno Beach, FL 33408 Sheet Address Turkey Point Plant 10/212004 1

of 2

3 WO#: 33020989-01 CR#:

N/A Unit

2. Plant Name 9760 SW 344 Street Florida City, FL 33035 Address
3. Work Performed by Florida Power and Light Co.

Nare 9760 SW 344 Street Florida City, FL 33035 Address Type Code Symbc Authorization Nurr Expiration Date Repair Organization, P.O. No. Job No., etc.

)I Stamp NIA iber N/A N/A C

4. Identification of System:

Intake Cooling Water System #:

19 Quality Grour

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 19 55 Edition, 19 98 Edition, N/A
Addenda, 2000
Addenda, N/A N/A Code Case Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Name of Component Mfg Serial Number Name of Mfg National Board Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No mm 4

+

4 4

F 3A ICW Pump Discharge Check Valve N/A SN# 6175 N/A 13-50-311 N/A Installed N

3A ICW Pump Discharge N/A N# 46590 N/A NIA N/A Removed N

Check Valve I_

7. Description of Work:

Install Spare Valve

8. Tests Conducted:

Hydrostatic:

NIA Other N/A Pneumatic N/A Nominal Operating Pressure 20 Test Temperature 78 deg F 04-004-3 Pressure 15 psig

Sheet 2 of 2 FORM NIS-2 (Back) arks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp N/A Certificate of Authorization No.

NIA Expiration Date:

NMA Signed Date Owner or Owners Designee, tie CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described In this Owners Report during the period of tz-Io-03 to i j

- °.5 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code. Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Inspector's Signature Commissions FA 477 4C

a )_

National Board, State. Providence, and Endorsements Date i 5-s-os 04-004-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl

.wner Florida Power and Light Co.

Name 700 Universe Blvd. Juno Beach, FL 33408 Date Sheet Address Turkey Point Plant 10/3/2004 1

of 2

3 WO#: 33015160-07 CR#:

N/A Unit

2. Plant Name 9760 SW 344 Street Florida City, FL 33035 Address
3. Work Performed by Florida Power and Light Co.

Name Repair Organization, P.O. No, Job No., etc.

Type Code Symbol Stamp N/A Authorization Number NIA Expiration Date NIA 9760 SW 344 Street Florida City, FL 33035 Address

4. Identification of System:

Auxiliary Feedwater System #:

75 Quality Group C

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 55 Edition, 19 98 Edition, N/A
Addenda, 2000
Addenda, N/A Code Case N416-2 Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Name of Component Name of Mfg Mfg Serial Number National Board Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No Ask B Aux Feed pump N/A SN 0601001 N/A IP2B N/A Corrected N
7. Description of Work:

A damaged threaded connection was modified and made to a socket weld per PCM 03-095.

8. Tests Conducted:

Hydrostatic:

Other N/A Pneumatic NIA Nominal Operating Pressure X

Test Temperature 95 deg F 04-005-3 N/A Pressure 1400 psig

Sheet 2 of 2 FORM NIS-2 (Back)

.emarks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair conforms to the rules of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Expiration Date:

N/A Signed Is/

SU Cant Date Owner or Owners Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described in this Owners Report during the period of g-Zo-03 to 1-4-Os and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report In accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.

Inspectors Signature Commissions Ž5t72fA*L*

)

National Board, State. Providence, and Endorsements Date 04-005-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi wner Florida Power and Light Co.

Date Narne 700 Universe Blvd. Juno Beach, FL 33408 Sheet Address Turkey Point Plant Unit 1014/2004 1

of 2

3 WO#: 32018395-01 CR#:

N/A Repair Organization, P.O. No, Job No., etc.

2. Plant Narne 9760 SW 344 Street Florida City, FL 33035 Address
3. Work Performed by _

Florida Power and Light Co.

Name 9760 SW 344 Street Florida City, FL 33035 Type Code Symbol Stamp Authorization Number Expiration Date System #:

47 Quality Group 1N4/t%

N/A NMA Address CVCS Charging and Letdown

4. Identification of System:

B

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xi Utilized for Repairs or Replacements 19 55 Edition, N/A
Addenda, N/A Code Case 1998 Edition, 2000
Addenda, N416-2 Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Mfg Serial Number Name of Component Name of Mfg National Board Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No 4

4

+

U Isolation Valve N/A N/A N/A 3-1315 N/A Installed N

Pipe N/A N/A N/A SC# 0030938 N/A Installed N

7. Description of Work:

Install new valve and piping by welding

8. Tests Conducted:

Hydrostatic:

N/A Other N/A Pneumatic N/A Pressure 2350 psig Nominal Operating Pressure NOP Test Temperature 110 deg F 04-006-3

Sheet 2 of 2 FORM NIS-2 (Back) e marks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp NIA Certificate of Authorization No.

NIA Expiration Date:

N/A Signed

) S s--b c-ii Date Owner or Owner's Designee, Tine CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have Inspected the components described in this Owners Report during the period of 4-17-03 to 1-4-o5 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report In accordance with the requirements of ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Inspector's Signature Commissions Ft 477 (

VLG%_)

National Board, State. Providence, and Endorsements

/ or Date 04-006-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl wner Florida Power and Light Co.

Date Name 700 Universe Blvd. Juno Beach, FL 33408 Address Turkey Point Plant Name 9760 SW 344 Street Florida City, FL 33035 Sheet 10/1712004 1

of 2

3 WO#: 33022331-01 CR#:

N/A Unit

2. Plant Address
3. Work Performed by Florida Power and Light Co.

Name 9760 SW 344 Street Florida City, FL 33035 Type Code Symbol Authorization Numt Expiration Date System #:

71 Quality Group lepafrOrganization. P.O. No. Job No.. etc.

Stamp N/A ber NIA N/A B

Address Steam Generators

4. Identification of System:
5. (a) Applicable Construction Code ASME Vill (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 65 Edition, 19 98 Edition, 65
Addenda, 2000
Addenda, NIA N..

/ A.

N/A Code Case Code Case

6. Identification of Components Repaired or Replaced and Replacement Components Name of Component Name of Mfg Mfg Serial Number National Board Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No 3C Steam Generator N/A 13E210C N/A Corrected NIA N/A N
7. Description of Work:

Replace the bolting of the Handhole/Wrapper plug flange of the 3C Steam Generator

8. Tests Conducted:

Hydrostatic:

Other N/A Pneumatic N/A Nominal Operating Pressure N/A Test Temperature N/A deg F 04-007-3 NIA Pressure N/A psig

Sheet 2 of 2 FORM NIS-2 (Back)

  • emarks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp NIA Certificate of Authorization No.

NIA Expiration Date:

NIA Signed 1 SI-ID V' Date I

}2] IC _V_

Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described in this Owners Report during the period of 5-3 -o4 to 1 05 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.

Commissions AiZ 4e77,(+/-C 4/1 T Inspectors Signature National Board, State. Providence. and Endorsements Date 1-4-0s 04-007-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl wner Florida Power and Light Co.

Date Narne 700 Universe Blvd. Juno Beach, FL 33408 Sheet Address Turkey Point Plant 1015/2004 1

of 2

3 WO#: 34006371-02 CR#:

N/A Unit

2. Plant Nane 9760 SW 344 Street Florida City, FL 33035 Address
3. Work Performed by Florida Power and Light Co.

Name 9760 SW 344 Street Florida City, FL 33035 Repair Organization, P.O. No, Job No., etc.

Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date N/A Address Spent Fuel Pit Cooling

4. Identification of System:

System #:

33 Quality Group C

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1955 Edition, N/A Addenda.

19 98 Edition, 2000

Addenda, NIA Code Case NIA Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Name of Component Name of Mfg Mfg Serial Number National Board Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No Spent Fuel Pool Cooling Pump NIA NIA NIA 3P212B N/A Corrected N
7. Description of Work:

Install new bolting material on pump casing

8. Tests Conducted:

Hydrostatic:

N/A Other N/A Pneumatic N/A Nominal Operating Pressure N/A Test Temperature N/A deg F 04-008-3 Pressure N/A psig

Sheet 2 of 2 FORM NIS-2 (Back) emarks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp NIA Certificate of Authorization No.

N/A Expiration Date:

N/A Signed

.oK Date I

Owner or Owners Designee. itle CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described In this Owners Report during the period of 44 q04 to I or; and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report in accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

/Commissions Fl 4/77 C; Al:)

Inspector's Signature National Board, State, Providence. and Endorsements Date

/- 5-05 04-008-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl wner Florida Power and Light Co.

Name 700 Universe Blvd. Juno Beach, FL 33408 Date Sheet Address Turkey Point Plant 1015/2004 1

of 2

3 WO#: 33003591-01 CR#:

03-0207 Unit

2. Plant Name 9760 SW 344 Street Florida City, FL 33035 Address
3. Work Performed by Florida Power and Light Co.

Name Repair Organization, P.O. No. Job No., etc.

Type Code Symbol Stamp NMA Authorization Number N/A Expiration Date NMA 9760 SW 344 Street Florida City, FL 33035 Address

4. Identification of System:

Intake Cooling Water System #:

19 Quality Group C

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 55 Edition, N/A
Addenda, N/A Code Case 1998 Edition, 2000
Addenda, N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components National Board Name of Component Name of Mfg Mfg Serial Number Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No l

ll Component Support N/A N/A N/A Support Mark# F N/A Corrected N

7. Description of Work:

Replace degraded portion of support by welding

8. Tests Conducted:

Hydrostatic:

N/A Other N/A Pneumatic N/A Nominal Operating Pressure N/A Test Temperature N/A deg F 04-009-3 Pressure N/A psig

Sheet 2 of 2 FORM NIS-2 (Back)

  1. emarks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair conforms to the rules of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Expiration Date:

N/A Signed Szs Owner or Owneres Designee, Title Date CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described in this Owners Report during the period of 6-16 -a3 to I o 5 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions fe 417 4 C, Al r Inspector's Signature National Board, State, Providence. and Endorsements Date

/- 4_

WO 3003N1-oI 04-009-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Florida Power and Light Co.

Date 10 Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1

Address Turkey Point Plant Unit

)fwner

2. Plant 0/6/2004 of 2

3 01 CR#:

N/A Name 9760 SW 344 Street Florida City, FL 33035 WO#: 34004673-Address

3. Work Performed by Florida Power and Light Co.

Name 9760 SW 344 Street Florida City, FL 33035 Address

4. Identification of System:

Intake Cooling Water System #:

1

5. (a) Applicable Construction Code ASME Vill (b) Applicable Edition of Section Xi Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components Repair Organization. P.O. No, Job Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date N/A 9

Quality Group C

19 67 Edition, N/A

Addenda, N/A 19 98 Edition, 2000
Addenda, N/A No., etc.

Code Case Code Case Name of Component Name of Mfg Mfg Serial INumber Corrected, Removed or Installed National Board Other Identification Year Built ASME Code Stamp Yes/No Heat Exchanger (3A CCW)

N/A N/A N/A 13E207A N/A Corrected N

7. Description of Work:

Installed new bolting material

8. Tests Conducted:

Hydrostatic:

N/A Other N/A Pneumatic N/A Pressure N/A psig Nominal Operating Pressure N/A TestTemperature N/A deg F 04-010-3

Sheet 2 of 2 FORM NIS-2 (Back) q emarks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp NMA Certificate of Authorization No.

N/A Expiration Date:

N/A Signed I

Date Owner or Owners Designee. Ttle I

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Ha tford Connecticut, have inspectd the components described in this Owners Report during the period of aso to

/- r-o-or and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

G o__

/Commissions

,j42 1772 CZ W__

Inspectors Signature National Board, State, Providence, and Endorsements Date

/-

-O<

04-01 0-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi rvner Florida Power and Light Co.

Name 700 Universe Blvd. Juno Beach, FL 33408 Address Turkey Point Plant Name 9760 SW 344 Street Florida City, FL 33035 Date Sheet 10/6/2004 1

of 2

3 WO#: 34006953-01 CR#:

N/A

2. Plant Unit Address
3. Work Performed by Florida Power and Light Co.

Name 9760 SW 344 Street Florida City, FL 33035 Repair Organization, P.O. No, Job No.. etc.

Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date N/A Address

4. Identification of System:

Intake Cooling Water System #:

19 Quality Group C

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 55 Edition, 19 98 Edition, N/A
Addenda, 2000
Addenda, N/A Code Case N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components V

ASME Corrected, Code Name of Name of Mfg Mfg Serial National Other Year Removed or Stamp Component Number Board Identification Built Installed Yes/No Drain Valve N/A N/A N/A 3-50-364 N/A Installed N

7. Description of Work:

Install New Valve by a threaded connection

8. Tests Conducted:

Hydrostatic:

N/A Other N/A Pneumatic N/A Nominal Operating Pressure X

Test Temperature 75 deg F 04-011-3 Pressure 15 psig

Sheet 2 of 2 FORM NIS-2 (Back) marks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Expiration Date:

N/A Signed K

S1t-liri_

Date 42JR_1ad Owner or Owner's Designee, T~e CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described in this Owners Report during the period of 4 -%7- 04 to l 05 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

_'.4iAs Inspectors Signature Commissions AZ/ 17,7 Ao C, A G National Board, State, Providence, and Endorsements Date I-6a0o5 04-011-3

wner

2. Plant FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Florida Power and Light Co.

Date 10 Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1

Address Turkey Point Plant Unit 0/6/2004 of 2

3 01 CR#:

N/A Name 9760 SW 344 Street Florida City, FL 33035 WO#: 34001271-Address

3. Work Performed by Florida Power and Light Co.

Name 9760 SW 344 Street Florida City, FL 33035 Address

4. Identification of System:

Intake Cooling Water System #:

1

5. (a) Applicable Construction Code ASME VIII (b) Applicable Edition of Section XI Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components Repair Organization, P.O. No, Job No., etc.

Type Code Symbol Stamp NIA Authorization Number N/A Expiration Date N/A 9

Quality Group C

19 67 Edition, N/A

Addenda, N/A Code Case 19 98 Edition, 2000
Addenda, NIA Code Case National Board Name of Component Name of Mfg Mfg Serial Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No 4

4



WV Heat Exchanger (3C CCW)

N/A N/A N/A 3E207C N/A Corrected N

4 4 4

1'

7. Description of Work:

Install new bolting material on heat exchanger

8. Tests Conducted:

Hydrostatic:

N/A 0

Other N/A Pneumatic N/A Pressure N/A psig Nominal Operating Pressure N/A Test Temperature N/A deg F 04-012-3

Sheet 2 of 2 FORM NIS-2 (Back)

  • .emarks None CERTIFICATE OF C We certify that the statements made in the report are correct an' ASME Code, Section Xi.

