ML040280579

From kanterella
Jump to navigation Jump to search
Sensitivity Analysis - Soil. Dose Conversion Factor (and Related) Parameter Summary
ML040280579
Person / Time
Site: Yankee Rowe
(DPR-003)
Issue date: 11/26/2003
From:
Yankee Atomic Electric Co
To:
NRC/FSME
References
-RFPFR
Download: ML040280579 (66)


Text

1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/26/2003 14:53 Page 2 Summary : Yankee Rowe Sensitivity Analysis=soil File: Ag-108mDCGL.RAD Dose Conversion Factor (and Related) Parameter Summary File: FGR 13 Morbidity 0 ³ ³ Current ³ ³ Parameter Menu ³ Parameter ³ Value ³ Default ³ Name

ÅÅÅÅ B-1 ³ Dose conversion factors for inhalation, mrem/pCi: ³ ³ ³ B-1 ³ Ag-108m+D ³ 2.830E-04 ³ 2.830E-04 ³ DCF2( 1)

³ ³ ³ ³ D-1 ³ Dose conversion factors for ingestion, mrem/pCi: ³ ³ ³ D-1 ³ Ag-108m+D ³ 7.620E-06 ³ 7.620E-06 ³ DCF3( 1)

³ ³ ³ ³ D-34 ³ Food transfer factors: ³ ³ ³ D-34 ³ Ag-108m+D, plant/soil concentration ratio, dimensionless ³ 1.500E-01 ³ 1.500E-01 ³ RTF( 1,1)

D-34 ³ Ag-108m+D, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 3.000E-03 ³ 3.000E-03 ³ RTF( 1,2)

D-34 ³ Ag-108m+D, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 2.500E-02 ³ 2.500E-02 ³ RTF( 1,3)

³ ³ ³ ³ D-5 ³ Bioaccumulation factors, fresh water, L/kg: ³ ³ ³ D-5 ³ Ag-108m+D, fish ³ 5.000E+00 ³ 5.000E+00 ³ BIOFAC( 1,1)

D-5 ³ Ag-108m+D, crustacea and mollusks ³ 7.700E+02 ³ 7.700E+02 ³ BIOFAC( 1,2) 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/26/2003 14:53 Page 3 Summary : Yankee Rowe Sensitivity Analysis=soil File: Ag-108mDCGL.RAD Site-Specific Parameter Summary 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R011 ³ Area of contaminated zone (m**2) ³ 1.302E+04 ³ 1.000E+04 ³ --- ³ AREA R011 ³ Thickness of contaminated zone (m) ³ 1.975E+00 ³ 2.000E+00 ³ --- ³ THICK0 R011 ³ Length parallel to aquifer flow (m) ³ 1.290E+02 ³ 1.000E+02 ³ --- ³ LCZPAQ R011 ³ Basic radiation dose limit (mrem/yr) ³ 2.500E+01 ³ 2.500E+01 ³ --- ³ BRDL R011 ³ Time since placement of material (yr) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ TI R011 ³ Times for calculations (yr) ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ T( 2)

R011 ³ Times for calculations (yr) ³ 3.000E+00 ³ 3.000E+00 ³ --- ³ T( 3)

R011 ³ Times for calculations (yr) ³ 1.000E+01 ³ 1.000E+01 ³ --- ³ T( 4)

R011 ³ Times for calculations (yr) ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ T( 5)

R011 ³ Times for calculations (yr) ³ 1.000E+02 ³ 1.000E+02 ³ --- ³ T( 6)

R011 ³ Times for calculations (yr) ³ 3.000E+02 ³ 3.000E+02 ³ --- ³ T( 7)

R011 ³ Times for calculations (yr) ³ 1.000E+03 ³ 1.000E+03 ³ --- ³ T( 8)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T( 9)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T(10)

³ ³ ³ ³ ³ R012 ³ Initial principal radionuclide (pCi/g): Ag-108m ³ 1.000E+00 ³ 0.000E+00 ³ --- ³ S1( 1)

R012 ³ Concentration in groundwater (pCi/L): Ag-108m ³ not used ³ 0.000E+00 ³ --- ³ W1( 1)

³ ³ ³ ³ ³ R013 ³ Cover depth (m) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ COVER0 R013 ³ Density of cover material (g/cm**3) ³ not used ³ 1.500E+00 ³ --- ³ DENSCV R013 ³ Cover depth erosion rate (m/yr) ³ not used ³ 1.000E-03 ³ --- ³ VCV R013 ³ Density of contaminated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSCZ R013 ³ Contaminated zone erosion rate (m/yr) ³ 8.500E-04 ³ 1.000E-03 ³ --- ³ VCZ R013 ³ Contaminated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPCZ R013 ³ Contaminated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCCZ R013 ³ Contaminated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCCZ R013 ³ Contaminated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BCZ R013 ³ Average annual wind speed (m/sec) ³ 2.030E+00 ³ 2.000E+00 ³ --- ³ WIND R013 ³ Humidity in air (g/m**3) ³ not used ³ 8.000E+00 ³ --- ³ HUMID R013 ³ Evapotranspiration coefficient ³ 6.250E-01 ³ 5.000E-01 ³ --- ³ EVAPTR R013 ³ Precipitation (m/yr) ³ 1.200E+00 ³ 1.000E+00 ³ --- ³ PRECIP R013 ³ Irrigation (m/yr) ³ 4.350E-01 ³ 2.000E-01 ³ --- ³ RI R013 ³ Irrigation mode ³ overhead ³ overhead ³ --- ³ IDITCH R013 ³ Runoff coefficient ³ 6.000E-01 ³ 2.000E-01 ³ --- ³ RUNOFF R013 ³ Watershed area for nearby stream or pond (m**2) ³ 7.770E+05 ³ 1.000E+06 ³ --- ³ WAREA R013 ³ Accuracy for water/soil computations ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ EPS

³ ³ ³ ³ ³ R014 ³ Density of saturated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSAQ R014 ³ Saturated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPSZ R014 ³ Saturated zone effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPSZ R014 ³ Saturated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCSZ R014 ³ Saturated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+02 ³ --- ³ HCSZ R014 ³ Saturated zone hydraulic gradient ³ 1.000E-01 ³ 2.000E-02 ³ --- ³ HGWT R014 ³ Saturated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BSZ R014 ³ Water table drop rate (m/yr) ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ VWT R014 ³ Well pump intake depth (m below water table) ³ 1.451E+01 ³ 1.000E+01 ³ --- ³ DWIBWT R014 ³ Model: Nondispersion (ND) or Mass-Balance (MB) ³ ND ³ ND ³ --- ³ MODEL R014 ³ Well pumping rate (m**3/yr) ³ 1.323E+03 ³ 2.500E+02 ³ --- ³ UW

³ ³ ³ ³ ³ R015 ³ Number of unsaturated zone strata ³ 1 ³ 1 ³ --- ³ NS 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/26/2003 14:53 Page 4 Summary : Yankee Rowe Sensitivity Analysis=soil File: Ag-108mDCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R015 ³ Unsat. zone 1, thickness (m) ³ 1.820E+00 ³ 4.000E+00 ³ --- ³ H(1)

R015 ³ Unsat. zone 1, soil density (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSUZ(1)

R015 ³ Unsat. zone 1, total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPUZ(1)

R015 ³ Unsat. zone 1, effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPUZ(1)

R015 ³ Unsat. zone 1, field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCUZ(1)

R015 ³ Unsat. zone 1, soil-specific b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BUZ(1)

R015 ³ Unsat. zone 1, hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCUZ(1)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for Ag-108m ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 2.160E+02 ³ 0.000E+00 ³ --- ³ DCNUCC( 1)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 2.160E+02 ³ 0.000E+00 ³ --- ³ DCNUCU( 1,1)

R016 ³ Saturated zone (cm**3/g) ³ 2.160E+02 ³ 0.000E+00 ³ --- ³ DCNUCS( 1)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 5.324E-04 ³ ALEACH( 1)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 1)

³ ³ ³ ³ ³ R017 ³ Inhalation rate (m**3/yr) ³ 8.400E+03 ³ 8.400E+03 ³ --- ³ INHALR R017 ³ Mass loading for inhalation (g/m**3) ³ 2.330E-05 ³ 1.000E-04 ³ --- ³ MLINH R017 ³ Exposure duration ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ ED R017 ³ Shielding factor, inhalation ³ 5.500E-01 ³ 4.000E-01 ³ --- ³ SHF3 R017 ³ Shielding factor, external gamma ³ 3.980E-01 ³ 7.000E-01 ³ --- ³ SHF1 R017 ³ Fraction of time spent indoors ³ 6.571E-01 ³ 5.000E-01 ³ --- ³ FIND R017 ³ Fraction of time spent outdoors (on site) ³ 1.181E-01 ³ 2.500E-01 ³ --- ³ FOTD R017 ³ Shape factor flag, external gamma ³ 1.000E+00 ³ 1.000E+00 ³ >0 shows circular AREA. ³ FS R017 ³ Radii of shape factor array (used if FS = -1): ³ ³ ³ ³ R017 ³ Outer annular radius (m), ring 1: ³ not used ³ 5.000E+01 ³ --- ³ RAD_SHAPE(

1)

R017 ³ Outer annular radius (m), ring 2: ³ not used ³ 7.071E+01 ³ --- ³ RAD_SHAPE(

2)

R017 ³ Outer annular radius (m), ring 3: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

3)

R017 ³ Outer annular radius (m), ring 4: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

4)

R017 ³ Outer annular radius (m), ring 5: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

5)

R017 ³ Outer annular radius (m), ring 6: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

6)

R017 ³ Outer annular radius (m), ring 7: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

7)

R017 ³ Outer annular radius (m), ring 8: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

8)

R017 ³ Outer annular radius (m), ring 9: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

9)

R017 ³ Outer annular radius (m), ring 10: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (10)

R017 ³ Outer annular radius (m), ring 11: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (11)

R017 ³ Outer annular radius (m), ring 12: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (12)

³ ³ ³ ³ ³ R017 ³ Fractions of annular areas within AREA: ³ ³ ³ ³ R017 ³ Ring 1 ³ not used ³ 1.000E+00 ³ --- ³ FRACA( 1)

R017 ³ Ring 2 ³ not used ³ 2.732E-01 ³ --- ³ FRACA( 2)

R017 ³ Ring 3 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 3)

R017 ³ Ring 4 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 4)

R017 ³ Ring 5 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 5)

R017 ³ Ring 6 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 6)

R017 ³ Ring 7 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 7)

R017 ³ Ring 8 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 8)

R017 ³ Ring 9 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 9)

R017 ³ Ring 10 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(10)

R017 ³ Ring 11 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(11)

R017 ³ Ring 12 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(12)

³ ³ ³ ³ ³ 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/26/2003 14:53 Page 5 Summary : Yankee Rowe Sensitivity Analysis=soil File: Ag-108mDCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R018 ³ Fruits, vegetables and grain consumption (kg/yr) ³ 1.120E+02 ³ 1.600E+02 ³ --- ³ DIET(1)

R018 ³ Leafy vegetable consumption (kg/yr) ³ 2.140E+01 ³ 1.400E+01 ³ --- ³ DIET(2)

R018 ³ Milk consumption (L/yr) ³ 2.330E+02 ³ 9.200E+01 ³ --- ³ DIET(3)

R018 ³ Meat and poultry consumption (kg/yr) ³ 6.510E+01 ³ 6.300E+01 ³ --- ³ DIET(4)

R018 ³ Fish consumption (kg/yr) ³ 2.060E+01 ³ 5.400E+00 ³ --- ³ DIET(5)

R018 ³ Other seafood consumption (kg/yr) ³ 9.000E-01 ³ 9.000E-01 ³ --- ³ DIET(6)

R018 ³ Soil ingestion rate (g/yr) ³ 1.826E+01 ³ 3.650E+01 ³ --- ³ SOIL R018 ³ Drinking water intake (L/yr) ³ 4.785E+02 ³ 5.100E+02 ³ --- ³ DWI R018 ³ Contamination fraction of drinking water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FDW R018 ³ Contamination fraction of household water ³ not used ³ 1.000E+00 ³ --- ³ FHHW R018 ³ Contamination fraction of livestock water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FLW R018 ³ Contamination fraction of irrigation water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FIRW R018 ³ Contamination fraction of aquatic food ³ 1.000E+00 ³ 5.000E-01 ³ --- ³ FR9 R018 ³ Contamination fraction of plant food ³ 1.000E+00 ³-1 ³ --- ³ FPLANT R018 ³ Contamination fraction of meat ³ 1.000E+00 ³-1 ³ --- ³ FMEAT R018 ³ Contamination fraction of milk ³ 1.000E+00 ³-1 ³ --- ³ FMILK

³ ³ ³ ³ ³ R019 ³ Livestock fodder intake for meat (kg/day) ³ 2.710E+01 ³ 6.800E+01 ³ --- ³ LFI5 R019 ³ Livestock fodder intake for milk (kg/day) ³ 6.320E+01 ³ 5.500E+01 ³ --- ³ LFI6 R019 ³ Livestock water intake for meat (L/day) ³ 5.060E+01 ³ 5.000E+01 ³ --- ³ LWI5 R019 ³ Livestock water intake for milk (L/day) ³ 6.000E+01 ³ 1.600E+02 ³ --- ³ LWI6 R019 ³ Livestock soil intake (kg/day) ³ 5.000E-01 ³ 5.000E-01 ³ --- ³ LSI R019 ³ Mass loading for foliar deposition (g/m**3) ³ 4.000E-04 ³ 1.000E-04 ³ --- ³ MLFD R019 ³ Depth of soil mixing layer (m) ³ 2.300E-01 ³ 1.500E-01 ³ --- ³ DM R019 ³ Depth of roots (m) ³ 2.050E+00 ³ 9.000E-01 ³ --- ³ DROOT R019 ³ Drinking water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWDW R019 ³ Household water fraction from ground water ³ not used ³ 1.000E+00 ³ --- ³ FGWHH R019 ³ Livestock water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWLW R019 ³ Irrigation fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWIR

³ ³ ³ ³ ³ R19B ³ Wet weight crop yield for Non-Leafy (kg/m**2) ³ 1.750E+00 ³ 7.000E-01 ³ --- ³ YV(1)

R19B ³ Wet weight crop yield for Leafy (kg/m**2) ³ 2.889E+00 ³ 1.500E+00 ³ --- ³ YV(2)

R19B ³ Wet weight crop yield for Fodder (kg/m**2) ³ 1.887E+00 ³ 1.100E+00 ³ --- ³ YV(3)

R19B ³ Growing Season for Non-Leafy (years) ³ 2.460E-01 ³ 1.700E-01 ³ --- ³ TE(1)

R19B ³ Growing Season for Leafy (years) ³ 1.230E-01 ³ 2.500E-01 ³ --- ³ TE(2)

R19B ³ Growing Season for Fodder (years) ³ 8.200E-02 ³ 8.000E-02 ³ --- ³ TE(3)

R19B ³ Translocation Factor for Non-Leafy ³ 1.000E-01 ³ 1.000E-01 ³ --- ³ TIV(1)

R19B ³ Translocation Factor for Leafy ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(2)

R19B ³ Translocation Factor for Fodder ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(3)

R19B ³ Dry Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(1)

R19B ³ Dry Foliar Interception Fraction for Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(2)

R19B ³ Dry Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(3)

R19B ³ Wet Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(1)

R19B ³ Wet Foliar Interception Fraction for Leafy ³ 5.800E-01 ³ 2.500E-01 ³ --- ³ RWET(2)

R19B ³ Wet Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(3)

R19B ³ Weathering Removal Constant for Vegetation ³ 3.300E+01 ³ 2.000E+01 ³ --- ³ WLAM

³ ³ ³ ³ ³ C14 ³ C-12 concentration in water (g/cm**3) ³ not used ³ 2.000E-05 ³ --- ³ C12WTR C14 ³ C-12 concentration in contaminated soil (g/g) ³ not used ³ 3.000E-02 ³ --- ³ C12CZ C14 ³ Fraction of vegetation carbon from soil ³ not used ³ 2.000E-02 ³ --- ³ CSOIL C14 ³ Fraction of vegetation carbon from air ³ not used ³ 9.800E-01 ³ --- ³ CAIR 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/26/2003 14:53 Page 6 Summary : Yankee Rowe Sensitivity Analysis=soil File: Ag-108mDCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ C14 ³ C-14 evasion layer thickness in soil (m) ³ not used ³ 3.000E-01 ³ --- ³ DMC C14 ³ C-14 evasion flux rate from soil (1/sec) ³ not used ³ 7.000E-07 ³ --- ³ EVSN C14 ³ C-12 evasion flux rate from soil (1/sec) ³ not used ³ 1.000E-10 ³ --- ³ REVSN C14 ³ Fraction of grain in beef cattle feed ³ not used ³ 8.000E-01 ³ --- ³ AVFG4 C14 ³ Fraction of grain in milk cow feed ³ not used ³ 2.000E-01 ³ --- ³ AVFG5 C14 ³ DCF correction factor for gaseous forms of C14 ³ not used ³ 8.894E+01 ³ --- ³ CO2F

³ ³ ³ ³ ³ STOR ³ Storage times of contaminated foodstuffs (days): ³ ³ ³ ³ STOR ³ Fruits, non-leafy vegetables, and grain ³ 1.400E+01 ³ 1.400E+01 ³ --- ³ STOR_T(1)

STOR ³ Leafy vegetables ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(2)

STOR ³ Milk ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(3)

STOR ³ Meat and poultry ³ 2.000E+01 ³ 2.000E+01 ³ --- ³ STOR_T(4)

STOR ³ Fish ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(5)

STOR ³ Crustacea and mollusks ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(6)

STOR ³ Well water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(7)

STOR ³ Surface water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(8)

STOR ³ Livestock fodder ³ 4.500E+01 ³ 4.500E+01 ³ --- ³ STOR_T(9)

³ ³ ³ ³ ³ R021 ³ Thickness of building foundation (m) ³ not used ³ 1.500E-01 ³ --- ³ FLOOR1 R021 ³ Bulk density of building foundation (g/cm**3) ³ not used ³ 2.400E+00 ³ --- ³ DENSFL R021 ³ Total porosity of the cover material ³ not used ³ 4.000E-01 ³ --- ³ TPCV R021 ³ Total porosity of the building foundation ³ not used ³ 1.000E-01 ³ --- ³ TPFL R021 ³ Volumetric water content of the cover material ³ not used ³ 5.000E-02 ³ --- ³ PH2OCV R021 ³ Volumetric water content of the foundation ³ not used ³ 3.000E-02 ³ --- ³ PH2OFL R021 ³ Diffusion coefficient for radon gas (m/sec): ³ ³ ³ ³ R021 ³ in cover material ³ not used ³ 2.000E-06 ³ --- ³ DIFCV R021 ³ in foundation material ³ not used ³ 3.000E-07 ³ --- ³ DIFFL R021 ³ in contaminated zone soil ³ not used ³ 2.000E-06 ³ --- ³ DIFCZ R021 ³ Radon vertical dimension of mixing (m) ³ not used ³ 2.000E+00 ³ --- ³ HMIX R021 ³ Average building air exchange rate (1/hr) ³ not used ³ 5.000E-01 ³ --- ³ REXG R021 ³ Height of the building (room) (m) ³ not used ³ 2.500E+00 ³ --- ³ HRM R021 ³ Building interior area factor ³ not used ³ 0.000E+00 ³ --- ³ FAI R021 ³ Building depth below ground surface (m) ³ not used ³-1.000E+00 ³ --- ³ DMFL R021 ³ Emanating power of Rn-222 gas ³ not used ³ 2.500E-01 ³ --- ³ EMANA(1)

R021 ³ Emanating power of Rn-220 gas ³ not used ³ 1.500E-01 ³ --- ³ EMANA(2)

³ ³ ³ ³ ³ TITL ³ Number of graphical time points ³ 32 ³ --- ³ --- ³ NPTS TITL ³ Maximum number of integration points for dose ³ 17 ³ --- ³ --- ³ LYMAX TITL ³ Maximum number of integration points for risk ³ 1 ³ --- ³ --- ³ KYMAX

1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/26/2003 14:53 Page 7 Summary : Yankee Rowe Sensitivity Analysis=soil File: Ag-108mDCGL.RAD Summary of Pathway Selections Pathway ³ User Selection

Å 1 -- external gamma ³ active 2 -- inhalation (w/o radon)³ active 3 -- plant ingestion ³ active 4 -- meat ingestion ³ active 5 -- milk ingestion ³ active 6 -- aquatic foods ³ active 7 -- drinking water ³ active 8 -- soil ingestion ³ active 9 -- radon ³ suppressed Find peak pathway doses ³ active

1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/11/2003 10:34 Page 2 Summary : Yankee Rowe Sensitivity Analysis=soil File: Am-241_DCGL.RAD Dose Conversion Factor (and Related) Parameter Summary File: YR soil DCGL lib 0 ³ ³ Current ³ ³ Parameter Menu ³ Parameter ³ Value ³ Default ³ Name

ÅÅÅÅ B-1 ³ Dose conversion factors for inhalation, mrem/pCi: ³ ³ ³ B-1 ³ Am-241 ³ 4.440E-01 ³ 4.440E-01 ³ DCF2( 1)

B-1 ³ Np-237+D ³ 5.400E-01 ³ 5.400E-01 ³ DCF2( 2)

B-1 ³ Th-229+D ³ 2.160E+00 ³ 2.160E+00 ³ DCF2( 3)

B-1 ³ U-233 ³ 1.350E-01 ³ 1.350E-01 ³ DCF2( 4)

³ ³ ³ ³ D-1 ³ Dose conversion factors for ingestion, mrem/pCi: ³ ³ ³ D-1 ³ Am-241 ³ 3.640E-03 ³ 3.640E-03 ³ DCF3( 1)

D-1 ³ Np-237+D ³ 4.440E-03 ³ 4.440E-03 ³ DCF3( 2)

D-1 ³ Th-229+D ³ 4.030E-03 ³ 4.030E-03 ³ DCF3( 3)

D-1 ³ U-233 ³ 2.890E-04 ³ 2.890E-04 ³ DCF3( 4)

³ ³ ³ ³ D-34 ³ Food transfer factors: ³ ³ ³ D-34 ³ Am-241, plant/soil concentration ratio, dimensionless ³ 1.830E-03 ³ 1.000E-03 ³ RTF( 1,1)

D-34 ³ Am-241, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 5.000E-05 ³ 5.000E-05 ³ RTF( 1,2)

D-34 ³ Am-241, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 2.000E-06 ³ 2.000E-06 ³ RTF( 1,3)

D-34 ³ ³ ³ ³ D-34 ³ Np-237+D, plant/soil concentration ratio, dimensionless ³ 2.000E-02 ³ 2.000E-02 ³ RTF( 2,1)

D-34 ³ Np-237+D, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 1.000E-03 ³ 1.000E-03 ³ RTF( 2,2)

D-34 ³ Np-237+D, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 5.000E-06 ³ 5.000E-06 ³ RTF( 2,3)

D-34 ³ ³ ³ ³ D-34 ³ Th-229+D, plant/soil concentration ratio, dimensionless ³ 1.000E-03 ³ 1.000E-03 ³ RTF( 3,1)

D-34 ³ Th-229+D, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 1.000E-04 ³ 1.000E-04 ³ RTF( 3,2)

D-34 ³ Th-229+D, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 5.000E-06 ³ 5.000E-06 ³ RTF( 3,3)

D-34 ³ ³ ³ ³ D-34 ³ U-233, plant/soil concentration ratio, dimensionless ³ 2.500E-03 ³ 2.500E-03 ³ RTF( 4,1)

D-34 ³ U-233, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 3.400E-04 ³ 3.400E-04 ³ RTF( 4,2)

D-34 ³ U-233, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 6.000E-04 ³ 6.000E-04 ³ RTF( 4,3)

³ ³ ³ ³ D-5 ³ Bioaccumulation factors, fresh water, L/kg: ³ ³ ³ D-5 ³ Am-241, fish ³ 3.000E+01 ³ 3.000E+01 ³ BIOFAC( 1,1)

D-5 ³ Am-241, crustacea and mollusks ³ 1.000E+03 ³ 1.000E+03 ³ BIOFAC( 1,2)

D-5 ³ ³ ³ ³ D-5 ³ Np-237+D, fish ³ 3.000E+01 ³ 3.000E+01 ³ BIOFAC( 2,1)

D-5 ³ Np-237+D, crustacea and mollusks ³ 4.000E+02 ³ 4.000E+02 ³ BIOFAC( 2,2)

D-5 ³ ³ ³ ³ D-5 ³ Th-229+D, fish ³ 1.000E+02 ³ 1.000E+02 ³ BIOFAC( 3,1)

D-5 ³ Th-229+D, crustacea and mollusks ³ 5.000E+02 ³ 5.000E+02 ³ BIOFAC( 3,2)

D-5 ³ ³ ³ ³ D-5 ³ U-233, fish ³ 1.000E+01 ³ 1.000E+01 ³ BIOFAC( 4,1)

D-5 ³ U-233, crustacea and mollusks ³ 6.000E+01 ³ 6.000E+01 ³ BIOFAC( 4,2) 1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/11/2003 10:34 Page 3 Summary : Yankee Rowe Sensitivity Analysis=soil File: Am-241_DCGL.RAD Site-Specific Parameter Summary 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R011 ³ Area of contaminated zone (m**2) ³ 1.302E+04 ³ 1.000E+04 ³ --- ³ AREA R011 ³ Thickness of contaminated zone (m) ³ 1.975E+00 ³ 2.000E+00 ³ --- ³ THICK0 R011 ³ Length parallel to aquifer flow (m) ³ 1.290E+02 ³ 1.000E+02 ³ --- ³ LCZPAQ R011 ³ Basic radiation dose limit (mrem/yr) ³ 2.500E+01 ³ 2.500E+01 ³ --- ³ BRDL R011 ³ Time since placement of material (yr) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ TI R011 ³ Times for calculations (yr) ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ T( 2)

R011 ³ Times for calculations (yr) ³ 3.000E+00 ³ 3.000E+00 ³ --- ³ T( 3)

R011 ³ Times for calculations (yr) ³ 1.000E+01 ³ 1.000E+01 ³ --- ³ T( 4)

R011 ³ Times for calculations (yr) ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ T( 5)

R011 ³ Times for calculations (yr) ³ 1.000E+02 ³ 1.000E+02 ³ --- ³ T( 6)

R011 ³ Times for calculations (yr) ³ 3.000E+02 ³ 3.000E+02 ³ --- ³ T( 7)

R011 ³ Times for calculations (yr) ³ 1.000E+03 ³ 1.000E+03 ³ --- ³ T( 8)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T( 9)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T(10)

³ ³ ³ ³ ³ R012 ³ Initial principal radionuclide (pCi/g): Am-241 ³ 1.000E+00 ³ 0.000E+00 ³ --- ³ S1( 1)

R012 ³ Concentration in groundwater (pCi/L): Am-241 ³ not used ³ 0.000E+00 ³ --- ³ W1( 1)

³ ³ ³ ³ ³ R013 ³ Cover depth (m) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ COVER0 R013 ³ Density of cover material (g/cm**3) ³ not used ³ 1.500E+00 ³ --- ³ DENSCV R013 ³ Cover depth erosion rate (m/yr) ³ not used ³ 1.000E-03 ³ --- ³ VCV R013 ³ Density of contaminated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSCZ R013 ³ Contaminated zone erosion rate (m/yr) ³ 8.500E-04 ³ 1.000E-03 ³ --- ³ VCZ R013 ³ Contaminated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPCZ R013 ³ Contaminated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCCZ R013 ³ Contaminated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCCZ R013 ³ Contaminated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BCZ R013 ³ Average annual wind speed (m/sec) ³ 2.030E+00 ³ 2.000E+00 ³ --- ³ WIND R013 ³ Humidity in air (g/m**3) ³ not used ³ 8.000E+00 ³ --- ³ HUMID R013 ³ Evapotranspiration coefficient ³ 6.250E-01 ³ 5.000E-01 ³ --- ³ EVAPTR R013 ³ Precipitation (m/yr) ³ 1.200E+00 ³ 1.000E+00 ³ --- ³ PRECIP R013 ³ Irrigation (m/yr) ³ 4.350E-01 ³ 2.000E-01 ³ --- ³ RI R013 ³ Irrigation mode ³ overhead ³ overhead ³ --- ³ IDITCH R013 ³ Runoff coefficient ³ 6.000E-01 ³ 2.000E-01 ³ --- ³ RUNOFF R013 ³ Watershed area for nearby stream or pond (m**2) ³ 7.770E+05 ³ 1.000E+06 ³ --- ³ WAREA R013 ³ Accuracy for water/soil computations ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ EPS

³ ³ ³ ³ ³ R014 ³ Density of saturated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSAQ

R014 ³ Saturated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPSZ R014 ³ Saturated zone effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPSZ R014 ³ Saturated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCSZ R014 ³ Saturated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+02 ³ --- ³ HCSZ R014 ³ Saturated zone hydraulic gradient ³ 1.000E-01 ³ 2.000E-02 ³ --- ³ HGWT R014 ³ Saturated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BSZ R014 ³ Water table drop rate (m/yr) ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ VWT R014 ³ Well pump intake depth (m below water table) ³ 1.451E+01 ³ 1.000E+01 ³ --- ³ DWIBWT R014 ³ Model: Nondispersion (ND) or Mass-Balance (MB) ³ ND ³ ND ³ --- ³ MODEL R014 ³ Well pumping rate (m**3/yr) ³ 1.323E+03 ³ 2.500E+02 ³ --- ³ UW

³ ³ ³ ³ ³ R015 ³ Number of unsaturated zone strata ³ 1 ³ 1 ³ --- ³ NS 1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/11/2003 10:34 Page 4 Summary : Yankee Rowe Sensitivity Analysis=soil File: Am-241_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R015 ³ Unsat. zone 1, thickness (m) ³ 1.820E+00 ³ 4.000E+00 ³ --- ³ H(1)

R015 ³ Unsat. zone 1, soil density (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSUZ(1)

R015 ³ Unsat. zone 1, total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPUZ(1)

R015 ³ Unsat. zone 1, effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPUZ(1)

R015 ³ Unsat. zone 1, field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCUZ(1)

R015 ³ Unsat. zone 1, soil-specific b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BUZ(1)

R015 ³ Unsat. zone 1, hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCUZ(1)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for Am-241 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 1.445E+03 ³ 2.000E+01 ³ --- ³ DCNUCC( 1)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 1.445E+03 ³ 2.000E+01 ³ --- ³ DCNUCU( 1,1)

R016 ³ Saturated zone (cm**3/g) ³ 1.445E+03 ³ 2.000E+01 ³ --- ³ DCNUCS( 1)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 7.959E-05 ³ ALEACH( 1)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 1)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for daughter Np-237 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 1.700E+01 ³-1.000E+00 ³ --- ³ DCNUCC( 2)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 1.700E+01 ³-1.000E+00 ³ --- ³ DCNUCU( 2,1)

R016 ³ Saturated zone (cm**3/g) ³ 1.700E+01 ³-1.000E+00 ³ --- ³ DCNUCS( 2)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 6.747E-03 ³ ALEACH( 2)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 2)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for daughter Th-229 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 5.884E+03 ³ 6.000E+04 ³ --- ³ DCNUCC( 3)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 5.884E+03 ³ 6.000E+04 ³ --- ³ DCNUCU( 3,1)

R016 ³ Saturated zone (cm**3/g) ³ 5.884E+03 ³ 6.000E+04 ³ --- ³ DCNUCS( 3)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 1.955E-05 ³ ALEACH( 3)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 3)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for daughter U-233 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 1.260E+02 ³ 5.000E+01 ³ --- ³ DCNUCC( 4)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 1.260E+02 ³ 5.000E+01 ³ --- ³ DCNUCU( 4,1)

R016 ³ Saturated zone (cm**3/g) ³ 1.260E+02 ³ 5.000E+01 ³ --- ³ DCNUCS( 4)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 9.125E-04 ³ ALEACH( 4)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 4)

