|
---|
Category:License-Monthly Operating Report
MONTHYEARNRC 2005-0080, February 2005 Monthly Operating Report for Point Beach Nuclear Plant, Unit 1 & 22005-08-19019 August 2005 February 2005 Monthly Operating Report for Point Beach Nuclear Plant, Unit 1 & 2 NRC 2005-0034, February 2005 Monthly Operating Report for Point Beach Units 1 & 22005-03-14014 March 2005 February 2005 Monthly Operating Report for Point Beach Units 1 & 2 NRC 2005-0025, January 2005 Monthly Operating Report for Point Beach Nuclear Plant, Units I and 22005-02-10010 February 2005 January 2005 Monthly Operating Report for Point Beach Nuclear Plant, Units I and 2 NRC 2005-0011, December 2004 Monthly Operating Report for Point Beach, Units 1 & 22005-01-13013 January 2005 December 2004 Monthly Operating Report for Point Beach, Units 1 & 2 NRC 2004-0136, November 2004 Monthly Operating Report for Point Beach Nuclear Plant, Units 1 and 22004-12-13013 December 2004 November 2004 Monthly Operating Report for Point Beach Nuclear Plant, Units 1 and 2 NRC 2004-0118, October 2004 Monthly Operating Report for Point Beach, Units 1 and 22004-11-0808 November 2004 October 2004 Monthly Operating Report for Point Beach, Units 1 and 2 NRC 2004-0105, September 2004 Monthly Operating Report for Point Beach Units 1 and 22004-10-12012 October 2004 September 2004 Monthly Operating Report for Point Beach Units 1 and 2 NRC 2004-0095, August 2004 Monthly Operating Report for Point Beach Nuclear Plant Units 1 and 22004-09-15015 September 2004 August 2004 Monthly Operating Report for Point Beach Nuclear Plant Units 1 and 2 NRC 2004-0080, July 2004 Monthly Operating Report for Point Beach Units 1 and 22004-08-12012 August 2004 July 2004 Monthly Operating Report for Point Beach Units 1 and 2 NRC 2004-0074, June 2004 Monthly Operating Report for Point Beach Nuclear Plant, Units 1 & 22004-07-14014 July 2004 June 2004 Monthly Operating Report for Point Beach Nuclear Plant, Units 1 & 2 NRC 2004-0061, April 2004 Revised Monthly Operating Report for Point Beach, Units 1 and 22004-06-0404 June 2004 April 2004 Revised Monthly Operating Report for Point Beach, Units 1 and 2 NRC 2004-0049, April 2004 Monthly Operating Report Regarding Point Beach Nuclear Plant Units 1 and 22004-05-11011 May 2004 April 2004 Monthly Operating Report Regarding Point Beach Nuclear Plant Units 1 and 2 NRC 2004-0037, March 2004 Monthly Operating Report for Point Beach Units 1 & 22004-04-12012 April 2004 March 2004 Monthly Operating Report for Point Beach Units 1 & 2 NRC 2004-0027, February 2004 Monthly Operating for Point Beach Units 1 and 22004-03-12012 March 2004 February 2004 Monthly Operating for Point Beach Units 1 and 2 NRC 2004-0018, January 2004 Monthly Operating Report for Point Beach, Units 1 and 22004-02-12012 February 2004 January 2004 Monthly Operating Report for Point Beach, Units 1 and 2 NRC 2004-0003, December 2003 Monthly Operating Report for Point Beach, Units 1 and 22004-01-12012 January 2004 December 2003 Monthly Operating Report for Point Beach, Units 1 and 2 NRC 2003-0117, November 2003 Monthly Operating Report for Point Beach, Units 1 and 22003-12-11011 December 2003 November 2003 Monthly Operating Report for Point Beach, Units 1 and 2 NRC 2003-0109, September 2003 Monthly Operating Report for Point Beach Nuclear Plant2003-11-11011 November 2003 September 2003 Monthly Operating Report for Point Beach Nuclear Plant NRC 2003-0093, September 2003 Monthly Operating Report for Point Beach2003-10-13013 October 2003 September 2003 Monthly Operating Report for Point Beach NRC 2003-0082, August 2003 Monthly Operating Report for Point Beach Units 1 and 22003-09-11011 September 2003 August 2003 Monthly Operating Report for Point Beach Units 1 and 2 NRC 2003-0061, June 2003 Monthly Operating Report for Point Beach Units 1 & 22003-07-11011 July 2003 June 2003 Monthly