Type Code Symbol Stamp Certificate of Authorization No.

N/A Signed I

Ad Owner o Owners Designee. Title CERTIFICATE OF INSER' I, the undersigned, holding a valid commission issued by the Na' the state of Florida and employed by HSBCT of Hartford, Conne Owners Report during the period of,-O4 and state that to the best of my knowledge and belief, the Owne measures described in this Owners' Report in accordance with t By signing this certificate neither the Inspector nor his employer concerning the examinations and corrective measures described Inspector nor his employer shall be liable in any manner for any kind arising from or connected with this inspection.

Inspectors Signature Date COMPLIANCE d this replacement conforms to the rules of the N/A Expiration Date:

NMA rGo

D W

v Date _3 -2 VICE INSPECTION tional Board of Boiler and Pressure Vessel Inspectors and cticut, have Inspe ted the components described in this to r has performed examinations and taken corrective he requirements of ASME Code, Section Xi.

makes any warranty, expressed or implied, I in this Owners' Report. Furthermore, neither the personal injury or property damage or a loss of any Commissions /a7O2 (4s,4 A ZJ__

National Board. State, Providence, and Endorsements 04-012-3

Omer

2. Plant
3. Work Performec FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI Florida Power and Light Co.

Date 10 Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1

Address Turkey Point Plant Unit 1512004 of 2

3 01 CR#:

N/A I by Name 9760 SW 344 Street Florida City, FL 33035 WO#: 34017422-l Address Florida Power and Light Co.

Name 9760 SW 344 Street Florida City, FL 33035 Address

4. Identification of System:

Intake Cooling Water System #:

1

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section XI Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components Repair Organization, P.O. No, Job Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date NIA 9

Quality Group C

19 55 Edition, N/A

Addenda, N/A 1998 Edition, 2000
Addenda, N/A No., etc.

Code Case Code Case Name of Component Name of Mfg Mfg Serial National Number Board Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No IN 3B ICW Pump Discharge Check Valve N/A D2885 N/A 13-50-321 N/A Installed N

3B ICW Pump Discharge N/A 46590 N/A 3-50-321 N/A Removed N

Check Valve

7. Description of Work:

Install new valve

8. Tests Conducted:

Hydrostatic:

N/A Other N/A Pneumatic N/A Pressure 23 psig Nominal Operating Pressure NOP Test Temperature 82 deg F 04-013-3

Sheet 2 of 2 FORM NIS-2 (Back) marks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No.

NIA Expiration Date:

N/A Signed Owner's Ies ignee,A tle CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described in this Owners Report during the period of U-2-o4 to 1-5-0S and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions

  1. 477 (hcI, )

Inspector's Signature Natonal Board, State, Providence, and Endorsements Date

/- 5-06 04-013-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi Florida Power and Light Co.

Date 10/

Narne 700 Universe Blvd. Juno Beach, FL 33408 Sheet I

Address Turkey Point Plant Unit

'1412004 of 2

3 01 CR#:

N/A

2. Plant Name 9760 SW 344 Street Florida City, FL 33035 WO#: 33012526-
3. Work Performed by Address Florida Power and Light Co.

Name 9760 SW 344 Street Florida City, FL 33035 Address

4. Identification of System:

Spent Fuel Pit Cooling System #:

3

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components Repair Organization, P.O. No, Job No., etc.

Type Code Symbol Stamp NMA Authorization Number N/A Expiration Date N/A 33 Quality Group C

19 55 Edition, N/A

Addenda, N/A Code Case 19 98 Edition, 2000
Addenda, N/A Code Case Name of Component Name of Mfg Mfg Serial National NumberI Board Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No Pump (3A SFPC)

N/A N/A N/A l3P212A N/A I Corrected N

I I

I I

I I

I

7. Description of Work:

Install new casing bolting material

8. Tests Conducted:

Hydrostatic:

N/A 0

Other N/A Pneumatic N/A Pressure N/A psig Nominal Operating Pressure N/A Test Temperature N/A deg F 04-014-3

Sheet 2 of 2 FORM NIS-2 (Back) emarks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Expiration Date:

N/A Signed Date 1i2.9/-

Owner or Owner's Designee, TitlI CERTIFICATE OF INSERVICE INSPECTION

1. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described in this Owners Report during the period of 9-1q -

1 4

to Bl 05 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report In accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions A/ 477 C Al, I,)_

Inspectors Signature National Board, State, Providence, and Endorsements Date

/ 5 04-014-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi

Date Namre 700 Universe Blvd. Juno Beach, FL 33408 Address Turkey Point Plant Sheet 10/17/2004 1

of 2

3 WO#: 34008530-01 CR#:

N/A Repair Organization, P.O. No, Job No., etc.

Unit

2. Plant Name 9760 SW 344 Street Florida City, FL 33035 Address
3. Work Performed by Florida Power and Light Co.

Name 9760 SW 344 Street Florida City, FL 33035 Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date N/A Address Spent Fuel Pit Cooling

4. Identification of System:

System #:

33 Quality Group C

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xi Utilized for Repairs or Replacements 19 55 Edition, 19 98 Edition, N/A
Addenda, 2000
Addenda, N/A Code Case N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Name of Mfg Name of Component Mfg Serial Number National Board Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No Pump (38 Spent Fuel cooling)

N/A 13P212B N/A Corrected N/A N/A N

7. Description of Work:

Replace pump casing bolting

8. Tests Conducted:

Hydrostatic:

N/A Other N/A Pneumatic N/A Nominal Operating Pressure N/A Test Temperature N/A deg F 04-015-3 Pressure N/A psig

Sheet 2 of 2 FORM NIS-2 (Back) emarks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Expiration Date:

N/A Signed I

Ei5 c

o-O_

Date l

l 2_5/aq__

Owner or Owner's Designee, Titld' CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described in this Owners Report during the period of 6-1o-o4 to I 0 5 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report In accordance with the requirements of ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

_Commissions Ft 477 C_

Inspectors Signature National Board. State. Providence and Endorsements Date

/-4-oh 04-015-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI ner Florida Power and Light Co.

Date Narne 700 Universe Blvd. Juno Beach, FL 33408 Address Turkey Point Plant Narne 9760 SW 344 Street Florida City, FL 33035 Sheet 10/6/2004 1

of 2

3 WO#: 34011856-01 CR#:

N/A Repair Organization. P.O. No, Job No.. etc.

Unit

2. Plant Address
3. Work Performed by Florida Power and Light Co.

Namfe 9760 SW 344 Street Florida City, FL 33035 Type Code Symbol Stamp Authorization Number Expiration Date N/A N/A N/A Address

4. Identification of System:

Intake Cooling Water System #:

19 Quality Group C

5. (a) Applicable Construction Code ASME Vill (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 19 67 Edition, 19 98 Edition, N/A
Addenda, 2000
Addenda, N/A Code Case N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Name of Component l Name of Mfg Mfg Serial Number National Board Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No Heat Exchanger (3C CCW)

NMA NMA N/A 3E207C NWA Corrected N

7. Description of Work:

Install new bolting material

8. Tests Conducted:

Hydrostatic:

NMA Other NMA Pneumatic N/A Nominal Operating Pressure N/A Pressure N/A psig Test Temperature N/A deg F 04-016-3

Sheet 2 of 2 FORM NIS-2 (Back)

  • emarks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.

Type Code Symbol Stamp NMA Certificate of Authorization No.

N/A Expiration Date:

N/A Signed Date J 2 sVc-2 Owner or Owners Designee, TitU I

CERTIFICATE OF INSERVICE INSPECTION 1 the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described in this Owners Report during the period of S-23 -o 4 to

/-S--05 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report In accordance with the requirements of ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.

C Commissions qE 477 (A, C, A Inspectors Signature National Board, State, Providence. and Endorsements Date 05 04-016-3

ner

2. Plant FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Florida Power and Light Co.

Date 10 Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1

Address Turkey Point Plant Unit

/7/2004 of 2

3 01 CR#:

N/A Name 9760 SW 344 Street Florida City, FL 33035 WO#: 34012308-Address Repair Organization, P.O. No. Job No.. etc.

3. Work Performed by Florida Power and Light Co.

Type Code Symbol Stamp N/A Name Authorization Number N/A 9760 SW 344 Street Florida City, FL 33035 Expiration Date N/A Address

4. Identification of System:

CVCS Charging and Letdown System #:

47 Quality Group B

5. (a) Applicable Construction Code B31.1 1955 Edition, N/A
Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 19 98 Edition, 2000
Addenda, N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Name of Mfg Name of Component Mfg Serial National Number Board Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No mm 4

+

+

4 4-W Isolation Valve NIA N/A N/A 13-1315 NIA Corrected N

7. Description of Work:

Install new valve bonnet and seal weld

8. Tests Conducted:

Hydrostatic:

N/A Other NIA Pneumatic N/A Pressure 2400 psig Nominal Operating Pressure X

Test Temperature 111.7 deg F 04-017-3

Sheet 2 of 2 FORM NIS-2 (Back)

  • marks None CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp N/A Certificate of Authorization No.

NMA Expiration Date:

N/A Signed

_I 3

I Date J

_L Owner or Owner's Designee, Title' CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartfqrd, Connecticut. have inspected the components described in this Owners Report during the period of _

to I 4-05 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report In accordance with the requirements of ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore. neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions j

National Board, State. Providence, and Endorsements Inspector's Signature Date

/- I4-s 04-017-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi ner Florida Power and Light Co.

Date Name 700 Universe Blvd. Juno Beach, FL 33408 Address Turkey Point Plant Sheet 10/20/2004 1

of 2

3 WO#: 33023668-01 CR#:

N/A Repair Organization, P.O. No, Job No.. etc.

Unit

2. Plant Name 9760 SW 344 Street Florida City, FL 33035 Address Florida Power and Light Co.
3. Work Performed by 9760
4. Identification of System:

Name SW 344 Street Florida City, FL 33035 Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date N/A Address Residual Heat Removal System #:

50 Quality Group A

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xi Utilized for Repairs or Replacements 19 55 Edition, 19 98 Edition, N/A
Addenda, 2000
Addenda, N/A Code Case N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Name of Component Name of Mfg Mfg Serial Number National Board Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No Check Valve NMA N/A N/A N/A Corrected 3-876B N
7. Description of Work:

Replace bolting material on valve

8. Tests Conducted:

Hydrostatic:

N/A Other NIA Pneumatic N/A Nominal Operating Pressure NIA Test Temperature N/A deg F 04-018-3 Pressure N/A psig

Sheet 2 of 2 FORM NIS-2 (Back) emarks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code,Section XI.

Type Code Symbol Stamp NIA Certificate of Authorization No.

N/A Expiration Date:

NIA Signed t-Date Owner or Owners Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described in this Owners Report during the period of 5-21-0q to 1-4-a3 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

.Commissions 4777 4-C, go)

Inspector's Signature National Board, State, Providence. and Endorsements Date

/ A

'J 04-018-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl wner Florida Power and Light Co.

Name 700 Universe Blvd. Juno Beach, FL 33408 Date Sheet Address Turkey Point Plant 10/20/2004 1

of 2

3 WO#: 33023669-01 CR#:

N/A Unit

2. Plant Name 9760 SW 344 Street Florida City, FL 33035 Address
3. Work Performed by Florida Power and Light Co.

Name 9760 SW 344 Street Florida City, FL 33035 Repair Organization, P.O. No, Job No.. etc.

Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date N/A Address Residual Heat Removal

4. Idenlification of System:

System #:

50 Quality Group A

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 55 Edition, 1998 Edition, N/A Addenda.

2000

Addenda, N/A Code Case N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Name of Component Name of Mfg N/A Mfg Serial Number National Board Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No I.-

I 4

4 4

Check Valve NMA N/A 13-876D N/A Corrected N

7. Description of Work:

Replace bolting material on Valve

8. Tests Conducted:

Hydrostatic:

N/A Other N/A Pneumatic N/A Pressure N/A psig Nominal Operating Pressure N/A Test Temperature N/A deg F 04-019-3

Sheet 2 of 2 FORM NIS-2 (Back) emarks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.

Type Code Symbol Stamp NIA Certificate of Authorization No.

NIA Expiration Date:

N/A Signed 1____

Date I

I-l

_l Owner or Owners Designee, Ti le CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut. have inspected the components described in this Owners Report during the period of 5-2J-o4 to 1 05 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions

/r:Z 472 (,

C, J1 l)

Inspector's Signature National Board, State, Providence, and Endorsements Date 04-019-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI wner Florida Power and Light Co.

Narne 700 Universe Blvd. Juno Beach, FL 33408 Date Sheet

2. Plant Address Turkey Point Plant Name 9760 SW 344 Street Florida City, FL 33035 Address Unit 10/21/2004 I

of 2

3 WO#: 33009476-01 CR#:

N/A

3. Work Performed by Florida Power and Light Co.

Name Repair Organization, P.O. No, Job No., etc.

Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date NIA 9760 SW 344 Street Florida City, FL 33035 Address

4. Identification of System:

CVCS Charging and Letdown System #:

47 Quality Group A

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 55 Edition, 19 98 Edition, N/A
Addenda, 2000
Addenda, N/A Code Case N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Name of Component Name of Mfg Mfg Serial Number National Board Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No mu

+

t 1

F Control Valve N/A N/A N/A I CV-3-310A N/A Corrected N

7. Description of Work:

Replace bonnet bolting on Valve

8. Tests Conducted:

Hydrostatic:

N/A 0

Other NMA Pneumatic N/A Nominal Operating Pressure N/A Pressure N/A psig Test Temperature N/A deg F 04-020-3

Sheet 2 of 2 FORM NIS-2 (Back) marks None CERTIFICATE OF C We certify that the statements made In the report are correct an(

ASME Code. Section Xl.

Type Code Symbol Stamp Certificate of Authorization No.

NMA Signed 1 Owner or Owners Designee, Titl CERTIFICATE OF INSER 1, the undersigned, holding a valid commission issued by the Na the state of Florida and employed by HSBCT of Hartford. Conne Owners Report during the period of IO-7-o4.