³ ³ ³ ³ ³ R017 ³ Inhalation rate (m**3/yr) ³ 8.400E+03 ³ 8.400E+03 ³ --- ³ INHALR R017 ³ Mass loading for inhalation (g/m**3) ³ 2.330E-05 ³ 1.000E-04 ³ --- ³ MLINH R017 ³ Exposure duration ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ ED R017 ³ Shielding factor, inhalation ³ 5.500E-01 ³ 4.000E-01 ³ --- ³ SHF3 R017 ³ Shielding factor, external gamma ³ 2.725E-01 ³ 7.000E-01 ³ --- ³ SHF1 R017 ³ Fraction of time spent indoors ³ 6.571E-01 ³ 5.000E-01 ³ --- ³ FIND R017 ³ Fraction of time spent outdoors (on site) ³ 1.181E-01 ³ 2.500E-01 ³ --- ³ FOTD R017 ³ Shape factor flag, external gamma ³ 1.000E+00 ³ 1.000E+00 ³ >0 shows circular AREA. ³ FS 1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/11/2003 10:34 Page 5 Summary : Yankee Rowe Sensitivity Analysis=soil File: Am-241_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R017 ³ Radii of shape factor array (used if FS = -1): ³ ³ ³ ³ R017 ³ Outer annular radius (m), ring 1: ³ not used ³ 5.000E+01 ³ --- ³ RAD_SHAPE(

1)

R017 ³ Outer annular radius (m), ring 2: ³ not used ³ 7.071E+01 ³ --- ³ RAD_SHAPE(

2)

R017 ³ Outer annular radius (m), ring 3: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

3)

R017 ³ Outer annular radius (m), ring 4: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

4)

R017 ³ Outer annular radius (m), ring 5: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

5)

R017 ³ Outer annular radius (m), ring 6: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

6)

R017 ³ Outer annular radius (m), ring 7: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

7)

R017 ³ Outer annular radius (m), ring 8: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

8)

R017 ³ Outer annular radius (m), ring 9: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

9)

R017 ³ Outer annular radius (m), ring 10: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (10)

R017 ³ Outer annular radius (m), ring 11: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (11)

R017 ³ Outer annular radius (m), ring 12: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE

(12)

³ ³ ³ ³ ³ R017 ³ Fractions of annular areas within AREA: ³ ³ ³ ³ R017 ³ Ring 1 ³ not used ³ 1.000E+00 ³ --- ³ FRACA( 1)

R017 ³ Ring 2 ³ not used ³ 2.732E-01 ³ --- ³ FRACA( 2)

R017 ³ Ring 3 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 3)

R017 ³ Ring 4 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 4)

R017 ³ Ring 5 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 5)

R017 ³ Ring 6 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 6)

R017 ³ Ring 7 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 7)

R017 ³ Ring 8 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 8)

R017 ³ Ring 9 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 9)

R017 ³ Ring 10 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(10)

R017 ³ Ring 11 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(11)

R017 ³ Ring 12 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(12)

³ ³ ³ ³ ³ R018 ³ Fruits, vegetables and grain consumption (kg/yr) ³ 1.120E+02 ³ 1.600E+02 ³ --- ³ DIET(1)

R018 ³ Leafy vegetable consumption (kg/yr) ³ 2.140E+01 ³ 1.400E+01 ³ --- ³ DIET(2)

R018 ³ Milk consumption (L/yr) ³ 2.330E+02 ³ 9.200E+01 ³ --- ³ DIET(3)

R018 ³ Meat and poultry consumption (kg/yr) ³ 6.510E+01 ³ 6.300E+01 ³ --- ³ DIET(4)

R018 ³ Fish consumption (kg/yr) ³ 2.060E+01 ³ 5.400E+00 ³ --- ³ DIET(5)

R018 ³ Other seafood consumption (kg/yr) ³ 9.000E-01 ³ 9.000E-01 ³ --- ³ DIET(6)

R018 ³ Soil ingestion rate (g/yr) ³ 1.826E+01 ³ 3.650E+01 ³ --- ³ SOIL R018 ³ Drinking water intake (L/yr) ³ 4.785E+02 ³ 5.100E+02 ³ --- ³ DWI R018 ³ Contamination fraction of drinking water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FDW R018 ³ Contamination fraction of household water ³ not used ³ 1.000E+00 ³ --- ³ FHHW R018 ³ Contamination fraction of livestock water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FLW R018 ³ Contamination fraction of irrigation water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FIRW R018 ³ Contamination fraction of aquatic food ³ 1.000E+00 ³ 5.000E-01 ³ --- ³ FR9 R018 ³ Contamination fraction of plant food ³ 1.000E+00 ³-1 ³ --- ³ FPLANT R018 ³ Contamination fraction of meat ³ 1.000E+00 ³-1 ³ --- ³ FMEAT R018 ³ Contamination fraction of milk ³ 1.000E+00 ³-1 ³ --- ³ FMILK

³ ³ ³ ³ ³ R019 ³ Livestock fodder intake for meat (kg/day) ³ 2.710E+01 ³ 6.800E+01 ³ --- ³ LFI5 R019 ³ Livestock fodder intake for milk (kg/day) ³ 6.320E+01 ³ 5.500E+01 ³ --- ³ LFI6 R019 ³ Livestock water intake for meat (L/day) ³ 5.060E+01 ³ 5.000E+01 ³ --- ³ LWI5 R019 ³ Livestock water intake for milk (L/day) ³ 6.000E+01 ³ 1.600E+02 ³ --- ³ LWI6 R019 ³ Livestock soil intake (kg/day) ³ 5.000E-01 ³ 5.000E-01 ³ --- ³ LSI R019 ³ Mass loading for foliar deposition (g/m**3) ³ 4.000E-04 ³ 1.000E-04 ³ --- ³ MLFD 1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/11/2003 10:34 Page 6 Summary : Yankee Rowe Sensitivity Analysis=soil File: Am-241_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R019 ³ Depth of soil mixing layer (m) ³ 2.300E-01 ³ 1.500E-01 ³ --- ³ DM R019 ³ Depth of roots (m) ³ 1.170E+00 ³ 9.000E-01 ³ --- ³ DROOT R019 ³ Drinking water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWDW R019 ³ Household water fraction from ground water ³ not used ³ 1.000E+00 ³ --- ³ FGWHH R019 ³ Livestock water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWLW R019 ³ Irrigation fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWIR

³ ³ ³ ³ ³ R19B ³ Wet weight crop yield for Non-Leafy (kg/m**2) ³ 1.750E+00 ³ 7.000E-01 ³ --- ³ YV(1)

R19B ³ Wet weight crop yield for Leafy (kg/m**2) ³ 2.889E+00 ³ 1.500E+00 ³ --- ³ YV(2)

R19B ³ Wet weight crop yield for Fodder (kg/m**2) ³ 1.887E+00 ³ 1.100E+00 ³ --- ³ YV(3)

R19B ³ Growing Season for Non-Leafy (years) ³ 2.460E-01 ³ 1.700E-01 ³ --- ³ TE(1)

R19B ³ Growing Season for Leafy (years) ³ 1.230E-01 ³ 2.500E-01 ³ --- ³ TE(2)

R19B ³ Growing Season for Fodder (years) ³ 8.200E-02 ³ 8.000E-02 ³ --- ³ TE(3)

R19B ³ Translocation Factor for Non-Leafy ³ 1.000E-01 ³ 1.000E-01 ³ --- ³ TIV(1)

R19B ³ Translocation Factor for Leafy ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(2)

R19B ³ Translocation Factor for Fodder ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(3)

R19B ³ Dry Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(1)

R19B ³ Dry Foliar Interception Fraction for Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(2)

R19B ³ Dry Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(3)

R19B ³ Wet Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(1)

R19B ³ Wet Foliar Interception Fraction for Leafy ³ 5.800E-01 ³ 2.500E-01 ³ --- ³ RWET(2)

R19B ³ Wet Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(3)

R19B ³ Weathering Removal Constant for Vegetation ³ 3.300E+01 ³ 2.000E+01 ³ --- ³ WLAM

³ ³ ³ ³ ³ C14 ³ C-12 concentration in water (g/cm**3) ³ not used ³ 2.000E-05 ³ --- ³ C12WTR C14 ³ C-12 concentration in contaminated soil (g/g) ³ not used ³ 3.000E-02 ³ --- ³ C12CZ C14 ³ Fraction of vegetation carbon from soil ³ not used ³ 2.000E-02 ³ --- ³ CSOIL C14 ³ Fraction of vegetation carbon from air ³ not used ³ 9.800E-01 ³ --- ³ CAIR C14 ³ C-14 evasion layer thickness in soil (m) ³ not used ³ 3.000E-01 ³ --- ³ DMC C14 ³ C-14 evasion flux rate from soil (1/sec) ³ not used ³ 7.000E-07 ³ --- ³ EVSN C14 ³ C-12 evasion flux rate from soil (1/sec) ³ not used ³ 1.000E-10 ³ --- ³ REVSN C14 ³ Fraction of grain in beef cattle feed ³ not used ³ 8.000E-01 ³ --- ³ AVFG4 C14 ³ Fraction of grain in milk cow feed ³ not used ³ 2.000E-01 ³ --- ³ AVFG5 C14 ³ DCF correction factor for gaseous forms of C14 ³ not used ³ 8.894E+01 ³ --- ³ CO2F

³ ³ ³ ³ ³ STOR ³ Storage times of contaminated foodstuffs (days): ³ ³ ³ ³ STOR ³ Fruits, non-leafy vegetables, and grain ³ 1.400E+01 ³ 1.400E+01 ³ --- ³ STOR_T(1)

STOR ³ Leafy vegetables ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(2)

STOR ³ Milk ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(3)

STOR ³ Meat and poultry ³ 2.000E+01 ³ 2.000E+01 ³ --- ³ STOR_T(4)

STOR ³ Fish ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(5)

STOR ³ Crustacea and mollusks ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(6)

STOR ³ Well water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(7)

STOR ³ Surface water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(8)

STOR ³ Livestock fodder ³ 4.500E+01 ³ 4.500E+01 ³ --- ³ STOR_T(9)

³ ³ ³ ³ ³ R021 ³ Thickness of building foundation (m) ³ not used ³ 1.500E-01 ³ --- ³ FLOOR1 R021 ³ Bulk density of building foundation (g/cm**3) ³ not used ³ 2.400E+00 ³ --- ³ DENSFL R021 ³ Total porosity of the cover material ³ not used ³ 4.000E-01 ³ --- ³ TPCV

R021 ³ Total porosity of the building foundation ³ not used ³ 1.000E-01 ³ --- ³ TPFL R021 ³ Volumetric water content of the cover material ³ not used ³ 5.000E-02 ³ --- ³ PH2OCV 1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/11/2003 10:34 Page 7 Summary : Yankee Rowe Sensitivity Analysis=soil File: Am-241_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R021 ³ Volumetric water content of the foundation ³ not used ³ 3.000E-02 ³ --- ³ PH2OFL R021 ³ Diffusion coefficient for radon gas (m/sec): ³ ³ ³ ³ R021 ³ in cover material ³ not used ³ 2.000E-06 ³ --- ³ DIFCV R021 ³ in foundation material ³ not used ³ 3.000E-07 ³ --- ³ DIFFL R021 ³ in contaminated zone soil ³ not used ³ 2.000E-06 ³ --- ³ DIFCZ R021 ³ Radon vertical dimension of mixing (m) ³ not used ³ 2.000E+00 ³ --- ³ HMIX R021 ³ Average building air exchange rate (1/hr) ³ not used ³ 5.000E-01 ³ --- ³ REXG R021 ³ Height of the building (room) (m) ³ not used ³ 2.500E+00 ³ --- ³ HRM R021 ³ Building interior area factor ³ not used ³ 0.000E+00 ³ --- ³ FAI R021 ³ Building depth below ground surface (m) ³ not used ³-1.000E+00 ³ --- ³ DMFL R021 ³ Emanating power of Rn-222 gas ³ not used ³ 2.500E-01 ³ --- ³ EMANA(1)

R021 ³ Emanating power of Rn-220 gas ³ not used ³ 1.500E-01 ³ --- ³ EMANA(2)

³ ³ ³ ³ ³ TITL ³ Number of graphical time points ³ 32 ³ --- ³ --- ³ NPTS TITL ³ Maximum number of integration points for dose ³ 17 ³ --- ³ --- ³ LYMAX TITL ³ Maximum number of integration points for risk ³ 1 ³ --- ³ --- ³ KYMAX

Summary of Pathway Selections Pathway ³ User Selection

Å 1 -- external gamma ³ active 2 -- inhalation (w/o radon)³ active 3 -- plant ingestion ³ active 4 -- meat ingestion ³ active 5 -- milk ingestion ³ active 6 -- aquatic foods ³ active 7 -- drinking water ³ active 8 -- soil ingestion ³ active 9 -- radon ³ suppressed Find peak pathway doses ³ active

1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/26/2003 15:09 Page 2 Summary : Yankee Rowe Sensitivity Analysis=soil File: C14_DCGL.RAD Dose Conversion Factor (and Related) Parameter Summary File: FGR 13 Morbidity 0 ³ ³ Current ³ ³ Parameter Menu ³ Parameter ³ Value ³ Default ³ Name

ÅÅÅÅ B-1 ³ Dose conversion factors for inhalation, mrem/pCi: ³ ³ ³ B-1 ³ C-14 ³ 2.090E-06 ³ 2.090E-06 ³ DCF2( 1)

³ ³ ³ ³ D-1 ³ Dose conversion factors for ingestion, mrem/pCi: ³ ³ ³ D-1 ³ C-14 ³ 2.090E-06 ³ 2.090E-06 ³ DCF3( 1)

³ ³ ³ ³ D-34 ³ Food transfer factors: ³ ³ ³ D-34 ³ C-14, plant/soil concentration ratio, dimensionless ³ 5.500E+00 ³ 5.500E+00 ³ RTF( 1,1)

D-34 ³ C-14, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 3.100E-02 ³ 3.100E-02 ³ RTF( 1,2)

D-34 ³ C-14, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 1.200E-02 ³ 1.200E-02 ³ RTF( 1,3)

³ ³ ³ ³ D-5 ³ Bioaccumulation factors, fresh water, L/kg: ³ ³ ³ D-5 ³ C-14, fish ³ 5.000E+04 ³ 5.000E+04 ³ BIOFAC( 1,1)

D-5 ³ C-14, crustacea and mollusks ³ 9.100E+03 ³ 9.100E+03 ³ BIOFAC( 1,2) 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/26/2003 15:09 Page 3 Summary : Yankee Rowe Sensitivity Analysis=soil File: C14_DCGL.RAD Site-Specific Parameter Summary 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R011 ³ Area of contaminated zone (m**2) ³ 1.302E+04 ³ 1.000E+04 ³ --- ³ AREA R011 ³ Thickness of contaminated zone (m) ³ 2.890E+00 ³ 2.000E+00 ³ --- ³ THICK0 R011 ³ Length parallel to aquifer flow (m) ³ 1.290E+02 ³ 1.000E+02 ³ --- ³ LCZPAQ R011 ³ Basic radiation dose limit (mrem/yr) ³ 2.500E+01 ³ 2.500E+01 ³ --- ³ BRDL R011 ³ Time since placement of material (yr) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ TI R011 ³ Times for calculations (yr) ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ T( 2)

R011 ³ Times for calculations (yr) ³ 3.000E+00 ³ 3.000E+00 ³ --- ³ T( 3)

R011 ³ Times for calculations (yr) ³ 1.000E+01 ³ 1.000E+01 ³ --- ³ T( 4)

R011 ³ Times for calculations (yr) ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ T( 5)

R011 ³ Times for calculations (yr) ³ 1.000E+02 ³ 1.000E+02 ³ --- ³ T( 6)

R011 ³ Times for calculations (yr) ³ 3.000E+02 ³ 3.000E+02 ³ --- ³ T( 7)

R011 ³ Times for calculations (yr) ³ 1.000E+03 ³ 1.000E+03 ³ --- ³ T( 8)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T( 9)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T(10)

³ ³ ³ ³ ³ R012 ³ Initial principal radionuclide (pCi/g): C-14 ³ 1.000E+00 ³ 0.000E+00 ³ --- ³ S1( 1)

R012 ³ Concentration in groundwater (pCi/L): C-14 ³ not used ³ 0.000E+00 ³ --- ³ W1( 1)

³ ³ ³ ³ ³ R013 ³ Cover depth (m) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ COVER0 R013 ³ Density of cover material (g/cm**3) ³ not used ³ 1.500E+00 ³ --- ³ DENSCV R013 ³ Cover depth erosion rate (m/yr) ³ not used ³ 1.000E-03 ³ --- ³ VCV R013 ³ Density of contaminated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSCZ R013 ³ Contaminated zone erosion rate (m/yr) ³ 8.500E-04 ³ 1.000E-03 ³ --- ³ VCZ R013 ³ Contaminated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPCZ R013 ³ Contaminated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCCZ R013 ³ Contaminated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCCZ R013 ³ Contaminated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BCZ R013 ³ Average annual wind speed (m/sec) ³ 2.030E+00 ³ 2.000E+00 ³ --- ³ WIND R013 ³ Humidity in air (g/m**3) ³ not used ³ 8.000E+00 ³ --- ³ HUMID R013 ³ Evapotranspiration coefficient ³ 6.250E-01 ³ 5.000E-01 ³ --- ³ EVAPTR R013 ³ Precipitation (m/yr) ³ 1.200E+00 ³ 1.000E+00 ³ --- ³ PRECIP R013 ³ Irrigation (m/yr) ³ 4.350E-01 ³ 2.000E-01 ³ --- ³ RI R013 ³ Irrigation mode ³ overhead ³ overhead ³ --- ³ IDITCH R013 ³ Runoff coefficient ³ 6.000E-01 ³ 2.000E-01 ³ --- ³ RUNOFF R013 ³ Watershed area for nearby stream or pond (m**2) ³ 7.770E+05 ³ 1.000E+06 ³ --- ³ WAREA R013 ³ Accuracy for water/soil computations ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ EPS

³ ³ ³ ³ ³ R014 ³ Density of saturated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSAQ R014 ³ Saturated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPSZ R014 ³ Saturated zone effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPSZ R014 ³ Saturated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCSZ R014 ³ Saturated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+02 ³ --- ³ HCSZ R014 ³ Saturated zone hydraulic gradient ³ 1.000E-01 ³ 2.000E-02 ³ --- ³ HGWT R014 ³ Saturated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BSZ R014 ³ Water table drop rate (m/yr) ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ VWT R014 ³ Well pump intake depth (m below water table) ³ 1.451E+01 ³ 1.000E+01 ³ --- ³ DWIBWT R014 ³ Model: Nondispersion (ND) or Mass-Balance (MB) ³ ND ³ ND ³ --- ³ MODEL R014 ³ Well pumping rate (m**3/yr) ³ 1.323E+03 ³ 2.500E+02 ³ --- ³ UW

³ ³ ³ ³ ³ R015 ³ Number of unsaturated zone strata ³ 1 ³ 1 ³ --- ³ NS 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/26/2003 15:09 Page 4 Summary : Yankee Rowe Sensitivity Analysis=soil File: C14_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R015 ³ Unsat. zone 1, thickness (m) ³ 1.820E+00 ³ 4.000E+00 ³ --- ³ H(1)

R015 ³ Unsat. zone 1, soil density (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSUZ(1)

R015 ³ Unsat. zone 1, total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPUZ(1)

R015 ³ Unsat. zone 1, effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPUZ(1)

R015 ³ Unsat. zone 1, field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCUZ(1)

R015 ³ Unsat. zone 1, soil-specific b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BUZ(1)

R015 ³ Unsat. zone 1, hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCUZ(1)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for C-14 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 1.100E+01 ³ 0.000E+00 ³ --- ³ DCNUCC( 1)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 1.100E+01 ³ 0.000E+00 ³ --- ³ DCNUCU( 1,1)

R016 ³ Saturated zone (cm**3/g) ³ 1.100E+01 ³ 0.000E+00 ³ --- ³ DCNUCS( 1)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 7.115E-03 ³ ALEACH( 1)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 1)

³ ³ ³ ³ ³ R017 ³ Inhalation rate (m**3/yr) ³ 8.400E+03 ³ 8.400E+03 ³ --- ³ INHALR R017 ³ Mass loading for inhalation (g/m**3) ³ 2.330E-05 ³ 1.000E-04 ³ --- ³ MLINH R017 ³ Exposure duration ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ ED R017 ³ Shielding factor, inhalation ³ 5.500E-01 ³ 4.000E-01 ³ --- ³ SHF3 R017 ³ Shielding factor, external gamma ³ 2.725E-01 ³ 7.000E-01 ³ --- ³ SHF1 R017 ³ Fraction of time spent indoors ³ 6.571E-01 ³ 5.000E-01 ³ --- ³ FIND R017 ³ Fraction of time spent outdoors (on site) ³ 1.181E-01 ³ 2.500E-01 ³ --- ³ FOTD R017 ³ Shape factor flag, external gamma ³ 1.000E+00 ³ 1.000E+00 ³ >0 shows circular AREA. ³ FS R017 ³ Radii of shape factor array (used if FS = -1): ³ ³ ³ ³ R017 ³ Outer annular radius (m), ring 1: ³ not used ³ 5.000E+01 ³ --- ³ RAD_SHAPE(

1)

R017 ³ Outer annular radius (m), ring 2: ³ not used ³ 7.071E+01 ³ --- ³ RAD_SHAPE(

2)

R017 ³ Outer annular radius (m), ring 3: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

3)

R017 ³ Outer annular radius (m), ring 4: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

4)

R017 ³ Outer annular radius (m), ring 5: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

5)

R017 ³ Outer annular radius (m), ring 6: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

6)

R017 ³ Outer annular radius (m), ring 7: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

7)

R017 ³ Outer annular radius (m), ring 8: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

8)

R017 ³ Outer annular radius (m), ring 9: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

9)

R017 ³ Outer annular radius (m), ring 10: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (10)

R017 ³ Outer annular radius (m), ring 11: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (11)

R017 ³ Outer annular radius (m), ring 12: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (12)

³ ³ ³ ³ ³ R017 ³ Fractions of annular areas within AREA: ³ ³ ³ ³ R017 ³ Ring 1 ³ not used ³ 1.000E+00 ³ --- ³ FRACA( 1)

R017 ³ Ring 2 ³ not used ³ 2.732E-01 ³ --- ³ FRACA( 2)

R017 ³ Ring 3 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 3)

R017 ³ Ring 4 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 4)

R017 ³ Ring 5 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 5)

R017 ³ Ring 6 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 6)

R017 ³ Ring 7 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 7)

R017 ³ Ring 8 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 8)

R017 ³ Ring 9 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 9)

R017 ³ Ring 10 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(10)

R017 ³ Ring 11 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(11)

R017 ³ Ring 12 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(12)

³ ³ ³ ³ ³ 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/26/2003 15:09 Page 5 Summary : Yankee Rowe Sensitivity Analysis=soil File: C14_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R018 ³ Fruits, vegetables and grain consumption (kg/yr) ³ 1.120E+02 ³ 1.600E+02 ³ --- ³ DIET(1)

R018 ³ Leafy vegetable consumption (kg/yr) ³ 2.140E+01 ³ 1.400E+01 ³ --- ³ DIET(2)

R018 ³ Milk consumption (L/yr) ³ 2.330E+02 ³ 9.200E+01 ³ --- ³ DIET(3)

R018 ³ Meat and poultry consumption (kg/yr) ³ 6.510E+01 ³ 6.300E+01 ³ --- ³ DIET(4)

R018 ³ Fish consumption (kg/yr) ³ 2.060E+01 ³ 5.400E+00 ³ --- ³ DIET(5)

R018 ³ Other seafood consumption (kg/yr) ³ 9.000E-01 ³ 9.000E-01 ³ --- ³ DIET(6)

R018 ³ Soil ingestion rate (g/yr) ³ 1.826E+01 ³ 3.650E+01 ³ --- ³ SOIL R018 ³ Drinking water intake (L/yr) ³ 4.785E+02 ³ 5.100E+02 ³ --- ³ DWI R018 ³ Contamination fraction of drinking water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FDW R018 ³ Contamination fraction of household water ³ not used ³ 1.000E+00 ³ --- ³ FHHW R018 ³ Contamination fraction of livestock water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FLW R018 ³ Contamination fraction of irrigation water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FIRW R018 ³ Contamination fraction of aquatic food ³ 1.000E+00 ³ 5.000E-01 ³ --- ³ FR9 R018 ³ Contamination fraction of plant food ³ 1.000E+00 ³-1 ³ --- ³ FPLANT R018 ³ Contamination fraction of meat ³ 1.000E+00 ³-1 ³ --- ³ FMEAT R018 ³ Contamination fraction of milk ³ 1.000E+00 ³-1 ³ --- ³ FMILK

³ ³ ³ ³ ³ R019 ³ Livestock fodder intake for meat (kg/day) ³ 2.710E+01 ³ 6.800E+01 ³ --- ³ LFI5 R019 ³ Livestock fodder intake for milk (kg/day) ³ 6.320E+01 ³ 5.500E+01 ³ --- ³ LFI6 R019 ³ Livestock water intake for meat (L/day) ³ 5.060E+01 ³ 5.000E+01 ³ --- ³ LWI5 R019 ³ Livestock water intake for milk (L/day) ³ 6.000E+01 ³ 1.600E+02 ³ --- ³ LWI6 R019 ³ Livestock soil intake (kg/day) ³ 5.000E-01 ³ 5.000E-01 ³ --- ³ LSI R019 ³ Mass loading for foliar deposition (g/m**3) ³ 4.000E-04 ³ 1.000E-04 ³ --- ³ MLFD R019 ³ Depth of soil mixing layer (m) ³ 2.300E-01 ³ 1.500E-01 ³ --- ³ DM R019 ³ Depth of roots (m) ³ 1.170E+00 ³ 9.000E-01 ³ --- ³ DROOT R019 ³ Drinking water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWDW R019 ³ Household water fraction from ground water ³ not used ³ 1.000E+00 ³ --- ³ FGWHH R019 ³ Livestock water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWLW R019 ³ Irrigation fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWIR

³ ³ ³ ³ ³ R19B ³ Wet weight crop yield for Non-Leafy (kg/m**2) ³ 1.750E+00 ³ 7.000E-01 ³ --- ³ YV(1)

R19B ³ Wet weight crop yield for Leafy (kg/m**2) ³ 2.889E+00 ³ 1.500E+00 ³ --- ³ YV(2)

R19B ³ Wet weight crop yield for Fodder (kg/m**2) ³ 1.887E+00 ³ 1.100E+00 ³ --- ³ YV(3)

R19B ³ Growing Season for Non-Leafy (years) ³ 2.460E-01 ³ 1.700E-01 ³ --- ³ TE(1)

R19B ³ Growing Season for Leafy (years) ³ 1.230E-01 ³ 2.500E-01 ³ --- ³ TE(2)

R19B ³ Growing Season for Fodder (years) ³ 8.200E-02 ³ 8.000E-02 ³ --- ³ TE(3)

R19B ³ Translocation Factor for Non-Leafy ³ 1.000E-01 ³ 1.000E-01 ³ --- ³ TIV(1)

R19B ³ Translocation Factor for Leafy ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(2)

R19B ³ Translocation Factor for Fodder ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(3)

R19B ³ Dry Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(1)

R19B ³ Dry Foliar Interception Fraction for Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(2)

R19B ³ Dry Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(3)

R19B ³ Wet Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(1)

R19B ³ Wet Foliar Interception Fraction for Leafy ³ 5.800E-01 ³ 2.500E-01 ³ --- ³ RWET(2)

R19B ³ Wet Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(3)

R19B ³ Weathering Removal Constant for Vegetation ³ 3.300E+01 ³ 2.000E+01 ³ --- ³ WLAM

³ ³ ³ ³ ³ C14 ³ C-12 concentration in water (g/cm**3) ³ 2.000E-05 ³ 2.000E-05 ³ --- ³ C12WTR C14 ³ C-12 concentration in contaminated soil (g/g) ³ 3.000E-02 ³ 3.000E-02 ³ --- ³ C12CZ C14 ³ Fraction of vegetation carbon from soil ³ 2.000E-02 ³ 2.000E-02 ³ --- ³ CSOIL C14 ³ Fraction of vegetation carbon from air ³ 9.800E-01 ³ 9.800E-01 ³ --- ³ CAIR 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/26/2003 15:09 Page 6 Summary : Yankee Rowe Sensitivity Analysis=soil File: C14_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ C14 ³ C-14 evasion layer thickness in soil (m) ³ 4.270E-01 ³ 3.000E-01 ³ --- ³ DMC C14 ³ C-14 evasion flux rate from soil (1/sec) ³ 7.000E-07 ³ 7.000E-07 ³ --- ³ EVSN C14 ³ C-12 evasion flux rate from soil (1/sec) ³ 1.000E-10 ³ 1.000E-10 ³ --- ³ REVSN C14 ³ Fraction of grain in beef cattle feed ³ 2.500E-01 ³ 8.000E-01 ³ --- ³ AVFG4 C14 ³ Fraction of grain in milk cow feed ³ 1.000E-01 ³ 2.000E-01 ³ --- ³ AVFG5 C14 ³ DCF correction factor for gaseous forms of C14 ³ 8.894E+01 ³ 8.894E+01 ³ --- ³ CO2F

³ ³ ³ ³ ³ STOR ³ Storage times of contaminated foodstuffs (days): ³ ³ ³ ³ STOR ³ Fruits, non-leafy vegetables, and grain ³ 1.400E+01 ³ 1.400E+01 ³ --- ³ STOR_T(1)

STOR ³ Leafy vegetables ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(2)

STOR ³ Milk ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(3)

STOR ³ Meat and poultry ³ 2.000E+01 ³ 2.000E+01 ³ --- ³ STOR_T(4)

STOR ³ Fish ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(5)

STOR ³ Crustacea and mollusks ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(6)

STOR ³ Well water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(7)

STOR ³ Surface water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(8)

STOR ³ Livestock fodder ³ 4.500E+01 ³ 4.500E+01 ³ --- ³ STOR_T(9)

³ ³ ³ ³ ³ R021 ³ Thickness of building foundation (m) ³ not used ³ 1.500E-01 ³ --- ³ FLOOR1 R021 ³ Bulk density of building foundation (g/cm**3) ³ not used ³ 2.400E+00 ³ --- ³ DENSFL R021 ³ Total porosity of the cover material ³ not used ³ 4.000E-01 ³ --- ³ TPCV R021 ³ Total porosity of the building foundation ³ not used ³ 1.000E-01 ³ --- ³ TPFL R021 ³ Volumetric water content of the cover material ³ not used ³ 5.000E-02 ³ --- ³ PH2OCV R021 ³ Volumetric water content of the foundation ³ not used ³ 3.000E-02 ³ --- ³ PH2OFL R021 ³ Diffusion coefficient for radon gas (m/sec): ³ ³ ³ ³ R021 ³ in cover material ³ not used ³ 2.000E-06 ³ --- ³ DIFCV R021 ³ in foundation material ³ not used ³ 3.000E-07 ³ --- ³ DIFFL R021 ³ in contaminated zone soil ³ not used ³ 2.000E-06 ³ --- ³ DIFCZ R021 ³ Radon vertical dimension of mixing (m) ³ not used ³ 2.000E+00 ³ --- ³ HMIX R021 ³ Average building air exchange rate (1/hr) ³ not used ³ 5.000E-01 ³ --- ³ REXG R021 ³ Height of the building (room) (m) ³ not used ³ 2.500E+00 ³ --- ³ HRM R021 ³ Building interior area factor ³ not used ³ 0.000E+00 ³ --- ³ FAI R021 ³ Building depth below ground surface (m) ³ not used ³-1.000E+00 ³ --- ³ DMFL R021 ³ Emanating power of Rn-222 gas ³ not used ³ 2.500E-01 ³ --- ³ EMANA(1)

R021 ³ Emanating power of Rn-220 gas ³ not used ³ 1.500E-01 ³ --- ³ EMANA(2)

³ ³ ³ ³ ³ TITL ³ Number of graphical time points ³ 32 ³ --- ³ --- ³ NPTS TITL ³ Maximum number of integration points for dose ³ 17 ³ --- ³ --- ³ LYMAX TITL ³ Maximum number of integration points for risk ³ 1 ³ --- ³ --- ³ KYMAX

1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/26/2003 15:09 Page 7 Summary : Yankee Rowe Sensitivity Analysis=soil File: C14_DCGL.RAD Summary of Pathway Selections Pathway ³ User Selection

Å 1 -- external gamma ³ active 2 -- inhalation (w/o radon)³ active 3 -- plant ingestion ³ active 4 -- meat ingestion ³ active 5 -- milk ingestion ³ active 6 -- aquatic foods ³ active 7 -- drinking water ³ active 8 -- soil ingestion ³ active 9 -- radon ³ suppressed Find peak pathway doses ³ active

1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/03/2003 11:50 Page 2 Summary : Yankee Rowe Sensitivity Analysis=soil File: Cm-243_DCGL.RAD Dose Conversion Factor (and Related) Parameter Summary File: YR soil DCGL Cm lib 0 ³ ³ Current ³ ³ Parameter Menu ³ Parameter ³ Value ³ Default ³ Name