Operating Report for Point Beach Units 1 & 2 NRC 2003-0054, May 2003 Monthly Operating Report for Point Beach Units 1 and 22003-06-0909 June 2003 May 2003 Monthly Operating Report for Point Beach Units 1 and 2 NRC 2003-0041, April 2003 Monthly Operating Report for Point Beach Units 1 & 22003-05-12012 May 2003 April 2003 Monthly Operating Report for Point Beach Units 1 & 2 NRC 2003-0032, March 2003 Monthly Operating Report for Point Beach, Units 1 & 22003-04-0707 April 2003 March 2003 Monthly Operating Report for Point Beach, Units 1 & 2 NRC 2003-0022, February 2003 Monthly Operating Report for Point Beach, Units 1 and 22003-03-0606 March 2003 February 2003 Monthly Operating Report for Point Beach, Units 1 and 2 NRC 2003-0013, January 2003 Monthly Operating Report for Point Beach Nuclear Plant, Units 1 & 22003-02-11011 February 2003 January 2003 Monthly Operating Report for Point Beach Nuclear Plant, Units 1 & 2 NRC 2003-0003, December 2002 Monthly Operating Report for Point Beach Nuclear Plant, Units 1 & 22003-01-0606 January 2003 December 2002 Monthly Operating Report for Point Beach Nuclear Plant, Units 1 & 2 NRC 2002-0106, November 2002 Monthly Operating Report for Point Beach Nuclear Plant, Units 1 & 22002-12-10010 December 2002 November 2002 Monthly Operating Report for Point Beach Nuclear Plant, Units 1 & 2 NRC 2002-0100, October 2002 Monthly Operating Report for Point Beach Units 1 & 22002-11-15015 November 2002 October 2002 Monthly Operating Report for Point Beach Units 1 & 2 NRC 2002-0088, September 2002 Monthly Operating Report for Point Beach Units 1 & 22002-10-0202 October 2002 September 2002 Monthly Operating Report for Point Beach Units 1 & 2 NRC 2002-0078, August 2002 Monthly Operating Report for Point Beach Units 1 & 22002-09-0909 September 2002 August 2002 Monthly Operating Report for Point Beach Units 1 & 2 NRC 2002-0066, July 2002 Monthly Operating Report for Point Beach Units 1 & 22002-08-12012 August 2002 July 2002 Monthly Operating Report for Point Beach Units 1 & 2 NRC 2002-0058, June 2002 Monthly Operating Report for Point Beach Units 1 & 22002-07-0909 July 2002 June 2002 Monthly Operating Report for Point Beach Units 1 & 2 NRC 2002-0049, May 2002 Monthly Operating Report for Point Beach Units 1 & 22002-06-0505 June 2002 May 2002 Monthly Operating Report for Point Beach Units 1 & 2 NRC 2002-0034, April 2002 Monthly Operating Report for Point Beach, Units 1 & 22002-05-0303 May 2002 April 2002 Monthly Operating Report for Point Beach, Units 1 & 2 NRC 2002-0025, March 2002 Monthly Operating Report for Point Beach Nuclear Plant Units 1 & 22002-04-15015 April 2002 March 2002 Monthly Operating Report for Point Beach Nuclear Plant Units 1 & 2 NRC 2002-0021, February 2002 Monthly Operating Report for Point Beach, Units 1 & 22002-03-15015 March 2002 February 2002 Monthly Operating Report for Point Beach, Units 1 & 2 NRC 2002-0014, January 2002 Monthly Operating Report for Point Beach, Units 1 & 22002-02-15015 February 2002 January 2002 Monthly Operating Report for Point Beach, Units 1 & 2 NRC 2002-0003, December 2001 Monthly Operating Report for Point Beach Nuclear Plant Unit 1 and 22002-01-0707 January 2002 December 2001 Monthly Operating Report for Point Beach Nuclear Plant Unit 1 and 2 2005-08-19
[Table view] |
Text
Committed to NuclearExcellene Point Beach Nuclear Plant Operated by Nuclear Management Company, LLC October 12, 2004 NRC 2004-0105 TS 5.6.3 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555 Point Beach Nuclear Plant, Units 1 and 2 Dockets 50-266 and 50-301 License Nos. DPR-24 and DPR-27 Monthly Operating Report In accordance with Technical Specification 5.6.3, Enclosure 1 contains the Monthly Operating Report for September 2004 for the Point Beach Nuclear Plant, Units 1 and 2.
This letter contains no new commitments and no revisions to existing commitments.