I and state that to the best of my knowledge and belief, the Owne measures described In this Owners' Report in accordance with t By signing this certificate neither the Inspector nor his employer concerning the examinations and corrective measures described Inspector nor his employer shall be liable in any manner for any kind arising from or connected with this inspection.

Inspectors Signature Date I-4_-

0 COMPLIANCE d this replacement conforms to the rules of the N/A Expiration Date:

N/A Date j_12S l X g VICE INSPECTION tional Board of Boiler and Pressure Vessel Inspectors and cticut, have inspected the components described in this to _

4-05 r has performed examinations and taken corrective he requirements of ASME Code,Section XI.

makes any warranty, expressed or implied, I in this Owners' Report. Furthermore, neither the personal injury or property damage or a loss of any Commissions F2I 7 National Board. State, Providence, and Endorsements 04-020-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl

.wner Florida Power and Lighi Co.

Date Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet

2. Plant Address Turkey Point Plant Name 9760 SW 344 Street Florida City, FL 33035 Address Unit 11/2/2004 1

of 2

3 WO#: 34000102-01 CR#:

NMA

3. Work Performed by Florida Power and Light Co.

Name 9760 SW 344 Street Florida City, FL 33035 Type Code Symbc Authorization Nurr Expiration Date System #:

64 Quality Grou:

Repair Organization, P.O. No, Job No., etc.

)l Stamp N/A iber N/A N/A B

Address Safety Injection Accumulator

4. Identification of System:
5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 55 Edition, 19 98 Edition, N/A
Addenda, 2000
Addenda, N/A N/A Code Case Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Name of Component Name of Mfg Mfg Serial Number National BoardI Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No t

+

Relief Valve N/A N/A N/A RV-3-858C N/A Corrected N

7. Description of Work:

Install new bolting material on Valve

8. Tests Conducted:

Hydrostatic:

N/A Pneumatic N/A 0

Nominal Operating Pressure N/A Test Temperature N/A deg F 04-021-3 Other N/A Pressure N/A psig

Sheet 2 of 2 FORM NIS-2 (Back)

.emarks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No.

NMA Expiration Date:

N/A Signed Date I J7Zj)

Owner or Owner's Designee, Titl' CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described in this Owners Report during the period of 43-11-04 to 1-4 -o0S and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report In accordance with the requirements of ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions

/2 7

-50 4, C, 4/1)

Inspectors Signature National Board, State, Providence. and Endorsements Date

/- 4 r

04-021-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Florida Power and Light Co.

Date 11 Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet Address Turkey Point Plant Unit Wner

2. Plant

/4/2004 of 2

3 01 CR#:

N/A

-1 Name 9760 SW 344 Street Florida City, FL 33035 WO#: 34000031-Address Repair Organization, P.O. No. Job No., etc.

3. Work Performed by Florida Power and Light Co.

Type Code Symbol Stamp N/A Name 9760 SW 344 Street Florida City, FL 33035 Expiration Date N/A Address ExriDtN

4. Identification of System:

Component Cooling Water System #:

30 Quality Group C

5. (a) Applicable Construction Code B31.1 1955 Edition, N/A
Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 98 Edition, 2000
Addenda, N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Name of Component Name of Mfg Mfg Serial Number National Board I Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No

+

I

+I Relief Valve for Normal Containment Cooler D Consolidated TH18078 NMA RV-3-1428 Relief Valve for Normal Containment Cooler D Consolidated TK36209 N/A RV-3-1428 N/A N/A Removed Installed N

N

_________ 1

7. Description of Work:

Install Spare Relief Valve

8. Tests Conducted:

Hydrostatic:

N/A Other N/A Pneumatic N/A Pressure __20 _psig Nominal Operating Pressure Test Temperature 79 X

deg F 04-022-3

Sheet 2 of 2 FORM NIS-2 (Back) emarks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Expiration Date:

N/A Signed SJ k tov; Date 1Zj 2 1 7-Owner or Owners Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described in this Owners Report during the period of 9-2 -o4 to

/- 5-05 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report In accordance with the requirements of ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

__Commissions At 4'?

(4, C, -$JJ7 Inspectors Signature National Board, State, Providence. and Endorsements Date 1-5-oS 04-022-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi

.wner Florida Power and Light Co.

Date Narne 700 Universe Blvd. Juno Beach, FL 33408 Sheet Address Turkey Point Plant Unit 11/912004 1

of 2

3 WO#: 33005126-03 CR#: 04-10639 Repair Organization, P.O. No, Job No., etc.

.IIA

2. Plant Nane 9760 SW 344 Street Florida City, FL 33035 Address Florida Power and Light Co.

Narne

3. Work Performed by 9760 SW 344 Street Florida City, FL 33035 Type Code Symbol Stamp Authorization Number Expiration Date System #:

62 Quality Group l N/A N/A N/A Address Safety Injection

4. Identification of System:

A

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 55 Edition, 19 98 Edition, NIA
Addenda, 2000
Addenda, N/A Code Case N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Year Built Name of Component Name of Mfg Mfg Serial Number National Board Other Identification Corrected, Removed or Installed ASME Code Stamp Yes/No Component Support N/A NIA lMark#F NIA NIA Installed N
7. Description of Work:

Install Pipe support Mark#F

8. Tests Conducted:

Hydrostatic:

N/A I

Other N/A Pneumatic NIA Nominal Operating Pressure NIA Test Temperature N/A deg F 04-023-3 Pressure N/A psig

Sheet 2 of 2 FORM NIS-2 (Back)

  • emarks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code,Section XI.

Type Code Symbol Stamp NIA Certificate of Authorization No.

N/A Expiration Date:

NIA Signed

_==

Date Owner or Owner's Designee.,il CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described in this Owners Report during the period of 1q24104 / 5 cc to

/15. O5 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code. Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

'Commissions t 49772

, c, C,A )

Inspectors Signature National Board, State, Providence, and Endorsements Date

/- 5

-S5 04-023-3

wn er

2. Plant
3. Work Performet FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Florida Power and Light Co.

Date 11/

Namo 700 Universe Blvd. Juno Beach, FL 33408 Sheet I

Address Turkey Point Plant Unit 10/2004 of 2

3 01 CR#:

NIA C

I by 1

Name 9760 SW 344 Street Florida City, FL 33035 WO#: 33012172-Address Florida Power and Light Co.

S Name 9760 SW 344 Street Florida City, FL 33035 Address

4. Identification of System:

CVCS Charging and Letdown System #: A

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section XI Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components Repair Organization, P.O. No. Job No., etc.

Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date N/A 47 Quality Group B

19 55 Edition, N/A

Addenda, NIA Code Case 19 98 Edition, 2000
Addenda, N/A Code Case National Board Name of Component Name of Mfg Mfg Serial INumber Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No lME U l Bypass valve N/A N/A I N/A 3-295 N/A Corrected N
7. Description of Work:

Install new bolting material in Valve

8. Tests Conducted:

Hydrostatic:

N/A 0

Other N/A Pneumatic N/A Pressure N/A

. psig Nominal Operating Pressure N/A Test Temperature N/A deg F 04-024-3

Sheet 2 of 2 FORM NIS-2 (Back) emarks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Expiration Date:

NIA Signed WIS I

csa>Ls Date Owner or Owner's Designee. Tithe I'

0 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described In this Owners Report during the period of

/1 4 to l-5-cS-and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions F442?

7 4 C J

p, z )

National Board, State. Providence. and Endorsements Inspector's Signature Date 0

04-024-3

Owner

2. Plant FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Florida Power and Light Co.

Date 11/

Name 700 Universe Blvd. Juno Beach. FL 33408 Sheet I

Address Turkey Point Plant Unit 10/2004 of 2

3 01 CR#:

N/A Name 9760 SW 344 Street Florida City, FL 33035 WO#: 33022950-l Address

3. Work Performed by Florida Power and Light Co.

Name 9760 SW 344 Street Florida City, FL 33035 Address

4. Identification of System:

CVCS Charging and Letdown System #:

4

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section XI Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components Repair Organization, P.O. No, Job No.. etc.

Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date NMA 7

Quality Group A

19 55 Edition, NIA

Addenda, N/A Code Case 19 98 Edition, 2000
Addenda, NMA Code Case U

ASME Corrected, Code Name of Name of Mfg Mfg Serial National Other Year Removed or Stamp Component Number Board Identification Built Installed Yes/No I

Isolation Valve N/A N/A N/A 3-312C N/A Corrected N

7. Description of Work:

Install new bolting material in valve

8. Tests Conducted:

Hydrostatic:

N/A Other N/A Pneumatic N/A Pressure N/A psig Nominal Operating Pressure N/A Test Temperature N/A deg F 04-025-3

Sheet 2 of 2 FORM NIS-2 (Back) emarks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp NMA Certificate of Authorization No.

NIA Expiration Date:

NIA Signed IS

_S_%

-ov Date I ')-/

Owner or Owner's Designee, Tit-CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described in this Owners Report during the period of II.3o-o4 to

/- 5-0 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

7 11-Commissions Pr 1 7?

(4, C, J ?

National Board, State, Providence, and Endorsements Inspector's Signature Date

/ Os 0

04-025-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Florida Power and Light Co.

Date 11/10/2004 Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1

of Address Turkey Point Plant Unit 3

Wner

2. Plant
3. Work Performei 2

CR#:

N/A i by Name

)760 SW 344 Street Florida City, FL 33035 WO#: 34008570-01 Address Florida Power and Light Co.

5 Name 9760 SW 344 Street Florida City. FL 33035 Address

4. Identification of System:

CVCS Charging and Letdown System #:

4

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components Repair Organization. P.O. No. Job No., etc.

Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date N/A 7

Quality Group B

19 55 Edition, N/A

Addenda, NMA Code Case 19 98 Edition, 2000
Addenda, N/A Code Case Name of Component Name of Mfg Mfg Serial National INumber IBoard Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No A111114 V F Isolation Valve NMA N/A N/A 3-269 NMA Installed N
7. Description of Work:

Install new valve and bolting material

8. Tests Conducted:

Hydrostatic:

N/A 0

Other N/A Pneumatic N/A Pressure 19.9 psig Nominal Operating Pressure Test Temperature 89 X

deg F 04-026-3

Sheet 2 of 2 FORM NIS-2 (Back) e marks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No.

NIA Expiration Date:

N/A Signed I 'S

':1r

_Date I By;Pot8 Owner or Owner's Designee, Titte CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartfosd, Connecticut, have inspected the components described in this Owners Report during the period of 7-Z o-Ot to

/ °5 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report In accordance with the requirements of ASME Code. Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

,4 Commissions Ad 27 4'?

C, l,

__)

Inspectors Signature Nalional Board, State, Providence, and Endorsements Date

-j_-__

04-026-3

wner

2. Plant
3. Work Performet
4. Identification of FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi Florida Power and Light Co.

Date 11i Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet I

Address Turkey Point Plant Unit P1 1/2004 of 2

3 01 CR#:

N/A 976C 1by 976C System:

Name I SW 344 Street Florida City, FL 33035 WO#: 34001110-Address Florida Power and Light Co.

Name I SW 344 Street Florida City, FL 33035 Repair Organization, P.O. No. Job No., etc.

Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date N/A System #:

56 Quality Group B

Address Containment Emergency Filters

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 19 55 Edition, N/A
Addenda, 19 98 Edition, 2000
Addenda, N/A Code Case N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Name of Component Name of Mfg Mfg Serial INumber National Board Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No

'EE 4

.4.

-

4 I

I Isolation Valve NMA N/A N/A SV-3-2910 N/A Corrected N

7. Description of Work:

Reweld bonnet seal weld on valve

8. Tests Conducted:

Hydrostatic:

N/A Other N/A Pneumatic N/A Pressure N/A psig Nominal Operating Pressure N/A Test Temperature N/A deg F 04-027-3

Sheet 2 of 2 FORM NIS-2 (Back)

  • emarks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Expiration Date:

N/A Signed 12 k-Date l

j4 Owner or Owner's Designee, TitIl CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described in this Owners Report during the period of

- oZ -o4-to

(- O0 -os and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

le, Commissions

/-L 4 7? /

cA4,)

Inspector's Signature National Board, State, Providence, and Endorsements Date 1-5-0 5

04-027-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl wfner

2. Plant Florida Power and Light Co.

Date Narne 700 Universe Blvd. Juno Beach, FL 33408 Address Turkey Point Plant Sheet 11/1212004 1

of 2

3 WO#: 34018233-01 CR#:

N/A Repair Organization, P.O. No. Job No., etc.

Unit Name 9760 SW 344 Street Florida City, FL 33035 Address

3. Work Performed by Florida Power and Light Co.

Narne 9760 SW 344 Street Florida City, FL 33035 Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date N/A Address Safety Injection Accumulator

4. Identification of System:

System #:

64 Quality Group B

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 55 Edition, 19 98 Edition, N/A
Addenda, 2000 Addenda.

N/A N/A Code Case Code Case

6. Identification of Components Repaired or Replaced and Replacement Components Name of Component Name of Mfg Mfg Serial Number National Board Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No I

Control Valve N/A CV-3-851C N/A Corrected N/A N/A N

7. Description of Work:

Install new bolting material on valve

8. Tests Conducted:

Hydrostatic:

N/A Other N/A Pneumatic N/A Nominal Operating Pressure N/A Test Temperature N/A deg F 04-028-3 Pressure N/A psig

Sheet 2 of 2 FORM NIS-2 (Back) emarks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code. Section Xi.

Type Code Symbol Stamp N/A Certificate of Authorization No.

Signed N/A Expiration D.3te:

NMA Date I2.) 1_ll4 ay J S -)

--, ii e3 cw" " A e5 V-

'7

§

{4-}5 5

  • it}4z);&

Go Owner or Owners Designee. Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut. have inspected the components described in this Owners Report during the period of I1a-W-o4 to I o5 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

"&15" 1--

Commissions i:'t 477(A, C.A1 )

2Z___

National Board. State. Providence, and Endorsements Inspectors Signature Date I -$-

oS 04-028-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl

.wner

2. Plant Florida Power and Light Co.

Date Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet Address Turkey Point Plant Name 9760 SW 344 Street Florida City, FL 33035 1/11212004 1

of 2

3 WO#: 33022904-01 CR#:

NMA Unit Address

3. Work Performed by Florida Power and Light Co.

Name 9760 SW 344 Street Florida City, FL 33035 Repair Organization. P.O. No, Job No., etc.