ÅÅÅÅ B-1 ³ Dose conversion factors for inhalation, mrem/pCi: ³ ³ ³ B-1 ³ Ac-227+D ³ 6.720E+00 ³ 6.720E+00 ³ DCF2( 1)

B-1 ³ Am-243+D ³ 4.400E-01 ³ 4.400E-01 ³ DCF2( 2)

B-1 ³ Cm-243 ³ 3.070E-01 ³ 3.070E-01 ³ DCF2( 3)

B-1 ³ Pa-231 ³ 1.280E+00 ³ 1.280E+00 ³ DCF2( 5)

B-1 ³ Pu-239 ³ 4.290E-01 ³ 4.290E-01 ³ DCF2( 6)

B-1 ³ U-235+D ³ 1.230E-01 ³ 1.230E-01 ³ DCF2( 7)

³ ³ ³ ³ D-1 ³ Dose conversion factors for ingestion, mrem/pCi: ³ ³ ³ D-1 ³ Ac-227+D ³ 1.480E-02 ³ 1.480E-02 ³ DCF3( 1)

D-1 ³ Am-243+D ³ 3.630E-03 ³ 3.630E-03 ³ DCF3( 2)

D-1 ³ Cm-243 ³ 2.510E-03 ³ 2.510E-03 ³ DCF3( 3)

D-1 ³ Pa-231 ³ 1.060E-02 ³ 1.060E-02 ³ DCF3( 5)

D-1 ³ Pu-239 ³ 3.540E-03 ³ 3.540E-03 ³ DCF3( 6)

D-1 ³ U-235+D ³ 2.670E-04 ³ 2.670E-04 ³ DCF3( 7)

³ ³ ³ ³ D-34 ³ Food transfer factors: ³ ³ ³ D-34 ³ Ac-227+D, plant/soil concentration ratio, dimensionless ³ 2.500E-03 ³ 2.500E-03 ³ RTF( 1,1)

D-34 ³ Ac-227+D, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 2.000E-05 ³ 2.000E-05 ³ RTF( 1,2)

D-34 ³ Ac-227+D, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 2.000E-05 ³ 2.000E-05 ³ RTF( 1,3)

D-34 ³ ³ ³ ³ D-34 ³ Am-243+D, plant/soil concentration ratio, dimensionless ³ 1.000E-03 ³ 1.000E-03 ³ RTF( 2,1)

D-34 ³ Am-243+D, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 5.000E-05 ³ 5.000E-05 ³ RTF( 2,2)

D-34 ³ Am-243+D, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 2.000E-06 ³ 2.000E-06 ³ RTF( 2,3)

D-34 ³ ³ ³ ³ D-34 ³ Cm-243, plant/soil concentration ratio, dimensionless ³ 1.830E-03 ³ 1.000E-03 ³ RTF( 3,1)

D-34 ³ Cm-243, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 2.000E-05 ³ 2.000E-05 ³ RTF( 3,2)

D-34 ³ Cm-243, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 2.000E-06 ³ 2.000E-06 ³ RTF( 3,3)

D-34 ³ ³ ³ ³ D-34 ³ Pa-231, plant/soil concentration ratio, dimensionless ³ 1.000E-02 ³ 1.000E-02 ³ RTF( 5,1)

D-34 ³ Pa-231, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 5.000E-03 ³ 5.000E-03 ³ RTF( 5,2)

D-34 ³ Pa-231, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 5.000E-06 ³ 5.000E-06 ³ RTF( 5,3)

D-34 ³ ³ ³ ³ D-34 ³ Pu-239, plant/soil concentration ratio, dimensionless ³ 1.000E-03 ³ 1.000E-03 ³ RTF( 6,1)

D-34 ³ Pu-239, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 1.000E-04 ³ 1.000E-04 ³ RTF( 6,2)

D-34 ³ Pu-239, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 1.000E-06 ³ 1.000E-06 ³ RTF( 6,3)

D-34 ³ ³ ³ ³ D-34 ³ U-235+D, plant/soil concentration ratio, dimensionless ³ 2.500E-03 ³ 2.500E-03 ³ RTF( 7,1)

D-34 ³ U-235+D, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 3.400E-04 ³ 3.400E-04 ³ RTF( 7,2)

D-34 ³ U-235+D, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 6.000E-04 ³ 6.000E-04 ³ RTF( 7,3)

³ ³ ³ ³ D-5 ³ Bioaccumulation factors, fresh water, L/kg: ³ ³ ³ D-5 ³ Ac-227+D, fish ³ 1.500E+01 ³ 1.500E+01 ³ BIOFAC( 1,1)

D-5 ³ Ac-227+D, crustacea and mollusks ³ 1.000E+03 ³ 1.000E+03 ³ BIOFAC( 1,2)

D-5 ³ ³ ³ ³ D-5 ³ Am-243+D, fish ³ 3.000E+01 ³ 3.000E+01 ³ BIOFAC( 2,1)

D-5 ³ Am-243+D, crustacea and mollusks ³ 1.000E+03 ³ 1.000E+03 ³ BIOFAC( 2,2)

D-5 ³ ³ ³ ³ D-5 ³ Cm-243, fish ³ 3.000E+01 ³ 3.000E+01 ³ BIOFAC( 3,1)

D-5 ³ Cm-243, crustacea and mollusks ³ 1.000E+03 ³ 1.000E+03 ³ BIOFAC( 3,2)

D-5 ³ ³ ³ ³ 1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/03/2003 11:50 Page 3 Summary : Yankee Rowe Sensitivity Analysis=soil File: Cm-243_DCGL.RAD Dose Conversion Factor (and Related) Parameter Summary (continued)

File: YR soil DCGL Cm lib 0 ³ ³ Current ³ ³ Parameter Menu ³ Parameter ³ Value ³ Default ³ Name

ÅÅÅÅ D-5 ³ Pa-231, fish ³ 1.000E+01 ³ 1.000E+01 ³ BIOFAC( 5,1)

D-5 ³ Pa-231, crustacea and mollusks ³ 1.100E+02 ³ 1.100E+02 ³ BIOFAC( 5,2)

D-5 ³ ³ ³ ³ D-5 ³ Pu-239, fish ³ 3.000E+01 ³ 3.000E+01 ³ BIOFAC( 6,1)

D-5 ³ Pu-239, crustacea and mollusks ³ 1.000E+02 ³ 1.000E+02 ³ BIOFAC( 6,2)

D-5 ³ ³ ³ ³ D-5 ³ U-235+D, fish ³ 1.000E+01 ³ 1.000E+01 ³ BIOFAC( 7,1)

D-5 ³ U-235+D, crustacea and mollusks ³ 6.000E+01 ³ 6.000E+01 ³ BIOFAC( 7,2) 1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/03/2003 11:50 Page 4 Summary : Yankee Rowe Sensitivity Analysis=soil File: Cm-243_DCGL.RAD Site-Specific Parameter Summary 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R011 ³ Area of contaminated zone (m**2) ³ 1.302E+04 ³ 1.000E+04 ³ --- ³ AREA R011 ³ Thickness of contaminated zone (m) ³ 1.975E+00 ³ 2.000E+00 ³ --- ³ THICK0 R011 ³ Length parallel to aquifer flow (m) ³ 1.290E+02 ³ 1.000E+02 ³ --- ³ LCZPAQ R011 ³ Basic radiation dose limit (mrem/yr) ³ 2.500E+01 ³ 2.500E+01 ³ --- ³ BRDL R011 ³ Time since placement of material (yr) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ TI R011 ³ Times for calculations (yr) ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ T( 2)

R011 ³ Times for calculations (yr) ³ 3.000E+00 ³ 3.000E+00 ³ --- ³ T( 3)

R011 ³ Times for calculations (yr) ³ 1.000E+01 ³ 1.000E+01 ³ --- ³ T( 4)

R011 ³ Times for calculations (yr) ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ T( 5)

R011 ³ Times for calculations (yr) ³ 1.000E+02 ³ 1.000E+02 ³ --- ³ T( 6)

R011 ³ Times for calculations (yr) ³ 3.000E+02 ³ 3.000E+02 ³ --- ³ T( 7)

R011 ³ Times for calculations (yr) ³ 1.000E+03 ³ 1.000E+03 ³ --- ³ T( 8)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T( 9)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T(10)

³ ³ ³ ³ ³ R012 ³ Initial principal radionuclide (pCi/g): Cm-243 ³ 1.000E+00 ³ 0.000E+00 ³ --- ³ S1( 3)

R012 ³ Concentration in groundwater (pCi/L): Cm-243 ³ not used ³ 0.000E+00 ³ --- ³ W1( 3)

³ ³ ³ ³ ³ R013 ³ Cover depth (m) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ COVER0 R013 ³ Density of cover material (g/cm**3) ³ not used ³ 1.500E+00 ³ --- ³ DENSCV R013 ³ Cover depth erosion rate (m/yr) ³ not used ³ 1.000E-03 ³ --- ³ VCV R013 ³ Density of contaminated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSCZ R013 ³ Contaminated zone erosion rate (m/yr) ³ 8.500E-04 ³ 1.000E-03 ³ --- ³ VCZ R013 ³ Contaminated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPCZ R013 ³ Contaminated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCCZ R013 ³ Contaminated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCCZ R013 ³ Contaminated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BCZ R013 ³ Average annual wind speed (m/sec) ³ 2.030E+00 ³ 2.000E+00 ³ --- ³ WIND R013 ³ Humidity in air (g/m**3) ³ not used ³ 8.000E+00 ³ --- ³ HUMID R013 ³ Evapotranspiration coefficient ³ 6.250E-01 ³ 5.000E-01 ³ --- ³ EVAPTR R013 ³ Precipitation (m/yr) ³ 1.200E+00 ³ 1.000E+00 ³ --- ³ PRECIP R013 ³ Irrigation (m/yr) ³ 4.350E-01 ³ 2.000E-01 ³ --- ³ RI R013 ³ Irrigation mode ³ overhead ³ overhead ³ --- ³ IDITCH R013 ³ Runoff coefficient ³ 6.000E-01 ³ 2.000E-01 ³ --- ³ RUNOFF R013 ³ Watershed area for nearby stream or pond (m**2) ³ 7.770E+05 ³ 1.000E+06 ³ --- ³ WAREA R013 ³ Accuracy for water/soil computations ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ EPS

³ ³ ³ ³ ³ R014 ³ Density of saturated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSAQ R014 ³ Saturated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPSZ R014 ³ Saturated zone effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPSZ R014 ³ Saturated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCSZ R014 ³ Saturated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+02 ³ --- ³ HCSZ R014 ³ Saturated zone hydraulic gradient ³ 1.000E-01 ³ 2.000E-02 ³ --- ³ HGWT R014 ³ Saturated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BSZ R014 ³ Water table drop rate (m/yr) ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ VWT R014 ³ Well pump intake depth (m below water table) ³ 1.451E+01 ³ 1.000E+01 ³ --- ³ DWIBWT R014 ³ Model: Nondispersion (ND) or Mass-Balance (MB) ³ ND ³ ND ³ --- ³ MODEL R014 ³ Well pumping rate (m**3/yr) ³ 1.323E+03 ³ 2.500E+02 ³ --- ³ UW

³ ³ ³ ³ ³ R015 ³ Number of unsaturated zone strata ³ 1 ³ 1 ³ --- ³ NS 1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/03/2003 11:50 Page 5 Summary : Yankee Rowe Sensitivity Analysis=soil File: Cm-243_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R015 ³ Unsat. zone 1, thickness (m) ³ 1.820E+00 ³ 4.000E+00 ³ --- ³ H(1)

R015 ³ Unsat. zone 1, soil density (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSUZ(1)

R015 ³ Unsat. zone 1, total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPUZ(1)

R015 ³ Unsat. zone 1, effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPUZ(1)

R015 ³ Unsat. zone 1, field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCUZ(1)

R015 ³ Unsat. zone 1, soil-specific b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BUZ(1)

R015 ³ Unsat. zone 1, hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCUZ(1)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for Cm-243 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 6.761E+03 ³-1.000E+00 ³ --- ³ DCNUCC( 3)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 6.761E+03 ³-1.000E+00 ³ --- ³ DCNUCU( 3,1)

R016 ³ Saturated zone (cm**3/g) ³ 6.761E+03 ³-1.000E+00 ³ --- ³ DCNUCS( 3)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 1.701E-05 ³ ALEACH( 3)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 3)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for daughter Ac-227 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 8.250E+02 ³ 2.000E+01 ³ --- ³ DCNUCC( 1)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 8.250E+02 ³ 2.000E+01 ³ --- ³ DCNUCU( 1,1)

R016 ³ Saturated zone (cm**3/g) ³ 8.250E+02 ³ 2.000E+01 ³ --- ³ DCNUCS( 1)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 1.394E-04 ³ ALEACH( 1)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 1)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for daughter Am-243 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 1.445E+03 ³ 2.000E+01 ³ --- ³ DCNUCC( 2)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 1.445E+03 ³ 2.000E+01 ³ --- ³ DCNUCU( 2,1)

R016 ³ Saturated zone (cm**3/g) ³ 1.445E+03 ³ 2.000E+01 ³ --- ³ DCNUCS( 2)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 7.959E-05 ³ ALEACH( 2)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 2)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for daughter Pa-231 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 3.800E+02 ³ 5.000E+01 ³ --- ³ DCNUCC( 5)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 3.800E+02 ³ 5.000E+01 ³ --- ³ DCNUCU( 5,1)

R016 ³ Saturated zone (cm**3/g) ³ 3.800E+02 ³ 5.000E+01 ³ --- ³ DCNUCS( 5)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 3.026E-04 ³ ALEACH( 5)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 5)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for daughter Pu-239 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 9.530E+02 ³ 2.000E+03 ³ --- ³ DCNUCC( 6)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 9.530E+02 ³ 2.000E+03 ³ --- ³ DCNUCU( 6,1)

R016 ³ Saturated zone (cm**3/g) ³ 9.530E+02 ³ 2.000E+03 ³ --- ³ DCNUCS( 6)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 1.207E-04 ³ ALEACH( 6)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 6)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for daughter U-235 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 1.260E+02 ³ 5.000E+01 ³ --- ³ DCNUCC( 7)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 1.260E+02 ³ 5.000E+01 ³ --- ³ DCNUCU( 7,1)

R016 ³ Saturated zone (cm**3/g) ³ 1.260E+02 ³ 5.000E+01 ³ --- ³ DCNUCS( 7)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 9.125E-04 ³ ALEACH( 7)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 7)

³ ³ ³ ³ ³

R017 ³ Inhalation rate (m**3/yr) ³ 8.400E+03 ³ 8.400E+03 ³ --- ³ INHALR 1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/03/2003 11:50 Page 6 Summary : Yankee Rowe Sensitivity Analysis=soil File: Cm-243_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R017 ³ Mass loading for inhalation (g/m**3) ³ 2.330E-05 ³ 1.000E-04 ³ --- ³ MLINH R017 ³ Exposure duration ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ ED R017 ³ Shielding factor, inhalation ³ 5.500E-01 ³ 4.000E-01 ³ --- ³ SHF3 R017 ³ Shielding factor, external gamma ³ 3.980E-01 ³ 7.000E-01 ³ --- ³ SHF1 R017 ³ Fraction of time spent indoors ³ 6.571E-01 ³ 5.000E-01 ³ --- ³ FIND R017 ³ Fraction of time spent outdoors (on site) ³ 1.181E-01 ³ 2.500E-01 ³ --- ³ FOTD R017 ³ Shape factor flag, external gamma ³ 1.000E+00 ³ 1.000E+00 ³ >0 shows circular AREA. ³ FS R017 ³ Radii of shape factor array (used if FS = -1): ³ ³ ³ ³ R017 ³ Outer annular radius (m), ring 1: ³ not used ³ 5.000E+01 ³ --- ³ RAD_SHAPE(

1)

R017 ³ Outer annular radius (m), ring 2: ³ not used ³ 7.071E+01 ³ --- ³ RAD_SHAPE(

2)

R017 ³ Outer annular radius (m), ring 3: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

3)

R017 ³ Outer annular radius (m), ring 4: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

4)

R017 ³ Outer annular radius (m), ring 5: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

5)

R017 ³ Outer annular radius (m), ring 6: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

6)

R017 ³ Outer annular radius (m), ring 7: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

7)

R017 ³ Outer annular radius (m), ring 8: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

8)

R017 ³ Outer annular radius (m), ring 9: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

9)

R017 ³ Outer annular radius (m), ring 10: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (10)

R017 ³ Outer annular radius (m), ring 11: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (11)

R017 ³ Outer annular radius (m), ring 12: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (12)

³ ³ ³ ³ ³ R017 ³ Fractions of annular areas within AREA: ³ ³ ³ ³ R017 ³ Ring 1 ³ not used ³ 1.000E+00 ³ --- ³ FRACA( 1)

R017 ³ Ring 2 ³ not used ³ 2.732E-01 ³ --- ³ FRACA( 2)

R017 ³ Ring 3 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 3)

R017 ³ Ring 4 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 4)

R017 ³ Ring 5 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 5)

R017 ³ Ring 6 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 6)

R017 ³ Ring 7 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 7)

R017 ³ Ring 8 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 8)

R017 ³ Ring 9 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 9)

R017 ³ Ring 10 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(10)

R017 ³ Ring 11 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(11)

R017 ³ Ring 12 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(12)

³ ³ ³ ³ ³ R018 ³ Fruits, vegetables and grain consumption (kg/yr) ³ 1.120E+02 ³ 1.600E+02 ³ --- ³ DIET(1)

R018 ³ Leafy vegetable consumption (kg/yr) ³ 2.140E+01 ³ 1.400E+01 ³ --- ³ DIET(2)

R018 ³ Milk consumption (L/yr) ³ 2.330E+02 ³ 9.200E+01 ³ --- ³ DIET(3)

R018 ³ Meat and poultry consumption (kg/yr) ³ 6.510E+01 ³ 6.300E+01 ³ --- ³ DIET(4)

R018 ³ Fish consumption (kg/yr) ³ 2.060E+01 ³ 5.400E+00 ³ --- ³ DIET(5)

R018 ³ Other seafood consumption (kg/yr) ³ 9.000E-01 ³ 9.000E-01 ³ --- ³ DIET(6)

R018 ³ Soil ingestion rate (g/yr) ³ 1.826E+01 ³ 3.650E+01 ³ --- ³ SOIL R018 ³ Drinking water intake (L/yr) ³ 4.785E+02 ³ 5.100E+02 ³ --- ³ DWI R018 ³ Contamination fraction of drinking water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FDW R018 ³ Contamination fraction of household water ³ not used ³ 1.000E+00 ³ --- ³ FHHW R018 ³ Contamination fraction of livestock water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FLW R018 ³ Contamination fraction of irrigation water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FIRW R018 ³ Contamination fraction of aquatic food ³ 1.000E+00 ³ 5.000E-01 ³ --- ³ FR9 R018 ³ Contamination fraction of plant food ³ 1.000E+00 ³-1 ³ --- ³ FPLANT R018 ³ Contamination fraction of meat ³ 1.000E+00 ³-1 ³ --- ³ FMEAT R018 ³ Contamination fraction of milk ³ 1.000E+00 ³-1 ³ --- ³ FMILK 1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/03/2003 11:50 Page 7 Summary : Yankee Rowe Sensitivity Analysis=soil File: Cm-243_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R019 ³ Livestock fodder intake for meat (kg/day) ³ 2.710E+01 ³ 6.800E+01 ³ --- ³ LFI5 R019 ³ Livestock fodder intake for milk (kg/day) ³ 6.320E+01 ³ 5.500E+01 ³ --- ³ LFI6 R019 ³ Livestock water intake for meat (L/day) ³ 5.060E+01 ³ 5.000E+01 ³ --- ³ LWI5 R019 ³ Livestock water intake for milk (L/day) ³ 6.000E+01 ³ 1.600E+02 ³ --- ³ LWI6 R019 ³ Livestock soil intake (kg/day) ³ 5.000E-01 ³ 5.000E-01 ³ --- ³ LSI R019 ³ Mass loading for foliar deposition (g/m**3) ³ 4.000E-04 ³ 1.000E-04 ³ --- ³ MLFD R019 ³ Depth of soil mixing layer (m) ³ 2.300E-01 ³ 1.500E-01 ³ --- ³ DM R019 ³ Depth of roots (m) ³ 1.170E+00 ³ 9.000E-01 ³ --- ³ DROOT R019 ³ Drinking water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWDW R019 ³ Household water fraction from ground water ³ not used ³ 1.000E+00 ³ --- ³ FGWHH R019 ³ Livestock water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWLW R019 ³ Irrigation fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWIR

³ ³ ³ ³ ³ R19B ³ Wet weight crop yield for Non-Leafy (kg/m**2) ³ 1.750E+00 ³ 7.000E-01 ³ --- ³ YV(1)

R19B ³ Wet weight crop yield for Leafy (kg/m**2) ³ 2.889E+00 ³ 1.500E+00 ³ --- ³ YV(2)

R19B ³ Wet weight crop yield for Fodder (kg/m**2) ³ 1.887E+00 ³ 1.100E+00 ³ --- ³ YV(3)

R19B ³ Growing Season for Non-Leafy (years) ³ 2.460E-01 ³ 1.700E-01 ³ --- ³ TE(1)

R19B ³ Growing Season for Leafy (years) ³ 1.230E-01 ³ 2.500E-01 ³ --- ³ TE(2)

R19B ³ Growing Season for Fodder (years) ³ 8.200E-02 ³ 8.000E-02 ³ --- ³ TE(3)

R19B ³ Translocation Factor for Non-Leafy ³ 1.000E-01 ³ 1.000E-01 ³ --- ³ TIV(1)

R19B ³ Translocation Factor for Leafy ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(2)

R19B ³ Translocation Factor for Fodder ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(3)

R19B ³ Dry Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(1)

R19B ³ Dry Foliar Interception Fraction for Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(2)

R19B ³ Dry Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(3)

R19B ³ Wet Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(1)

R19B ³ Wet Foliar Interception Fraction for Leafy ³ 5.800E-01 ³ 2.500E-01 ³ --- ³ RWET(2)

R19B ³ Wet Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(3)

R19B ³ Weathering Removal Constant for Vegetation ³ 3.300E+01 ³ 2.000E+01 ³ --- ³ WLAM

³ ³ ³ ³ ³ C14 ³ C-12 concentration in water (g/cm**3) ³ not used ³ 2.000E-05 ³ --- ³ C12WTR C14 ³ C-12 concentration in contaminated soil (g/g) ³ not used ³ 3.000E-02 ³ --- ³ C12CZ C14 ³ Fraction of vegetation carbon from soil ³ not used ³ 2.000E-02 ³ --- ³ CSOIL C14 ³ Fraction of vegetation carbon from air ³ not used ³ 9.800E-01 ³ --- ³ CAIR C14 ³ C-14 evasion layer thickness in soil (m) ³ not used ³ 3.000E-01 ³ --- ³ DMC C14 ³ C-14 evasion flux rate from soil (1/sec) ³ not used ³ 7.000E-07 ³ --- ³ EVSN C14 ³ C-12 evasion flux rate from soil (1/sec) ³ not used ³ 1.000E-10 ³ --- ³ REVSN C14 ³ Fraction of grain in beef cattle feed ³ not used ³ 8.000E-01 ³ --- ³ AVFG4 C14 ³ Fraction of grain in milk cow feed ³ not used ³ 2.000E-01 ³ --- ³ AVFG5 C14 ³ DCF correction factor for gaseous forms of C14 ³ not used ³ 8.894E+01 ³ --- ³ CO2F

³ ³ ³ ³ ³ STOR ³ Storage times of contaminated foodstuffs (days): ³ ³ ³ ³ STOR ³ Fruits, non-leafy vegetables, and grain ³ 1.400E+01 ³ 1.400E+01 ³ --- ³ STOR_T(1)

STOR ³ Leafy vegetables ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(2)

STOR ³ Milk ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(3)

STOR ³ Meat and poultry ³ 2.000E+01 ³ 2.000E+01 ³ --- ³ STOR_T(4)

STOR ³ Fish ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(5)

STOR ³ Crustacea and mollusks ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(6)

STOR ³ Well water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(7)

STOR ³ Surface water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(8)

STOR ³ Livestock fodder ³ 4.500E+01 ³ 4.500E+01 ³ --- ³ STOR_T(9) 1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/03/2003 11:50 Page 8 Summary : Yankee Rowe Sensitivity Analysis=soil File: Cm-243_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R021 ³ Thickness of building foundation (m) ³ not used ³ 1.500E-01 ³ --- ³ FLOOR1 R021 ³ Bulk density of building foundation (g/cm**3) ³ not used ³ 2.400E+00 ³ --- ³ DENSFL R021 ³ Total porosity of the cover material ³ not used ³ 4.000E-01 ³ --- ³ TPCV R021 ³ Total porosity of the building foundation ³ not used ³ 1.000E-01 ³ --- ³ TPFL R021 ³ Volumetric water content of the cover material ³ not used ³ 5.000E-02 ³ --- ³ PH2OCV R021 ³ Volumetric water content of the foundation ³ not used ³ 3.000E-02 ³ --- ³ PH2OFL R021 ³ Diffusion coefficient for radon gas (m/sec): ³ ³ ³ ³ R021 ³ in cover material ³ not used ³ 2.000E-06 ³ --- ³ DIFCV R021 ³ in foundation material ³ not used ³ 3.000E-07 ³ --- ³ DIFFL R021 ³ in contaminated zone soil ³ not used ³ 2.000E-06 ³ --- ³ DIFCZ R021 ³ Radon vertical dimension of mixing (m) ³ not used ³ 2.000E+00 ³ --- ³ HMIX R021 ³ Average building air exchange rate (1/hr) ³ not used ³ 5.000E-01 ³ --- ³ REXG R021 ³ Height of the building (room) (m) ³ not used ³ 2.500E+00 ³ --- ³ HRM R021 ³ Building interior area factor ³ not used ³ 0.000E+00 ³ --- ³ FAI R021 ³ Building depth below ground surface (m) ³ not used ³-1.000E+00 ³ --- ³ DMFL R021 ³ Emanating power of Rn-222 gas ³ not used ³ 2.500E-01 ³ --- ³ EMANA(1)

R021 ³ Emanating power of Rn-220 gas ³ not used ³ 1.500E-01 ³ --- ³ EMANA(2)

³ ³ ³ ³ ³ TITL ³ Number of graphical time points ³ 32 ³ --- ³ --- ³ NPTS TITL ³ Maximum number of integration points for dose ³ 17 ³ --- ³ --- ³ LYMAX TITL ³ Maximum number of integration points for risk ³ 1 ³ --- ³ --- ³ KYMAX

Summary of Pathway Selections Pathway ³ User Selection

Å 1 -- external gamma ³ active 2 -- inhalation (w/o radon)³ active 3 -- plant ingestion ³ active 4 -- meat ingestion ³ active 5 -- milk ingestion ³ active 6 -- aquatic foods ³ active 7 -- drinking water ³ active 8 -- soil ingestion ³ active 9 -- radon ³ suppressed Find peak pathway doses ³ active

1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/26/2003 15:37 Page 2 Summary : Yankee Rowe Sensitivity Analysis=soil File: Co-60_DCGL.RAD Dose Conversion Factor (and Related) Parameter Summary File: YR soil DCGL lib 0 ³ ³ Current ³ ³ Parameter Menu ³ Parameter ³ Value ³ Default ³ Name

ÅÅÅÅ B-1 ³ Dose conversion factors for inhalation, mrem/pCi: ³ ³ ³ B-1 ³ Co-60 ³ 2.190E-04 ³ 2.190E-04 ³ DCF2( 1)

³ ³ ³ ³ D-1 ³ Dose conversion factors for ingestion, mrem/pCi: ³ ³ ³ D-1 ³ Co-60 ³ 2.690E-05 ³ 2.690E-05 ³ DCF3( 1)

³ ³ ³ ³ D-34 ³ Food transfer factors: ³ ³ ³ D-34 ³ Co-60, plant/soil concentration ratio, dimensionless ³ 1.458E-01 ³ 8.000E-02 ³ RTF( 1,1)

D-34 ³ Co-60, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 5.856E-02 ³ 2.000E-02 ³ RTF( 1,2)

D-34 ³ Co-60, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 2.000E-03 ³ 2.000E-03 ³ RTF( 1,3)

³ ³ ³ ³ D-5 ³ Bioaccumulation factors, fresh water, L/kg: ³ ³ ³ D-5 ³ Co-60, fish ³ 3.000E+02 ³ 3.000E+02 ³ BIOFAC( 1,1)

D-5 ³ Co-60, crustacea and mollusks ³ 2.000E+02 ³ 2.000E+02 ³ BIOFAC( 1,2) 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/26/2003 15:37 Page 3 Summary : Yankee Rowe Sensitivity Analysis=soil File: Co-60_DCGL.RAD Site-Specific Parameter Summary 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R011 ³ Area of contaminated zone (m**2) ³ 1.302E+04 ³ 1.000E+04 ³ --- ³ AREA R011 ³ Thickness of contaminated zone (m) ³ 1.975E+00 ³ 2.000E+00 ³ --- ³ THICK0 R011 ³ Length parallel to aquifer flow (m) ³ 1.290E+02 ³ 1.000E+02 ³ --- ³ LCZPAQ R011 ³ Basic radiation dose limit (mrem/yr) ³ 2.500E+01 ³ 2.500E+01 ³ --- ³ BRDL R011 ³ Time since placement of material (yr) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ TI R011 ³ Times for calculations (yr) ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ T( 2)

R011 ³ Times for calculations (yr) ³ 3.000E+00 ³ 3.000E+00 ³ --- ³ T( 3)

R011 ³ Times for calculations (yr) ³ 1.000E+01 ³ 1.000E+01 ³ --- ³ T( 4)

R011 ³ Times for calculations (yr) ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ T( 5)

R011 ³ Times for calculations (yr) ³ 1.000E+02 ³ 1.000E+02 ³ --- ³ T( 6)

R011 ³ Times for calculations (yr) ³ 3.000E+02 ³ 3.000E+02 ³ --- ³ T( 7)

R011 ³ Times for calculations (yr) ³ 1.000E+03 ³ 1.000E+03 ³ --- ³ T( 8)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T( 9)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T(10)

³ ³ ³ ³ ³ R012 ³ Initial principal radionuclide (pCi/g): Co-60 ³ 1.000E+00 ³ 0.000E+00 ³ --- ³ S1( 1)

R012 ³ Concentration in groundwater (pCi/L): Co-60 ³ not used ³ 0.000E+00 ³ --- ³ W1( 1)

³ ³ ³ ³ ³ R013 ³ Cover depth (m) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ COVER0 R013 ³ Density of cover material (g/cm**3) ³ not used ³ 1.500E+00 ³ --- ³ DENSCV R013 ³ Cover depth erosion rate (m/yr) ³ not used ³ 1.000E-03 ³ --- ³ VCV R013 ³ Density of contaminated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSCZ R013 ³ Contaminated zone erosion rate (m/yr) ³ 8.500E-04 ³ 1.000E-03 ³ --- ³ VCZ R013 ³ Contaminated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPCZ R013 ³ Contaminated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCCZ R013 ³ Contaminated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCCZ R013 ³ Contaminated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BCZ R013 ³ Average annual wind speed (m/sec) ³ 2.030E+00 ³ 2.000E+00 ³ --- ³ WIND R013 ³ Humidity in air (g/m**3) ³ not used ³ 8.000E+00 ³ --- ³ HUMID R013 ³ Evapotranspiration coefficient ³ 6.250E-01 ³ 5.000E-01 ³ --- ³ EVAPTR R013 ³ Precipitation (m/yr) ³ 1.200E+00 ³ 1.000E+00 ³ --- ³ PRECIP R013 ³ Irrigation (m/yr) ³ 4.350E-01 ³ 2.000E-01 ³ --- ³ RI R013 ³ Irrigation mode ³ overhead ³ overhead ³ --- ³ IDITCH R013 ³ Runoff coefficient ³ 6.000E-01 ³ 2.000E-01 ³ --- ³ RUNOFF R013 ³ Watershed area for nearby stream or pond (m**2) ³ 7.770E+05 ³ 1.000E+06 ³ --- ³ WAREA R013 ³ Accuracy for water/soil computations ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ EPS