Dennis L. Koehl Site Vice-President, P mt Beach Nuclear Plant Nuclear Management Company, LLC Enclosure cc: Administrator, Region IlIl, USNRC Project Manager, Point Beach Nuclear Plant, USNRC Resident Inspector, Point Beach Nuclear Plant, USNRC PSCW INPO Records Center I','
6590 Nuclear Road
Telephone: 920.755.2321
ENCLOSURE I MONTHLY OPERATING REPORT 4 pages follow
OPERATING DATA REPORT DOCKET NO. 50-266 UNIT NAME POINT BEACH NUCLEAR PLANT - UNIT 1 DATE 10/04/04 COMPLETED BY Kim M. Locke TELEPHONE 920-755-6420 REPORTING PERIOD September - 2004
- 1. DESIGN ELECTRICAL RATING (MWE-NET) 522.0
- 2. MAXIMUM DEPENDABLE CAPACITY (MWE-NET) 516.0 MONTH YEAR TO DATE CUMULATIVE
- 3. NUMBER OF HOURS REACTOR WAS CRITICAL 720.0 5,015.4 245,161.3
- 4. NUMBER OF HOURS THE GENERATOR WAS ON LINE 720.0 4,977.7 241,574.4
- 5. UNIT RESERVED SHUTDOWN HOURS 0.0 0.0 846.9
- 6. NET ELECTRICAL ENERGY (MWH) 365,470.5 2,498,193.5 112,392,505.5 DATA REPORTED AND FACTORS CALCULATED AS REQUESTED IN NRC GENERIC LETTER 97-02 DATED MAY 15, 1997
UNIT SHUTDOWNS DOCKET NO. 50-266 UNIT NAME POINT BEACH NUCLEAR PLANT - UNIT 1 DATE 10/14/04 COMPLETED BY Kim M. Locke TELEPHONE 920-755-6420 REPORTING PERIOD: Sectember 2004 (Month/Year)
TYPE METHOD OF CAUSE/CORRECTIVE NO. DATE F: FORCED DURATION REASON (1) SHUTTING ACTIONS S: SCHEDULED (HOURS) DOWN (2) COMMENTS N/A N/A N/A N/A N/A N/AN/A (1) Reason (2) Method A. Equipment Failure (Explain) 1. Manual B. Maintenance or Test 2. Manual Trip/Scram C. Refueling 3. Automatic Trip/Scram D. Regulatory Restriction 4. Continuation E. Operator Training/license Examination 5. Other (Explain)
F. Administrative G. Operational Error (Explain)
H. Other(Explain)
SUMMARY
Unit I average daily power for the month of September was 507.6 MWe.
There were no LERs issued in September for Unit 1.
OPERATING DATA REPORT DOCKET NO. 50-301 UNIT NAME POINT BEACH NUCLEAR PLANT - UNIT 2 DATE 10/04/04 COMPLETED BY Kim M. Locke TELEPHONE 920-755-6420 REPORTING PERIOD September - 2004
- 1. DESIGN ELECTRICAL RATING (MWE-NET) 522.0
- 2. MAXIMUM DEPENDABLE CAPACITY (MWE-NET) 518.0 MONTH YEAR TO DATE CUMULATIVE
- 3. NUMBER OF HOURS REACTOR WAS CRITICAL 720.0 6,499.9 239,847.6
- 4. NUMBER OF HOURS THE GENERATOR WAS ON LINE 720.0 6,464.9 236,701.7
- 5. UNIT RESERVED SHUTDOWN HOURS 0.0 0.0 302.2
- 6. NET ELECTRICAL ENERGY (MWH) 372,725.5 3,345,495.5 111,846,577.0 DATA REPORTED AND FACTORS CALCULATED AS REQUESTED IN NRC GENERIC LETTER 97-02 DATED MAY 15, 1997
UNIT SHUTDOWNS DOCKET NO. 50-301 UNIT NAME POINT BEACH NUCLEAR PLANT - UNIT 2 DATE 10/14/04 COMPLETED BY Kim M. Locke TELEPHONE 920-755-6420 REPORTING PERIOD: September 2004 (Month/Year)
TYPE METHOD OF CACTIONS CTV NO. DATE F: FORCED DURATION REASON (1) SHUTTING ACTIONS S: SCHEDULED (HOURS) DOWN (2) COMMENTS N/A N/A N/A N/A N/A N/A N/A (1) Reason (2) Method A. Equipment Failure (Explain) 1. Manual B. Maintenance or Test 2. Manual Trip/Scram C. Refueling 3. Automatic Trip/Scram D. Regulatory Restriction 4. Continuation E. Operator Training/license Examination 5. Other (Explain)
F. Administrative G. Operational Error (Explain)
H. Other (Explain)
SUMMARY
Unit 2 average daily power for the month of September was 517.7 MWe.
There were no LERs issued in September for Unit 2.