Type Code Symbol Stamp N/A Authorization Number NIA Expiration Date N/A Address Safety Injection

4. Identification of System:

System #:

62 Quality Group B

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xi Utilized for Repairs or Replacements 19 55 Edition, N/A
Addenda, N/A Code Case 19 98 Edition, 2000
Addenda, N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Name of Component Name of Mfg Mfg Serial National Number Board Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No

+

I t

A Isolation Valve N/A N/A N/A 3-897A NIA Corrected N

I

7. Description of Work:

Install new flange bolting

8. Tests Conducted:

Hydrostatic:

N/A 0

Other NIA Pneumatic N/A Pressure N/A psig Nominal Operating Pressure NIA Test Temperature N/A deg F 04029-3

Sheet 2 of 2 FORM NIS-2 (Back) emarks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp NIA Certificate of Authorization No.

NWA Expiration Date:

NMA Signed I

Sv 5.i--)

Date J

Ll;jo

/

Owner or Owners Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described in this Owners Report during the period of 3--lo4 to I-so and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code. Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.

4 e g

Commissions

/IC 472 (i, C4 /

V, Inspector's Signature National Board, State, Providence, and Endorsements Date 1-505 04-029-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl

.N ner

2. Plant Florida Power and Light Co.

Date Name 700 Universe Blvd. Juno Beach, FL 33408 Address Turkey Point Plant Name 9760 SW 344 Street Florida City, FL 33035 Sheet 11)12/2004 1

of 2

3 WO#: 33021285-01 CR#:

N/A Unit Address

3. Work Performed by Florida Power and Light Co.

Name 9760 SW 344 Street Florida City, FL 33035 Repair Organization. P.O. No, Job No., etc.

Type Code Symbol Stamp NIA Authorization Number N/A Expiration Date N/A Component Cooling Water System #:

30 Quality Group

4. Identification of System:

C

5. (a) Applicable Construction Code _

B31.1 (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 19 55 Edition, 19 98 Edition, N/A

Addenda, 2000
Addenda, NIA Code Case N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Name of Component Name of Mfg Mfg Serial Number National Board Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No I.

I t

t Relief Valve for Emergency Containment Cooler A Relief Valve for Emergency Containment Cooler A N/A N/A TH18075 N/A RV-3-1425 N/A Removed N

TM34081

-N/A RV-3-1425

-N/A Installed l

N

7. Description of Work:

Install Spare Valve

8. Tests Conducted:

Hydrostatic:

N/A W

Other N/A Pneumatic N/A Pressure 20 psig Nominal Operating Pressure X

Test Temperature 79 deg F 04-030-3

Sheet 2 of 2 FORM NIS-2 (Back) t marks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Expiration Date:

N/A Signed I

Date 21,c, Owner or Owners Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of H rtford, Connecticut, have inspected the components described in this Owners Report during the period of i-ill- 0' to I 0o5 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report In accordance with the requirements of ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

G o Commissions _/1 2

72 C

Al, Yx)

Inspector's Signature National Board, State. Providence. and Endorsements Date 04-030-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Florida Power and light Co.

Date Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet

2. Plant Address Turkey Point Plant Name 9760 SW 344 Street Florida City, FL 33035 Address Unit 11/1212004 1

of 2

3 WO#: 33016751-01 CR#:

NIA Repair Organizatlon, P.O. No, Job No, etc.

3. Work Performed by Florida Power and Light Co.

Name Type Code Symbol Stamp Authorization Number Expiration Date N/A NIA N/A 9760 SW 344 Street Florida City, FL 33035 Address

4. Identification of System:

Intake Cooling Water System #:

19 Quality Group C

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section XI Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components 1955 Edition, 19 98 Edition, N/A
Addenda, N/A 2000
Addenda, N/A Code Case Code Case ASME Corrected, Code Name of Name of Mfg Mfg Serial National Other Year Removed or Stamp Component Number Board Identification Built Installed Yes/No Pipe Elbow on Basket Strainer N/A N/A N/A BS-3-1403 N/A Installed N

backwash

7. Description of Work:

Replace corroded 4" elbow and bolting

8. Tests Conducted:

Hydrostatic:

N/A Other N/A Pneumatic N/A Nominal Operating Pressure X

Test Temperature 79 deg F 04-031-3 Pressure 15 psig

Sheet 2 of 2 FORM NIS-2 (Back) arks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Expiration Date:

NIA Signed Date 2 - 9S& 0 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartfor 1, Connecticut, have inspected the components described in this Owners Report during the period of 90 9

to

/- 5' 0.5 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Inspectors Signature Commissions *4 47?

C I-)__

National Board, State. Providence, and Endorsements Date

/- 5-°S 04-031-3

.vner

2. Plant
3. Work Performei FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Seciion Xl Florida Power and Light Co.

Date 1111212004 Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet I

of Address Turkev Point Plant Unit 3

2 CR#:

N/A d by Name 9760 SW 344 Street Florida City, FL 33035 WO#: 31017889-01 Address Florida Power and Light Co.

f Name 9760 SW 344 Street Florida City, FL 33035 Address

4. Identification of System:

Component Cooling Water System #:

3

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components Repair Organization, P.O. No. Job No., etc.

Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date N/A 0

Quality Group C

19 55 Edition, N/A

Addenda, N/A Code Case 1998 Edition.

2000

Addenda, N/A Code Case Name of Component Name of Mfg Mfg Serial National I NumberI Board Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No V

Pipe downstream of valve 3-711B N/A NIA N/A 13-711B NMA Installed N

7. Description of Work:

Install new pipe downstream of valve 3-711 B by welding

8. Tests Conducted:

Hydrostatic:

NIA Other N/A Pneumatic NIA Pressure 54 psig Nominal Operating Pressure X

Test Temperature 81 deg F 04032-3

Sheet 2 of 2 FORM NIS-2 (Back) e marks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp N/A Certificate of Authorization No.

NMA Expiration Date:

N/A Signed e

I S

&u-SA v Owner or Owiners Designee, Title Date J L b-° CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described in this Owners Report during the period of 10-.i -o4 to I - S-0 %

and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

/

Commissions

  • t 47

(

2 C2

, L_

Inspectors Signature National Board, State. Providence. and Endorsements Date 1-.5-0$5 0

04-032-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl

.wner Florida Power and Lighi Co.

Name 700 Universe Blvd. Juno Beach, FL 33408 Date Sheet Address Turkey Point Plant 11/13/2004 1

of 2

3 WO#: 33023249-01 CR#:

N/A Unit

2. Plant Name 9760 SW 344 Street Florida City, FL 33035 Address
3. Work Performed by Florida Power and Light Co.

Name 9760 SW 344 Street Florida City, FL 33035 Repair OrganIzatlon, P.O. No. Job No., etc.

N/A Type Code Symbol Stamp Authorization Number Expiration Date System #:

30 Quality Group N/A N/A Address Component Cooling Water

4. Identification of System:

C

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1955 Edition, N/A
Addenda, N/A CodeCase 1998 Edition, 2000
Addenda, N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Name of Component Name of Mfg Mfg Serial Number National Board Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No 4

4

+

+

+

V Pipe N/A N/A N/A CCW pipe at M004 N/A Corrected N

I I

I

7. Description of Work:

Perform Weld Buildup of Corroded pipe on CCW pipe at Penetration M004 to Aux Bld 10' Pipeway

8. Tests Conducted:

Hydrostatic:

NIA Other N/A Pneumatic N/A Nominal Operating Pressure N/A Test Temperature N/A deg F 04-033-3 Pressure N/A psig

Sheet 2 of 2 FORM NIS-2 (Back)

.emarks None CERTIFICATE OF C We certify that the statements made in the report are correct ani ASME Code,Section XI.

Type Code Symbol Stamp Certificate of Authorization No.

N/A Signed I 5 Un Owner or Owner's Design, Title 0

COMPLIANCE I this replacement conforms to the rules of the N/A Expiration Date:

NIA Date _

X J CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described in this Owners Report during the period of (O-ZI-o4 to I 05 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.

C Commissions 42 477 (4,C4 A/,J Inspectors Signature National Board, State, Providence, and Endorsements Date

/- A-

°0 04-033-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI w

ner Florida Power and Light Co.

Name 700 Universe Blvd. Juno Beach, FL 33408 Date Sheet Address Turkey Point Plant 11/1912004 1

of 2

3 WO#: 34011613-01 CR#:

N/A Unit

2. Plant Name 9760 SW 344 Street Florida City, FL 33035 Address Florida Power and Uoht Co.

Repair Orl

3. Work Performed by 9760
4. Identification of System:

Name SW 344 Street Florida City, FL 33035 Type Code Symbol Stamp Authorization Number Expiration Date System #:

64 Quality Group ianization, P.O. No. Job No., etc.

NIA NMA N/A B

Address Safety Injection Accumulator

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 55 Edition, 1998 Edition, NIA
Addenda, 2000
Addenda, NIA Code Case N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Mfg Serial Number Year Built Name of Component Name of Mfg National Board Other Identification Corrected, Removed or Installed ASME Code Stamp Yes/No
4.

4 4

4

4.

4 Relief Valve N/A NIA NMA I RV-3-858A N/A Corrected N

7. Description of Work:

Install new bolting material

8. Tests Conducted:

Hydrostatic:

NIA Other N/A Pneumatic N/A Pressure N/A psig Nominal Operating Pressure N/A Test Temperature N/A deg F 04-034-3

Sheet 2 of 2 FORM NIS-2 (Back)

.emarks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.

Type Code Symbol Stamp NIA Certificate of Authorization No.

N/A NExpiration Date:

NIA Signed Ow n, or TDate

_1 2_Lj-/

Owner or Owners Designee, Tite I

CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut. have inspected the components described in this Owners Report during the period of q-z,-o4 to I -

-o and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Inspectors Signature Commissions

/i! 477 (, A) iJ, X )

National Board, State. Providence. and Endorsements Date 04-034-3

.)wrler

2. Plant
3. Work Performec FORM NIS.2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Florida Power and Light Co.

Date 11/

Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet I

Address Turkey Point Plant Unit 1912004 of 2

3 01 CR#:

N/A d

I by Name 9760 SW 344 Street Florida City, FL 33035 Address Florida Power and Light Co.

WO#: 34011614-1 E

Name 9760 SW 344 Street Florida City, FL 33035 Address

4. Identification of System:

Safety Injection Accumulator System #:

6

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section XI Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components Name of Name of Mfg Mfg Serial National Component Number Board Idf Repair Organization, P.O. No, Job No., etc.

Type Code Symbol Stamp NIA Authorization Number N/A Expiration Date N/A 4

Quality Group B

1955 Edition, N/A

Addenda, NIA Code Case 19 98 Edition, 2000
Addenda, NIA Code Case Other rlification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No A41 141 Relief Valve N/A N/A N/A RV-3-858B N/A Corrected N
7. Description of Work:

Install new bolting material

8. Tests Conducted:

Hydrostatic:

NIA V

Other N/A Pneumatic N/A Pressure N/A psig Nominal Operating Pressure N/A Test Temperature N/A deg F 04-035-3

Sheet 2 of 2 FORM NIS-2 (Back) emarks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No.

NIA Expiration Date:

NMA Signed a

sv, L.0 Date IZ)2 6/

Owner or Owners Designee. Titl&

CERTIFICATE OF INSERVICE INSPECTION 1 the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut. have inspected the components described in this Owners Report during the period of 7-ZI1-04 to I °-c<

and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

_ /Commissions for 774 C 4 a

Inspectors Signature National Board. State, Providence, and Endorsements Date 04-035-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl

.)

ner Florida Power and Light Co.

Narne 700 Universe Blvd. Juno Beach, FL 33408 Date Sheet Address Turkey Point Plant 11119/2004 I

of 2

3 WO#: 33021720-01 CR#:

NIA Unit

2. Plant Name 9760 SW 344 Street Florida City, FL 33035 Address Florida Power and Liaht Co.

Repair Or

3. Work Performed by Name 9760 SW 344 Street Florida City, FL 33035 Type Code Symbol Stamp Authorization Number Expiration Date System #:

105 Quality Group ganization, P.O. No, Job No., etc.

NIA NMA NMA Address Supports and Hangers

4. Identification of System:

B

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xi Utilized for Repairs or Replacements 19 55 Edition, NIA
Addenda, NIA Code Case 19 98 Edition, 2000
Addenda, N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Name of Component Name of Mfg Mfg Serial Number National Board Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No Snubbe N/

Inst W

Snubber PSA 27081 N/A 3-1094 NMA Installed N

Snubber PSA 27092 N/A N/A N/A Removed N

7. Description of Work:

Install new snubber

6. Tests Conducted:

Hydrostatic:

N/A 0

Other NMA Pneumatic N/A Pressure NIA psig Nominal Operating Pressure N/A Test Temperature N/A deg F 04-036-3

Sheet 2 of 2 FORM NIS-2 (Back) emarks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replaced component conforms to the rules of the ASME Code, Section Xl.

Type Code Symbol Stamp NIA Certificate of Authorization No.

NIA Expiration Date:

NIA Signed I

Go v-i C--

Date 12IZB

.,q___

Owner or Owners Designee, Title

_J SI CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartf rd, Connecticut, havejnspectd the components described In this Owners Report during the period of _

to

/-A O

and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code.Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.

Commissions j2 Go S

2 Inspetors Signature National Board, State, Providence, and Endorsements Date

/A

(-o.<

04-036-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl

.wner Florida Power and Lighi Co.

Date Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet Address Turkey Point Plant 11/2012004 1

of 2

3 WO#: 34004417-01 CR#:

N/A Unit

2. Plant Name 9760 SW 344 Street Florida City, FL 33035 Address
3. Work Performed by Florida Power and Light Co.

Name 9760 SW 344 Street Florida City, FL 33035 Adds....

Repair Organization. P.O. No, Job No.. etc.

Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date N/A Component Cooling Water System #:

30 Quality Group

4. Identification of System:

C

5. (a) Applicable Construction Code ASME VIII (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 19 67 Edition, 19 98 Edition, NIA
Addenda, 2000
Addenda, N/A Code Case N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components National Board Name of Component Name of Mfg Mfg Serial Number Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No

+

+

t Heat Exchanger (3B CCW)

N/A N/A N/A 13E207B N/A Corrected N

7. Description of Work:

Install Helicoil and new bolting material in channel head of heat exchanger

8. Tests Conducted:

Hydrostatic:

N/A Other N/A Pneumatic N/A Pressure N/A psig Nominal Operating Pressure N/A Test Temperature N/A deg F 04-037-3

Sheet 2 of 2 FORM NIS-2 (Back) emarks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Expiration Date:

N/A Signed

_v-___

Date _ 1_1_/

Owner or Owners Designee, Title 1 I CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartfo d, Connecticut, have inspe ed the components described in this Owners Report during the period of _

_Z__-__

to

/-__-___

and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report In accordance with the requirements of ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

2'11 nsetors Signature Commissions X/ 47 7 7V, cog

)

National Board, State, Providence, and Endorsements Date I-F'-04<

04-037-3

) wner

2. Plant FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi Florida Power and Light Co.

Date 11122/2004 Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet I

of Address Turkey Point Plant Unit 3

2 CR#:

N/A Name 9760 SW 344 Street Florida City, FL 33035 WO#: 34008571-01 Address

3. Work Performed by Florida Power and Light Co.

Name 9760 SW 344 Street Florida City, FL 33035 Address

4. Identification of System:

Component Cooling Water System #:

3

5. (a) Applicable Construction Code ASME VilI (b) Applicable Edition of Section XI Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components Repair Organizatfon. P.O. No, Job No., etc.

Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date N/A 30 Quality Group C

1967 Edition, N/A

Addenda, N/A Code Case 1998 Edition, 2000
Addenda, N/A Code Case Mfg Serial Number National Board Name of Component Name of Mfg Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No t

t Heat Exchanger (3C CCW)

N/A N/A N/A 13E207C N/A Corrected N

7. Description of Work:

Install Helicoils and new bolting in damaged holes on Heat Exchanger

8. Tests Conducted:

Hydrostatic:

N/A 0

Other N/A Pneumatic N/A Pressure N/A psig Nominal Operating Pressure N/A Test Temperature N/A deg F 04-038-3

Sheet 2 of 2 FORM NIS-2 (Back) emarks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair conforms to the rules of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No.

NIA

-Expiration Date:

N/A Signed

=

yrP I S I Sp..

_lo,- Date j21ZSiocY 1

Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described in this Owners Report during the period of

/0-2404 to 2-1-05 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report In accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

I Commissions

/I'

$<72 47

, C Al, _J Inspectors ignature National Board, State. Providence, and Endorsements Date 2_/-Ox-04-038-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl wner Florida Power and Light Co.

Name ju~~~Nnc Eczh L2, Date Address Turkey Point Plant 11n23/2004 i

2 3

WO#: 31022850-01 CR#:

N/A Unit

2. Plant Name 9760 SW 344 Street Florida City, FL 33035 Address
3. Work Performed by Florida Power and Light Co.

Name 9760 SW 344 Street Florida City, FL 33035 Address Repair Organization P.O. No. Job No., etc.

Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date NMA

4. Identification of System:

Intake Cooling Water System #:

19 Quality Group C

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 55 Edition, 19 98 Edition, N/A
Addenda, NIA Code Case 2000
Addenda, N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Name of Mfg Name of Component Mfg Serial Number National Board Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No

+

4 Isolation Valve to Basket Strainer N/A 7-69579-3 N/A 3-50-349 N/A Removed N

Isolation Valve to basket NIA 550009D NIA 3-50-349 N/A Installed N

strainer D-2-2

7. Description of Work:

Install Spare and replace bolting material

8. Tests Conducted:

Hydrostatic:

N/A Other N/A Pneumatic N/A Nominal Operating Pressure X

Pressure 14 psig Test Temperature 81 deg F 04-039-3

Sheet 2 of 2 FORM NIS-2 (Back) marks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No.

NMA Expiration Date:

NIA Signed

_ _D _

Owner or Owner's Designee, Titfe Date I

CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, onnecticut, have inspeted the components described in this Owners Report during the period of 3-t-o to

/

or and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Inspectors Signature Commissions _/E

?2 L,2,1J4)

National Board, State, Providence, and Endorsements I-Date 04-039-3

-w ner

2. Plant
3. Work Performec FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI Florida Power and Light Co.

Date 11/23/2004 Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1

of Address Turkey Point Plant Unit 3

2 CR#:

N/A I by Name 9760 SW 344 Street Florida City, FL 33035 WO#: 30006362-01 Address Florida Power and Liqht Co.

r Name 9760 SW 344 Street Florida City, FL 33035 Address

4. Identification of System:

Intake Cooling Water System #:

1

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section XI Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components Repair Organization, P.O. No, Job No., etc.

Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date N/A 9

Quality Group C

19 55 Edition, N/A

Addenda, N/A Code Case 19 98 Edition, 2000
Addenda, N/A Code Case Mfg Serial Number Name of Component Name of Mfg National Board Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No 4

+

4

+

t 4

4 F

Isolation Valve N/A 550009D D-3-1 N/A 3-50-350 N/A Installed N

Isolation Valve N/A 50270-1-2 N/A 3-50-350 N/A Removed N

7. Description of Work:

Install New Valve and replace some bolting material

8. Tests Conducted:

Hydrostatic:

N/A Other N/A Pneumatic N/A Pressure 14 psig Nominal Operating Pressure X

Test Temperature 81 deg F 04-040-3

Sheet 2 of 2 FORM NIS-2 (Back) m arks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Expiration Date:

N/A Signed Date if zg~

L __

Owner or Owners Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described in this Owners Report during the period of 7-1L-O '

to

/-B-O5 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners Report In accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

/Commissions

'Z o

}

Inspector's Signature National Board, State, Providence, and Endorsements Date

/-

V

°<

04-040-3

ner

2. Plant
3. Work Performnei FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi Florida Power and Light Co.

Date l1/

Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet I

Address Ttirkev Pnint Plant Unit 124/2004 of 2

3

01 CR#

N/A d by Name 9760 SW 344 Street Florida City, FL 33035 Address Florida Power and Light Co.

WO#: 31007526-Narne 9760 SW 344 Street Florida City, FL 33035 Address

4. Identification of System:

Intake Cooling Water System #:

1

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xt Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components Repair Organization, P.O. No. Job No., etc.

Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date NMA 9

Quality Group C

19 55 Edition, NIA

Addenda, N/A Code Case 19 98 Edition, 2000
Addenda, N/A Code Case Name of Component Name of Mfg Mfg Serial National Number I Board Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No ICW Header Isolation Valve N/A 549514D D-1-1 N/A 3-50-307 N/A Installed N

ICW Header Isolation Valve N/A CI-11125-N/A 3-50-307 N/A Removed N

Support N/A N/A N/A Mark# M-196-1 N/A Corrected N

7. Description of Work:

Install new Valve and bolting material and modify support M-196-1

8. Tests Conducted:

Hydrostatic:

NIA 0

Other N/A Pneumatic N/A Pressure 22 psig Nominal Operating Pressure X

Test Temperature 84 deg F 04-041-3

Sheet 2 of 2 FORM NIS-2 (Back) emarks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.

Type Code Symbol Stamp NIA Certificate of Authorization No.

N/A Expiration Date:

N/A Signed I

=

51s' u

w..-

Date 12#lzIc:1 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I. the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartfor, Connecticut, have inspected the components described in this Owners Report during the period of y

to

/-

6 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.

14 ~.

~

Commissions _

477 f*,

3 /

National Board, State, Providence, and Endorsements "I

Inspector's Signature Date

/-0-1 04-041-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi

.vner Florida Power and Light Co.

Name 700 Universe Blvd. Juno Beach, FL 33408 Date Sheet Address Turkey Point Plant 11/24/2004 1

of 2

3 WO#: 31020694-01 CR#:

N/A Unit

2. Plant Name 9760 SW 344 Street Florida City, FL 33035 Address
3. Work Performed by Florida Power and Light Co.

Narne 9760 SW 344 Street Florida City, FL 33035 Repair Organization, P.O. No, Job No.. etc.

Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date N/A Address

4. Identification of System:

Residual Heat Removal System #:

50 Quality Group B

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 19 55 Edition, 19 98 Edition, N/A
Addenda, 2000
Addenda, N/A N/A Code Case Code Case
6. Identification of Components Repaired or Replaced and Replacement Components ASME Corrected, Code Name of Name of Mfg Mfg Serial National Other Year Removed or Stamp Component Number Board Identification Built Installed Yes/No Isolation Valve N/A N/A N/A 3-752A N/A Corrected N
7. Description of Work:

Install new corrosion resistant bolting material in valve

8. Tests Conducted:

Hydrostatic:

Other N/A Pneumatic N/A Nominal Operating Pressure N/A Test Temperalure N/A deg F 04-042-3 N/A Pressure N/A psig

Sheet 2 of 2 FORM NIS-2 (Back) emarks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Expiration Date:

N/A Signed Own-er or Date Signed

~

Owner or Owner's Designee, tite J"

CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspecgd the components described in this Owners Report during the period of 9-zr to

/-

Of v

and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report In accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions

/:

177 (#,7 Inspectors Signature National Board, State, Providence, and Endorsements Date

/-

Y' O<

04-042-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi

)w ner Florida Power and LIght Co.

Name 700 Universe Blvd. Juno Beach, FL 33408 Date Sheet Address Turkey Point Plant 11/2412004 1

of 2

3 WO#: 31020695-01 CR#:

NMA Repair Organization, P.O. No, Job No., etc.

Unit

2. Plant Narne 9760 SW 344 Street Florida City, FL 33035 Address
3. Work Performed by Florida Power and Light Co.

Name 9760 SW 344 Street Florida City, FL 33035 Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date N/A Address Residual Heat Removal

4. Identification of System:

System #:

50 Quality Group B

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 55 Edition, 19 98 Edition, NIA
Addenda, 2000
Addenda, N/A Code Case N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Name of Mfg Name of Component Mfg Serial Number National Board Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No AMENERI W

Isolation Valve N/A N/A N/A 3-752B N/A Corrected N

I

7. Description of Work:

Install new corrosion resistant bolting material

8. Tests Conducted:

Hydrostatic:

N/A Other N/A Pneumatic N/A Nominal Operating Pressure N/A Test Temperature N/A deg F 04-043-3 Pressure N/A psig

Sheet 2 of 2 FORM NIS-2 (Back) emarks None CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No.

NIA Expiration Date:

N/A Signed Date Owner or Owners Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected tJe components described in this Owners Report during the period of

-Zdg-Z.

to

/-_ _

_Z and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

'11 Inspectors Signature Commissions _. "?

17 C

J National Board, State. Providence. and Endorsements Date

/- ZZ-c'*

04-043-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi

.wner

2. Plant Florida Power and Light Co.

Name 700 Universe Blvd. Juno Beach, FL 33408 Date Sheet Unit 11/29/2004 1

of 2

Address Turkey Point Plant WO#: 34000317-01 CR#:

N/A Name 9760 SW 344 Street Florida City, FL 33035 Address

3. Work Performed by Florida Power and Light Co.

Name 9760 SW 344 Street Florida City, FL 33035 Repair Organization, P.O. No. Job No., etc.

Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date N/A Address Main Steam

4. Identification of System:

System #:

72 Quality Group B

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xi Utilized for Repairs or Replacements 19 55 Edition, 1998 Edition, N/A
Addenda, 2000
Addenda, N/A Code Case NIA Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Name of Mfg Name of i

Component Mfg Serial Number National Board Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No U

Bypass Valve N/A N/A N/A MOV-3-1400 N/A Corrected N

7. Description of Work:

Install new Bonnet and replace bonnet bolting

8. Tests Conducted:

Hydrostatic:

NIA Other NIA Pneumatic N/A Pressure __989 psig Nominal Operating Pressure X

Test Temperature 315 deg F 04-044-3

Sheet 2 of 2 FORM NIS-2 (Back)

.marks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Expiration Date:

NIA Signed

-SJ6o v

Owner or Owner's Designee, Title Date A SCALP; /

t CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Con ecticut, have inspected t-components described in this Owners Report during the period of

! W- ° F to 1-OS___

and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report In accordance with the requirements of ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

__g

___Commissions

/Z _7? (4 /,

Inspector's Signature National Board. State, Providence, and Endorsements Date

/_

,im 04-044-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl w.ner Florida Power and Lighi Co.

Date Name 700 Universe Blvd. Juno Beach, FL 33408 Address Turkey Point Plant 12/1/2004 1

of 2

Sheet Unit

2. Plant Name 9760 SW 344 Street Florida City, FL 33035 3

WO#: 33021534-02 CR#:

N/A Repair Organization, P.O. No, Job No., etc.

Address

3. Work Performed by Florida Power and Light Co.

Name 9760 SW 344 Street Florida City, FL 33035 Type Code Symbol Stamp Authorization Number Expiration Date N/A N/A NMA Address

4. Identification of System:

Main Steam System #:

72 Quality Group B

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 19 55 Edition, 1998 Edition, N/A
Addenda, 2000
Addenda, N/A N/A Code Case Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Name of Component Name of Mfg Mfg Serial Number National Board Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No Bypass Valve N/A MOV-3-1401 N/A Corrected N/A N/A N

N

7. Description of Work:

Install new bonnet, install helicoil and replace bonnet bolting

8. Tests Conducted:

Hydrostatic:

N/A 0

Other N/A Pneumatic N/A Nominal Operating Pressure X

Pressure 985 psig Test Temperature 315 deg F 04-045-3

Sheet 2 of 2 FORM NIS-2 (Back) eemarks None CERTIFICATE OF C We certify that the statements made in the report are correct anc ASME Code, Section Xl.

Type Code Symbol Stamp Certificate of Authorization No.

N/A Signed

~

Owner or Owner's Designee, Title CERTIFICATE OF INSERT 1, the undersigned, holding a valid commission issued by the Nat the state of Florida and employed by HSBCT of Hartford. Conne Owners Report during the period of fo-Z4-04 t

and state that to the best of my knowledge and belief, the Owner measures described in this Owners Report in accordance with tI By signing this certificate neither the Inspector nor his employer i concerning the examinations and corrective measures described Inspector nor his employer shall be liable in any manner for any I kind arising from or connected with this inspection.