³ ³ ³ ³ ³ R014 ³ Density of saturated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSAQ R014 ³ Saturated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPSZ R014 ³ Saturated zone effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPSZ R014 ³ Saturated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCSZ R014 ³ Saturated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+02 ³ --- ³ HCSZ R014 ³ Saturated zone hydraulic gradient ³ 1.000E-01 ³ 2.000E-02 ³ --- ³ HGWT R014 ³ Saturated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BSZ R014 ³ Water table drop rate (m/yr) ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ VWT R014 ³ Well pump intake depth (m below water table) ³ 1.451E+01 ³ 1.000E+01 ³ --- ³ DWIBWT R014 ³ Model: Nondispersion (ND) or Mass-Balance (MB) ³ ND ³ ND ³ --- ³ MODEL R014 ³ Well pumping rate (m**3/yr) ³ 1.323E+03 ³ 2.500E+02 ³ --- ³ UW

³ ³ ³ ³ ³ R015 ³ Number of unsaturated zone strata ³ 1 ³ 1 ³ --- ³ NS 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/26/2003 15:37 Page 4 Summary : Yankee Rowe Sensitivity Analysis=soil File: Co-60_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R015 ³ Unsat. zone 1, thickness (m) ³ 1.820E+00 ³ 4.000E+00 ³ --- ³ H(1)

R015 ³ Unsat. zone 1, soil density (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSUZ(1)

R015 ³ Unsat. zone 1, total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPUZ(1)

R015 ³ Unsat. zone 1, effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPUZ(1)

R015 ³ Unsat. zone 1, field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCUZ(1)

R015 ³ Unsat. zone 1, soil-specific b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BUZ(1)

R015 ³ Unsat. zone 1, hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCUZ(1)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for Co-60 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 2.350E+02 ³ 1.000E+03 ³ --- ³ DCNUCC( 1)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 2.350E+02 ³ 1.000E+03 ³ --- ³ DCNUCU( 1,1)

R016 ³ Saturated zone (cm**3/g) ³ 2.350E+02 ³ 1.000E+03 ³ --- ³ DCNUCS( 1)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 4.893E-04 ³ ALEACH( 1)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 1)

³ ³ ³ ³ ³ R017 ³ Inhalation rate (m**3/yr) ³ 8.400E+03 ³ 8.400E+03 ³ --- ³ INHALR R017 ³ Mass loading for inhalation (g/m**3) ³ 2.330E-05 ³ 1.000E-04 ³ --- ³ MLINH R017 ³ Exposure duration ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ ED R017 ³ Shielding factor, inhalation ³ 5.500E-01 ³ 4.000E-01 ³ --- ³ SHF3 R017 ³ Shielding factor, external gamma ³ 3.980E-01 ³ 7.000E-01 ³ --- ³ SHF1 R017 ³ Fraction of time spent indoors ³ 6.571E-01 ³ 5.000E-01 ³ --- ³ FIND R017 ³ Fraction of time spent outdoors (on site) ³ 1.181E-01 ³ 2.500E-01 ³ --- ³ FOTD R017 ³ Shape factor flag, external gamma ³ 1.000E+00 ³ 1.000E+00 ³ >0 shows circular AREA. ³ FS R017 ³ Radii of shape factor array (used if FS = -1): ³ ³ ³ ³ R017 ³ Outer annular radius (m), ring 1: ³ not used ³ 5.000E+01 ³ --- ³ RAD_SHAPE(

1)

R017 ³ Outer annular radius (m), ring 2: ³ not used ³ 7.071E+01 ³ --- ³ RAD_SHAPE(

2)

R017 ³ Outer annular radius (m), ring 3: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

3)

R017 ³ Outer annular radius (m), ring 4: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

4)

R017 ³ Outer annular radius (m), ring 5: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

5)

R017 ³ Outer annular radius (m), ring 6: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

6)

R017 ³ Outer annular radius (m), ring 7: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

7)

R017 ³ Outer annular radius (m), ring 8: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

8)

R017 ³ Outer annular radius (m), ring 9: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

9)

R017 ³ Outer annular radius (m), ring 10: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (10)

R017 ³ Outer annular radius (m), ring 11: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (11)

R017 ³ Outer annular radius (m), ring 12: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (12)

³ ³ ³ ³ ³ R017 ³ Fractions of annular areas within AREA: ³ ³ ³ ³ R017 ³ Ring 1 ³ not used ³ 1.000E+00 ³ --- ³ FRACA( 1)

R017 ³ Ring 2 ³ not used ³ 2.732E-01 ³ --- ³ FRACA( 2)

R017 ³ Ring 3 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 3)

R017 ³ Ring 4 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 4)

R017 ³ Ring 5 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 5)

R017 ³ Ring 6 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 6)

R017 ³ Ring 7 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 7)

R017 ³ Ring 8 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 8)

R017 ³ Ring 9 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 9)

R017 ³ Ring 10 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(10)

R017 ³ Ring 11 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(11)

R017 ³ Ring 12 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(12)

³ ³ ³ ³ ³ 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/26/2003 15:37 Page 5 Summary : Yankee Rowe Sensitivity Analysis=soil File: Co-60_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R018 ³ Fruits, vegetables and grain consumption (kg/yr) ³ 1.120E+02 ³ 1.600E+02 ³ --- ³ DIET(1)

R018 ³ Leafy vegetable consumption (kg/yr) ³ 2.140E+01 ³ 1.400E+01 ³ --- ³ DIET(2)

R018 ³ Milk consumption (L/yr) ³ 2.330E+02 ³ 9.200E+01 ³ --- ³ DIET(3)

R018 ³ Meat and poultry consumption (kg/yr) ³ 6.510E+01 ³ 6.300E+01 ³ --- ³ DIET(4)

R018 ³ Fish consumption (kg/yr) ³ 2.060E+01 ³ 5.400E+00 ³ --- ³ DIET(5)

R018 ³ Other seafood consumption (kg/yr) ³ 9.000E-01 ³ 9.000E-01 ³ --- ³ DIET(6)

R018 ³ Soil ingestion rate (g/yr) ³ 1.826E+01 ³ 3.650E+01 ³ --- ³ SOIL R018 ³ Drinking water intake (L/yr) ³ 4.785E+02 ³ 5.100E+02 ³ --- ³ DWI R018 ³ Contamination fraction of drinking water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FDW R018 ³ Contamination fraction of household water ³ not used ³ 1.000E+00 ³ --- ³ FHHW R018 ³ Contamination fraction of livestock water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FLW R018 ³ Contamination fraction of irrigation water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FIRW R018 ³ Contamination fraction of aquatic food ³ 1.000E+00 ³ 5.000E-01 ³ --- ³ FR9 R018 ³ Contamination fraction of plant food ³ 1.000E+00 ³-1 ³ --- ³ FPLANT R018 ³ Contamination fraction of meat ³ 1.000E+00 ³-1 ³ --- ³ FMEAT R018 ³ Contamination fraction of milk ³ 1.000E+00 ³-1 ³ --- ³ FMILK

³ ³ ³ ³ ³ R019 ³ Livestock fodder intake for meat (kg/day) ³ 2.710E+01 ³ 6.800E+01 ³ --- ³ LFI5 R019 ³ Livestock fodder intake for milk (kg/day) ³ 6.320E+01 ³ 5.500E+01 ³ --- ³ LFI6 R019 ³ Livestock water intake for meat (L/day) ³ 5.060E+01 ³ 5.000E+01 ³ --- ³ LWI5 R019 ³ Livestock water intake for milk (L/day) ³ 6.000E+01 ³ 1.600E+02 ³ --- ³ LWI6 R019 ³ Livestock soil intake (kg/day) ³ 5.000E-01 ³ 5.000E-01 ³ --- ³ LSI R019 ³ Mass loading for foliar deposition (g/m**3) ³ 4.000E-04 ³ 1.000E-04 ³ --- ³ MLFD R019 ³ Depth of soil mixing layer (m) ³ 2.300E-01 ³ 1.500E-01 ³ --- ³ DM R019 ³ Depth of roots (m) ³ 2.050E+00 ³ 9.000E-01 ³ --- ³ DROOT R019 ³ Drinking water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWDW R019 ³ Household water fraction from ground water ³ not used ³ 1.000E+00 ³ --- ³ FGWHH R019 ³ Livestock water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWLW R019 ³ Irrigation fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWIR

³ ³ ³ ³ ³ R19B ³ Wet weight crop yield for Non-Leafy (kg/m**2) ³ 1.750E+00 ³ 7.000E-01 ³ --- ³ YV(1)

R19B ³ Wet weight crop yield for Leafy (kg/m**2) ³ 2.889E+00 ³ 1.500E+00 ³ --- ³ YV(2)

R19B ³ Wet weight crop yield for Fodder (kg/m**2) ³ 1.887E+00 ³ 1.100E+00 ³ --- ³ YV(3)

R19B ³ Growing Season for Non-Leafy (years) ³ 2.460E-01 ³ 1.700E-01 ³ --- ³ TE(1)

R19B ³ Growing Season for Leafy (years) ³ 1.230E-01 ³ 2.500E-01 ³ --- ³ TE(2)

R19B ³ Growing Season for Fodder (years) ³ 8.200E-02 ³ 8.000E-02 ³ --- ³ TE(3)

R19B ³ Translocation Factor for Non-Leafy ³ 1.000E-01 ³ 1.000E-01 ³ --- ³ TIV(1)

R19B ³ Translocation Factor for Leafy ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(2)

R19B ³ Translocation Factor for Fodder ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(3)

R19B ³ Dry Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(1)

R19B ³ Dry Foliar Interception Fraction for Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(2)

R19B ³ Dry Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(3)

R19B ³ Wet Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(1)

R19B ³ Wet Foliar Interception Fraction for Leafy ³ 5.800E-01 ³ 2.500E-01 ³ --- ³ RWET(2)

R19B ³ Wet Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(3)

R19B ³ Weathering Removal Constant for Vegetation ³ 3.300E+01 ³ 2.000E+01 ³ --- ³ WLAM

³ ³ ³ ³ ³ C14 ³ C-12 concentration in water (g/cm**3) ³ not used ³ 2.000E-05 ³ --- ³ C12WTR C14 ³ C-12 concentration in contaminated soil (g/g) ³ not used ³ 3.000E-02 ³ --- ³ C12CZ C14 ³ Fraction of vegetation carbon from soil ³ not used ³ 2.000E-02 ³ --- ³ CSOIL C14 ³ Fraction of vegetation carbon from air ³ not used ³ 9.800E-01 ³ --- ³ CAIR 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/26/2003 15:37 Page 6 Summary : Yankee Rowe Sensitivity Analysis=soil File: Co-60_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ C14 ³ C-14 evasion layer thickness in soil (m) ³ not used ³ 3.000E-01 ³ --- ³ DMC C14 ³ C-14 evasion flux rate from soil (1/sec) ³ not used ³ 7.000E-07 ³ --- ³ EVSN C14 ³ C-12 evasion flux rate from soil (1/sec) ³ not used ³ 1.000E-10 ³ --- ³ REVSN C14 ³ Fraction of grain in beef cattle feed ³ not used ³ 8.000E-01 ³ --- ³ AVFG4 C14 ³ Fraction of grain in milk cow feed ³ not used ³ 2.000E-01 ³ --- ³ AVFG5 C14 ³ DCF correction factor for gaseous forms of C14 ³ not used ³ 8.894E+01 ³ --- ³ CO2F

³ ³ ³ ³ ³ STOR ³ Storage times of contaminated foodstuffs (days): ³ ³ ³ ³ STOR ³ Fruits, non-leafy vegetables, and grain ³ 1.400E+01 ³ 1.400E+01 ³ --- ³ STOR_T(1)

STOR ³ Leafy vegetables ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(2)

STOR ³ Milk ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(3)

STOR ³ Meat and poultry ³ 2.000E+01 ³ 2.000E+01 ³ --- ³ STOR_T(4)

STOR ³ Fish ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(5)

STOR ³ Crustacea and mollusks ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(6)

STOR ³ Well water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(7)

STOR ³ Surface water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(8)

STOR ³ Livestock fodder ³ 4.500E+01 ³ 4.500E+01 ³ --- ³ STOR_T(9)

³ ³ ³ ³ ³ R021 ³ Thickness of building foundation (m) ³ not used ³ 1.500E-01 ³ --- ³ FLOOR1 R021 ³ Bulk density of building foundation (g/cm**3) ³ not used ³ 2.400E+00 ³ --- ³ DENSFL R021 ³ Total porosity of the cover material ³ not used ³ 4.000E-01 ³ --- ³ TPCV R021 ³ Total porosity of the building foundation ³ not used ³ 1.000E-01 ³ --- ³ TPFL R021 ³ Volumetric water content of the cover material ³ not used ³ 5.000E-02 ³ --- ³ PH2OCV R021 ³ Volumetric water content of the foundation ³ not used ³ 3.000E-02 ³ --- ³ PH2OFL R021 ³ Diffusion coefficient for radon gas (m/sec): ³ ³ ³ ³ R021 ³ in cover material ³ not used ³ 2.000E-06 ³ --- ³ DIFCV R021 ³ in foundation material ³ not used ³ 3.000E-07 ³ --- ³ DIFFL R021 ³ in contaminated zone soil ³ not used ³ 2.000E-06 ³ --- ³ DIFCZ R021 ³ Radon vertical dimension of mixing (m) ³ not used ³ 2.000E+00 ³ --- ³ HMIX R021 ³ Average building air exchange rate (1/hr) ³ not used ³ 5.000E-01 ³ --- ³ REXG R021 ³ Height of the building (room) (m) ³ not used ³ 2.500E+00 ³ --- ³ HRM R021 ³ Building interior area factor ³ not used ³ 0.000E+00 ³ --- ³ FAI R021 ³ Building depth below ground surface (m) ³ not used ³-1.000E+00 ³ --- ³ DMFL R021 ³ Emanating power of Rn-222 gas ³ not used ³ 2.500E-01 ³ --- ³ EMANA(1)

R021 ³ Emanating power of Rn-220 gas ³ not used ³ 1.500E-01 ³ --- ³ EMANA(2)

³ ³ ³ ³ ³ TITL ³ Number of graphical time points ³ 32 ³ --- ³ --- ³ NPTS TITL ³ Maximum number of integration points for dose ³ 17 ³ --- ³ --- ³ LYMAX TITL ³ Maximum number of integration points for risk ³ 1 ³ --- ³ --- ³ KYMAX

1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/26/2003 15:37 Page 7 Summary : Yankee Rowe Sensitivity Analysis=soil File: Co-60_DCGL.RAD Summary of Pathway Selections Pathway ³ User Selection

Å 1 -- external gamma ³ active 2 -- inhalation (w/o radon)³ active 3 -- plant ingestion ³ active 4 -- meat ingestion ³ active 5 -- milk ingestion ³ active 6 -- aquatic foods ³ active 7 -- drinking water ³ active 8 -- soil ingestion ³ active 9 -- radon ³ suppressed Find peak pathway doses ³ active

1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/02/2003 09:56 Page 2 Summary : Yankee Rowe Sensitivity Analysis=soil File: Cs-134_DCGL.RAD Dose Conversion Factor (and Related) Parameter Summary File: YR soil DCGL lib 0 ³ ³ Current ³ ³ Parameter Menu ³ Parameter ³ Value ³ Default ³ Name

ÅÅÅÅ B-1 ³ Dose conversion factors for inhalation, mrem/pCi: ³ ³ ³ B-1 ³ Cs-134 ³ 4.630E-05 ³ 4.630E-05 ³ DCF2( 1)

³ ³ ³ ³ D-1 ³ Dose conversion factors for ingestion, mrem/pCi: ³ ³ ³ D-1 ³ Cs-134 ³ 7.330E-05 ³ 7.330E-05 ³ DCF3( 1)

³ ³ ³ ³ D-34 ³ Food transfer factors: ³ ³ ³ D-34 ³ Cs-134, plant/soil concentration ratio, dimensionless ³ 7.820E-02 ³ 4.000E-02 ³ RTF( 1,1)

D-34 ³ Cs-134, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 6.510E-02 ³ 3.000E-02 ³ RTF( 1,2)

D-34 ³ Cs-134, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 1.390E-02 ³ 8.000E-03 ³ RTF( 1,3)

³ ³ ³ ³ D-5 ³ Bioaccumulation factors, fresh water, L/kg: ³ ³ ³ D-5 ³ Cs-134, fish ³ 2.000E+03 ³ 2.000E+03 ³ BIOFAC( 1,1)

D-5 ³ Cs-134, crustacea and mollusks ³ 1.000E+02 ³ 1.000E+02 ³ BIOFAC( 1,2) 1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/02/2003 09:56 Page 3 Summary : Yankee Rowe Sensitivity Analysis=soil File: Cs-134_DCGL.RAD Site-Specific Parameter Summary 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R011 ³ Area of contaminated zone (m**2) ³ 1.302E+04 ³ 1.000E+04 ³ --- ³ AREA R011 ³ Thickness of contaminated zone (m) ³ 1.975E+00 ³ 2.000E+00 ³ --- ³ THICK0 R011 ³ Length parallel to aquifer flow (m) ³ 1.290E+02 ³ 1.000E+02 ³ --- ³ LCZPAQ R011 ³ Basic radiation dose limit (mrem/yr) ³ 2.500E+01 ³ 2.500E+01 ³ --- ³ BRDL R011 ³ Time since placement of material (yr) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ TI R011 ³ Times for calculations (yr) ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ T( 2)

R011 ³ Times for calculations (yr) ³ 3.000E+00 ³ 3.000E+00 ³ --- ³ T( 3)

R011 ³ Times for calculations (yr) ³ 1.000E+01 ³ 1.000E+01 ³ --- ³ T( 4)

R011 ³ Times for calculations (yr) ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ T( 5)

R011 ³ Times for calculations (yr) ³ 1.000E+02 ³ 1.000E+02 ³ --- ³ T( 6)

R011 ³ Times for calculations (yr) ³ 3.000E+02 ³ 3.000E+02 ³ --- ³ T( 7)

R011 ³ Times for calculations (yr) ³ 1.000E+03 ³ 1.000E+03 ³ --- ³ T( 8)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T( 9)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T(10)

³ ³ ³ ³ ³ R012 ³ Initial principal radionuclide (pCi/g): Cs-134 ³ 1.000E+00 ³ 0.000E+00 ³ --- ³ S1( 1)

R012 ³ Concentration in groundwater (pCi/L): Cs-134 ³ not used ³ 0.000E+00 ³ --- ³ W1( 1)

³ ³ ³ ³ ³ R013 ³ Cover depth (m) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ COVER0 R013 ³ Density of cover material (g/cm**3) ³ not used ³ 1.500E+00 ³ --- ³ DENSCV R013 ³ Cover depth erosion rate (m/yr) ³ not used ³ 1.000E-03 ³ --- ³ VCV R013 ³ Density of contaminated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSCZ R013 ³ Contaminated zone erosion rate (m/yr) ³ 8.500E-04 ³ 1.000E-03 ³ --- ³ VCZ R013 ³ Contaminated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPCZ R013 ³ Contaminated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCCZ R013 ³ Contaminated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCCZ R013 ³ Contaminated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BCZ R013 ³ Average annual wind speed (m/sec) ³ 2.030E+00 ³ 2.000E+00 ³ --- ³ WIND R013 ³ Humidity in air (g/m**3) ³ not used ³ 8.000E+00 ³ --- ³ HUMID R013 ³ Evapotranspiration coefficient ³ 6.250E-01 ³ 5.000E-01 ³ --- ³ EVAPTR R013 ³ Precipitation (m/yr) ³ 1.200E+00 ³ 1.000E+00 ³ --- ³ PRECIP R013 ³ Irrigation (m/yr) ³ 4.350E-01 ³ 2.000E-01 ³ --- ³ RI R013 ³ Irrigation mode ³ overhead ³ overhead ³ --- ³ IDITCH R013 ³ Runoff coefficient ³ 6.000E-01 ³ 2.000E-01 ³ --- ³ RUNOFF R013 ³ Watershed area for nearby stream or pond (m**2) ³ 7.770E+05 ³ 1.000E+06 ³ --- ³ WAREA R013 ³ Accuracy for water/soil computations ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ EPS

³ ³ ³ ³ ³ R014 ³ Density of saturated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSAQ R014 ³ Saturated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPSZ R014 ³ Saturated zone effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPSZ R014 ³ Saturated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCSZ R014 ³ Saturated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+02 ³ --- ³ HCSZ R014 ³ Saturated zone hydraulic gradient ³ 1.000E-01 ³ 2.000E-02 ³ --- ³ HGWT R014 ³ Saturated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BSZ R014 ³ Water table drop rate (m/yr) ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ VWT R014 ³ Well pump intake depth (m below water table) ³ 1.451E+01 ³ 1.000E+01 ³ --- ³ DWIBWT R014 ³ Model: Nondispersion (ND) or Mass-Balance (MB) ³ ND ³ ND ³ --- ³ MODEL R014 ³ Well pumping rate (m**3/yr) ³ 1.323E+03 ³ 2.500E+02 ³ --- ³ UW

³ ³ ³ ³ ³ R015 ³ Number of unsaturated zone strata ³ 1 ³ 1 ³ --- ³ NS 1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/02/2003 09:56 Page 4 Summary : Yankee Rowe Sensitivity Analysis=soil File: Cs-134_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R015 ³ Unsat. zone 1, thickness (m) ³ 1.820E+00 ³ 4.000E+00 ³ --- ³ H(1)

R015 ³ Unsat. zone 1, soil density (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSUZ(1)

R015 ³ Unsat. zone 1, total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPUZ(1)

R015 ³ Unsat. zone 1, effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPUZ(1)

R015 ³ Unsat. zone 1, field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCUZ(1)

R015 ³ Unsat. zone 1, soil-specific b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BUZ(1)

R015 ³ Unsat. zone 1, hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCUZ(1)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for Cs-134 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 4.460E+02 ³ 1.000E+03 ³ --- ³ DCNUCC( 1)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 4.460E+02 ³ 1.000E+03 ³ --- ³ DCNUCU( 1,1)

R016 ³ Saturated zone (cm**3/g) ³ 4.460E+02 ³ 1.000E+03 ³ --- ³ DCNUCS( 1)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 2.579E-04 ³ ALEACH( 1)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 1)

³ ³ ³ ³ ³ R017 ³ Inhalation rate (m**3/yr) ³ 8.400E+03 ³ 8.400E+03 ³ --- ³ INHALR R017 ³ Mass loading for inhalation (g/m**3) ³ 2.330E-05 ³ 1.000E-04 ³ --- ³ MLINH R017 ³ Exposure duration ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ ED R017 ³ Shielding factor, inhalation ³ 5.500E-01 ³ 4.000E-01 ³ --- ³ SHF3 R017 ³ Shielding factor, external gamma ³ 3.980E-01 ³ 7.000E-01 ³ --- ³ SHF1 R017 ³ Fraction of time spent indoors ³ 6.571E-01 ³ 5.000E-01 ³ --- ³ FIND R017 ³ Fraction of time spent outdoors (on site) ³ 1.181E-01 ³ 2.500E-01 ³ --- ³ FOTD R017 ³ Shape factor flag, external gamma ³ 1.000E+00 ³ 1.000E+00 ³ >0 shows circular AREA. ³ FS R017 ³ Radii of shape factor array (used if FS = -1): ³ ³ ³ ³ R017 ³ Outer annular radius (m), ring 1: ³ not used ³ 5.000E+01 ³ --- ³ RAD_SHAPE(

1)

R017 ³ Outer annular radius (m), ring 2: ³ not used ³ 7.071E+01 ³ --- ³ RAD_SHAPE(

2)

R017 ³ Outer annular radius (m), ring 3: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

3)

R017 ³ Outer annular radius (m), ring 4: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

4)

R017 ³ Outer annular radius (m), ring 5: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

5)

R017 ³ Outer annular radius (m), ring 6: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

6)

R017 ³ Outer annular radius (m), ring 7: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

7)

R017 ³ Outer annular radius (m), ring 8: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

8)

R017 ³ Outer annular radius (m), ring 9: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

9)

R017 ³ Outer annular radius (m), ring 10: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (10)

R017 ³ Outer annular radius (m), ring 11: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (11)

R017 ³ Outer annular radius (m), ring 12: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (12)

³ ³ ³ ³ ³ R017 ³ Fractions of annular areas within AREA: ³ ³ ³ ³ R017 ³ Ring 1 ³ not used ³ 1.000E+00 ³ --- ³ FRACA( 1)

R017 ³ Ring 2 ³ not used ³ 2.732E-01 ³ --- ³ FRACA( 2)

R017 ³ Ring 3 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 3)

R017 ³ Ring 4 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 4)

R017 ³ Ring 5 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 5)

R017 ³ Ring 6 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 6)

R017 ³ Ring 7 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 7)

R017 ³ Ring 8 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 8)

R017 ³ Ring 9 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 9)

R017 ³ Ring 10 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(10)

R017 ³ Ring 11 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(11)

R017 ³ Ring 12 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(12)

³ ³ ³ ³ ³ 1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/02/2003 09:56 Page 5 Summary : Yankee Rowe Sensitivity Analysis=soil File: Cs-134_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R018 ³ Fruits, vegetables and grain consumption (kg/yr) ³ 1.120E+02 ³ 1.600E+02 ³ --- ³ DIET(1)

R018 ³ Leafy vegetable consumption (kg/yr) ³ 2.140E+01 ³ 1.400E+01 ³ --- ³ DIET(2)

R018 ³ Milk consumption (L/yr) ³ 2.330E+02 ³ 9.200E+01 ³ --- ³ DIET(3)

R018 ³ Meat and poultry consumption (kg/yr) ³ 6.510E+01 ³ 6.300E+01 ³ --- ³ DIET(4)

R018 ³ Fish consumption (kg/yr) ³ 2.060E+01 ³ 5.400E+00 ³ --- ³ DIET(5)

R018 ³ Other seafood consumption (kg/yr) ³ 9.000E-01 ³ 9.000E-01 ³ --- ³ DIET(6)

R018 ³ Soil ingestion rate (g/yr) ³ 1.826E+01 ³ 3.650E+01 ³ --- ³ SOIL R018 ³ Drinking water intake (L/yr) ³ 4.785E+02 ³ 5.100E+02 ³ --- ³ DWI R018 ³ Contamination fraction of drinking water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FDW R018 ³ Contamination fraction of household water ³ not used ³ 1.000E+00 ³ --- ³ FHHW R018 ³ Contamination fraction of livestock water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FLW R018 ³ Contamination fraction of irrigation water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FIRW R018 ³ Contamination fraction of aquatic food ³ 1.000E+00 ³ 5.000E-01 ³ --- ³ FR9 R018 ³ Contamination fraction of plant food ³ 1.000E+00 ³-1 ³ --- ³ FPLANT R018 ³ Contamination fraction of meat ³ 1.000E+00 ³-1 ³ --- ³ FMEAT R018 ³ Contamination fraction of milk ³ 1.000E+00 ³-1 ³ --- ³ FMILK

³ ³ ³ ³ ³ R019 ³ Livestock fodder intake for meat (kg/day) ³ 2.710E+01 ³ 6.800E+01 ³ --- ³ LFI5 R019 ³ Livestock fodder intake for milk (kg/day) ³ 6.320E+01 ³ 5.500E+01 ³ --- ³ LFI6 R019 ³ Livestock water intake for meat (L/day) ³ 5.060E+01 ³ 5.000E+01 ³ --- ³ LWI5 R019 ³ Livestock water intake for milk (L/day) ³ 6.000E+01 ³ 1.600E+02 ³ --- ³ LWI6 R019 ³ Livestock soil intake (kg/day) ³ 5.000E-01 ³ 5.000E-01 ³ --- ³ LSI R019 ³ Mass loading for foliar deposition (g/m**3) ³ 4.000E-04 ³ 1.000E-04 ³ --- ³ MLFD R019 ³ Depth of soil mixing layer (m) ³ 2.300E-01 ³ 1.500E-01 ³ --- ³ DM R019 ³ Depth of roots (m) ³ 1.170E+00 ³ 9.000E-01 ³ --- ³ DROOT R019 ³ Drinking water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWDW R019 ³ Household water fraction from ground water ³ not used ³ 1.000E+00 ³ --- ³ FGWHH R019 ³ Livestock water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWLW R019 ³ Irrigation fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWIR

³ ³ ³ ³ ³ R19B ³ Wet weight crop yield for Non-Leafy (kg/m**2) ³ 1.750E+00 ³ 7.000E-01 ³ --- ³ YV(1)

R19B ³ Wet weight crop yield for Leafy (kg/m**2) ³ 2.889E+00 ³ 1.500E+00 ³ --- ³ YV(2)

R19B ³ Wet weight crop yield for Fodder (kg/m**2) ³ 1.887E+00 ³ 1.100E+00 ³ --- ³ YV(3)

R19B ³ Growing Season for Non-Leafy (years) ³ 2.460E-01 ³ 1.700E-01 ³ --- ³ TE(1)

R19B ³ Growing Season for Leafy (years) ³ 1.230E-01 ³ 2.500E-01 ³ --- ³ TE(2)

R19B ³ Growing Season for Fodder (years) ³ 8.200E-02 ³ 8.000E-02 ³ --- ³ TE(3)

R19B ³ Translocation Factor for Non-Leafy ³ 1.000E-01 ³ 1.000E-01 ³ --- ³ TIV(1)

R19B ³ Translocation Factor for Leafy ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(2)

R19B ³ Translocation Factor for Fodder ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(3)

R19B ³ Dry Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(1)

R19B ³ Dry Foliar Interception Fraction for Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(2)

R19B ³ Dry Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(3)

R19B ³ Wet Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(1)

R19B ³ Wet Foliar Interception Fraction for Leafy ³ 5.800E-01 ³ 2.500E-01 ³ --- ³ RWET(2)

R19B ³ Wet Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(3)

R19B ³ Weathering Removal Constant for Vegetation ³ 3.300E+01 ³ 2.000E+01 ³ --- ³ WLAM

³ ³ ³ ³ ³ C14 ³ C-12 concentration in water (g/cm**3) ³ not used ³ 2.000E-05 ³ --- ³ C12WTR C14 ³ C-12 concentration in contaminated soil (g/g) ³ not used ³ 3.000E-02 ³ --- ³ C12CZ C14 ³ Fraction of vegetation carbon from soil ³ not used ³ 2.000E-02 ³ --- ³ CSOIL C14 ³ Fraction of vegetation carbon from air ³ not used ³ 9.800E-01 ³ --- ³ CAIR 1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/02/2003 09:56 Page 6 Summary : Yankee Rowe Sensitivity Analysis=soil File: Cs-134_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ C14 ³ C-14 evasion layer thickness in soil (m) ³ not used ³ 3.000E-01 ³ --- ³ DMC C14 ³ C-14 evasion flux rate from soil (1/sec) ³ not used ³ 7.000E-07 ³ --- ³ EVSN C14 ³ C-12 evasion flux rate from soil (1/sec) ³ not used ³ 1.000E-10 ³ --- ³ REVSN C14 ³ Fraction of grain in beef cattle feed ³ not used ³ 8.000E-01 ³ --- ³ AVFG4 C14 ³ Fraction of grain in milk cow feed ³ not used ³ 2.000E-01 ³ --- ³ AVFG5 C14 ³ DCF correction factor for gaseous forms of C14 ³ not used ³ 8.894E+01 ³ --- ³ CO2F

³ ³ ³ ³ ³ STOR ³ Storage times of contaminated foodstuffs (days): ³ ³ ³ ³ STOR ³ Fruits, non-leafy vegetables, and grain ³ 1.400E+01 ³ 1.400E+01 ³ --- ³ STOR_T(1)

STOR ³ Leafy vegetables ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(2)

STOR ³ Milk ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(3)

STOR ³ Meat and poultry ³ 2.000E+01 ³ 2.000E+01 ³ --- ³ STOR_T(4)

STOR ³ Fish ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(5)

STOR ³ Crustacea and mollusks ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(6)

STOR ³ Well water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(7)

STOR ³ Surface water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(8)

STOR ³ Livestock fodder ³ 4.500E+01 ³ 4.500E+01 ³ --- ³ STOR_T(9)

³ ³ ³ ³ ³ R021 ³ Thickness of building foundation (m) ³ not used ³ 1.500E-01 ³ --- ³ FLOOR1 R021 ³ Bulk density of building foundation (g/cm**3) ³ not used ³ 2.400E+00 ³ --- ³ DENSFL R021 ³ Total porosity of the cover material ³ not used ³ 4.000E-01 ³ --- ³ TPCV R021 ³ Total porosity of the building foundation ³ not used ³ 1.000E-01 ³ --- ³ TPFL R021 ³ Volumetric water content of the cover material ³ not used ³ 5.000E-02 ³ --- ³ PH2OCV R021 ³ Volumetric water content of the foundation ³ not used ³ 3.000E-02 ³ --- ³ PH2OFL R021 ³ Diffusion coefficient for radon gas (m/sec): ³ ³ ³ ³ R021 ³ in cover material ³ not used ³ 2.000E-06 ³ --- ³ DIFCV R021 ³ in foundation material ³ not used ³ 3.000E-07 ³ --- ³ DIFFL R021 ³ in contaminated zone soil ³ not used ³ 2.000E-06 ³ --- ³ DIFCZ R021 ³ Radon vertical dimension of mixing (m) ³ not used ³ 2.000E+00 ³ --- ³ HMIX R021 ³ Average building air exchange rate (1/hr) ³ not used ³ 5.000E-01 ³ --- ³ REXG R021 ³ Height of the building (room) (m) ³ not used ³ 2.500E+00 ³ --- ³ HRM R021 ³ Building interior area factor ³ not used ³ 0.000E+00 ³ --- ³ FAI R021 ³ Building depth below ground surface (m) ³ not used ³-1.000E+00 ³ --- ³ DMFL R021 ³ Emanating power of Rn-222 gas ³ not used ³ 2.500E-01 ³ --- ³ EMANA(1)

R021 ³ Emanating power of Rn-220 gas ³ not used ³ 1.500E-01 ³ --- ³ EMANA(2)

³ ³ ³ ³ ³ TITL ³ Number of graphical time points ³ 32 ³ --- ³ --- ³ NPTS TITL ³ Maximum number of integration points for dose ³ 17 ³ --- ³ --- ³ LYMAX TITL ³ Maximum number of integration points for risk ³ 1 ³ --- ³ --- ³ KYMAX

1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/02/2003 09:56 Page 7 Summary : Yankee Rowe Sensitivity Analysis=soil File: Cs-134_DCGL.RAD Summary of Pathway Selections Pathway ³ User Selection

Å 1 -- external gamma ³ active 2 -- inhalation (w/o radon)³ active 3 -- plant ingestion ³ active 4 -- meat ingestion ³ active 5 -- milk ingestion ³ active 6 -- aquatic foods ³ active 7 -- drinking water ³ active 8 -- soil ingestion ³ active 9 -- radon ³ suppressed Find peak pathway doses ³ active

1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/26/2003 16:26 Page 2 Summary : Yankee Rowe Sensitivity Analysis=soil File: Cs-137_DCGL.RAD Dose Conversion Factor (and Related) Parameter Summary File: YR soil DCGL lib 0 ³ ³ Current ³ ³ Parameter Menu ³ Parameter ³ Value ³ Default ³ Name

ÅÅÅÅ B-1 ³ Dose conversion factors for inhalation, mrem/pCi: ³ ³ ³ B-1 ³ Cs-137+D ³ 3.190E-05 ³ 3.190E-05 ³ DCF2( 1)

³ ³ ³ ³ D-1 ³ Dose conversion factors for ingestion, mrem/pCi: ³ ³ ³ D-1 ³ Cs-137+D ³ 5.000E-05 ³ 5.000E-05 ³ DCF3( 1)

³ ³ ³ ³ D-34 ³ Food transfer factors: ³ ³ ³ D-34 ³ Cs-137+D, plant/soil concentration ratio, dimensionless ³ 7.820E-02 ³ 4.000E-02 ³ RTF( 1,1)

D-34 ³ Cs-137+D, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 6.510E-02 ³ 3.000E-02 ³ RTF( 1,2)

D-34 ³ Cs-137+D, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 1.390E-02 ³ 8.000E-03 ³ RTF( 1,3)

³ ³ ³ ³ D-5 ³ Bioaccumulation factors, fresh water, L/kg: ³ ³ ³ D-5 ³ Cs-137+D, fish ³ 2.000E+03 ³ 2.000E+03 ³ BIOFAC( 1,1)

D-5 ³ Cs-137+D, crustacea and mollusks ³ 1.000E+02 ³ 1.000E+02 ³ BIOFAC( 1,2) 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/26/2003 16:26 Page 3 Summary : Yankee Rowe Sensitivity Analysis=soil File: Cs-137_DCGL.RAD Site-Specific Parameter Summary 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R011 ³ Area of contaminated zone (m**2) ³ 1.302E+04 ³ 1.000E+04 ³ --- ³ AREA R011 ³ Thickness of contaminated zone (m) ³ 1.975E+00 ³ 2.000E+00 ³ --- ³ THICK0 R011 ³ Length parallel to aquifer flow (m) ³ 1.290E+02 ³ 1.000E+02 ³ --- ³ LCZPAQ R011 ³ Basic radiation dose limit (mrem/yr) ³ 2.500E+01 ³ 2.500E+01 ³ --- ³ BRDL R011 ³ Time since placement of material (yr) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ TI R011 ³ Times for calculations (yr) ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ T( 2)

R011 ³ Times for calculations (yr) ³ 3.000E+00 ³ 3.000E+00 ³ --- ³ T( 3)

R011 ³ Times for calculations (yr) ³ 1.000E+01 ³ 1.000E+01 ³ --- ³ T( 4)

R011 ³ Times for calculations (yr) ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ T( 5)

R011 ³ Times for calculations (yr) ³ 1.000E+02 ³ 1.000E+02 ³ --- ³ T( 6)

R011 ³ Times for calculations (yr) ³ 3.000E+02 ³ 3.000E+02 ³ --- ³ T( 7)

R011 ³ Times for calculations (yr) ³ 1.000E+03 ³ 1.000E+03 ³ --- ³ T( 8)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T( 9)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T(10)

³ ³ ³ ³ ³ R012 ³ Initial principal radionuclide (pCi/g): Cs-137 ³ 1.000E+00 ³ 0.000E+00 ³ --- ³ S1( 1)

R012 ³ Concentration in groundwater (pCi/L): Cs-137 ³ not used ³ 0.000E+00 ³ --- ³ W1( 1)

³ ³ ³ ³ ³ R013 ³ Cover depth (m) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ COVER0 R013 ³ Density of cover material (g/cm**3) ³ not used ³ 1.500E+00 ³ --- ³ DENSCV R013 ³ Cover depth erosion rate (m/yr) ³ not used ³ 1.000E-03 ³ --- ³ VCV R013 ³ Density of contaminated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSCZ R013 ³ Contaminated zone erosion rate (m/yr) ³ 8.500E-04 ³ 1.000E-03 ³ --- ³ VCZ R013 ³ Contaminated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPCZ R013 ³ Contaminated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCCZ R013 ³ Contaminated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCCZ R013 ³ Contaminated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BCZ R013 ³ Average annual wind speed (m/sec) ³ 2.030E+00 ³ 2.000E+00 ³ --- ³ WIND R013 ³ Humidity in air (g/m**3) ³ not used ³ 8.000E+00 ³ --- ³ HUMID R013 ³ Evapotranspiration coefficient ³ 6.250E-01 ³ 5.000E-01 ³ --- ³ EVAPTR R013 ³ Precipitation (m/yr) ³ 1.200E+00 ³ 1.000E+00 ³ --- ³ PRECIP R013 ³ Irrigation (m/yr) ³ 4.350E-01 ³ 2.000E-01 ³ --- ³ RI R013 ³ Irrigation mode ³ overhead ³ overhead ³ --- ³ IDITCH R013 ³ Runoff coefficient ³ 6.000E-01 ³ 2.000E-01 ³ --- ³ RUNOFF R013 ³ Watershed area for nearby stream or pond (m**2) ³ 7.770E+05 ³ 1.000E+06 ³ --- ³ WAREA R013 ³ Accuracy for water/soil computations ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ EPS

³ ³ ³ ³ ³ R014 ³ Density of saturated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSAQ R014 ³ Saturated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPSZ R014 ³ Saturated zone effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPSZ R014 ³ Saturated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCSZ R014 ³ Saturated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+02 ³ --- ³ HCSZ R014 ³ Saturated zone hydraulic gradient ³ 1.000E-01 ³ 2.000E-02 ³ --- ³ HGWT R014 ³ Saturated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BSZ R014 ³ Water table drop rate (m/yr) ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ VWT R014 ³ Well pump intake depth (m below water table) ³ 1.451E+01 ³ 1.000E+01 ³ --- ³ DWIBWT R014 ³ Model: Nondispersion (ND) or Mass-Balance (MB) ³ ND ³ ND ³ --- ³ MODEL R014 ³ Well pumping rate (m**3/yr) ³ 1.323E+03 ³ 2.500E+02 ³ --- ³ UW

³ ³ ³ ³ ³ R015 ³ Number of unsaturated zone strata ³ 1 ³ 1 ³ --- ³ NS 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/26/2003 16:26 Page 4 Summary : Yankee Rowe Sensitivity Analysis=soil File: Cs-137_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R015 ³ Unsat. zone 1, thickness (m) ³ 1.820E+00 ³ 4.000E+00 ³ --- ³ H(1)

R015 ³ Unsat. zone 1, soil density (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSUZ(1)

R015 ³ Unsat. zone 1, total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPUZ(1)

R015 ³ Unsat. zone 1, effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPUZ(1)

R015 ³ Unsat. zone 1, field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCUZ(1)

R015 ³ Unsat. zone 1, soil-specific b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BUZ(1)

R015 ³ Unsat. zone 1, hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCUZ(1)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for Cs-137 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 4.460E+02 ³ 1.000E+03 ³ --- ³ DCNUCC( 1)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 4.460E+02 ³ 1.000E+03 ³ --- ³ DCNUCU( 1,1)

R016 ³ Saturated zone (cm**3/g) ³ 4.460E+02 ³ 1.000E+03 ³ --- ³ DCNUCS( 1)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 2.579E-04 ³ ALEACH( 1)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 1)

³ ³ ³ ³ ³ R017 ³ Inhalation rate (m**3/yr) ³ 8.400E+03 ³ 8.400E+03 ³ --- ³ INHALR R017 ³ Mass loading for inhalation (g/m**3) ³ 2.330E-05 ³ 1.000E-04 ³ --- ³ MLINH R017 ³ Exposure duration ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ ED R017 ³ Shielding factor, inhalation ³ 5.500E-01 ³ 4.000E-01 ³ --- ³ SHF3 R017 ³ Shielding factor, external gamma ³ 3.980E-01 ³ 7.000E-01 ³ --- ³ SHF1 R017 ³ Fraction of time spent indoors ³ 6.571E-01 ³ 5.000E-01 ³ --- ³ FIND R017 ³ Fraction of time spent outdoors (on site) ³ 1.181E-01 ³ 2.500E-01 ³ --- ³ FOTD R017 ³ Shape factor flag, external gamma ³ 1.000E+00 ³ 1.000E+00 ³ >0 shows circular AREA. ³ FS R017 ³ Radii of shape factor array (used if FS = -1): ³ ³ ³ ³ R017 ³ Outer annular radius (m), ring 1: ³ not used ³ 5.000E+01 ³ --- ³ RAD_SHAPE(

1)

R017 ³ Outer annular radius (m), ring 2: ³ not used ³ 7.071E+01 ³ --- ³ RAD_SHAPE(

2)

R017 ³ Outer annular radius (m), ring 3: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

3)

R017 ³ Outer annular radius (m), ring 4: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

4)

R017 ³ Outer annular radius (m), ring 5: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

5)

R017 ³ Outer annular radius (m), ring 6: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

6)

R017 ³ Outer annular radius (m), ring 7: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

7)

R017 ³ Outer annular radius (m), ring 8: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

8)

R017 ³ Outer annular radius (m), ring 9: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

9)

R017 ³ Outer annular radius (m), ring 10: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (10)

R017 ³ Outer annular radius (m), ring 11: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (11)

R017 ³ Outer annular radius (m), ring 12: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (12)

³ ³ ³ ³ ³ R017 ³ Fractions of annular areas within AREA: ³ ³ ³ ³ R017 ³ Ring 1 ³ not used ³ 1.000E+00 ³ --- ³ FRACA( 1)

R017 ³ Ring 2 ³ not used ³ 2.732E-01 ³ --- ³ FRACA( 2)

R017 ³ Ring 3 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 3)

R017 ³ Ring 4 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 4)

R017 ³ Ring 5 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 5)

R017 ³ Ring 6 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 6)

R017 ³ Ring 7 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 7)

R017 ³ Ring 8 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 8)

R017 ³ Ring 9 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 9)

R017 ³ Ring 10 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(10)

R017 ³ Ring 11 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(11)

R017 ³ Ring 12 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(12)

³ ³ ³ ³ ³ 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/26/2003 16:26 Page 5 Summary : Yankee Rowe Sensitivity Analysis=soil File: Cs-137_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R018 ³ Fruits, vegetables and grain consumption (kg/yr) ³ 1.120E+02 ³ 1.600E+02 ³ --- ³ DIET(1)

R018 ³ Leafy vegetable consumption (kg/yr) ³ 2.140E+01 ³ 1.400E+01 ³ --- ³ DIET(2)

R018 ³ Milk consumption (L/yr) ³ 2.330E+02 ³ 9.200E+01 ³ --- ³ DIET(3)

R018 ³ Meat and poultry consumption (kg/yr) ³ 6.510E+01 ³ 6.300E+01 ³ --- ³ DIET(4)

R018 ³ Fish consumption (kg/yr) ³ 2.060E+01 ³ 5.400E+00 ³ --- ³ DIET(5)

R018 ³ Other seafood consumption (kg/yr) ³ 9.000E-01 ³ 9.000E-01 ³ --- ³ DIET(6)

R018 ³ Soil ingestion rate (g/yr) ³ 1.826E+01 ³ 3.650E+01 ³ --- ³ SOIL R018 ³ Drinking water intake (L/yr) ³ 4.785E+02 ³ 5.100E+02 ³ --- ³ DWI R018 ³ Contamination fraction of drinking water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FDW R018 ³ Contamination fraction of household water ³ not used ³ 1.000E+00 ³ --- ³ FHHW R018 ³ Contamination fraction of livestock water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FLW R018 ³ Contamination fraction of irrigation water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FIRW R018 ³ Contamination fraction of aquatic food ³ 1.000E+00 ³ 5.000E-01 ³ --- ³ FR9 R018 ³ Contamination fraction of plant food ³ 1.000E+00 ³-1 ³ --- ³ FPLANT R018 ³ Contamination fraction of meat ³ 1.000E+00 ³-1 ³ --- ³ FMEAT R018 ³ Contamination fraction of milk ³ 1.000E+00 ³-1 ³ --- ³ FMILK

³ ³ ³ ³ ³ R019 ³ Livestock fodder intake for meat (kg/day) ³ 2.710E+01 ³ 6.800E+01 ³ --- ³ LFI5 R019 ³ Livestock fodder intake for milk (kg/day) ³ 6.320E+01 ³ 5.500E+01 ³ --- ³ LFI6 R019 ³ Livestock water intake for meat (L/day) ³ 5.060E+01 ³ 5.000E+01 ³ --- ³ LWI5 R019 ³ Livestock water intake for milk (L/day) ³ 6.000E+01 ³ 1.600E+02 ³ --- ³ LWI6 R019 ³ Livestock soil intake (kg/day) ³ 5.000E-01 ³ 5.000E-01 ³ --- ³ LSI R019 ³ Mass loading for foliar deposition (g/m**3) ³ 4.000E-04 ³ 1.000E-04 ³ --- ³ MLFD R019 ³ Depth of soil mixing layer (m) ³ 2.300E-01 ³ 1.500E-01 ³ --- ³ DM R019 ³ Depth of roots (m) ³ 1.170E+00 ³ 9.000E-01 ³ --- ³ DROOT R019 ³ Drinking water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWDW R019 ³ Household water fraction from ground water ³ not used ³ 1.000E+00 ³ --- ³ FGWHH R019 ³ Livestock water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWLW R019 ³ Irrigation fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWIR

³ ³ ³ ³ ³ R19B ³ Wet weight crop yield for Non-Leafy (kg/m**2) ³ 1.750E+00 ³ 7.000E-01 ³ --- ³ YV(1)

R19B ³ Wet weight crop yield for Leafy (kg/m**2) ³ 2.889E+00 ³ 1.500E+00 ³ --- ³ YV(2)

R19B ³ Wet weight crop yield for Fodder (kg/m**2) ³ 1.887E+00 ³ 1.100E+00 ³ --- ³ YV(3)

R19B ³ Growing Season for Non-Leafy (years) ³ 2.460E-01 ³ 1.700E-01 ³ --- ³ TE(1)

R19B ³ Growing Season for Leafy (years) ³ 1.230E-01 ³ 2.500E-01 ³ --- ³ TE(2)

R19B ³ Growing Season for Fodder (years) ³ 8.200E-02 ³ 8.000E-02 ³ --- ³ TE(3)

R19B ³ Translocation Factor for Non-Leafy ³ 1.000E-01 ³ 1.000E-01 ³ --- ³ TIV(1)

R19B ³ Translocation Factor for Leafy ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(2)

R19B ³ Translocation Factor for Fodder ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(3)

R19B ³ Dry Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(1)

R19B ³ Dry Foliar Interception Fraction for Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(2)

R19B ³ Dry Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(3)

R19B ³ Wet Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(1)

R19B ³ Wet Foliar Interception Fraction for Leafy ³ 5.800E-01 ³ 2.500E-01 ³ --- ³ RWET(2)

R19B ³ Wet Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(3)

R19B ³ Weathering Removal Constant for Vegetation ³ 3.300E+01 ³ 2.000E+01 ³ --- ³ WLAM

³ ³ ³ ³ ³ C14 ³ C-12 concentration in water (g/cm**3) ³ not used ³ 2.000E-05 ³ --- ³ C12WTR C14 ³ C-12 concentration in contaminated soil (g/g) ³ not used ³ 3.000E-02 ³ --- ³ C12CZ C14 ³ Fraction of vegetation carbon from soil ³ not used ³ 2.000E-02 ³ --- ³ CSOIL C14 ³ Fraction of vegetation carbon from air ³ not used ³ 9.800E-01 ³ --- ³ CAIR 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/26/2003 16:26 Page 6 Summary : Yankee Rowe Sensitivity Analysis=soil File: Cs-137_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ C14 ³ C-14 evasion layer thickness in soil (m) ³ not used ³ 3.000E-01 ³ --- ³ DMC C14 ³ C-14 evasion flux rate from soil (1/sec) ³ not used ³ 7.000E-07 ³ --- ³ EVSN C14 ³ C-12 evasion flux rate from soil (1/sec) ³ not used ³ 1.000E-10 ³ --- ³ REVSN C14 ³ Fraction of grain in beef cattle feed ³ not used ³ 8.000E-01 ³ --- ³ AVFG4 C14 ³ Fraction of grain in milk cow feed ³ not used ³ 2.000E-01 ³ --- ³ AVFG5 C14 ³ DCF correction factor for gaseous forms of C14 ³ not used ³ 8.894E+01 ³ --- ³ CO2F

³ ³ ³ ³ ³ STOR ³ Storage times of contaminated foodstuffs (days): ³ ³ ³ ³ STOR ³ Fruits, non-leafy vegetables, and grain ³ 1.400E+01 ³ 1.400E+01 ³ --- ³ STOR_T(1)

STOR ³ Leafy vegetables ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(2)

STOR ³ Milk ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(3)

STOR ³ Meat and poultry ³ 2.000E+01 ³ 2.000E+01 ³ --- ³ STOR_T(4)

STOR ³ Fish ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(5)

STOR ³ Crustacea and mollusks ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(6)

STOR ³ Well water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(7)

STOR ³ Surface water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(8)

STOR ³ Livestock fodder ³ 4.500E+01 ³ 4.500E+01 ³ --- ³ STOR_T(9)

³ ³ ³ ³ ³ R021 ³ Thickness of building foundation (m) ³ not used ³ 1.500E-01 ³ --- ³ FLOOR1 R021 ³ Bulk density of building foundation (g/cm**3) ³ not used ³ 2.400E+00 ³ --- ³ DENSFL R021 ³ Total porosity of the cover material ³ not used ³ 4.000E-01 ³ --- ³ TPCV R021 ³ Total porosity of the building foundation ³ not used ³ 1.000E-01 ³ --- ³ TPFL R021 ³ Volumetric water content of the cover material ³ not used ³ 5.000E-02 ³ --- ³ PH2OCV R021 ³ Volumetric water content of the foundation ³ not used ³ 3.000E-02 ³ --- ³ PH2OFL R021 ³ Diffusion coefficient for radon gas (m/sec): ³ ³ ³ ³ R021 ³ in cover material ³ not used ³ 2.000E-06 ³ --- ³ DIFCV R021 ³ in foundation material ³ not used ³ 3.000E-07 ³ --- ³ DIFFL R021 ³ in contaminated zone soil ³ not used ³ 2.000E-06 ³ --- ³ DIFCZ R021 ³ Radon vertical dimension of mixing (m) ³ not used ³ 2.000E+00 ³ --- ³ HMIX R021 ³ Average building air exchange rate (1/hr) ³ not used ³ 5.000E-01 ³ --- ³ REXG R021 ³ Height of the building (room) (m) ³ not used ³ 2.500E+00 ³ --- ³ HRM R021 ³ Building interior area factor ³ not used ³ 0.000E+00 ³ --- ³ FAI R021 ³ Building depth below ground surface (m) ³ not used ³-1.000E+00 ³ --- ³ DMFL R021 ³ Emanating power of Rn-222 gas ³ not used ³ 2.500E-01 ³ --- ³ EMANA(1)

R021 ³ Emanating power of Rn-220 gas ³ not used ³ 1.500E-01 ³ --- ³ EMANA(2)

³ ³ ³ ³ ³ TITL ³ Number of graphical time points ³ 32 ³ --- ³ --- ³ NPTS TITL ³ Maximum number of integration points for dose ³ 17 ³ --- ³ --- ³ LYMAX TITL ³ Maximum number of integration points for risk ³ 1 ³ --- ³ --- ³ KYMAX

1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/26/2003 16:26 Page 7 Summary : Yankee Rowe Sensitivity Analysis=soil File: Cs-137_DCGL.RAD Summary of Pathway Selections Pathway ³ User Selection

Å 1 -- external gamma ³ active 2 -- inhalation (w/o radon)³ active 3 -- plant ingestion ³ active 4 -- meat ingestion ³ active 5 -- milk ingestion ³ active 6 -- aquatic foods ³ active 7 -- drinking water ³ active 8 -- soil ingestion ³ active 9 -- radon ³ suppressed Find peak pathway doses ³ active

1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 07:28 Page 2 Summary : Yankee Rowe Sensitivity Analysis=soil File: Eu-152_DCGL.RAD Dose Conversion Factor (and Related) Parameter Summary File: FGR 13 Morbidity 0 ³ ³ Current ³ ³ Parameter Menu ³ Parameter ³ Value ³ Default ³ Name

ÅÅÅÅ B-1 ³ Dose conversion factors for inhalation, mrem/pCi: ³ ³ ³ B-1 ³ Eu-152 ³ 2.210E-04 ³ 2.210E-04 ³ DCF2( 1)

B-1 ³ Gd-152 ³ 2.430E-01 ³ 2.430E-01 ³ DCF2( 3)

³ ³ ³ ³ D-1 ³ Dose conversion factors for ingestion, mrem/pCi: ³ ³ ³ D-1 ³ Eu-152 ³ 6.480E-06 ³ 6.480E-06 ³ DCF3( 1)

D-1 ³ Gd-152 ³ 1.610E-04 ³ 1.610E-04 ³ DCF3( 3)

³ ³ ³ ³ D-34 ³ Food transfer factors: ³ ³ ³ D-34 ³ Eu-152, plant/soil concentration ratio, dimensionless ³ 2.500E-03 ³ 2.500E-03 ³ RTF( 1,1)

D-34 ³ Eu-152, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 2.000E-03 ³ 2.000E-03 ³ RTF( 1,2)

D-34 ³ Eu-152, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 2.000E-05 ³ 2.000E-05 ³ RTF( 1,3)

D-34 ³ ³ ³ ³ D-34 ³ Gd-152, plant/soil concentration ratio, dimensionless ³ 2.500E-03 ³ 2.500E-03 ³ RTF( 3,1)

D-34 ³ Gd-152, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 2.000E-03 ³ 2.000E-03 ³ RTF( 3,2)

D-34 ³ Gd-152, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 2.000E-05 ³ 2.000E-05 ³ RTF( 3,3)

³ ³ ³ ³ D-5 ³ Bioaccumulation factors, fresh water, L/kg: ³ ³ ³ D-5 ³ Eu-152, fish ³ 5.000E+01 ³ 5.000E+01 ³ BIOFAC( 1,1)

D-5 ³ Eu-152, crustacea and mollusks ³ 1.000E+03 ³ 1.000E+03 ³ BIOFAC( 1,2)

D-5 ³ ³ ³ ³ D-5 ³ Gd-152, fish ³ 2.500E+01 ³ 2.500E+01 ³ BIOFAC( 3,1)

D-5 ³ Gd-152, crustacea and mollusks ³ 1.000E+03 ³ 1.000E+03 ³ BIOFAC( 3,2) 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 07:28 Page 3 Summary : Yankee Rowe Sensitivity Analysis=soil File: Eu-152_DCGL.RAD Site-Specific Parameter Summary 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R011 ³ Area of contaminated zone (m**2) ³ 1.302E+04 ³ 1.000E+04 ³ --- ³ AREA R011 ³ Thickness of contaminated zone (m) ³ 1.975E+00 ³ 2.000E+00 ³ --- ³ THICK0 R011 ³ Length parallel to aquifer flow (m) ³ 1.290E+02 ³ 1.000E+02 ³ --- ³ LCZPAQ R011 ³ Basic radiation dose limit (mrem/yr) ³ 2.500E+01 ³ 2.500E+01 ³ --- ³ BRDL R011 ³ Time since placement of material (yr) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ TI R011 ³ Times for calculations (yr) ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ T( 2)

R011 ³ Times for calculations (yr) ³ 3.000E+00 ³ 3.000E+00 ³ --- ³ T( 3)

R011 ³ Times for calculations (yr) ³ 1.000E+01 ³ 1.000E+01 ³ --- ³ T( 4)

R011 ³ Times for calculations (yr) ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ T( 5)

R011 ³ Times for calculations (yr) ³ 1.000E+02 ³ 1.000E+02 ³ --- ³ T( 6)

R011 ³ Times for calculations (yr) ³ 3.000E+02 ³ 3.000E+02 ³ --- ³ T( 7)

R011 ³ Times for calculations (yr) ³ 1.000E+03 ³ 1.000E+03 ³ --- ³ T( 8)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T( 9)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T(10)

³ ³ ³ ³ ³ R012 ³ Initial principal radionuclide (pCi/g): Eu-152 ³ 1.000E+00 ³ 0.000E+00 ³ --- ³ S1( 1)

R012 ³ Concentration in groundwater (pCi/L): Eu-152 ³ not used ³ 0.000E+00 ³ --- ³ W1( 1)

³ ³ ³ ³ ³ R013 ³ Cover depth (m) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ COVER0 R013 ³ Density of cover material (g/cm**3) ³ not used ³ 1.500E+00 ³ --- ³ DENSCV R013 ³ Cover depth erosion rate (m/yr) ³ not used ³ 1.000E-03 ³ --- ³ VCV R013 ³ Density of contaminated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSCZ R013 ³ Contaminated zone erosion rate (m/yr) ³ 8.500E-04 ³ 1.000E-03 ³ --- ³ VCZ R013 ³ Contaminated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPCZ R013 ³ Contaminated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCCZ R013 ³ Contaminated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCCZ R013 ³ Contaminated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BCZ R013 ³ Average annual wind speed (m/sec) ³ 2.030E+00 ³ 2.000E+00 ³ --- ³ WIND R013 ³ Humidity in air (g/m**3) ³ not used ³ 8.000E+00 ³ --- ³ HUMID R013 ³ Evapotranspiration coefficient ³ 6.250E-01 ³ 5.000E-01 ³ --- ³ EVAPTR R013 ³ Precipitation (m/yr) ³ 1.200E+00 ³ 1.000E+00 ³ --- ³ PRECIP R013 ³ Irrigation (m/yr) ³ 4.350E-01 ³ 2.000E-01 ³ --- ³ RI R013 ³ Irrigation mode ³ overhead ³ overhead ³ --- ³ IDITCH R013 ³ Runoff coefficient ³ 6.000E-01 ³ 2.000E-01 ³ --- ³ RUNOFF R013 ³ Watershed area for nearby stream or pond (m**2) ³ 7.770E+05 ³ 1.000E+06 ³ --- ³ WAREA R013 ³ Accuracy for water/soil computations ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ EPS

³ ³ ³ ³ ³ R014 ³ Density of saturated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSAQ R014 ³ Saturated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPSZ R014 ³ Saturated zone effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPSZ R014 ³ Saturated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCSZ R014 ³ Saturated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+02 ³ --- ³ HCSZ R014 ³ Saturated zone hydraulic gradient ³ 1.000E-01 ³ 2.000E-02 ³ --- ³ HGWT R014 ³ Saturated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BSZ R014 ³ Water table drop rate (m/yr) ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ VWT R014 ³ Well pump intake depth (m below water table) ³ 1.451E+01 ³ 1.000E+01 ³ --- ³ DWIBWT R014 ³ Model: Nondispersion (ND) or Mass-Balance (MB) ³ ND ³ ND ³ --- ³ MODEL R014 ³ Well pumping rate (m**3/yr) ³ 1.323E+03 ³ 2.500E+02 ³ --- ³ UW

³ ³ ³ ³ ³ R015 ³ Number of unsaturated zone strata ³ 1 ³ 1 ³ --- ³ NS 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 07:28 Page 4 Summary : Yankee Rowe Sensitivity Analysis=soil File: Eu-152_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R015 ³ Unsat. zone 1, thickness (m) ³ 1.820E+00 ³ 4.000E+00 ³ --- ³ H(1)

R015 ³ Unsat. zone 1, soil density (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSUZ(1)

R015 ³ Unsat. zone 1, total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPUZ(1)

R015 ³ Unsat. zone 1, effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPUZ(1)

R015 ³ Unsat. zone 1, field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCUZ(1)

R015 ³ Unsat. zone 1, soil-specific b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BUZ(1)

R015 ³ Unsat. zone 1, hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCUZ(1)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for Eu-152 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 8.250E+02 ³-1.000E+00 ³ --- ³ DCNUCC( 1)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 8.250E+02 ³-1.000E+00 ³ --- ³ DCNUCU( 1,1)

R016 ³ Saturated zone (cm**3/g) ³ 8.250E+02 ³-1.000E+00 ³ --- ³ DCNUCS( 1)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 1.394E-04 ³ ALEACH( 1)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 1)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for daughter Gd-152 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 8.250E+02 ³-1.000E+00 ³ --- ³ DCNUCC( 3)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 8.250E+02 ³-1.000E+00 ³ --- ³ DCNUCU( 3,1)

R016 ³ Saturated zone (cm**3/g) ³ 8.250E+02 ³-1.000E+00 ³ --- ³ DCNUCS( 3)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 1.394E-04 ³ ALEACH( 3)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 3)

³ ³ ³ ³ ³ R017 ³ Inhalation rate (m**3/yr) ³ 8.400E+03 ³ 8.400E+03 ³ --- ³ INHALR R017 ³ Mass loading for inhalation (g/m**3) ³ 2.330E-05 ³ 1.000E-04 ³ --- ³ MLINH R017 ³ Exposure duration ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ ED R017 ³ Shielding factor, inhalation ³ 5.500E-01 ³ 4.000E-01 ³ --- ³ SHF3 R017 ³ Shielding factor, external gamma ³ 3.980E-01 ³ 7.000E-01 ³ --- ³ SHF1 R017 ³ Fraction of time spent indoors ³ 6.571E-01 ³ 5.000E-01 ³ --- ³ FIND R017 ³ Fraction of time spent outdoors (on site) ³ 1.181E-01 ³ 2.500E-01 ³ --- ³ FOTD R017 ³ Shape factor flag, external gamma ³ 1.000E+00 ³ 1.000E+00 ³ >0 shows circular AREA. ³ FS R017 ³ Radii of shape factor array (used if FS = -1): ³ ³ ³ ³ R017 ³ Outer annular radius (m), ring 1: ³ not used ³ 5.000E+01 ³ --- ³ RAD_SHAPE(

1)

R017 ³ Outer annular radius (m), ring 2: ³ not used ³ 7.071E+01 ³ --- ³ RAD_SHAPE(

2)

R017 ³ Outer annular radius (m), ring 3: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

3)

R017 ³ Outer annular radius (m), ring 4: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

4)

R017 ³ Outer annular radius (m), ring 5: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

5)

R017 ³ Outer annular radius (m), ring 6: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

6)

R017 ³ Outer annular radius (m), ring 7: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

7)