Inspectors Signature Date

/-_

0 COMPLIANCE d this replacement conforms to the rules of the N/A Expiration Date:

N/A

_< _V x ov Date I2 Do iVICE INSPECTION ional Board of Boiler and Pressure Vessel Inspectors and cticut, have inspected the components described in this to

/-

r has performed examinations and taken corrective ie requirements of ASME Code, Section Xl.

makes any warranty, expressed or implied, in this Owners' Report. Furthermore, neither the personal injury or property damage or a loss of any Commissions

/

1e7 (o C,

National Board, State, Providence, and Endorsements 04-045-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi wner Florida Power and Light Co.

Date Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet

2. Plant Address Turkey Point Plant Name 9760 SW 344 Street Florida City, FL 33035 Unit 11129/2004 1

of 2

3 WO#: 34000316-01 CR#:

N/A Repair Organization. P.O. No, Job No., etc.

Address Florida Power and Light Co.

3. Work Performed by Name 9760 SW 344 Street Florida City, FL 33035 Address Type Code Symbol Stamp Authorization Number Expiration Date N/A N/A N/A
4. Identification of System:

Main Steam

-System #:

72 Quality Group B

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 55 Edition, N/A
Addenda, 19 98 Edition, 2000
Addenda, N/A Code Case N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components ASME Corrected, Code Name of Name of Mfg Mfg Serial National Other Year Removed or Stamp Component Number Board Identification Built Installed Yes/No Bypass Valve NIA NIA N/A MOV-3-1402 N/A Corrected N

N

7. Description of Work:

Install new valve bonnet installed helicoils and replace bolting material

8. Tests Conducted:

Hydrostatic:

0 Other N/A Pneumatic NIA N/A Nominal Operating Pressure X

Test Temperature 315 deg F 04-046-3 Pressure 980 psig

Sheet 2 of 2 FORM NIS-2 (Back) e marks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code,Section XI.

Type Code Symbol Stamp NIA Certificate of Authorization No.

NMA Expiration Date:

N/A Signed OrR Date

_J_

Own-or Owners Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford. Connecticut. have inspected the components described in this Owners Report during the period of SO-$4-V'4' to

/- r-o S and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Inspectors Signature Commissions _/

<7 ', Ck

//i ZY National Board, State. Providence, and Endorsements Date 1-g-0'5 04-046-3

er

2. Plant
3. Work Performec FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi Florida Power and Light Co.

Date 11/

Nanme 700 Universe Blvd. Juno Beach, FL 33408 Sheet I

Address Turkey Point Plant Unit 29/2004 of 2

3 01 CR#:

N/A d by Name 9760 SW 344 Street Florida City, FL 33035 Address Florida Power and Light Co.

WO#: 31005377-Narme 9760 SW 344 Street Florida City, FL 33035 Address

4. Identification of System:

Safety Injection System #:

E

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xi Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components Repair Organization, P.O. No. Job No.. etc.

Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date NWA 62 Quality Group A

19 55 Edition, N/A

Addenda, N/A Code Case 19 98 Edition, 2000
Addenda, NIA Code Case Mfg Serial Number Name of Component Name of Mfg National Board Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No mu I

-1 F

Check Valve N/A N/A N/A 3-873A N/A Installed N

Pipe N/A N/A N/A SC# 0030938-1 N/A Installed N

7. Description of Work:

Install new valve and piping by welding

8. Tests Conducted:

Hydrostatic:

N/A 0

Other N/A Pneumatic NIA Pressure 1510 psig Nominal Operating Pressure X

Test Temperature 67 deg F 04-047-3

Sheet 2 of 2 FORM NIS-2 (Back)

.emarks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Expiration Date:

NIA Signed

, L-s Ab, Date Lb Owner or Owners Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described in'this Owners Report during the period of

/ 6-0

-f to

/-ZN and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.

I-Inspectors Signature Commissions Jkf ?

C, A/,>)

National Board, State. Providence, and Endorsements

/-&r - of, Date 04-047-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi Florida Power and Light Co.

Date 12 Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1

Address Turkey Point Plant Unit 2132004 of 2

3 01 CR#:

N/A vI 0l-n

3. Work Performed by Name 9760 SW 344 Street Florida City, FL 33035 Address Florida Power and Light Co.

WO#: 31005378-l Name 3760 SW 344 Street Florida City. FL 33035 Address

4. Identification of System:

Safety Injection

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacerr
6. Identification of Components Repaired or Replaced and Replacemen Repair Organization, P.O. No, Job No., etc.

Type Code Symbol Stamp N/A Authorization Number NIA Expiration Date N/A System #:

62 Quality Group A

19 55 Edition, N/A

Addenda, N/A Code Case ients 1998 Edition, 2000
Addenda, NIA Code Case t Components Name of Component Name of Mfg Mfg Serial Number National Board Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No mu 1

F Check Valve N/A N/A NIA 3-873B N/A Installed N

Pipe NIA N/A N/A SC# 0030938-1 N/A Installed N

7. Description of Work:

Install by welding new valve and piping

8. Tests Conducted:

Hydrostatic:

NIA 0

Other N/A Pneumatic NIA Pressure 1510 psig Nominal Operating Pressure X

Test Temperature 67 deg F 04.048-3

Sheet 2 of 2 FORM NIS-2 (Back)

O emarks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp N/A Certificate of Authorization No.

NIA Expiration Date:

N/A Signed

orOwner, IDevsignee T le Date Owner or Owners Designee, T Ire CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described in this Owners Report during the period of _____-/Y__0_

to

/- f'-5 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners Report in accordance with the requirements of ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

c_______.

Commissions Inspector's Signature National Board. State, Providence. and Endorsements Date

/4

°S 04-048-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI vner Florida Power and Light Co.

Date Name 700 Universe Blvd. Juno Beach, FL 33408 Address Turkey Point Plant Sheet 11129/2004 1

of 2

3 WO#: 34000703-01 CR#:

N/A Repair Organization. P.O. No, Job No., etc.

Unit

2. Plant Name 9760 SW 344 Street Florida City, FL 33035 Address
3. Work Performed by Florida Power and Light Co.

Name 9760 SW 344 Street Florida City, FL 33035 Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date N/A Address Auxiliary Feedwater

4. Identification of System:

System #:

75 Quality Group C

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1955 Edition, N/A
Addenda, 1998 Edition, 2000
Addenda, NMA Code Case N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components ASME Corrected, Code Name of Name of Mfg Mfg Serial National Other Year Removed or Stamp Component Number Board Identification Built Installed Yes/No Check Valve N/A N/A N/A 3-20-401 NIA Installed N
7. Description of Work:

Install new Valve and replace bolting material

8. Tests Conducted:

Hydrostatic:

N/A Other N/a Pneumatic N/A Nominal Operating Pressure X

Pressure 20 psig Test Temperature 74 deg F 04-049-3

Sheet 2 of 2 FORM NIS-2 (Back)

.emarks none CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No.

NMA Expiration Date:

N/A Signed Date JzzI s.1-0-1 --

Owner or Owner's Designee, Ttle CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described in this Owners Report during the period of lO-Z- 0 4 to I1-Z -0 5 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.

Inspector's Signature Commissions 4 77 (c, AI i, Aa)

National Board, State, Providence, and Endorsements Date 04-049-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl

. wner

2. Plant Florida Power and Light Co.

Namo 700 Universe Blvd. Juno Beach, FL 33408 Date Sheet Address 11130/2004 1

of 2

3 WO#: 33005126-01 CR#:

N/A Repaur Organization, P.O. No, Job No.. etc.

Turkey Point Plant Narne 9760 SW 344 Street Florida City, FL 33035 Address Unit

3. Work Performed by Florida Power and Light Co.

Nare Type Code Symbol Stamp Authorization Number Expiration Date N/A N/A 9760 SW 344 Street Florida City, FL 33035 Address N/A

4. Identification of System:

Safety Injection System #:

62 Quality Group A

5. (a) Applicable Construction Code B31.1 19 55 Edition, N/A
Addenda, 19 98 Edition, 2000
Addenda, N/A Code Case N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components Name of Component Name of Mfg Mfg Serial Number National Board Other Identification Year Built Corrected, Removed or '

Installed ASME Code Stamp Yes/No N/A N/A 13-873C W

Check Valve NIA N/A N/A13-873C N/A Corrected N

7. Description of Work:

Reweld bonnet seal weld

8. Tests Conducted:

Hydrostatic:

N/A Pneumatic N/A Nominal Operating Pressure N/A Other N/A Pressure N/A psig Test Temperature N/A deg F 04-050-3

Sheet 2 of 2 FORM NIS-2 (Back) marks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp NIA Certificate of Authorization No.

N/A Expiration Date:

N/A Signed s

o

_I_

Date Owner or Owner's Designee, Ti le CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described in this Owners Report during the period of

/D Zero to

/--r'-

5' and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Inspectors Signature Commissions C

Al)

National Board, State, Providen e, and Endorsements Date

/- d&-0o *-

04-050-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Owner Florida Power and Light Co.

Name 700 Universe Blvd. Juno Beach, FL 33408 Date Sheet Address Turkey Point Plant 11/30/2004 1

of 2

3 WO#: 31007667-01 CR#:

N/A Unit

2. Plant Name 9760 SW 344 Street Florida City, FL 33035 Address
3. Work Performed by Florida Power and Light Co.

Narne 9760 SW 344 Street Florida City, FL 33035 Repair Organization, P.O. No, Job No., etc.

Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date N/A Quality Group C

Address

4. Identification of System:

Intake Cooling Water System #:

1 L_

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xi Utilized for Repairs or Replacements 19 55 Edition, 1998 Edition, N/A
Addenda, 2000
Addenda, NIA N/A Code Case Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Name of Mfg Name of Component Mfg Serial Number Year Built National Board Other Identification Corrected, Removed or Installed ASME Code Stamp Yes/No 4

+

Isolation Valve N/A N/A N/A 3-50409 N/A Installed N

Check Valve N/A N/A N/A 3-50-410 N/A Installed N

7. Description of Work:

Install new valves

8. Tests Conducted:

Hydrostatic:

NIA 0

Other N/A Pneumatic N/A Nominal Operating Pressure X

Pressure 23 psig Test Temperature 74 deg F 04-051-3

Sheet 2 of 2 FORM NIS-2 (Back) marks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No.

NIA Expiration Date:

N/A Signed DV; Date 1 21.L D-r Owner or Owners Designee. Titd CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Harford Connecticut, have inspect5the components described in this Owners Report during the period of 731-o to 1-ZZ-O-.

and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report In accordance with the requirements of ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied.

concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Inspector's Signature Commissions A

7 National Board, State. Providence, and Endorsements Date 04-051-3

wner

2. Plant
3. Work Performei FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Florida Power and Light Co.

Date 11/

Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1

Address Turkey Point Plant Unit 30/2004 of 2

3 01 CR#:

N/A d by Name 1760 SW 344 Street Florida City, FL 33035 WO#: 33023667-l Address Florida Power and Liqht Co.

i Name 9760 SW 344 Street Florida City. FL 33035 Address

4. Identification of System:

CVCS Charging and Letdown System #:

4

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section XI Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components Repair Organization, P.O. No. Job No, etc.

Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date N/A 7

Quality Group B

19 55 Edition, N/A

Addenda, NIA Code Case 19 98 Edition, 2000
Addenda, N/A Code Case Name of Component Name of Mfg Mfg Serial INumber National Board Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No 4-4 F

I F

+

N/A Corrected N

Relief Valve N/A N/A N/A RV-3-382 NMA Corrected N

4-

7. Description of Work:

Install new bolting material

8. Tests Conducted:

Hydrostatic:

N/A Other N/A Pneumatic N/A Pressure N/A psig Nominal Operating Pressure N/A Test Temperature N/A deg F 04-052-3

Sheet 2 of 2 FORM NIS-2 (Back)

.marks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code.Section XI.

Type Code Symbol Stamp NIA Certificate of Authorization No.

N/A Expiration Date:

N/A Signed I 51 Date JJ42SJ.8 Owner or Owners Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartf Connecticut have inspected the components described in this Owners Report during the period of t-io o

/-_

and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions 7A z

4 Inspectors Signature National Board, State, Providence, and Endorsements Date

/,

Flo, 04-052-3

.v er

2. Plant
3. Work Performe, FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI Florida Power and Light Co.

Date 11/

Narne 700 Universe Blvd. Juno Beach, FL 33408 Sheet I

Address Turkey Point Plant Unit 29/2004 of 2

3 01 CR#:

NMA d by Name 9760 SW 344 Street Florida City, FL 33035 WO#: 34015594-l Address Florida Power and Light Co.

Nare 9760 SW 344 Street Florida City, FL 33035 Address

4. Identification of System:

Main Steam System #:

7

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section XI Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components Repair Organization, P.O. No. Job No., etc.

Type Code Symbol Stamp NMA Authorization Number N/A Expiration Date N/A 2

Quality Group B

19 55 Edition, N/A

Addenda, N/A Code Case 1998 Edition, 2000
Addenda, N/A Code Case U

ASME Corrected, Code Name of Name of Mfg Mfg Serial National Other Year Removed or Stamp Component Number Board Identification Built Installed Yes/No Check Valve N/A N/A N/A 3-10-319 N/A Corrected N

7. Description of Work:

Seal weld new valve seat in valve

8. Tests Conducted:

Hydrostatic:

N/A Other N/A Pneumatic N/A Pressure N/A psig Nominal Operating Pressure N/A Test Temperature N/A deg F 04-053-3

Sheet 2 of 2 FORM NIS-2 (Back) emarks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Expiration Date:

NIA Signed I

Date l23 2l

__l Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION

1. the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described in this Owners Report during the period of to

/^

A"-OS and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report In accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, conceming the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions PJ j,

/

/)

Inspectors Signature Nabonal Board, State, Providence. and Endorsements Date

/-Ad-05 04-053-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi orvner Florida Power and Light Co.

Name 700 Universe Blvd. Juno Beach, FL 33408 Date Sheet Address Turkey Point Plant 12/2/2004 1

of 2

3 WO#: 33010553-01 CR#:

Unit

2. Plant Name 9760 SW 344 Street Florida City, FL 33035 Address Florida Power and Light Co.
3. Work Performed by Name Repair Organization, P.O. No, Job No.. etc.

Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date N/A 9760 SW 344 Street Florida City, FL 33035 Address Reactor Coolant

4. Identification of System:

System #:

41 Quality Group a

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xi Utilized for Repairs or Replacements 19 55 Edition, 19 98 Edition.