R017 ³ Outer annular radius (m), ring 8: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

8)

R017 ³ Outer annular radius (m), ring 9: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

9)

R017 ³ Outer annular radius (m), ring 10: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (10)

R017 ³ Outer annular radius (m), ring 11: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (11)

R017 ³ Outer annular radius (m), ring 12: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (12)

³ ³ ³ ³ ³ 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 07:28 Page 5 Summary : Yankee Rowe Sensitivity Analysis=soil File: Eu-152_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R017 ³ Fractions of annular areas within AREA: ³ ³ ³ ³ R017 ³ Ring 1 ³ not used ³ 1.000E+00 ³ --- ³ FRACA( 1)

R017 ³ Ring 2 ³ not used ³ 2.732E-01 ³ --- ³ FRACA( 2)

R017 ³ Ring 3 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 3)

R017 ³ Ring 4 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 4)

R017 ³ Ring 5 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 5)

R017 ³ Ring 6 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 6)

R017 ³ Ring 7 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 7)

R017 ³ Ring 8 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 8)

R017 ³ Ring 9 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 9)

R017 ³ Ring 10 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(10)

R017 ³ Ring 11 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(11)

R017 ³ Ring 12 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(12)

³ ³ ³ ³ ³ R018 ³ Fruits, vegetables and grain consumption (kg/yr) ³ 1.120E+02 ³ 1.600E+02 ³ --- ³ DIET(1)

R018 ³ Leafy vegetable consumption (kg/yr) ³ 2.140E+01 ³ 1.400E+01 ³ --- ³ DIET(2)

R018 ³ Milk consumption (L/yr) ³ 2.330E+02 ³ 9.200E+01 ³ --- ³ DIET(3)

R018 ³ Meat and poultry consumption (kg/yr) ³ 6.510E+01 ³ 6.300E+01 ³ --- ³ DIET(4)

R018 ³ Fish consumption (kg/yr) ³ 2.060E+01 ³ 5.400E+00 ³ --- ³ DIET(5)

R018 ³ Other seafood consumption (kg/yr) ³ 9.000E-01 ³ 9.000E-01 ³ --- ³ DIET(6)

R018 ³ Soil ingestion rate (g/yr) ³ 1.826E+01 ³ 3.650E+01 ³ --- ³ SOIL R018 ³ Drinking water intake (L/yr) ³ 4.785E+02 ³ 5.100E+02 ³ --- ³ DWI R018 ³ Contamination fraction of drinking water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FDW R018 ³ Contamination fraction of household water ³ not used ³ 1.000E+00 ³ --- ³ FHHW R018 ³ Contamination fraction of livestock water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FLW R018 ³ Contamination fraction of irrigation water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FIRW R018 ³ Contamination fraction of aquatic food ³ 1.000E+00 ³ 5.000E-01 ³ --- ³ FR9 R018 ³ Contamination fraction of plant food ³ 1.000E+00 ³-1 ³ --- ³ FPLANT R018 ³ Contamination fraction of meat ³ 1.000E+00 ³-1 ³ --- ³ FMEAT R018 ³ Contamination fraction of milk ³ 1.000E+00 ³-1 ³ --- ³ FMILK

³ ³ ³ ³ ³ R019 ³ Livestock fodder intake for meat (kg/day) ³ 2.710E+01 ³ 6.800E+01 ³ --- ³ LFI5 R019 ³ Livestock fodder intake for milk (kg/day) ³ 6.320E+01 ³ 5.500E+01 ³ --- ³ LFI6 R019 ³ Livestock water intake for meat (L/day) ³ 5.060E+01 ³ 5.000E+01 ³ --- ³ LWI5 R019 ³ Livestock water intake for milk (L/day) ³ 6.000E+01 ³ 1.600E+02 ³ --- ³ LWI6 R019 ³ Livestock soil intake (kg/day) ³ 5.000E-01 ³ 5.000E-01 ³ --- ³ LSI R019 ³ Mass loading for foliar deposition (g/m**3) ³ 4.000E-04 ³ 1.000E-04 ³ --- ³ MLFD R019 ³ Depth of soil mixing layer (m) ³ 2.300E-01 ³ 1.500E-01 ³ --- ³ DM R019 ³ Depth of roots (m) ³ 2.050E+00 ³ 9.000E-01 ³ --- ³ DROOT R019 ³ Drinking water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWDW R019 ³ Household water fraction from ground water ³ not used ³ 1.000E+00 ³ --- ³ FGWHH R019 ³ Livestock water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWLW R019 ³ Irrigation fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWIR

³ ³ ³ ³ ³ R19B ³ Wet weight crop yield for Non-Leafy (kg/m**2) ³ 1.750E+00 ³ 7.000E-01 ³ --- ³ YV(1)

R19B ³ Wet weight crop yield for Leafy (kg/m**2) ³ 2.889E+00 ³ 1.500E+00 ³ --- ³ YV(2)

R19B ³ Wet weight crop yield for Fodder (kg/m**2) ³ 1.887E+00 ³ 1.100E+00 ³ --- ³ YV(3)

R19B ³ Growing Season for Non-Leafy (years) ³ 2.460E-01 ³ 1.700E-01 ³ --- ³ TE(1)

R19B ³ Growing Season for Leafy (years) ³ 1.230E-01 ³ 2.500E-01 ³ --- ³ TE(2)

R19B ³ Growing Season for Fodder (years) ³ 8.200E-02 ³ 8.000E-02 ³ --- ³ TE(3)

R19B ³ Translocation Factor for Non-Leafy ³ 1.000E-01 ³ 1.000E-01 ³ --- ³ TIV(1) 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 07:28 Page 6 Summary : Yankee Rowe Sensitivity Analysis=soil File: Eu-152_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R19B ³ Translocation Factor for Leafy ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(2)

R19B ³ Translocation Factor for Fodder ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(3)

R19B ³ Dry Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(1)

R19B ³ Dry Foliar Interception Fraction for Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(2)

R19B ³ Dry Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(3)

R19B ³ Wet Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(1)

R19B ³ Wet Foliar Interception Fraction for Leafy ³ 5.800E-01 ³ 2.500E-01 ³ --- ³ RWET(2)

R19B ³ Wet Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(3)

R19B ³ Weathering Removal Constant for Vegetation ³ 3.300E+01 ³ 2.000E+01 ³ --- ³ WLAM

³ ³ ³ ³ ³ C14 ³ C-12 concentration in water (g/cm**3) ³ not used ³ 2.000E-05 ³ --- ³ C12WTR C14 ³ C-12 concentration in contaminated soil (g/g) ³ not used ³ 3.000E-02 ³ --- ³ C12CZ C14 ³ Fraction of vegetation carbon from soil ³ not used ³ 2.000E-02 ³ --- ³ CSOIL C14 ³ Fraction of vegetation carbon from air ³ not used ³ 9.800E-01 ³ --- ³ CAIR C14 ³ C-14 evasion layer thickness in soil (m) ³ not used ³ 3.000E-01 ³ --- ³ DMC C14 ³ C-14 evasion flux rate from soil (1/sec) ³ not used ³ 7.000E-07 ³ --- ³ EVSN C14 ³ C-12 evasion flux rate from soil (1/sec) ³ not used ³ 1.000E-10 ³ --- ³ REVSN C14 ³ Fraction of grain in beef cattle feed ³ not used ³ 8.000E-01 ³ --- ³ AVFG4 C14 ³ Fraction of grain in milk cow feed ³ not used ³ 2.000E-01 ³ --- ³ AVFG5 C14 ³ DCF correction factor for gaseous forms of C14 ³ not used ³ 8.894E+01 ³ --- ³ CO2F

³ ³ ³ ³ ³ STOR ³ Storage times of contaminated foodstuffs (days): ³ ³ ³ ³ STOR ³ Fruits, non-leafy vegetables, and grain ³ 1.400E+01 ³ 1.400E+01 ³ --- ³ STOR_T(1)

STOR ³ Leafy vegetables ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(2)

STOR ³ Milk ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(3)

STOR ³ Meat and poultry ³ 2.000E+01 ³ 2.000E+01 ³ --- ³ STOR_T(4)

STOR ³ Fish ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(5)

STOR ³ Crustacea and mollusks ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(6)

STOR ³ Well water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(7)

STOR ³ Surface water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(8)

STOR ³ Livestock fodder ³ 4.500E+01 ³ 4.500E+01 ³ --- ³ STOR_T(9)

³ ³ ³ ³ ³ R021 ³ Thickness of building foundation (m) ³ not used ³ 1.500E-01 ³ --- ³ FLOOR1 R021 ³ Bulk density of building foundation (g/cm**3) ³ not used ³ 2.400E+00 ³ --- ³ DENSFL R021 ³ Total porosity of the cover material ³ not used ³ 4.000E-01 ³ --- ³ TPCV R021 ³ Total porosity of the building foundation ³ not used ³ 1.000E-01 ³ --- ³ TPFL R021 ³ Volumetric water content of the cover material ³ not used ³ 5.000E-02 ³ --- ³ PH2OCV R021 ³ Volumetric water content of the foundation ³ not used ³ 3.000E-02 ³ --- ³ PH2OFL R021 ³ Diffusion coefficient for radon gas (m/sec): ³ ³ ³ ³ R021 ³ in cover material ³ not used ³ 2.000E-06 ³ --- ³ DIFCV R021 ³ in foundation material ³ not used ³ 3.000E-07 ³ --- ³ DIFFL R021 ³ in contaminated zone soil ³ not used ³ 2.000E-06 ³ --- ³ DIFCZ R021 ³ Radon vertical dimension of mixing (m) ³ not used ³ 2.000E+00 ³ --- ³ HMIX R021 ³ Average building air exchange rate (1/hr) ³ not used ³ 5.000E-01 ³ --- ³ REXG R021 ³ Height of the building (room) (m) ³ not used ³ 2.500E+00 ³ --- ³ HRM R021 ³ Building interior area factor ³ not used ³ 0.000E+00 ³ --- ³ FAI R021 ³ Building depth below ground surface (m) ³ not used ³-1.000E+00 ³ --- ³ DMFL R021 ³ Emanating power of Rn-222 gas ³ not used ³ 2.500E-01 ³ --- ³ EMANA(1)

R021 ³ Emanating power of Rn-220 gas ³ not used ³ 1.500E-01 ³ --- ³ EMANA(2)

³ ³ ³ ³ ³ TITL ³ Number of graphical time points ³ 32 ³ --- ³ --- ³ NPTS TITL ³ Maximum number of integration points for dose ³ 17 ³ --- ³ --- ³ LYMAX 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 07:28 Page 7 Summary : Yankee Rowe Sensitivity Analysis=soil File: Eu-152_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ TITL ³ Maximum number of integration points for risk ³ 1 ³ --- ³ --- ³ KYMAX

Summary of Pathway Selections

Pathway ³ User Selection

Å 1 -- external gamma ³ active 2 -- inhalation (w/o radon)³ active 3 -- plant ingestion ³ active 4 -- meat ingestion ³ active 5 -- milk ingestion ³ active 6 -- aquatic foods ³ active 7 -- drinking water ³ active 8 -- soil ingestion ³ active 9 -- radon ³ suppressed Find peak pathway doses ³ active

1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 07:39 Page 2 Summary : Yankee Rowe Sensitivity Analysis=soil File: Eu-154_DCGL.RAD Dose Conversion Factor (and Related) Parameter Summary File: FGR 13 Morbidity 0 ³ ³ Current ³ ³ Parameter Menu ³ Parameter ³ Value ³ Default ³ Name

ÅÅÅÅ B-1 ³ Dose conversion factors for inhalation, mrem/pCi: ³ ³ ³ B-1 ³ Eu-154 ³ 2.860E-04 ³ 2.860E-04 ³ DCF2( 1)

³ ³ ³ ³ D-1 ³ Dose conversion factors for ingestion, mrem/pCi: ³ ³ ³ D-1 ³ Eu-154 ³ 9.550E-06 ³ 9.550E-06 ³ DCF3( 1)

³ ³ ³ ³ D-34 ³ Food transfer factors: ³ ³ ³ D-34 ³ Eu-154, plant/soil concentration ratio, dimensionless ³ 2.500E-03 ³ 2.500E-03 ³ RTF( 1,1)

D-34 ³ Eu-154, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 2.000E-03 ³ 2.000E-03 ³ RTF( 1,2)

D-34 ³ Eu-154, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 2.000E-05 ³ 2.000E-05 ³ RTF( 1,3)

³ ³ ³ ³ D-5 ³ Bioaccumulation factors, fresh water, L/kg: ³ ³ ³ D-5 ³ Eu-154, fish ³ 5.000E+01 ³ 5.000E+01 ³ BIOFAC( 1,1)

D-5 ³ Eu-154, crustacea and mollusks ³ 1.000E+03 ³ 1.000E+03 ³ BIOFAC( 1,2) 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 07:39 Page 3 Summary : Yankee Rowe Sensitivity Analysis=soil File: Eu-154_DCGL.RAD Site-Specific Parameter Summary 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R011 ³ Area of contaminated zone (m**2) ³ 1.302E+04 ³ 1.000E+04 ³ --- ³ AREA R011 ³ Thickness of contaminated zone (m) ³ 1.975E+00 ³ 2.000E+00 ³ --- ³ THICK0 R011 ³ Length parallel to aquifer flow (m) ³ 1.290E+02 ³ 1.000E+02 ³ --- ³ LCZPAQ R011 ³ Basic radiation dose limit (mrem/yr) ³ 2.500E+01 ³ 2.500E+01 ³ --- ³ BRDL R011 ³ Time since placement of material (yr) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ TI R011 ³ Times for calculations (yr) ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ T( 2)

R011 ³ Times for calculations (yr) ³ 3.000E+00 ³ 3.000E+00 ³ --- ³ T( 3)

R011 ³ Times for calculations (yr) ³ 1.000E+01 ³ 1.000E+01 ³ --- ³ T( 4)

R011 ³ Times for calculations (yr) ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ T( 5)

R011 ³ Times for calculations (yr) ³ 1.000E+02 ³ 1.000E+02 ³ --- ³ T( 6)

R011 ³ Times for calculations (yr) ³ 3.000E+02 ³ 3.000E+02 ³ --- ³ T( 7)

R011 ³ Times for calculations (yr) ³ 1.000E+03 ³ 1.000E+03 ³ --- ³ T( 8)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T( 9)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T(10)

³ ³ ³ ³ ³ R012 ³ Initial principal radionuclide (pCi/g): Eu-154 ³ 1.000E+00 ³ 0.000E+00 ³ --- ³ S1( 1)

R012 ³ Concentration in groundwater (pCi/L): Eu-154 ³ not used ³ 0.000E+00 ³ --- ³ W1( 1)

³ ³ ³ ³ ³ R013 ³ Cover depth (m) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ COVER0 R013 ³ Density of cover material (g/cm**3) ³ not used ³ 1.500E+00 ³ --- ³ DENSCV R013 ³ Cover depth erosion rate (m/yr) ³ not used ³ 1.000E-03 ³ --- ³ VCV R013 ³ Density of contaminated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSCZ R013 ³ Contaminated zone erosion rate (m/yr) ³ 8.500E-04 ³ 1.000E-03 ³ --- ³ VCZ R013 ³ Contaminated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPCZ R013 ³ Contaminated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCCZ R013 ³ Contaminated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCCZ R013 ³ Contaminated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BCZ R013 ³ Average annual wind speed (m/sec) ³ 2.030E+00 ³ 2.000E+00 ³ --- ³ WIND R013 ³ Humidity in air (g/m**3) ³ not used ³ 8.000E+00 ³ --- ³ HUMID R013 ³ Evapotranspiration coefficient ³ 6.250E-01 ³ 5.000E-01 ³ --- ³ EVAPTR R013 ³ Precipitation (m/yr) ³ 1.200E+00 ³ 1.000E+00 ³ --- ³ PRECIP R013 ³ Irrigation (m/yr) ³ 4.350E-01 ³ 2.000E-01 ³ --- ³ RI R013 ³ Irrigation mode ³ overhead ³ overhead ³ --- ³ IDITCH R013 ³ Runoff coefficient ³ 6.000E-01 ³ 2.000E-01 ³ --- ³ RUNOFF R013 ³ Watershed area for nearby stream or pond (m**2) ³ 7.770E+05 ³ 1.000E+06 ³ --- ³ WAREA R013 ³ Accuracy for water/soil computations ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ EPS

³ ³ ³ ³ ³ R014 ³ Density of saturated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSAQ R014 ³ Saturated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPSZ R014 ³ Saturated zone effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPSZ R014 ³ Saturated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCSZ R014 ³ Saturated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+02 ³ --- ³ HCSZ R014 ³ Saturated zone hydraulic gradient ³ 1.000E-01 ³ 2.000E-02 ³ --- ³ HGWT R014 ³ Saturated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BSZ R014 ³ Water table drop rate (m/yr) ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ VWT R014 ³ Well pump intake depth (m below water table) ³ 1.451E+01 ³ 1.000E+01 ³ --- ³ DWIBWT R014 ³ Model: Nondispersion (ND) or Mass-Balance (MB) ³ ND ³ ND ³ --- ³ MODEL R014 ³ Well pumping rate (m**3/yr) ³ 1.323E+03 ³ 2.500E+02 ³ --- ³ UW

³ ³ ³ ³ ³ R015 ³ Number of unsaturated zone strata ³ 1 ³ 1 ³ --- ³ NS 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 07:39 Page 4 Summary : Yankee Rowe Sensitivity Analysis=soil File: Eu-154_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R015 ³ Unsat. zone 1, thickness (m) ³ 1.820E+00 ³ 4.000E+00 ³ --- ³ H(1)

R015 ³ Unsat. zone 1, soil density (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSUZ(1)

R015 ³ Unsat. zone 1, total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPUZ(1)

R015 ³ Unsat. zone 1, effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPUZ(1)

R015 ³ Unsat. zone 1, field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCUZ(1)

R015 ³ Unsat. zone 1, soil-specific b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BUZ(1)

R015 ³ Unsat. zone 1, hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCUZ(1)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for Eu-154 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 8.250E+02 ³-1.000E+00 ³ --- ³ DCNUCC( 1)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 8.250E+02 ³-1.000E+00 ³ --- ³ DCNUCU( 1,1)

R016 ³ Saturated zone (cm**3/g) ³ 8.250E+02 ³-1.000E+00 ³ --- ³ DCNUCS( 1)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 1.394E-04 ³ ALEACH( 1)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 1)

³ ³ ³ ³ ³ R017 ³ Inhalation rate (m**3/yr) ³ 8.400E+03 ³ 8.400E+03 ³ --- ³ INHALR R017 ³ Mass loading for inhalation (g/m**3) ³ 2.330E-05 ³ 1.000E-04 ³ --- ³ MLINH R017 ³ Exposure duration ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ ED R017 ³ Shielding factor, inhalation ³ 5.500E-01 ³ 4.000E-01 ³ --- ³ SHF3 R017 ³ Shielding factor, external gamma ³ 3.980E-01 ³ 7.000E-01 ³ --- ³ SHF1 R017 ³ Fraction of time spent indoors ³ 6.571E-01 ³ 5.000E-01 ³ --- ³ FIND R017 ³ Fraction of time spent outdoors (on site) ³ 1.181E-01 ³ 2.500E-01 ³ --- ³ FOTD R017 ³ Shape factor flag, external gamma ³ 1.000E+00 ³ 1.000E+00 ³ >0 shows circular AREA. ³ FS R017 ³ Radii of shape factor array (used if FS = -1): ³ ³ ³ ³ R017 ³ Outer annular radius (m), ring 1: ³ not used ³ 5.000E+01 ³ --- ³ RAD_SHAPE(

1)

R017 ³ Outer annular radius (m), ring 2: ³ not used ³ 7.071E+01 ³ --- ³ RAD_SHAPE(

2)

R017 ³ Outer annular radius (m), ring 3: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

3)

R017 ³ Outer annular radius (m), ring 4: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

4)

R017 ³ Outer annular radius (m), ring 5: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

5)

R017 ³ Outer annular radius (m), ring 6: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

6)

R017 ³ Outer annular radius (m), ring 7: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

7)

R017 ³ Outer annular radius (m), ring 8: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

8)

R017 ³ Outer annular radius (m), ring 9: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

9)

R017 ³ Outer annular radius (m), ring 10: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (10)

R017 ³ Outer annular radius (m), ring 11: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (11)

R017 ³ Outer annular radius (m), ring 12: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (12)

³ ³ ³ ³ ³ R017 ³ Fractions of annular areas within AREA: ³ ³ ³ ³ R017 ³ Ring 1 ³ not used ³ 1.000E+00 ³ --- ³ FRACA( 1)

R017 ³ Ring 2 ³ not used ³ 2.732E-01 ³ --- ³ FRACA( 2)

R017 ³ Ring 3 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 3)

R017 ³ Ring 4 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 4)

R017 ³ Ring 5 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 5)

R017 ³ Ring 6 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 6)

R017 ³ Ring 7 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 7)

R017 ³ Ring 8 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 8)

R017 ³ Ring 9 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 9)

R017 ³ Ring 10 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(10)

R017 ³ Ring 11 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(11)

R017 ³ Ring 12 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(12)

³ ³ ³ ³ ³ 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 07:39 Page 5 Summary : Yankee Rowe Sensitivity Analysis=soil File: Eu-154_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R018 ³ Fruits, vegetables and grain consumption (kg/yr) ³ 1.120E+02 ³ 1.600E+02 ³ --- ³ DIET(1)

R018 ³ Leafy vegetable consumption (kg/yr) ³ 2.140E+01 ³ 1.400E+01 ³ --- ³ DIET(2)

R018 ³ Milk consumption (L/yr) ³ 2.330E+02 ³ 9.200E+01 ³ --- ³ DIET(3)

R018 ³ Meat and poultry consumption (kg/yr) ³ 6.510E+01 ³ 6.300E+01 ³ --- ³ DIET(4)

R018 ³ Fish consumption (kg/yr) ³ 2.060E+01 ³ 5.400E+00 ³ --- ³ DIET(5)

R018 ³ Other seafood consumption (kg/yr) ³ 9.000E-01 ³ 9.000E-01 ³ --- ³ DIET(6)

R018 ³ Soil ingestion rate (g/yr) ³ 1.826E+01 ³ 3.650E+01 ³ --- ³ SOIL R018 ³ Drinking water intake (L/yr) ³ 4.785E+02 ³ 5.100E+02 ³ --- ³ DWI R018 ³ Contamination fraction of drinking water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FDW R018 ³ Contamination fraction of household water ³ not used ³ 1.000E+00 ³ --- ³ FHHW R018 ³ Contamination fraction of livestock water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FLW R018 ³ Contamination fraction of irrigation water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FIRW R018 ³ Contamination fraction of aquatic food ³ 1.000E+00 ³ 5.000E-01 ³ --- ³ FR9 R018 ³ Contamination fraction of plant food ³ 1.000E+00 ³-1 ³ --- ³ FPLANT R018 ³ Contamination fraction of meat ³ 1.000E+00 ³-1 ³ --- ³ FMEAT R018 ³ Contamination fraction of milk ³ 1.000E+00 ³-1 ³ --- ³ FMILK

³ ³ ³ ³ ³ R019 ³ Livestock fodder intake for meat (kg/day) ³ 2.710E+01 ³ 6.800E+01 ³ --- ³ LFI5 R019 ³ Livestock fodder intake for milk (kg/day) ³ 6.320E+01 ³ 5.500E+01 ³ --- ³ LFI6 R019 ³ Livestock water intake for meat (L/day) ³ 5.060E+01 ³ 5.000E+01 ³ --- ³ LWI5 R019 ³ Livestock water intake for milk (L/day) ³ 6.000E+01 ³ 1.600E+02 ³ --- ³ LWI6 R019 ³ Livestock soil intake (kg/day) ³ 5.000E-01 ³ 5.000E-01 ³ --- ³ LSI R019 ³ Mass loading for foliar deposition (g/m**3) ³ 4.000E-04 ³ 1.000E-04 ³ --- ³ MLFD R019 ³ Depth of soil mixing layer (m) ³ 2.300E-01 ³ 1.500E-01 ³ --- ³ DM R019 ³ Depth of roots (m) ³ 2.050E+00 ³ 9.000E-01 ³ --- ³ DROOT R019 ³ Drinking water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWDW R019 ³ Household water fraction from ground water ³ not used ³ 1.000E+00 ³ --- ³ FGWHH R019 ³ Livestock water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWLW R019 ³ Irrigation fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWIR

³ ³ ³ ³ ³ R19B ³ Wet weight crop yield for Non-Leafy (kg/m**2) ³ 1.750E+00 ³ 7.000E-01 ³ --- ³ YV(1)

R19B ³ Wet weight crop yield for Leafy (kg/m**2) ³ 2.889E+00 ³ 1.500E+00 ³ --- ³ YV(2)

R19B ³ Wet weight crop yield for Fodder (kg/m**2) ³ 1.887E+00 ³ 1.100E+00 ³ --- ³ YV(3)

R19B ³ Growing Season for Non-Leafy (years) ³ 2.460E-01 ³ 1.700E-01 ³ --- ³ TE(1)

R19B ³ Growing Season for Leafy (years) ³ 1.230E-01 ³ 2.500E-01 ³ --- ³ TE(2)

R19B ³ Growing Season for Fodder (years) ³ 8.200E-02 ³ 8.000E-02 ³ --- ³ TE(3)

R19B ³ Translocation Factor for Non-Leafy ³ 1.000E-01 ³ 1.000E-01 ³ --- ³ TIV(1)

R19B ³ Translocation Factor for Leafy ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(2)

R19B ³ Translocation Factor for Fodder ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(3)

R19B ³ Dry Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(1)

R19B ³ Dry Foliar Interception Fraction for Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(2)

R19B ³ Dry Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(3)

R19B ³ Wet Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(1)

R19B ³ Wet Foliar Interception Fraction for Leafy ³ 5.800E-01 ³ 2.500E-01 ³ --- ³ RWET(2)

R19B ³ Wet Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(3)

R19B ³ Weathering Removal Constant for Vegetation ³ 3.300E+01 ³ 2.000E+01 ³ --- ³ WLAM

³ ³ ³ ³ ³ C14 ³ C-12 concentration in water (g/cm**3) ³ not used ³ 2.000E-05 ³ --- ³ C12WTR C14 ³ C-12 concentration in contaminated soil (g/g) ³ not used ³ 3.000E-02 ³ --- ³ C12CZ C14 ³ Fraction of vegetation carbon from soil ³ not used ³ 2.000E-02 ³ --- ³ CSOIL C14 ³ Fraction of vegetation carbon from air ³ not used ³ 9.800E-01 ³ --- ³ CAIR 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 07:39 Page 6 Summary : Yankee Rowe Sensitivity Analysis=soil File: Eu-154_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ C14 ³ C-14 evasion layer thickness in soil (m) ³ not used ³ 3.000E-01 ³ --- ³ DMC C14 ³ C-14 evasion flux rate from soil (1/sec) ³ not used ³ 7.000E-07 ³ --- ³ EVSN C14 ³ C-12 evasion flux rate from soil (1/sec) ³ not used ³ 1.000E-10 ³ --- ³ REVSN C14 ³ Fraction of grain in beef cattle feed ³ not used ³ 8.000E-01 ³ --- ³ AVFG4 C14 ³ Fraction of grain in milk cow feed ³ not used ³ 2.000E-01 ³ --- ³ AVFG5 C14 ³ DCF correction factor for gaseous forms of C14 ³ not used ³ 8.894E+01 ³ --- ³ CO2F

³ ³ ³ ³ ³ STOR ³ Storage times of contaminated foodstuffs (days): ³ ³ ³ ³ STOR ³ Fruits, non-leafy vegetables, and grain ³ 1.400E+01 ³ 1.400E+01 ³ --- ³ STOR_T(1)

STOR ³ Leafy vegetables ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(2)

STOR ³ Milk ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(3)

STOR ³ Meat and poultry ³ 2.000E+01 ³ 2.000E+01 ³ --- ³ STOR_T(4)

STOR ³ Fish ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(5)

STOR ³ Crustacea and mollusks ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(6)

STOR ³ Well water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(7)

STOR ³ Surface water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(8)

STOR ³ Livestock fodder ³ 4.500E+01 ³ 4.500E+01 ³ --- ³ STOR_T(9)

³ ³ ³ ³ ³ R021 ³ Thickness of building foundation (m) ³ not used ³ 1.500E-01 ³ --- ³ FLOOR1 R021 ³ Bulk density of building foundation (g/cm**3) ³ not used ³ 2.400E+00 ³ --- ³ DENSFL R021 ³ Total porosity of the cover material ³ not used ³ 4.000E-01 ³ --- ³ TPCV R021 ³ Total porosity of the building foundation ³ not used ³ 1.000E-01 ³ --- ³ TPFL R021 ³ Volumetric water content of the cover material ³ not used ³ 5.000E-02 ³ --- ³ PH2OCV R021 ³ Volumetric water content of the foundation ³ not used ³ 3.000E-02 ³ --- ³ PH2OFL R021 ³ Diffusion coefficient for radon gas (m/sec): ³ ³ ³ ³ R021 ³ in cover material ³ not used ³ 2.000E-06 ³ --- ³ DIFCV R021 ³ in foundation material ³ not used ³ 3.000E-07 ³ --- ³ DIFFL R021 ³ in contaminated zone soil ³ not used ³ 2.000E-06 ³ --- ³ DIFCZ R021 ³ Radon vertical dimension of mixing (m) ³ not used ³ 2.000E+00 ³ --- ³ HMIX R021 ³ Average building air exchange rate (1/hr) ³ not used ³ 5.000E-01 ³ --- ³ REXG R021 ³ Height of the building (room) (m) ³ not used ³ 2.500E+00 ³ --- ³ HRM R021 ³ Building interior area factor ³ not used ³ 0.000E+00 ³ --- ³ FAI R021 ³ Building depth below ground surface (m) ³ not used ³-1.000E+00 ³ --- ³ DMFL R021 ³ Emanating power of Rn-222 gas ³ not used ³ 2.500E-01 ³ --- ³ EMANA(1)

R021 ³ Emanating power of Rn-220 gas ³ not used ³ 1.500E-01 ³ --- ³ EMANA(2)

³ ³ ³ ³ ³ TITL ³ Number of graphical time points ³ 32 ³ --- ³ --- ³ NPTS TITL ³ Maximum number of integration points for dose ³ 17 ³ --- ³ --- ³ LYMAX TITL ³ Maximum number of integration points for risk ³ 1 ³ --- ³ --- ³ KYMAX

1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 07:39 Page 7 Summary : Yankee Rowe Sensitivity Analysis=soil File: Eu-154_DCGL.RAD Summary of Pathway Selections Pathway ³ User Selection

Å 1 -- external gamma ³ active 2 -- inhalation (w/o radon)³ active 3 -- plant ingestion ³ active 4 -- meat ingestion ³ active 5 -- milk ingestion ³ active 6 -- aquatic foods ³ active 7 -- drinking water ³ active 8 -- soil ingestion ³ active 9 -- radon ³ suppressed Find peak pathway doses ³ active

1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 07:46 Page 2 Summary : Yankee Rowe Sensitivity Analysis=soil File: Eu-155_DCGL.RAD Dose Conversion Factor (and Related) Parameter Summary File: YR soil DCGL lib 0 ³ ³ Current ³ ³ Parameter Menu ³ Parameter ³ Value ³ Default ³ Name

ÅÅÅÅ B-1 ³ Dose conversion factors for inhalation, mrem/pCi: ³ ³ ³ B-1 ³ Eu-155 ³ 4.140E-05 ³ 4.140E-05 ³ DCF2( 1)

³ ³ ³ ³ D-1 ³ Dose conversion factors for ingestion, mrem/pCi: ³ ³ ³ D-1 ³ Eu-155 ³ 1.530E-06 ³ 1.530E-06 ³ DCF3( 1)

³ ³ ³ ³ D-34 ³ Food transfer factors: ³ ³ ³ D-34 ³ Eu-155, plant/soil concentration ratio, dimensionless ³ 4.210E-03 ³ 2.500E-03 ³ RTF( 1,1)

D-34 ³ Eu-155, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 2.000E-03 ³ 2.000E-03 ³ RTF( 1,2)

D-34 ³ Eu-155, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 2.000E-05 ³ 2.000E-05 ³ RTF( 1,3)

³ ³ ³ ³ D-5 ³ Bioaccumulation factors, fresh water, L/kg: ³ ³ ³ D-5 ³ Eu-155, fish ³ 5.000E+01 ³ 5.000E+01 ³ BIOFAC( 1,1)

D-5 ³ Eu-155, crustacea and mollusks ³ 1.000E+03 ³ 1.000E+03 ³ BIOFAC( 1,2) 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 07:46 Page 3 Summary : Yankee Rowe Sensitivity Analysis=soil File: Eu-155_DCGL.RAD Site-Specific Parameter Summary 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R011 ³ Area of contaminated zone (m**2) ³ 1.302E+04 ³ 1.000E+04 ³ --- ³ AREA R011 ³ Thickness of contaminated zone (m) ³ 1.975E+00 ³ 2.000E+00 ³ --- ³ THICK0 R011 ³ Length parallel to aquifer flow (m) ³ 1.290E+02 ³ 1.000E+02 ³ --- ³ LCZPAQ R011 ³ Basic radiation dose limit (mrem/yr) ³ 2.500E+01 ³ 2.500E+01 ³ --- ³ BRDL R011 ³ Time since placement of material (yr) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ TI R011 ³ Times for calculations (yr) ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ T( 2)

R011 ³ Times for calculations (yr) ³ 3.000E+00 ³ 3.000E+00 ³ --- ³ T( 3)

R011 ³ Times for calculations (yr) ³ 1.000E+01 ³ 1.000E+01 ³ --- ³ T( 4)

R011 ³ Times for calculations (yr) ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ T( 5)

R011 ³ Times for calculations (yr) ³ 1.000E+02 ³ 1.000E+02 ³ --- ³ T( 6)

R011 ³ Times for calculations (yr) ³ 3.000E+02 ³ 3.000E+02 ³ --- ³ T( 7)

R011 ³ Times for calculations (yr) ³ 1.000E+03 ³ 1.000E+03 ³ --- ³ T( 8)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T( 9)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T(10)

³ ³ ³ ³ ³ R012 ³ Initial principal radionuclide (pCi/g): Eu-155 ³ 1.000E+00 ³ 0.000E+00 ³ --- ³ S1( 1)

R012 ³ Concentration in groundwater (pCi/L): Eu-155 ³ not used ³ 0.000E+00 ³ --- ³ W1( 1)

³ ³ ³ ³ ³ R013 ³ Cover depth (m) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ COVER0 R013 ³ Density of cover material (g/cm**3) ³ not used ³ 1.500E+00 ³ --- ³ DENSCV R013 ³ Cover depth erosion rate (m/yr) ³ not used ³ 1.000E-03 ³ --- ³ VCV R013 ³ Density of contaminated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSCZ R013 ³ Contaminated zone erosion rate (m/yr) ³ 8.500E-04 ³ 1.000E-03 ³ --- ³ VCZ R013 ³ Contaminated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPCZ R013 ³ Contaminated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCCZ R013 ³ Contaminated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCCZ R013 ³ Contaminated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BCZ R013 ³ Average annual wind speed (m/sec) ³ 2.030E+00 ³ 2.000E+00 ³ --- ³ WIND R013 ³ Humidity in air (g/m**3) ³ not used ³ 8.000E+00 ³ --- ³ HUMID R013 ³ Evapotranspiration coefficient ³ 6.250E-01 ³ 5.000E-01 ³ --- ³ EVAPTR R013 ³ Precipitation (m/yr) ³ 1.200E+00 ³ 1.000E+00 ³ --- ³ PRECIP R013 ³ Irrigation (m/yr) ³ 4.350E-01 ³ 2.000E-01 ³ --- ³ RI R013 ³ Irrigation mode ³ overhead ³ overhead ³ --- ³ IDITCH R013 ³ Runoff coefficient ³ 6.000E-01 ³ 2.000E-01 ³ --- ³ RUNOFF R013 ³ Watershed area for nearby stream or pond (m**2) ³ 7.770E+05 ³ 1.000E+06 ³ --- ³ WAREA R013 ³ Accuracy for water/soil computations ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ EPS

³ ³ ³ ³ ³ R014 ³ Density of saturated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSAQ R014 ³ Saturated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPSZ R014 ³ Saturated zone effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPSZ R014 ³ Saturated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCSZ R014 ³ Saturated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+02 ³ --- ³ HCSZ R014 ³ Saturated zone hydraulic gradient ³ 1.000E-01 ³ 2.000E-02 ³ --- ³ HGWT R014 ³ Saturated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BSZ R014 ³ Water table drop rate (m/yr) ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ VWT R014 ³ Well pump intake depth (m below water table) ³ 1.451E+01 ³ 1.000E+01 ³ --- ³ DWIBWT R014 ³ Model: Nondispersion (ND) or Mass-Balance (MB) ³ ND ³ ND ³ --- ³ MODEL R014 ³ Well pumping rate (m**3/yr) ³ 1.323E+03 ³ 2.500E+02 ³ --- ³ UW

³ ³ ³ ³ ³ R015 ³ Number of unsaturated zone strata ³ 1 ³ 1 ³ --- ³ NS 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 07:46 Page 4 Summary : Yankee Rowe Sensitivity Analysis=soil File: Eu-155_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R015 ³ Unsat. zone 1, thickness (m) ³ 1.820E+00 ³ 4.000E+00 ³ --- ³ H(1)

R015 ³ Unsat. zone 1, soil density (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSUZ(1)

R015 ³ Unsat. zone 1, total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPUZ(1)

R015 ³ Unsat. zone 1, effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPUZ(1)

R015 ³ Unsat. zone 1, field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCUZ(1)

R015 ³ Unsat. zone 1, soil-specific b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BUZ(1)

R015 ³ Unsat. zone 1, hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCUZ(1)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for Eu-155 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 8.250E+02 ³-1.000E+00 ³ --- ³ DCNUCC( 1)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 8.250E+02 ³-1.000E+00 ³ --- ³ DCNUCU( 1,1)

R016 ³ Saturated zone (cm**3/g) ³ 8.250E+02 ³-1.000E+00 ³ --- ³ DCNUCS( 1)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 1.394E-04 ³ ALEACH( 1)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 1)

³ ³ ³ ³ ³ R017 ³ Inhalation rate (m**3/yr) ³ 8.400E+03 ³ 8.400E+03 ³ --- ³ INHALR R017 ³ Mass loading for inhalation (g/m**3) ³ 2.330E-05 ³ 1.000E-04 ³ --- ³ MLINH R017 ³ Exposure duration ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ ED R017 ³ Shielding factor, inhalation ³ 5.500E-01 ³ 4.000E-01 ³ --- ³ SHF3 R017 ³ Shielding factor, external gamma ³ 3.980E-01 ³ 7.000E-01 ³ --- ³ SHF1 R017 ³ Fraction of time spent indoors ³ 6.571E-01 ³ 5.000E-01 ³ --- ³ FIND R017 ³ Fraction of time spent outdoors (on site) ³ 1.181E-01 ³ 2.500E-01 ³ --- ³ FOTD R017 ³ Shape factor flag, external gamma ³ 1.000E+00 ³ 1.000E+00 ³ >0 shows circular AREA. ³ FS R017 ³ Radii of shape factor array (used if FS = -1): ³ ³ ³ ³ R017 ³ Outer annular radius (m), ring 1: ³ not used ³ 5.000E+01 ³ --- ³ RAD_SHAPE(

1)

R017 ³ Outer annular radius (m), ring 2: ³ not used ³ 7.071E+01 ³ --- ³ RAD_SHAPE(

2)

R017 ³ Outer annular radius (m), ring 3: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

3)

R017 ³ Outer annular radius (m), ring 4: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

4)

R017 ³ Outer annular radius (m), ring 5: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

5)

R017 ³ Outer annular radius (m), ring 6: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

6)

R017 ³ Outer annular radius (m), ring 7: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

7)

R017 ³ Outer annular radius (m), ring 8: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

8)

R017 ³ Outer annular radius (m), ring 9: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

9)

R017 ³ Outer annular radius (m), ring 10: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (10)

R017 ³ Outer annular radius (m), ring 11: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (11)

R017 ³ Outer annular radius (m), ring 12: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (12)

³ ³ ³ ³ ³ R017 ³ Fractions of annular areas within AREA: ³ ³ ³ ³ R017 ³ Ring 1 ³ not used ³ 1.000E+00 ³ --- ³ FRACA( 1)

R017 ³ Ring 2 ³ not used ³ 2.732E-01 ³ --- ³ FRACA( 2)

R017 ³ Ring 3 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 3)

R017 ³ Ring 4 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 4)

R017 ³ Ring 5 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 5)

R017 ³ Ring 6 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 6)

R017 ³ Ring 7 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 7)

R017 ³ Ring 8 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 8)

R017 ³ Ring 9 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 9)

R017 ³ Ring 10 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(10)

R017 ³ Ring 11 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(11)

R017 ³ Ring 12 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(12)

³ ³ ³ ³ ³ 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 07:46 Page 5 Summary : Yankee Rowe Sensitivity Analysis=soil File: Eu-155_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R018 ³ Fruits, vegetables and grain consumption (kg/yr) ³ 1.120E+02 ³ 1.600E+02 ³ --- ³ DIET(1)

R018 ³ Leafy vegetable consumption (kg/yr) ³ 2.140E+01 ³ 1.400E+01 ³ --- ³ DIET(2)

R018 ³ Milk consumption (L/yr) ³ 2.330E+02 ³ 9.200E+01 ³ --- ³ DIET(3)

R018 ³ Meat and poultry consumption (kg/yr) ³ 6.510E+01 ³ 6.300E+01 ³ --- ³ DIET(4)

R018 ³ Fish consumption (kg/yr) ³ 2.060E+01 ³ 5.400E+00 ³ --- ³ DIET(5)

R018 ³ Other seafood consumption (kg/yr) ³ 9.000E-01 ³ 9.000E-01 ³ --- ³ DIET(6)

R018 ³ Soil ingestion rate (g/yr) ³ 1.826E+01 ³ 3.650E+01 ³ --- ³ SOIL R018 ³ Drinking water intake (L/yr) ³ 4.785E+02 ³ 5.100E+02 ³ --- ³ DWI R018 ³ Contamination fraction of drinking water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FDW R018 ³ Contamination fraction of household water ³ not used ³ 1.000E+00 ³ --- ³ FHHW R018 ³ Contamination fraction of livestock water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FLW R018 ³ Contamination fraction of irrigation water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FIRW R018 ³ Contamination fraction of aquatic food ³ 1.000E+00 ³ 5.000E-01 ³ --- ³ FR9 R018 ³ Contamination fraction of plant food ³ 1.000E+00 ³-1 ³ --- ³ FPLANT R018 ³ Contamination fraction of meat ³ 1.000E+00 ³-1 ³ --- ³ FMEAT R018 ³ Contamination fraction of milk ³ 1.000E+00 ³-1 ³ --- ³ FMILK

³ ³ ³ ³ ³ R019 ³ Livestock fodder intake for meat (kg/day) ³ 2.710E+01 ³ 6.800E+01 ³ --- ³ LFI5 R019 ³ Livestock fodder intake for milk (kg/day) ³ 6.320E+01 ³ 5.500E+01 ³ --- ³ LFI6 R019 ³ Livestock water intake for meat (L/day) ³ 5.060E+01 ³ 5.000E+01 ³ --- ³ LWI5 R019 ³ Livestock water intake for milk (L/day) ³ 6.000E+01 ³ 1.600E+02 ³ --- ³ LWI6 R019 ³ Livestock soil intake (kg/day) ³ 5.000E-01 ³ 5.000E-01 ³ --- ³ LSI R019 ³ Mass loading for foliar deposition (g/m**3) ³ 4.000E-04 ³ 1.000E-04 ³ --- ³ MLFD R019 ³ Depth of soil mixing layer (m) ³ 2.300E-01 ³ 1.500E-01 ³ --- ³ DM R019 ³ Depth of roots (m) ³ 2.050E+00 ³ 9.000E-01 ³ --- ³ DROOT R019 ³ Drinking water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWDW R019 ³ Household water fraction from ground water ³ not used ³ 1.000E+00 ³ --- ³ FGWHH R019 ³ Livestock water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWLW R019 ³ Irrigation fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWIR

³ ³ ³ ³ ³ R19B ³ Wet weight crop yield for Non-Leafy (kg/m**2) ³ 1.750E+00 ³ 7.000E-01 ³ --- ³ YV(1)

R19B ³ Wet weight crop yield for Leafy (kg/m**2) ³ 2.889E+00 ³ 1.500E+00 ³ --- ³ YV(2)

R19B ³ Wet weight crop yield for Fodder (kg/m**2) ³ 1.887E+00 ³ 1.100E+00 ³ --- ³ YV(3)

R19B ³ Growing Season for Non-Leafy (years) ³ 2.460E-01 ³ 1.700E-01 ³ --- ³ TE(1)

R19B ³ Growing Season for Leafy (years) ³ 1.230E-01 ³ 2.500E-01 ³ --- ³ TE(2)

R19B ³ Growing Season for Fodder (years) ³ 8.200E-02 ³ 8.000E-02 ³ --- ³ TE(3)

R19B ³ Translocation Factor for Non-Leafy ³ 1.000E-01 ³ 1.000E-01 ³ --- ³ TIV(1)

R19B ³ Translocation Factor for Leafy ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(2)

R19B ³ Translocation Factor for Fodder ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(3)

R19B ³ Dry Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(1)

R19B ³ Dry Foliar Interception Fraction for Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(2)

R19B ³ Dry Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(3)

R19B ³ Wet Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(1)

R19B ³ Wet Foliar Interception Fraction for Leafy ³ 5.800E-01 ³ 2.500E-01 ³ --- ³ RWET(2)

R19B ³ Wet Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(3)

R19B ³ Weathering Removal Constant for Vegetation ³ 3.300E+01 ³ 2.000E+01 ³ --- ³ WLAM

³ ³ ³ ³ ³ C14 ³ C-12 concentration in water (g/cm**3) ³ not used ³ 2.000E-05 ³ --- ³ C12WTR C14 ³ C-12 concentration in contaminated soil (g/g) ³ not used ³ 3.000E-02 ³ --- ³ C12CZ C14 ³ Fraction of vegetation carbon from soil ³ not used ³ 2.000E-02 ³ --- ³ CSOIL C14 ³ Fraction of vegetation carbon from air ³ not used ³ 9.800E-01 ³ --- ³ CAIR 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 07:46 Page 6 Summary : Yankee Rowe Sensitivity Analysis=soil File: Eu-155_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ C14 ³ C-14 evasion layer thickness in soil (m) ³ not used ³ 3.000E-01 ³ --- ³ DMC C14 ³ C-14 evasion flux rate from soil (1/sec) ³ not used ³ 7.000E-07 ³ --- ³ EVSN C14 ³ C-12 evasion flux rate from soil (1/sec) ³ not used ³ 1.000E-10 ³ --- ³ REVSN C14 ³ Fraction of grain in beef cattle feed ³ not used ³ 8.000E-01 ³ --- ³ AVFG4 C14 ³ Fraction of grain in milk cow feed ³ not used ³ 2.000E-01 ³ --- ³ AVFG5 C14 ³ DCF correction factor for gaseous forms of C14 ³ not used ³ 8.894E+01 ³ --- ³ CO2F

³ ³ ³ ³ ³ STOR ³ Storage times of contaminated foodstuffs (days): ³ ³ ³ ³ STOR ³ Fruits, non-leafy vegetables, and grain ³ 1.400E+01 ³ 1.400E+01 ³ --- ³ STOR_T(1)

STOR ³ Leafy vegetables ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(2)

STOR ³ Milk ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(3)

STOR ³ Meat and poultry ³ 2.000E+01 ³ 2.000E+01 ³ --- ³ STOR_T(4)

STOR ³ Fish ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(5)

STOR ³ Crustacea and mollusks ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(6)

STOR ³ Well water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(7)

STOR ³ Surface water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(8)

STOR ³ Livestock fodder ³ 4.500E+01 ³ 4.500E+01 ³ --- ³ STOR_T(9)

³ ³ ³ ³ ³ R021 ³ Thickness of building foundation (m) ³ not used ³ 1.500E-01 ³ --- ³ FLOOR1 R021 ³ Bulk density of building foundation (g/cm**3) ³ not used ³ 2.400E+00 ³ --- ³ DENSFL R021 ³ Total porosity of the cover material ³ not used ³ 4.000E-01 ³ --- ³ TPCV R021 ³ Total porosity of the building foundation ³ not used ³ 1.000E-01 ³ --- ³ TPFL R021 ³ Volumetric water content of the cover material ³ not used ³ 5.000E-02 ³ --- ³ PH2OCV R021 ³ Volumetric water content of the foundation ³ not used ³ 3.000E-02 ³ --- ³ PH2OFL R021 ³ Diffusion coefficient for radon gas (m/sec): ³ ³ ³ ³ R021 ³ in cover material ³ not used ³ 2.000E-06 ³ --- ³ DIFCV R021 ³ in foundation material ³ not used ³ 3.000E-07 ³ --- ³ DIFFL R021 ³ in contaminated zone soil ³ not used ³ 2.000E-06 ³ --- ³ DIFCZ R021 ³ Radon vertical dimension of mixing (m) ³ not used ³ 2.000E+00 ³ --- ³ HMIX R021 ³ Average building air exchange rate (1/hr) ³ not used ³ 5.000E-01 ³ --- ³ REXG R021 ³ Height of the building (room) (m) ³ not used ³ 2.500E+00 ³ --- ³ HRM R021 ³ Building interior area factor ³ not used ³ 0.000E+00 ³ --- ³ FAI R021 ³ Building depth below ground surface (m) ³ not used ³-1.000E+00 ³ --- ³ DMFL R021 ³ Emanating power of Rn-222 gas ³ not used ³ 2.500E-01 ³ --- ³ EMANA(1)

R021 ³ Emanating power of Rn-220 gas ³ not used ³ 1.500E-01 ³ --- ³ EMANA(2)

³ ³ ³ ³ ³ TITL ³ Number of graphical time points ³ 32 ³ --- ³ --- ³ NPTS TITL ³ Maximum number of integration points for dose ³ 17 ³ --- ³ --- ³ LYMAX TITL ³ Maximum number of integration points for risk ³ 1 ³ --- ³ --- ³ KYMAX

1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 07:46 Page 7 Summary : Yankee Rowe Sensitivity Analysis=soil File: Eu-155_DCGL.RAD Summary of Pathway Selections Pathway ³ User Selection

Å 1 -- external gamma ³ active 2 -- inhalation (w/o radon)³ active 3 -- plant ingestion ³ active 4 -- meat ingestion ³ active 5 -- milk ingestion ³ active 6 -- aquatic foods ³ active 7 -- drinking water ³ active 8 -- soil ingestion ³ active 9 -- radon ³ suppressed Find peak pathway doses ³ active

1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 13:21 Page 2 Summary : Yankee Rowe Sensitivity Analysis=soil File: Fe55_DCGL.RAD Dose Conversion Factor (and Related) Parameter Summary File: YR soil DCGL lib 0 ³ ³ Current ³ ³ Parameter Menu ³ Parameter ³ Value ³ Default ³ Name

ÅÅÅÅ B-1 ³ Dose conversion factors for inhalation, mrem/pCi: ³ ³ ³ B-1 ³ Fe-55 ³ 2.690E-06 ³ 2.690E-06 ³ DCF2( 1)

³ ³ ³ ³ D-1 ³ Dose conversion factors for ingestion, mrem/pCi: ³ ³ ³ D-1 ³ Fe-55 ³ 6.070E-07 ³ 6.070E-07 ³ DCF3( 1)

³ ³ ³ ³ D-34 ³ Food transfer factors: ³ ³ ³ D-34 ³ Fe-55, plant/soil concentration ratio, dimensionless ³ 1.830E-03 ³ 1.000E-03 ³ RTF( 1,1)

D-34 ³ Fe-55, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 3.910E-02 ³ 2.000E-02 ³ RTF( 1,2)

D-34 ³ Fe-55, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 3.000E-04 ³ 3.000E-04 ³ RTF( 1,3)

³ ³ ³ ³ D-5 ³ Bioaccumulation factors, fresh water, L/kg: ³ ³ ³ D-5 ³ Fe-55, fish ³ 2.000E+02 ³ 2.000E+02 ³ BIOFAC( 1,1)

D-5 ³ Fe-55, crustacea and mollusks ³ 3.200E+03 ³ 3.200E+03 ³ BIOFAC( 1,2) 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 13:21 Page 3 Summary : Yankee Rowe Sensitivity Analysis=soil File: Fe55_DCGL.RAD Site-Specific Parameter Summary 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R011 ³ Area of contaminated zone (m**2) ³ 1.302E+04 ³ 1.000E+04 ³ --- ³ AREA R011 ³ Thickness of contaminated zone (m) ³ 1.975E+00 ³ 2.000E+00 ³ --- ³ THICK0 R011 ³ Length parallel to aquifer flow (m) ³ 1.290E+02 ³ 1.000E+02 ³ --- ³ LCZPAQ R011 ³ Basic radiation dose limit (mrem/yr) ³ 2.500E+01 ³ 2.500E+01 ³ --- ³ BRDL R011 ³ Time since placement of material (yr) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ TI R011 ³ Times for calculations (yr) ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ T( 2)

R011 ³ Times for calculations (yr) ³ 3.000E+00 ³ 3.000E+00 ³ --- ³ T( 3)

R011 ³ Times for calculations (yr) ³ 1.000E+01 ³ 1.000E+01 ³ --- ³ T( 4)

R011 ³ Times for calculations (yr) ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ T( 5)

R011 ³ Times for calculations (yr) ³ 1.000E+02 ³ 1.000E+02 ³ --- ³ T( 6)

R011 ³ Times for calculations (yr) ³ 3.000E+02 ³ 3.000E+02 ³ --- ³ T( 7)

R011 ³ Times for calculations (yr) ³ 1.000E+03 ³ 1.000E+03 ³ --- ³ T( 8)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T( 9)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T(10)

³ ³ ³ ³ ³ R012 ³ Initial principal radionuclide (pCi/g): Fe-55 ³ 1.000E+00 ³ 0.000E+00 ³ --- ³ S1( 1)

R012 ³ Concentration in groundwater (pCi/L): Fe-55 ³ not used ³ 0.000E+00 ³ --- ³ W1( 1)

³ ³ ³ ³ ³ R013 ³ Cover depth (m) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ COVER0 R013 ³ Density of cover material (g/cm**3) ³ not used ³ 1.500E+00 ³ --- ³ DENSCV R013 ³ Cover depth erosion rate (m/yr) ³ not used ³ 1.000E-03 ³ --- ³ VCV R013 ³ Density of contaminated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSCZ R013 ³ Contaminated zone erosion rate (m/yr) ³ 8.500E-04 ³ 1.000E-03 ³ --- ³ VCZ R013 ³ Contaminated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPCZ R013 ³ Contaminated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCCZ R013 ³ Contaminated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCCZ R013 ³ Contaminated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BCZ R013 ³ Average annual wind speed (m/sec) ³ 2.030E+00 ³ 2.000E+00 ³ --- ³ WIND R013 ³ Humidity in air (g/m**3) ³ not used ³ 8.000E+00 ³ --- ³ HUMID R013 ³ Evapotranspiration coefficient ³ 6.250E-01 ³ 5.000E-01 ³ --- ³ EVAPTR R013 ³ Precipitation (m/yr) ³ 1.200E+00 ³ 1.000E+00 ³ --- ³ PRECIP R013 ³ Irrigation (m/yr) ³ 4.350E-01 ³ 2.000E-01 ³ --- ³ RI R013 ³ Irrigation mode ³ overhead ³ overhead ³ --- ³ IDITCH R013 ³ Runoff coefficient ³ 6.000E-01 ³ 2.000E-01 ³ --- ³ RUNOFF R013 ³ Watershed area for nearby stream or pond (m**2) ³ 7.770E+05 ³ 1.000E+06 ³ --- ³ WAREA R013 ³ Accuracy for water/soil computations ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ EPS

³ ³ ³ ³ ³ R014 ³ Density of saturated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSAQ R014 ³ Saturated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPSZ R014 ³ Saturated zone effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPSZ R014 ³ Saturated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCSZ R014 ³ Saturated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+02 ³ --- ³ HCSZ R014 ³ Saturated zone hydraulic gradient ³ 1.000E-01 ³ 2.000E-02 ³ --- ³ HGWT R014 ³ Saturated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BSZ R014 ³ Water table drop rate (m/yr) ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ VWT R014 ³ Well pump intake depth (m below water table) ³ 1.451E+01 ³ 1.000E+01 ³ --- ³ DWIBWT R014 ³ Model: Nondispersion (ND) or Mass-Balance (MB) ³ ND ³ ND ³ --- ³ MODEL R014 ³ Well pumping rate (m**3/yr) ³ 1.323E+03 ³ 2.500E+02 ³ --- ³ UW

³ ³ ³ ³ ³ R015 ³ Number of unsaturated zone strata ³ 1 ³ 1 ³ --- ³ NS 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 13:21 Page 4 Summary : Yankee Rowe Sensitivity Analysis=soil File: Fe55_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R015 ³ Unsat. zone 1, thickness (m) ³ 1.820E+00 ³ 4.000E+00 ³ --- ³ H(1)

R015 ³ Unsat. zone 1, soil density (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSUZ(1)

R015 ³ Unsat. zone 1, total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPUZ(1)

R015 ³ Unsat. zone 1, effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPUZ(1)

R015 ³ Unsat. zone 1, field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCUZ(1)

R015 ³ Unsat. zone 1, soil-specific b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BUZ(1)

R015 ³ Unsat. zone 1, hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCUZ(1)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for Fe-55 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 2.090E+02 ³ 1.000E+03 ³ --- ³ DCNUCC( 1)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 2.090E+02 ³ 1.000E+03 ³ --- ³ DCNUCU( 1,1)

R016 ³ Saturated zone (cm**3/g) ³ 2.090E+02 ³ 1.000E+03 ³ --- ³ DCNUCS( 1)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 5.502E-04 ³ ALEACH( 1)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 1)

³ ³ ³ ³ ³ R017 ³ Inhalation rate (m**3/yr) ³ 8.400E+03 ³ 8.400E+03 ³ --- ³ INHALR R017 ³ Mass loading for inhalation (g/m**3) ³ 2.330E-05 ³ 1.000E-04 ³ --- ³ MLINH R017 ³ Exposure duration ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ ED R017 ³ Shielding factor, inhalation ³ 5.500E-01 ³ 4.000E-01 ³ --- ³ SHF3 R017 ³ Shielding factor, external gamma ³ 2.725E-01 ³ 7.000E-01 ³ --- ³ SHF1 R017 ³ Fraction of time spent indoors ³ 6.571E-01 ³ 5.000E-01 ³ --- ³ FIND R017 ³ Fraction of time spent outdoors (on site) ³ 1.181E-01 ³ 2.500E-01 ³ --- ³ FOTD R017 ³ Shape factor flag, external gamma ³ 1.000E+00 ³ 1.000E+00 ³ >0 shows circular AREA. ³ FS R017 ³ Radii of shape factor array (used if FS = -1): ³ ³ ³ ³ R017 ³ Outer annular radius (m), ring 1: ³ not used ³ 5.000E+01 ³ --- ³ RAD_SHAPE(

1)

R017 ³ Outer annular radius (m), ring 2: ³ not used ³ 7.071E+01 ³ --- ³ RAD_SHAPE(

2)

R017 ³ Outer annular radius (m), ring 3: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

3)

R017 ³ Outer annular radius (m), ring 4: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

4)

R017 ³ Outer annular radius (m), ring 5: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

5)

R017 ³ Outer annular radius (m), ring 6: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

6)

R017 ³ Outer annular radius (m), ring 7: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

7)

R017 ³ Outer annular radius (m), ring 8: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

8)

R017 ³ Outer annular radius (m), ring 9: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

9)

R017 ³ Outer annular radius (m), ring 10: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (10)

R017 ³ Outer annular radius (m), ring 11: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (11)

R017 ³ Outer annular radius (m), ring 12: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (12)

³ ³ ³ ³ ³ R017 ³ Fractions of annular areas within AREA: ³ ³ ³ ³ R017 ³ Ring 1 ³ not used ³ 1.000E+00 ³ --- ³ FRACA( 1)

R017 ³ Ring 2 ³ not used ³ 2.732E-01 ³ --- ³ FRACA( 2)

R017 ³ Ring 3 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 3)

R017 ³ Ring 4 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 4)

R017 ³ Ring 5 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 5)

R017 ³ Ring 6 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 6)

R017 ³ Ring 7 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 7)

R017 ³ Ring 8 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 8)

R017 ³ Ring 9 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 9)

R017 ³ Ring 10 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(10)

R017 ³ Ring 11 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(11)

R017 ³ Ring 12 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(12)

³ ³ ³ ³ ³ 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 13:21 Page 5 Summary : Yankee Rowe Sensitivity Analysis=soil File: Fe55_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R018 ³ Fruits, vegetables and grain consumption (kg/yr) ³ 1.120E+02 ³ 1.600E+02 ³ --- ³ DIET(1)

R018 ³ Leafy vegetable consumption (kg/yr) ³ 2.140E+01 ³ 1.400E+01 ³ --- ³ DIET(2)

R018 ³ Milk consumption (L/yr) ³ 2.330E+02 ³ 9.200E+01 ³ --- ³ DIET(3)

R018 ³ Meat and poultry consumption (kg/yr) ³ 6.510E+01 ³ 6.300E+01 ³ --- ³ DIET(4)

R018 ³ Fish consumption (kg/yr) ³ 2.060E+01 ³ 5.400E+00 ³ --- ³ DIET(5)

R018 ³ Other seafood consumption (kg/yr) ³ 9.000E-01 ³ 9.000E-01 ³ --- ³ DIET(6)

R018 ³ Soil ingestion rate (g/yr) ³ 1.826E+01 ³ 3.650E+01 ³ --- ³ SOIL R018 ³ Drinking water intake (L/yr) ³ 4.785E+02 ³ 5.100E+02 ³ --- ³ DWI R018 ³ Contamination fraction of drinking water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FDW R018 ³ Contamination fraction of household water ³ not used ³ 1.000E+00 ³ --- ³ FHHW R018 ³ Contamination fraction of livestock water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FLW R018 ³ Contamination fraction of irrigation water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FIRW R018 ³ Contamination fraction of aquatic food ³ 1.000E+00 ³ 5.000E-01 ³ --- ³ FR9 R018 ³ Contamination fraction of plant food ³ 1.000E+00 ³-1 ³ --- ³ FPLANT R018 ³ Contamination fraction of meat ³ 1.000E+00 ³-1 ³ --- ³ FMEAT R018 ³ Contamination fraction of milk ³ 1.000E+00 ³-1 ³ --- ³ FMILK

³ ³ ³ ³ ³ R019 ³ Livestock fodder intake for meat (kg/day) ³ 2.710E+01 ³ 6.800E+01 ³ --- ³ LFI5 R019 ³ Livestock fodder intake for milk (kg/day) ³ 6.320E+01 ³ 5.500E+01 ³ --- ³ LFI6 R019 ³ Livestock water intake for meat (L/day) ³ 5.060E+01 ³ 5.000E+01 ³ --- ³ LWI5 R019 ³ Livestock water intake for milk (L/day) ³ 6.000E+01 ³ 1.600E+02 ³ --- ³ LWI6 R019 ³ Livestock soil intake (kg/day) ³ 5.000E-01 ³ 5.000E-01 ³ --- ³ LSI R019 ³ Mass loading for foliar deposition (g/m**3) ³ 4.000E-04 ³ 1.000E-04 ³ --- ³ MLFD R019 ³ Depth of soil mixing layer (m) ³ 2.300E-01 ³ 1.500E-01 ³ --- ³ DM R019 ³ Depth of roots (m) ³ 2.050E+00 ³ 9.000E-01 ³ --- ³ DROOT R019 ³ Drinking water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWDW R019 ³ Household water fraction from ground water ³ not used ³ 1.000E+00 ³ --- ³ FGWHH R019 ³ Livestock water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWLW R019 ³ Irrigation fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWIR

³ ³ ³ ³ ³ R19B ³ Wet weight crop yield for Non-Leafy (kg/m**2) ³ 1.750E+00 ³ 7.000E-01 ³ --- ³ YV(1)

R19B ³ Wet weight crop yield for Leafy (kg/m**2) ³ 2.889E+00 ³ 1.500E+00 ³ --- ³ YV(2)

R19B ³ Wet weight crop yield for Fodder (kg/m**2) ³ 1.887E+00 ³ 1.100E+00 ³ --- ³ YV(3)

R19B ³ Growing Season for Non-Leafy (years) ³ 2.460E-01 ³ 1.700E-01 ³ --- ³ TE(1)

R19B ³ Growing Season for Leafy (years) ³ 1.230E-01 ³ 2.500E-01 ³ --- ³ TE(2)