N/A

Addenda, N/A Code Case 2000
Addenda, N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components I

ASME Corrected, Code Name of Name of Mfg Mfg Serial National Other Year Removed or Stamp Component Number Board Identification Built Installed Yes/No Pressurerizer Safety Valve N/A H51249-N/A RV-3-551 C N/A Removed N

1581 Pressurizer Safety Valve N/A N69877-N/A RV-3-551C N/A Installed N

01-0009

7. Description of Work:

Install Spare Valve and replace bolting material

8. Tests Conducted:

Hydrostatic:

N/A Other N/A Pneumatic N/A Pressure 2235 psig Nominal Operating Pressure X

Test Temperature 547 deg F 04-054-3

Sheet 2 of 2 FORM NIS-2 (Back) e marks None CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.

Type Code Symbol Stamp NIA Certificate of Authorization No.

NIA Expiration Date:

N/A Signed IS1 s I L

S ov Date 171t4&y-Owner or Owners Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford. Connecticut, have inspected e components described In this Owners Report during the period of 5S-Y o4t to

/-_

_at and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report In accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

__Commissions Ad Inspectors Signature National Board, State, Providence, and Endorsements Date

/-

- 0 04-054-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl wner Florida Power and Light Co.

Name 700 Universe Blvd. Juno Beach, FL 33408 Date Sheet Address Turkey Point Plant Unit 12/2/2004 1

of 2

3 WO#: 33010541-01 CR#:

NIA Repair Organization, P.O. No. Job No., etc.

KICA

2. Plant Name 9760 SW 344 Street Florida City, FL 33035 Address Florida Power and Light Co.
3. Work Performed by -

9760

4. Identification of System:

Name SW 344 Street Florida City, FL 33035 Address Reactor Coolant Type Code Symbol Stamp Authorization Number Expiration Date System #:

41 Quality Group I'ill N/A NIA A

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 55 Edition, 19 98 Edition, NIA
Addenda, 2000
Addenda, N/A Code Case N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Mfg Serial Number Name of Component Name of Mfg National Board Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No I

4 4

+

U Pressurizer Safety Valve N/A N69877-01-1580 N/A RV-3-551 B NIA Installed N

Pressurizer Safety Valve N/A N69877-N/A RV-3-551 B NMA Removed N

00-0004

7. Description of Work:

Install Spare Valve and replace bolting material

8. Tests Conducted:

Hydrostatic:

N/A Other N/A Pneumatic N/A Pressure 2235 psig Nominal Operating Pressure X

Test Temperature 547 deg F 04-055-3

Sheet 2 of 2 FORM NIS-2 (Back)

.marks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code,Section XI.

Type Code Symbol Stamp NIA Certificate of Authorization No.

NWA Expiration Date:

NIA Signed 1

e'?-

Date 2

Owner or Owner's Designee, itle CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford. Connecticut, have inspcted the components described In this Owners Report during the period of 5_5_04_ _

to

/-

Q and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Inspector's Signature Commissions,/i 4'77 41, C, &r National Board. State, Providence, and Endorsements Date 04-055-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Florida Power and Lighi Co.

Name 700 Universe Blvd. Juno Beach, FL 33408 Date Sheet Address Turkey Point Plant 12/3/2004 1

of 2

3 WO#: 32018647-01 CR#:

N/A Repair Organization, P.O. No, Job No., etc.

Unit

2. Plant Name 9760 SW 344 Street Florida City, FL 33035 Address
3. Work Performed by Florida Power and Light Co.

Name 9760 SW 344 Street Florida City, FL 33035 Type Code Symbol Stamp Authorization Number Expiration Date N/A N/A N/A Address

4. Identification of System:

CVCS Charging and Letdown System #:

47 Quality Group B

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 19 55 Edition, 19 98 Edition, N/A
Addenda, 2000
Addenda, N/A N/A Code Case Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Name of Component Name of Mfg Mfg Serial Number National Board Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No Isolation Valve N/A N/A N/A 3-293B N/A Installed N

Pipe N/A N/A N/A SC# 0030938-1 N/A Installed N

7. Description of Work:

Install by welding new valve and section of new pipe

8. Tests Conducted:

Hydrostatic:

N/A 0

Other N/A Pneumatic N/A Nominal Operating Pressure X

Pressure 2314 psig Test Temperature 110 deg F 04-056-3

Sheet 2 of 2 FORM NIS-2 (Back) marks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Expiration Date:

N/A Signed Date I

z.14osi Owner or Owners Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1 the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have insp"Id the components described in this Owners Report during the period of 4-Zl7-o5 to

_- /- oA and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report In accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied.

concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

_Commissions A /77 (j

af Inspectors Signature National Board, State. Providence. and Endorsements Date 04-056-3

or ner

2. Plant
3. Work Performec FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Florida Power and Light Co.

Date 11/

Namw 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1

Address Turkey Point Plant Unit 29/2004 of 2

3 01 CR#:

NMA I by Name

)760 SW 344 Street Florida City, FL 33035 Address Florida Power and Light Co.

WO#: 30009289-4 II Name D760 SW 344 Street Florida City, FL 33035 Address

4. Identification of System:

Main Steam System #:

7

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section XI Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components Repair Organization, P.O. No, Job No., etc.

Type Code Symbol Stamp N/A Authorization Number NMA Expiration Date N/A 72 Quality Group B

1955 Edition, N/A

Addenda, N/A Code Case 1998 Edition, 2000
Addenda, N/A Code Case ASME Corrected, Code Name of Name of Mfg Mfg Serial National Other Year Removed or Stamp Component Number Board Identification Built Installed Yes/No Control Valve N/A N/A N/A CV-3-1608 N/A Corrected N
7. Description of Work:

Replace valve seat and seal weld in valve

8. Tests Conducted:

Hydrostatic:

N/A 0

Other N/A Pneumatic N/A Pressure N/A psig Nominal Operating Pressure N/A Test Temperature N/A deg F 04057-3

Sheet 2 of 2 FORM NIS-2 (Back) marks None CERTIFICATE OF C We certify that the statements made in the report are correct an(

ASME Code, Section Xi.

Type Code Symbol Stamp Certificate of Authorization No.

N/A Signed Owner or Owners Designee. Tifle CERTIFICATE OF INSER'

1. the undersigned, holding a valid commission issued by the Nal the state of Florida and employed by HSBCT of Hartford. C nne Owners Report during the period of

/0- 91-0 z I

and state that to the best of my knowledge and belief, the Owne measures described in this Owners' Report in accordance with I.

By signing this certificate neither the Inspector nor his employer concerning the examinations and corrective measures described Inspector nor his employer shall be liable in any manner for any kind arising from or connected with this inspection.

Inspectoes Signature Date

/

0 COMPLIANCE I this replacement conforms to the rules of the N/A Expiration Date:

N/A

______t Date llIl j2l Oy VICE INSPECTION Jional Board of Boiler and Pressure Vessel Inspectors and cticut, have inspected the components described in this to

/-_-__ _

_J-r has performed examinations and taken corrective he requirements of ASME Code, Section Xl.

makes any warranty, expressed or implied, I in this Owners' Report. Furthermore, neither the personal injury or property damage or a loss of any Commissions

/e

`7f7?2 C, /

-)

National Board, State, Providence, and Endorsements 04-057-3

wner

2. Plant FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI Florida Power and Light Co.

Date 12 Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1

Address Turkey Point Plant Unit

/3/2004 of 2

3 01 CR#:

NIA Name 9760 SW 344 Street Florida City, FL 33035 Address

3. Work Performed by Florida Power and Light Co.

Name 9760 SW 344 Street Florida City, FL 33035 WO#: 33022084-Address

4. Identification of System:

main feedwater System #:

7

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section XI Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components Repair Organlzation, P.O. No. Job No., etc.

Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date N/A 4

Quality Group B

1955 Edition, NIA

Addenda, N/A Code Case 1998 Edition, 2000
Addenda, NIA Code Case Corrected, Removed or Installed ASME Code Stamp Yes/No Name of Component Name of Mfg Mfg Serial INational Number Board Other Identification Year Built

+

+

4 4

V Flow Control Valve on S/G A Main Feed N/A NMA N/A I FCV-3478 N/A Corrected N

7. Description of Work:

Replaced bolting material on valve

8. Tests Conducted:

Hydrostatic:

N/A Other N/A Pneumatic N/A Pressure N/A psig Nominal Operating Pressure N/A Test Temperature N/A deg F 04-058-3

Sheet 2 of 2 FORM NIS-2 (Back) marks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Expiration Date:

N/A Signed Si Is Date Owner or wners Designee. Titl CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Ponnecticut, have inspected the components described in this Owners Report during the period of

/V-

-°OSt to

/-Z

-o and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.

Commissions 7a6-17 (c, b7: -XJ)

Inspector's Signature National Board, State, Providence, and Endorsements Date

/-r-e S_ _

04-058-3

.wn er

2. Plant
3. Work Performec FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi Florida Power and Light Co.

Date 12 Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1

Address Turkey Point Plant Unit

/2/2004 of 2

3 01 CR#:

N/A dby Nann 1760 SW 344 Street Florida City, FL 33035 Address Florida Power and Light Co.

WO#: 34019617-Name 9760 SW 344 Street Florida City, FL 33035 Address

4. Identification of System:

Main Feedwater System #:

7

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components Repair Organization P... No. Job No.. etc.

Type Code Symbol Stamp N/A Authorization Number NMA Expiration Date NMA 4

Quality Group B

19 55 Edition, N/A

Addenda, N/A Code Case 19 98 Edition, 2000
Addenda, NIA Code Case Name of Mfg Name of Component Mfg Serial National Number I Board Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No

-1 t

1-Flow Control Valve on S/G A bypass FW N/A N/A N/A FCV-3-479 N/A Corrected N

7. Description of Work:

Tack weld of cage lock

8. Tests Conducted:

Hydrostatic:

NIA Other N/A Pneumatic N/A Pressure NIA psig Nominal Operating Pressure N/A Test Temperature N/A deg F 04-059-3

Sheet 2 of 2 FORM NIS-2 (Back)

  • marks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Expiration Date:

N/A Signed i

7 5

Date I lI Owner or Owners Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartforg, Connecticut, have inspected -he components described in this Owners Report during the period of to

/_-

gt and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code.Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

4 Commissions 7

6 Inspector's Signature National Board, State, Providence. and Endorsements Date

/-

04-059-3

wner

2. Plant
3. Work Performec FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI Florida Power and Light Co.

Date 12 Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet 1

Address Turkey Point Plant Unit 2312004 of 2

3 01 CR#:

N/A d by Name 9760 SW 344 Street Florida City, FL 33035 WO#: 34018385-i Address Florida Power and Light Co.

i Name 9760 SW 344 Street Florida City, FL 33035 Address

4. Identification of System:

Reactor Coolant

5. (a) Applicable Construction Code ASME IlIl (b) Applicable Edition of Section Xl Utilized for Repairs or Replacen
6. Identification of Components Repaired or Replaced and Replacemer Repair Organization, P.O. No, Job No, etc.

Type Code Symbol Stamp N/A Authorization Number NMA Expiration Date N/A

-System #:

41 Quality Group A

1965 Edition, N/A

Addenda, N/A Code Case nents 19 98 Edition, 2000
Addenda, N/A Code Case it Components Name of Component Year Built Name of Mfg Mfg Serial National Number Board Other Identification Corrected, Removed or Installed ASME Code Stamp Yes/No

-

4 4

4 4

+

F Pressurizer NMA NMA NMA l3T200 NMA Corrected N

7. Description of Work:

Replaced bolting material

8. Tests Conducted:

Hydrostatic:

N/A 0

Other N/A Pneumatic N/A Pressure N/A psig Nominal Operating Pressure N/A Test Temperature N/A deg F 04-060-3

Sheet 2 of 2 FORM NIS-2 (Back) marks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No.

NMA Expiration Date:

NIA Signed I

2S

i Owner or Owner's Designedu Title Date l

CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission Issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Ponnecticut, have inspected the components described in this Owners Report during the period of

//-/-

1 ' 4 to X- 0 5 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report In accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions AZ 7

(/

C Inspector's Signature National Board, State. Providence, and Endorsements Date 2-1o6 04-060-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl

  1. r ner
2. Plant Florida Power and Light Co.

Name 700 Universe Blvd. Juno Beach, FL 33408 Address Turkey Point Plant Name 9760 SW 344 Street Florida City, FL 33035 Date Sheet Unit 12/3/2004 1

of 2

3 WO#: 33010523-01 CR#:

NIA Repair Organization, P.O. No, Job No.. etc.

Address

3. Work Performed by Florida Power and Light Co.

Name 9760 SW 344 Street Florida City, FL 33035 Type Code Symbol Authorization Numt Expiration Date System #:

41 Quality Group Stamp N/A

,er N/A N/A A

Address Reactor Coolant

4. Identification of System:
5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1955 Edition, NIA
Addenda, 1998 Edition, 2000
Addenda, N/A Code Case N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components ASME Corrected, Code Name of Name of Mfg Mfg Serial National Other Year Removed or Stamp Component Number Board Identification Built Installed Yes/No Pressurizer Safety Valve N/A N69877-N/A RV-3-551A N/A Installed N

01-0008 Pressurizer Safety Valve NMA H51249-N/A RV-3-551A N/A Removed N

1579

7. Description of Work:

Installed Spare Valve and replaced bolting material

8. Tests Conducted:

Hydrostatic:

N/A 0

Other N/A Pneumatic N/A Nominal Operating Pressure X

Test Temperature 547 deg F 04-061-3 Pressure 2235 psig

Sheet 2 of 2 FORM NIS-2 (Back) marks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xl.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Expiration Date:

N/A Signed Date V__

Owner or Owner's Designee. Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described in this Owners Report during the period of 5-So-4 to

/-r-e74.

and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

_ <Commissions

/.

4v77 C AW e7 Inspectors Signature National Board, State, Providence. and Endorsements Date

/-

0°5 04-061-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl or ner Florida Power and Light Co.

Date Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet

2. Plant Address Turkey Point Plant Name 9760 SW 344 Street Florida City. FL 33035 Address Unit 1213/2004 1

of 2

3 WO#: 33021531-01 CR#:

NIA

3. Work Performed by Florida Power and Light Co.

Name Repair Organization, P.O. No, Job No, etc.

Type Code Symbol Stamp NIA Authorization Number N/A Expiration Date N/A 9760 SW 344 Street Florida City, FL 33035 Address

4. Identification of System:

Intake Cooling Water System #:

19 Quality Group C

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 55 Edition, N/A
Addenda, 19 98 Edition, 2000
Addenda, NIA Code Case N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components A111111 ASME Corrected, Code Name of Name of Mfg Mfg Serial National Other Year Removed or Stamp I

Component Number Board Identification Built Installed Yes/No Isolation Valve N/A NIA NIA 3-50-322 N/A Corrected N

7. Description of Work:

Replace bolting at valve

8. Tests Conducted:

Hydrostatic:

NIA Other NIA Pneumatic NIA Nominal Operating Pressure NIA Test Temperature N/A deg F 04-062-3 Pressure N/A psig

Sheet 2 of 2 FORM NIS-2 (Back) marks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Expiration Date:

N/A Signed O

r&7 AveS___

Date Owner or Owner's Designee, Ti e CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecicut, have inspeT d the components described in this Owners Report during the period of _

to

/- J-Ode and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this Inspection.

Commissions Inspectors Signature National Board, State, Providence. and Endorsements Date

/ 2r° 5 04-062-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Florida Power and Light Co.

Date 1I1 Narne 700 Universe Blvd. Juno Beach, FL 33408 Sheet I

Address Turkey Point Plant Unit n er

2. Plant
3. Work Performec 29/204 of 2

3 01 CR#:

N/A i by Name 9760 SW 344 Street Florida City, FL 33035 WO#: 34017723-Address Florida Power and Light Co.

Name 9760 SW 344 Street Florida City, FL 33035 Address

4. Identification of System:

CVCS Charging and Letdown System #:

4

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components Repair Organization, P.O. No, Job No., etc.

Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date N/A 7

Quality Group A

19 55 Edition, N/A

Addenda, N/A Code Case 19 98 Edition, 2000
Addenda, N/A Code Case U

ASME Corrected, Code Name of Name of Mfg Mfg Serial National Other Year Removed or Stamp Component Number Board Identification Built Installed Yes/No Component Support N/A N/A N/A 3-VCH-1 15 N/A Installed N

7. Description of Work:

Install new support

8. Tests Conducted:

Hydrostatic:

N/A 0

Other N/A Pneumatic N/A Pressure N/A psig Nominal Operating Pressure N/A Test Temperature N/A deg F 04-063-3

Sheet 2 of 2 FORM NIS-2 (Back) marks None CERTIFICATE OF C We certify that the statements made In the report are correct ant ASME Code, Section Xl.

Type Code Symbol Stamp Certificate of Authorization No.

N/A Signed J$ I SUpc Owner or Owner's Designee, Tine CERTIFICATE OF INSERI 1, the undersigned, holding a valid commission issued by the Nat the state of Florida and employed by HSBCT of Hartford, Connei Owners Report during the period of O

o

-Z/-4' and state that to the best of my knowledge and belief, the Ownei measures described in this Owners' Report in accordance with t1 By signing this certificate neither the Inspector nor his employer i concerning the examinations and corrective measures described Inspector nor his employer shall be liable In any manner for any I kind arising from or connected with this inspection.

Inspecor's Signature Date

/-

il-0 COMPLIANCE I this replacement conforms to the rules of the NIA Expiration Date:

N/A GY Date 1 2 -[1 5jay tVICE INSPECTION

ional Board of Boiler and Pressure Vessel Inspectors and
ticut, have inspectedthe components described in this o

/- d04?

r has performed examinations and taken corrective te requirements of ASME Code, Section Xl.

makes any warranty, expressed or implied, in this Owners' Report. Furthermore, neither the personal injury or property damage or a loss of any f 47,7 64,x, W)

Commissions O S-<

National Board, State, Providence, and Endorsements 04-063-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi Owner

2. Plant Florida Power and Light Co.

Date Name 700 Universe Blvd. Juno Beach, FL 33408 Address Turkey Point Plant Name 9760 SW 344 Street Florida City, FL 33035 Sheet Unit 12/3/2004 1

of 2

3 WO#: 34006019-03 CR#:

N/A Repair Organization. P.O. No, Job No., etc.

s.

IX Address

3. Work Performed by Florida Power and Light Co.

Name 9760 SW 344 Street Florida City, FL 33035 Type Code Symbol Stamp Authorization Number Expiration Date 1 N/A N/A N/A Address Auxiliary Feedwater

4. Identification of System:

System #:

75 Quality Group C

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xi Utilized for Repairs or Replacements 19 55 Edition, N/A
Addenda, 19 98 Edition, 2000
Addenda, N/A Code Case N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Name of Component Name of Mfg Mfg Serial Number National Board Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No Piping upsteam of Valve AFPD-3-008 I

N/A N/A IAFPD-3-008 N/A N/A Installed N

I

7. Description of Work:

Install new pipe upsteam of Valve AFPD-3-008

8. Tests Conducted:

Hydrostatic:

Other N/A Pneumatic NMA Nominal Operating Pressure X

N/A Pressure 1400 psig Test Temperature 76 deg F 04-064-3

Sheet 2 of 2 FORM NIS-2 (Back) emarks None CERTIFICATE OF We certify that the statements made in the report are correct ani ASME Code.Section XI.

Type Code Symbol Stamp Certificate of Authorization No.

N/A Signed c

1&S SUv Owner or Owner's Designee. Title CERTIFICATE OF INSER 1 the undersigned, holding a valid commission issued by the Nal the state of Florida and employed by HSBCT of Hartford, Conne Owners Report during the period of 3 Zig- 04 I

and state that to the best of my knowledge and belief, the Owne measures described in this Owners' Report in accordance wih th By signing this certificate neither the Inspector nor his employer concerning the examinations and corrective measures describec Inspector nor his employer shall be liable In any manner for any kind arising from or connected with this inspection.

Inspectors Signature Date 1-OS0 0

COMPLIANCE d this replacement conforms to the rules of the N/A Expiration Date:

NIA A'Lo J r0 Date __

0_ 1 VICE INSPECTION tional Board of Boiler and Pressure Vessel Inspectors and cticut, have inspected the components described in this to

/ -

_-0_

r has performed examinations and taken corrective he requirements of ASME Code,Section XI.

makes any warranty, expressed or Implied, I In this Owners Report. Furthermore, neitherthe personal injury or property damage or a loss of any Commissions fZi 4e7 (X, a,

A National Board, State, Providence, and Endorsements 04-064-3

.wner

2. Plant
3. Work Performec FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xl Florida Power and Light Co.

Date 12 Narro 700 Universe Blvd. Juno Beach, FL 33408 Sheet I

Address Turkey Point Plant Unit 2312004 of 2

3 DI CR#:

N/A I by Name 9760 SW 344 Street Florida City, FL 33035 WO#: 33013069-4 Address Florida Power and Light Co.

Name 9760 SW 344 Street Florida City, FL 33035 Address

4. Identification of System:

Intake Cooling Water System #:

1

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements
6. Identification of Components Repaired or Replaced and Replacement Components Repair Organization, P.O. No, Job No., etc.

Type Code Symbol Stamp N/A Authorization Number N/A Expiration Date NMA 9

Quality Group C

1955 Edition, N/A

Addenda, NIA Code Case 1998 Edition, 2000
Addenda, N/A Code Case Name of Component Name of Mfg Mfg Serial National Number Board Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No I -

-U 38 TPCW Heat exchanger isolation Valve N/A 7-96655-2 N/A IPOV-3-4883 N/A Removed N

38 TPCW Heat Exchanger N/A 5500090 N/A POV-34883 N/A Installed N

Isolation Valve D-1-1

7. Description of Work:

Install New Valve and replace bolting

8. Tests Conducted:

Hydrostatic:

N/A 0

Other N/A Pneumatic N/A Pressure 25 psig Nominal Operating Pressure X

Test Temperature 80 deg F 04-065-3

Sheet 2 of 2 FORM NIS-2 (Back)

.e marks None CERTIFICATE OF COMPLIANCE We certify that the statements made In the report are correct and this replacement conforms to the rules of the ASME Code. Section Xi.

Type Code Symbol Stamp N/A Certificate of Authorization No.

N/A Expiration Date:

N/A Signed T Date 124 xEL/oy Owner or Owners Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described in this Owners Report during the period of 7

o4 to

/1.-

05 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Inspectors Signature Commissions

-45_

National Board, State, Providence, and Endorsements Date 0

04-065-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi wner Florida Power and Light Co.

Nane 700 Universe Blvd. Juno Beach, FL 33408 Date Sheet Address Turkey Point Plant 12/3/2004 1

of 2

3 WO#: 33000466-02 CR#:

N/A Unit

2. Plant Name 9760 SW 344 Street Florida City, FL 33035 Address
3. Work Performed by Florida Power and Light Co.

Name 9760 SW 344 Street Florida City, FL 33035 Repair Or anization. P.O. No, Job No, etc.

N/A Type Code Symbol Stamp Authorization Number Expiration Date

_System #:

19 Quality Group N/A N/A Address Intake Cooling Water

4. Identification of System:

C

5. (a) Applicable Construction Code 831.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 19 55 Edition, N/A
Addenda, 19 98 Edition, 2000
Addenda, N/A Code Case N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components Name of Component I Name of Mfg Mfg Serial Number National Board Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No

+

4

+

U 3A TPCW Heat Exchanger Isolation Valve N/A 550009D D-1-2 N/A POV-34882 N/A Installed N

3A TPCW Heat Exchanger Isolation Valve N/A Illegible N/A N/A Removed POV.3-4882 N

7. Description of Work:

Install New Valve

8. Tests Conducted:

Hydrostatic:

N/A 0

Other N/A Pneumatic N/A Pressure 23 psig Nominal Operating Pressure X

Test Temperature 79 deg F 04-066-3

Sheet 2 of 2 FORM NIS-2 (Back) e marks Nc 40

)ne CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp NIA Certificate of Authorization No.

N/A Expiration Date:

NIA Signed.

5So__

Date

'2l>l9-__

Owner or Owners Designee, Title' CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford Connecticut, have inspested the components described in this Owners Report during the period of 6a7- 04 to

/-(- o.0 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Inspector's Signature Commissions

/

7 O

(

National Board. State. Providence, and Endorsements Date 04-066-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI wner Florida Power and Light Co.

Name 700 Universe Blvd. Juno Beach, FL 33408 Date Sheet Address Turkey Point Plant 12/6/2004 1

of 2

3 WO#: 34018922-01 CR#: 04-10708 Unit

2. Plant Name 9760 SW 344 Street Florida City, FL 33035
3. Work Performed bi
4. Identification of Sy!

Address Florida Power and Light Co.

Name 9760 SW 344 Street Florida City, FL 33035 Repair Org stem:

Address Auxiliary Feedwater Type Code Symbol Stamp Authorization Number Expiration Date System #:

75 Quality Group _

janIzatlon, P.O. No, Job No.. etc.

N/A NIA N/A B

5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 19 55 Edition, 19 98 Edition, N/A
Addenda, 2000
Addenda, NIA Code Case N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components ASME Corrected, Code Name of Name of Mfg Mfg Serial National Other Year Removed or Stamp Component Number Board Identification Built Installed Yes/No Piping upstream of valve 3 N/A N/A N/A 3-20-139 N/A Installed N

139 Component Support N/A N/A N/A 80117-H-321-01 N/A Installed N

7. Description of Work:

Install new pipe and install new support stantion

8. Tests Conducted:

Hydrostatic:

N/A Other N/A Pneumatic N/A Pressure 1400 psig Nominal Operating Pressure X

Test Temperature 80 deg F 04-067-3

Sheet 2 of 2 FORM NIS-2 (Back) e marks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp NMA Certificate of Authorization No.

N/A Expiration Date:

N/A Signed Owner o nves De Date _

24l<y Owner or Owner's Designee, TiOLL CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described in this Owners Report during the period of

,o-ZI-O4 to

/- e - ° and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described In this Owners' Report In accordance with the requirements of ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described In this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable In any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions

/

A*7)

Inspector's Signature National Board. State, Providence. and Endorsemen s Date A- - 0.5 04-067-3

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section Xi Florida Power and Light Co.

Date 12 Name 700 Universe Blvd. Juno Beach, FL 33408 Sheet Address Turkey Point Plant Unit

.w ner

2. Plant V/7/2004 of 2

3

.01 CR#:

N/A Name 9760 SW 344 Street Florida City, FL 33035 WO#: 34000755-Address Florida Power and Light Co.

3. Work Performed by 9760
4. Identification of System:

Name SW 344 Street Florida City, FL 33035 Address CVCS Charging and Letdown Repair Organization, P.O. No, Job No., etc.

Type Code Symbol Stamp NIA Authorization Number N/A Expiration Date N/A System #:

47 Quality Group B

19 55 Edition, N/A

Addenda, N/A Code Case nents 19 98 Edition, 2000
Addenda, N/A Code Case
5. (a) Applicable Construction Code B31.1 (b) Applicable Edition of Section Xl Utilized for Repairs or Replacen
6. Identification of Components Repaired or Replaced and Replacement Components Name of Component Name of Mfg Mfg Serial National INumber IBoard Other Identification Year Built Corrected, Removed or Installed ASME Code Stamp Yes/No 3A Charging Pump NIA N/A NMA 13-P201A NIA Installed N
7. Description of Work:

Install new pump

8. Tests Conducted:

Hydrostatic:

NWA Other N/A Pneumatic N/A Pressure 2390 psig Nominal Operating Pressure X

Test Temperature 122 deg F 04-068-3

Sheet 2 of 2 FORM NIS-2 (Back)

  • emarks None CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section Xi.

Type Code Symbol Stamp N/A Certificate of Authorization No.

NIA Expiration Date:

N/A Signed 1

I S

Date j

)j t8J ty Owner or Owners Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state of Florida and employed by HSBCT of Hartford, Connecticut, have inspected the components described in this Owners Report during the period of G-Za to

/- ZZ. 0 5 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners' Report in accordance with the requirements of ASME Code, Section Xi.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners' Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

0 Commissions AZ C9177 Z

Inspectors Signature Natonal Board, State, Providence, and Endorsements Date 1-Zg(2 04-068-3