R19B ³ Growing Season for Fodder (years) ³ 8.200E-02 ³ 8.000E-02 ³ --- ³ TE(3)

R19B ³ Translocation Factor for Non-Leafy ³ 1.000E-01 ³ 1.000E-01 ³ --- ³ TIV(1)

R19B ³ Translocation Factor for Leafy ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(2)

R19B ³ Translocation Factor for Fodder ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(3)

R19B ³ Dry Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(1)

R19B ³ Dry Foliar Interception Fraction for Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(2)

R19B ³ Dry Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(3)

R19B ³ Wet Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(1)

R19B ³ Wet Foliar Interception Fraction for Leafy ³ 5.800E-01 ³ 2.500E-01 ³ --- ³ RWET(2)

R19B ³ Wet Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(3)

R19B ³ Weathering Removal Constant for Vegetation ³ 3.300E+01 ³ 2.000E+01 ³ --- ³ WLAM

³ ³ ³ ³ ³ C14 ³ C-12 concentration in water (g/cm**3) ³ not used ³ 2.000E-05 ³ --- ³ C12WTR C14 ³ C-12 concentration in contaminated soil (g/g) ³ not used ³ 3.000E-02 ³ --- ³ C12CZ C14 ³ Fraction of vegetation carbon from soil ³ not used ³ 2.000E-02 ³ --- ³ CSOIL C14 ³ Fraction of vegetation carbon from air ³ not used ³ 9.800E-01 ³ --- ³ CAIR 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 13:21 Page 6 Summary : Yankee Rowe Sensitivity Analysis=soil File: Fe55_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ C14 ³ C-14 evasion layer thickness in soil (m) ³ not used ³ 3.000E-01 ³ --- ³ DMC C14 ³ C-14 evasion flux rate from soil (1/sec) ³ not used ³ 7.000E-07 ³ --- ³ EVSN C14 ³ C-12 evasion flux rate from soil (1/sec) ³ not used ³ 1.000E-10 ³ --- ³ REVSN C14 ³ Fraction of grain in beef cattle feed ³ not used ³ 8.000E-01 ³ --- ³ AVFG4 C14 ³ Fraction of grain in milk cow feed ³ not used ³ 2.000E-01 ³ --- ³ AVFG5 C14 ³ DCF correction factor for gaseous forms of C14 ³ not used ³ 8.894E+01 ³ --- ³ CO2F

³ ³ ³ ³ ³ STOR ³ Storage times of contaminated foodstuffs (days): ³ ³ ³ ³ STOR ³ Fruits, non-leafy vegetables, and grain ³ 1.400E+01 ³ 1.400E+01 ³ --- ³ STOR_T(1)

STOR ³ Leafy vegetables ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(2)

STOR ³ Milk ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(3)

STOR ³ Meat and poultry ³ 2.000E+01 ³ 2.000E+01 ³ --- ³ STOR_T(4)

STOR ³ Fish ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(5)

STOR ³ Crustacea and mollusks ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(6)

STOR ³ Well water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(7)

STOR ³ Surface water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(8)

STOR ³ Livestock fodder ³ 4.500E+01 ³ 4.500E+01 ³ --- ³ STOR_T(9)

³ ³ ³ ³ ³ R021 ³ Thickness of building foundation (m) ³ not used ³ 1.500E-01 ³ --- ³ FLOOR1 R021 ³ Bulk density of building foundation (g/cm**3) ³ not used ³ 2.400E+00 ³ --- ³ DENSFL R021 ³ Total porosity of the cover material ³ not used ³ 4.000E-01 ³ --- ³ TPCV R021 ³ Total porosity of the building foundation ³ not used ³ 1.000E-01 ³ --- ³ TPFL R021 ³ Volumetric water content of the cover material ³ not used ³ 5.000E-02 ³ --- ³ PH2OCV R021 ³ Volumetric water content of the foundation ³ not used ³ 3.000E-02 ³ --- ³ PH2OFL R021 ³ Diffusion coefficient for radon gas (m/sec): ³ ³ ³ ³ R021 ³ in cover material ³ not used ³ 2.000E-06 ³ --- ³ DIFCV R021 ³ in foundation material ³ not used ³ 3.000E-07 ³ --- ³ DIFFL R021 ³ in contaminated zone soil ³ not used ³ 2.000E-06 ³ --- ³ DIFCZ R021 ³ Radon vertical dimension of mixing (m) ³ not used ³ 2.000E+00 ³ --- ³ HMIX R021 ³ Average building air exchange rate (1/hr) ³ not used ³ 5.000E-01 ³ --- ³ REXG R021 ³ Height of the building (room) (m) ³ not used ³ 2.500E+00 ³ --- ³ HRM R021 ³ Building interior area factor ³ not used ³ 0.000E+00 ³ --- ³ FAI R021 ³ Building depth below ground surface (m) ³ not used ³-1.000E+00 ³ --- ³ DMFL R021 ³ Emanating power of Rn-222 gas ³ not used ³ 2.500E-01 ³ --- ³ EMANA(1)

R021 ³ Emanating power of Rn-220 gas ³ not used ³ 1.500E-01 ³ --- ³ EMANA(2)

³ ³ ³ ³ ³ TITL ³ Number of graphical time points ³ 32 ³ --- ³ --- ³ NPTS TITL ³ Maximum number of integration points for dose ³ 17 ³ --- ³ --- ³ LYMAX TITL ³ Maximum number of integration points for risk ³ 1 ³ --- ³ --- ³ KYMAX

1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 13:21 Page 7 Summary : Yankee Rowe Sensitivity Analysis=soil File: Fe55_DCGL.RAD Summary of Pathway Selections Pathway ³ User Selection

Å 1 -- external gamma ³ active 2 -- inhalation (w/o radon)³ active 3 -- plant ingestion ³ active 4 -- meat ingestion ³ active 5 -- milk ingestion ³ active 6 -- aquatic foods ³ active 7 -- drinking water ³ active 8 -- soil ingestion ³ active 9 -- radon ³ suppressed Find peak pathway doses ³ active

1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/26/2003 15:22 Page 2 Summary : Yankee Rowe Sensitivity Analysis=soil File: H-3_DCGL.RAD Dose Conversion Factor (and Related) Parameter Summary File: FGR 13 Morbidity 0 ³ ³ Current ³ ³ Parameter Menu ³ Parameter ³ Value ³ Default ³ Name

ÅÅÅÅ B-1 ³ Dose conversion factors for inhalation, mrem/pCi: ³ ³ ³ B-1 ³ H-3 ³ 6.400E-08 ³ 6.400E-08 ³ DCF2( 1)

³ ³ ³ ³ D-1 ³ Dose conversion factors for ingestion, mrem/pCi: ³ ³ ³ D-1 ³ H-3 ³ 6.400E-08 ³ 6.400E-08 ³ DCF3( 1)

³ ³ ³ ³ D-34 ³ Food transfer factors: ³ ³ ³ D-34 ³ H-3, plant/soil concentration ratio, dimensionless ³ 4.800E+00 ³ 4.800E+00 ³ RTF( 1,1)

D-34 ³ H-3, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 1.200E-02 ³ 1.200E-02 ³ RTF( 1,2)

D-34 ³ H-3, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 1.000E-02 ³ 1.000E-02 ³ RTF( 1,3)

³ ³ ³ ³ D-5 ³ Bioaccumulation factors, fresh water, L/kg: ³ ³ ³ D-5 ³ H-3, fish ³ 1.000E+00 ³ 1.000E+00 ³ BIOFAC( 1,1)

D-5 ³ H-3, crustacea and mollusks ³ 1.000E+00 ³ 1.000E+00 ³ BIOFAC( 1,2) 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/26/2003 15:22 Page 3 Summary : Yankee Rowe Sensitivity Analysis=soil File: H-3_DCGL.RAD Site-Specific Parameter Summary 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R011 ³ Area of contaminated zone (m**2) ³ 1.302E+04 ³ 1.000E+04 ³ --- ³ AREA R011 ³ Thickness of contaminated zone (m) ³ 2.890E+00 ³ 2.000E+00 ³ --- ³ THICK0 R011 ³ Length parallel to aquifer flow (m) ³ 1.290E+02 ³ 1.000E+02 ³ --- ³ LCZPAQ R011 ³ Basic radiation dose limit (mrem/yr) ³ 2.500E+01 ³ 2.500E+01 ³ --- ³ BRDL R011 ³ Time since placement of material (yr) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ TI R011 ³ Times for calculations (yr) ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ T( 2)

R011 ³ Times for calculations (yr) ³ 3.000E+00 ³ 3.000E+00 ³ --- ³ T( 3)

R011 ³ Times for calculations (yr) ³ 1.000E+01 ³ 1.000E+01 ³ --- ³ T( 4)

R011 ³ Times for calculations (yr) ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ T( 5)

R011 ³ Times for calculations (yr) ³ 1.000E+02 ³ 1.000E+02 ³ --- ³ T( 6)

R011 ³ Times for calculations (yr) ³ 3.000E+02 ³ 3.000E+02 ³ --- ³ T( 7)

R011 ³ Times for calculations (yr) ³ 1.000E+03 ³ 1.000E+03 ³ --- ³ T( 8)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T( 9)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T(10)

³ ³ ³ ³ ³ R012 ³ Initial principal radionuclide (pCi/g): H-3 ³ 1.000E+00 ³ 0.000E+00 ³ --- ³ S1( 1)

R012 ³ Concentration in groundwater (pCi/L): H-3 ³ not used ³ 0.000E+00 ³ --- ³ W1( 1)

³ ³ ³ ³ ³ R013 ³ Cover depth (m) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ COVER0 R013 ³ Density of cover material (g/cm**3) ³ not used ³ 1.500E+00 ³ --- ³ DENSCV R013 ³ Cover depth erosion rate (m/yr) ³ not used ³ 1.000E-03 ³ --- ³ VCV R013 ³ Density of contaminated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSCZ R013 ³ Contaminated zone erosion rate (m/yr) ³ 8.500E-04 ³ 1.000E-03 ³ --- ³ VCZ R013 ³ Contaminated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPCZ R013 ³ Contaminated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCCZ R013 ³ Contaminated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCCZ R013 ³ Contaminated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BCZ R013 ³ Average annual wind speed (m/sec) ³ 2.030E+00 ³ 2.000E+00 ³ --- ³ WIND R013 ³ Humidity in air (g/m**3) ³ 6.100E+00 ³ 8.000E+00 ³ --- ³ HUMID R013 ³ Evapotranspiration coefficient ³ 6.250E-01 ³ 5.000E-01 ³ --- ³ EVAPTR R013 ³ Precipitation (m/yr) ³ 1.200E+00 ³ 1.000E+00 ³ --- ³ PRECIP R013 ³ Irrigation (m/yr) ³ 4.350E-01 ³ 2.000E-01 ³ --- ³ RI R013 ³ Irrigation mode ³ overhead ³ overhead ³ --- ³ IDITCH R013 ³ Runoff coefficient ³ 6.000E-01 ³ 2.000E-01 ³ --- ³ RUNOFF R013 ³ Watershed area for nearby stream or pond (m**2) ³ 7.770E+05 ³ 1.000E+06 ³ --- ³ WAREA R013 ³ Accuracy for water/soil computations ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ EPS

³ ³ ³ ³ ³ R014 ³ Density of saturated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSAQ R014 ³ Saturated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPSZ R014 ³ Saturated zone effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPSZ R014 ³ Saturated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCSZ R014 ³ Saturated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+02 ³ --- ³ HCSZ R014 ³ Saturated zone hydraulic gradient ³ 1.000E-01 ³ 2.000E-02 ³ --- ³ HGWT R014 ³ Saturated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BSZ R014 ³ Water table drop rate (m/yr) ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ VWT R014 ³ Well pump intake depth (m below water table) ³ 1.451E+01 ³ 1.000E+01 ³ --- ³ DWIBWT R014 ³ Model: Nondispersion (ND) or Mass-Balance (MB) ³ ND ³ ND ³ --- ³ MODEL R014 ³ Well pumping rate (m**3/yr) ³ 1.323E+03 ³ 2.500E+02 ³ --- ³ UW

³ ³ ³ ³ ³ R015 ³ Number of unsaturated zone strata ³ 1 ³ 1 ³ --- ³ NS 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/26/2003 15:22 Page 4 Summary : Yankee Rowe Sensitivity Analysis=soil File: H-3_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R015 ³ Unsat. zone 1, thickness (m) ³ 1.820E+00 ³ 4.000E+00 ³ --- ³ H(1)

R015 ³ Unsat. zone 1, soil density (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSUZ(1)

R015 ³ Unsat. zone 1, total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPUZ(1)

R015 ³ Unsat. zone 1, effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPUZ(1)

R015 ³ Unsat. zone 1, field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCUZ(1)

R015 ³ Unsat. zone 1, soil-specific b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BUZ(1)

R015 ³ Unsat. zone 1, hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCUZ(1)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for H-3 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 4.300E-02 ³ 0.000E+00 ³ --- ³ DCNUCC( 1)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 6.000E-02 ³ 0.000E+00 ³ --- ³ DCNUCU( 1,1)

R016 ³ Saturated zone (cm**3/g) ³ 6.000E-02 ³ 0.000E+00 ³ --- ³ DCNUCS( 1)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 8.715E-01 ³ ALEACH( 1)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 1)

³ ³ ³ ³ ³ R017 ³ Inhalation rate (m**3/yr) ³ 8.400E+03 ³ 8.400E+03 ³ --- ³ INHALR R017 ³ Mass loading for inhalation (g/m**3) ³ 2.330E-05 ³ 1.000E-04 ³ --- ³ MLINH R017 ³ Exposure duration ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ ED R017 ³ Shielding factor, inhalation ³ 5.500E-01 ³ 4.000E-01 ³ --- ³ SHF3 R017 ³ Shielding factor, external gamma ³ 2.725E-01 ³ 7.000E-01 ³ --- ³ SHF1 R017 ³ Fraction of time spent indoors ³ 6.571E-01 ³ 5.000E-01 ³ --- ³ FIND R017 ³ Fraction of time spent outdoors (on site) ³ 1.181E-01 ³ 2.500E-01 ³ --- ³ FOTD R017 ³ Shape factor flag, external gamma ³ 1.000E+00 ³ 1.000E+00 ³ >0 shows circular AREA. ³ FS R017 ³ Radii of shape factor array (used if FS = -1): ³ ³ ³ ³ R017 ³ Outer annular radius (m), ring 1: ³ not used ³ 5.000E+01 ³ --- ³ RAD_SHAPE(

1)

R017 ³ Outer annular radius (m), ring 2: ³ not used ³ 7.071E+01 ³ --- ³ RAD_SHAPE(

2)

R017 ³ Outer annular radius (m), ring 3: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

3)

R017 ³ Outer annular radius (m), ring 4: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

4)

R017 ³ Outer annular radius (m), ring 5: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

5)

R017 ³ Outer annular radius (m), ring 6: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

6)

R017 ³ Outer annular radius (m), ring 7: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

7)

R017 ³ Outer annular radius (m), ring 8: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

8)

R017 ³ Outer annular radius (m), ring 9: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

9)

R017 ³ Outer annular radius (m), ring 10: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (10)

R017 ³ Outer annular radius (m), ring 11: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (11)

R017 ³ Outer annular radius (m), ring 12: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (12)

³ ³ ³ ³ ³ R017 ³ Fractions of annular areas within AREA: ³ ³ ³ ³ R017 ³ Ring 1 ³ not used ³ 1.000E+00 ³ --- ³ FRACA( 1)

R017 ³ Ring 2 ³ not used ³ 2.732E-01 ³ --- ³ FRACA( 2)

R017 ³ Ring 3 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 3)

R017 ³ Ring 4 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 4)

R017 ³ Ring 5 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 5)

R017 ³ Ring 6 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 6)

R017 ³ Ring 7 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 7)

R017 ³ Ring 8 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 8)

R017 ³ Ring 9 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 9)

R017 ³ Ring 10 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(10)

R017 ³ Ring 11 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(11)

R017 ³ Ring 12 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(12)

³ ³ ³ ³ ³ 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/26/2003 15:22 Page 5 Summary : Yankee Rowe Sensitivity Analysis=soil File: H-3_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R018 ³ Fruits, vegetables and grain consumption (kg/yr) ³ 1.120E+02 ³ 1.600E+02 ³ --- ³ DIET(1)

R018 ³ Leafy vegetable consumption (kg/yr) ³ 2.140E+01 ³ 1.400E+01 ³ --- ³ DIET(2)

R018 ³ Milk consumption (L/yr) ³ 2.330E+02 ³ 9.200E+01 ³ --- ³ DIET(3)

R018 ³ Meat and poultry consumption (kg/yr) ³ 6.510E+01 ³ 6.300E+01 ³ --- ³ DIET(4)

R018 ³ Fish consumption (kg/yr) ³ 2.060E+01 ³ 5.400E+00 ³ --- ³ DIET(5)

R018 ³ Other seafood consumption (kg/yr) ³ 9.000E-01 ³ 9.000E-01 ³ --- ³ DIET(6)

R018 ³ Soil ingestion rate (g/yr) ³ 1.826E+01 ³ 3.650E+01 ³ --- ³ SOIL R018 ³ Drinking water intake (L/yr) ³ 4.785E+02 ³ 5.100E+02 ³ --- ³ DWI R018 ³ Contamination fraction of drinking water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FDW R018 ³ Contamination fraction of household water ³ not used ³ 1.000E+00 ³ --- ³ FHHW R018 ³ Contamination fraction of livestock water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FLW R018 ³ Contamination fraction of irrigation water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FIRW R018 ³ Contamination fraction of aquatic food ³ 1.000E+00 ³ 5.000E-01 ³ --- ³ FR9 R018 ³ Contamination fraction of plant food ³ 1.000E+00 ³-1 ³ --- ³ FPLANT R018 ³ Contamination fraction of meat ³ 1.000E+00 ³-1 ³ --- ³ FMEAT R018 ³ Contamination fraction of milk ³ 1.000E+00 ³-1 ³ --- ³ FMILK

³ ³ ³ ³ ³ R019 ³ Livestock fodder intake for meat (kg/day) ³ 2.710E+01 ³ 6.800E+01 ³ --- ³ LFI5 R019 ³ Livestock fodder intake for milk (kg/day) ³ 6.320E+01 ³ 5.500E+01 ³ --- ³ LFI6 R019 ³ Livestock water intake for meat (L/day) ³ 5.060E+01 ³ 5.000E+01 ³ --- ³ LWI5 R019 ³ Livestock water intake for milk (L/day) ³ 6.000E+01 ³ 1.600E+02 ³ --- ³ LWI6 R019 ³ Livestock soil intake (kg/day) ³ 5.000E-01 ³ 5.000E-01 ³ --- ³ LSI R019 ³ Mass loading for foliar deposition (g/m**3) ³ 4.000E-04 ³ 1.000E-04 ³ --- ³ MLFD R019 ³ Depth of soil mixing layer (m) ³ 2.300E-01 ³ 1.500E-01 ³ --- ³ DM R019 ³ Depth of roots (m) ³ 1.170E+00 ³ 9.000E-01 ³ --- ³ DROOT R019 ³ Drinking water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWDW R019 ³ Household water fraction from ground water ³ not used ³ 1.000E+00 ³ --- ³ FGWHH R019 ³ Livestock water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWLW R019 ³ Irrigation fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWIR

³ ³ ³ ³ ³ R19B ³ Wet weight crop yield for Non-Leafy (kg/m**2) ³ 1.750E+00 ³ 7.000E-01 ³ --- ³ YV(1)

R19B ³ Wet weight crop yield for Leafy (kg/m**2) ³ 2.889E+00 ³ 1.500E+00 ³ --- ³ YV(2)

R19B ³ Wet weight crop yield for Fodder (kg/m**2) ³ 1.887E+00 ³ 1.100E+00 ³ --- ³ YV(3)

R19B ³ Growing Season for Non-Leafy (years) ³ 2.460E-01 ³ 1.700E-01 ³ --- ³ TE(1)

R19B ³ Growing Season for Leafy (years) ³ 1.230E-01 ³ 2.500E-01 ³ --- ³ TE(2)

R19B ³ Growing Season for Fodder (years) ³ 8.200E-02 ³ 8.000E-02 ³ --- ³ TE(3)

R19B ³ Translocation Factor for Non-Leafy ³ 1.000E-01 ³ 1.000E-01 ³ --- ³ TIV(1)

R19B ³ Translocation Factor for Leafy ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(2)

R19B ³ Translocation Factor for Fodder ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(3)

R19B ³ Dry Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(1)

R19B ³ Dry Foliar Interception Fraction for Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(2)

R19B ³ Dry Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(3)

R19B ³ Wet Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(1)

R19B ³ Wet Foliar Interception Fraction for Leafy ³ 5.800E-01 ³ 2.500E-01 ³ --- ³ RWET(2)

R19B ³ Wet Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(3)

R19B ³ Weathering Removal Constant for Vegetation ³ 3.300E+01 ³ 2.000E+01 ³ --- ³ WLAM

³ ³ ³ ³ ³ C14 ³ C-12 concentration in water (g/cm**3) ³ not used ³ 2.000E-05 ³ --- ³ C12WTR C14 ³ C-12 concentration in contaminated soil (g/g) ³ not used ³ 3.000E-02 ³ --- ³ C12CZ C14 ³ Fraction of vegetation carbon from soil ³ not used ³ 2.000E-02 ³ --- ³ CSOIL C14 ³ Fraction of vegetation carbon from air ³ not used ³ 9.800E-01 ³ --- ³ CAIR 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/26/2003 15:22 Page 6 Summary : Yankee Rowe Sensitivity Analysis=soil File: H-3_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ C14 ³ C-14 evasion layer thickness in soil (m) ³ not used ³ 3.000E-01 ³ --- ³ DMC C14 ³ C-14 evasion flux rate from soil (1/sec) ³ not used ³ 7.000E-07 ³ --- ³ EVSN C14 ³ C-12 evasion flux rate from soil (1/sec) ³ not used ³ 1.000E-10 ³ --- ³ REVSN C14 ³ Fraction of grain in beef cattle feed ³ not used ³ 8.000E-01 ³ --- ³ AVFG4 C14 ³ Fraction of grain in milk cow feed ³ not used ³ 2.000E-01 ³ --- ³ AVFG5 C14 ³ DCF correction factor for gaseous forms of C14 ³ not used ³ 8.894E+01 ³ --- ³ CO2F

³ ³ ³ ³ ³ STOR ³ Storage times of contaminated foodstuffs (days): ³ ³ ³ ³ STOR ³ Fruits, non-leafy vegetables, and grain ³ 1.400E+01 ³ 1.400E+01 ³ --- ³ STOR_T(1)

STOR ³ Leafy vegetables ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(2)

STOR ³ Milk ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(3)

STOR ³ Meat and poultry ³ 2.000E+01 ³ 2.000E+01 ³ --- ³ STOR_T(4)

STOR ³ Fish ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(5)

STOR ³ Crustacea and mollusks ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(6)

STOR ³ Well water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(7)

STOR ³ Surface water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(8)

STOR ³ Livestock fodder ³ 4.500E+01 ³ 4.500E+01 ³ --- ³ STOR_T(9)

³ ³ ³ ³ ³ R021 ³ Thickness of building foundation (m) ³ not used ³ 1.500E-01 ³ --- ³ FLOOR1 R021 ³ Bulk density of building foundation (g/cm**3) ³ not used ³ 2.400E+00 ³ --- ³ DENSFL R021 ³ Total porosity of the cover material ³ not used ³ 4.000E-01 ³ --- ³ TPCV R021 ³ Total porosity of the building foundation ³ not used ³ 1.000E-01 ³ --- ³ TPFL R021 ³ Volumetric water content of the cover material ³ not used ³ 5.000E-02 ³ --- ³ PH2OCV R021 ³ Volumetric water content of the foundation ³ not used ³ 3.000E-02 ³ --- ³ PH2OFL R021 ³ Diffusion coefficient for radon gas (m/sec): ³ ³ ³ ³ R021 ³ in cover material ³ not used ³ 2.000E-06 ³ --- ³ DIFCV R021 ³ in foundation material ³ not used ³ 3.000E-07 ³ --- ³ DIFFL R021 ³ in contaminated zone soil ³ not used ³ 2.000E-06 ³ --- ³ DIFCZ R021 ³ Radon vertical dimension of mixing (m) ³ not used ³ 2.000E+00 ³ --- ³ HMIX R021 ³ Average building air exchange rate (1/hr) ³ not used ³ 5.000E-01 ³ --- ³ REXG R021 ³ Height of the building (room) (m) ³ not used ³ 2.500E+00 ³ --- ³ HRM R021 ³ Building interior area factor ³ not used ³ 0.000E+00 ³ --- ³ FAI R021 ³ Building depth below ground surface (m) ³ not used ³-1.000E+00 ³ --- ³ DMFL R021 ³ Emanating power of Rn-222 gas ³ not used ³ 2.500E-01 ³ --- ³ EMANA(1)

R021 ³ Emanating power of Rn-220 gas ³ not used ³ 1.500E-01 ³ --- ³ EMANA(2)

³ ³ ³ ³ ³ TITL ³ Number of graphical time points ³ 32 ³ --- ³ --- ³ NPTS TITL ³ Maximum number of integration points for dose ³ 17 ³ --- ³ --- ³ LYMAX TITL ³ Maximum number of integration points for risk ³ 1 ³ --- ³ --- ³ KYMAX

1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/26/2003 15:22 Page 7 Summary : Yankee Rowe Sensitivity Analysis=soil File: H-3_DCGL.RAD Summary of Pathway Selections Pathway ³ User Selection

Å 1 -- external gamma ³ active 2 -- inhalation (w/o radon)³ active 3 -- plant ingestion ³ active 4 -- meat ingestion ³ active 5 -- milk ingestion ³ active 6 -- aquatic foods ³ active 7 -- drinking water ³ active 8 -- soil ingestion ³ active 9 -- radon ³ suppressed Find peak pathway doses ³ active

1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 08:16 Page 2 Summary : Yankee Rowe Sensitivity Analysis=soil File: Nb-94_DCGL.RAD Dose Conversion Factor (and Related) Parameter Summary File: FGR 13 Morbidity 0 ³ ³ Current ³ ³ Parameter Menu ³ Parameter ³ Value ³ Default ³ Name

ÅÅÅÅ B-1 ³ Dose conversion factors for inhalation, mrem/pCi: ³ ³ ³ B-1 ³ Nb-94 ³ 4.140E-04 ³ 4.140E-04 ³ DCF2( 1)

³ ³ ³ ³ D-1 ³ Dose conversion factors for ingestion, mrem/pCi: ³ ³ ³ D-1 ³ Nb-94 ³ 7.140E-06 ³ 7.140E-06 ³ DCF3( 1)

³ ³ ³ ³ D-34 ³ Food transfer factors: ³ ³ ³ D-34 ³ Nb-94, plant/soil concentration ratio, dimensionless ³ 1.000E-02 ³ 1.000E-02 ³ RTF( 1,1)

D-34 ³ Nb-94, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 3.000E-07 ³ 3.000E-07 ³ RTF( 1,2)

D-34 ³ Nb-94, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 2.000E-06 ³ 2.000E-06 ³ RTF( 1,3)

³ ³ ³ ³ D-5 ³ Bioaccumulation factors, fresh water, L/kg: ³ ³ ³ D-5 ³ Nb-94, fish ³ 3.000E+02 ³ 3.000E+02 ³ BIOFAC( 1,1)

D-5 ³ Nb-94, crustacea and mollusks ³ 1.000E+02 ³ 1.000E+02 ³ BIOFAC( 1,2) 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 08:16 Page 3 Summary : Yankee Rowe Sensitivity Analysis=soil File: Nb-94_DCGL.RAD Site-Specific Parameter Summary 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R011 ³ Area of contaminated zone (m**2) ³ 1.302E+04 ³ 1.000E+04 ³ --- ³ AREA R011 ³ Thickness of contaminated zone (m) ³ 1.975E+00 ³ 2.000E+00 ³ --- ³ THICK0 R011 ³ Length parallel to aquifer flow (m) ³ 1.290E+02 ³ 1.000E+02 ³ --- ³ LCZPAQ R011 ³ Basic radiation dose limit (mrem/yr) ³ 2.500E+01 ³ 2.500E+01 ³ --- ³ BRDL R011 ³ Time since placement of material (yr) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ TI R011 ³ Times for calculations (yr) ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ T( 2)

R011 ³ Times for calculations (yr) ³ 3.000E+00 ³ 3.000E+00 ³ --- ³ T( 3)

R011 ³ Times for calculations (yr) ³ 1.000E+01 ³ 1.000E+01 ³ --- ³ T( 4)

R011 ³ Times for calculations (yr) ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ T( 5)

R011 ³ Times for calculations (yr) ³ 1.000E+02 ³ 1.000E+02 ³ --- ³ T( 6)

R011 ³ Times for calculations (yr) ³ 3.000E+02 ³ 3.000E+02 ³ --- ³ T( 7)

R011 ³ Times for calculations (yr) ³ 1.000E+03 ³ 1.000E+03 ³ --- ³ T( 8)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T( 9)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T(10)

³ ³ ³ ³ ³ R012 ³ Initial principal radionuclide (pCi/g): Nb-94 ³ 1.000E+00 ³ 0.000E+00 ³ --- ³ S1( 1)

R012 ³ Concentration in groundwater (pCi/L): Nb-94 ³ not used ³ 0.000E+00 ³ --- ³ W1( 1)

³ ³ ³ ³ ³ R013 ³ Cover depth (m) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ COVER0 R013 ³ Density of cover material (g/cm**3) ³ not used ³ 1.500E+00 ³ --- ³ DENSCV R013 ³ Cover depth erosion rate (m/yr) ³ not used ³ 1.000E-03 ³ --- ³ VCV R013 ³ Density of contaminated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSCZ R013 ³ Contaminated zone erosion rate (m/yr) ³ 8.500E-04 ³ 1.000E-03 ³ --- ³ VCZ R013 ³ Contaminated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPCZ R013 ³ Contaminated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCCZ R013 ³ Contaminated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCCZ R013 ³ Contaminated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BCZ R013 ³ Average annual wind speed (m/sec) ³ 2.030E+00 ³ 2.000E+00 ³ --- ³ WIND R013 ³ Humidity in air (g/m**3) ³ not used ³ 8.000E+00 ³ --- ³ HUMID R013 ³ Evapotranspiration coefficient ³ 6.250E-01 ³ 5.000E-01 ³ --- ³ EVAPTR R013 ³ Precipitation (m/yr) ³ 1.200E+00 ³ 1.000E+00 ³ --- ³ PRECIP R013 ³ Irrigation (m/yr) ³ 4.350E-01 ³ 2.000E-01 ³ --- ³ RI R013 ³ Irrigation mode ³ overhead ³ overhead ³ --- ³ IDITCH R013 ³ Runoff coefficient ³ 6.000E-01 ³ 2.000E-01 ³ --- ³ RUNOFF R013 ³ Watershed area for nearby stream or pond (m**2) ³ 7.770E+05 ³ 1.000E+06 ³ --- ³ WAREA R013 ³ Accuracy for water/soil computations ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ EPS

³ ³ ³ ³ ³ R014 ³ Density of saturated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSAQ R014 ³ Saturated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPSZ R014 ³ Saturated zone effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPSZ R014 ³ Saturated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCSZ R014 ³ Saturated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+02 ³ --- ³ HCSZ R014 ³ Saturated zone hydraulic gradient ³ 1.000E-01 ³ 2.000E-02 ³ --- ³ HGWT R014 ³ Saturated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BSZ R014 ³ Water table drop rate (m/yr) ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ VWT R014 ³ Well pump intake depth (m below water table) ³ 1.451E+01 ³ 1.000E+01 ³ --- ³ DWIBWT R014 ³ Model: Nondispersion (ND) or Mass-Balance (MB) ³ ND ³ ND ³ --- ³ MODEL R014 ³ Well pumping rate (m**3/yr) ³ 1.323E+03 ³ 2.500E+02 ³ --- ³ UW

³ ³ ³ ³ ³ R015 ³ Number of unsaturated zone strata ³ 1 ³ 1 ³ --- ³ NS 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 08:16 Page 4 Summary : Yankee Rowe Sensitivity Analysis=soil File: Nb-94_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R015 ³ Unsat. zone 1, thickness (m) ³ 1.820E+00 ³ 4.000E+00 ³ --- ³ H(1)

R015 ³ Unsat. zone 1, soil density (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSUZ(1)

R015 ³ Unsat. zone 1, total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPUZ(1)

R015 ³ Unsat. zone 1, effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPUZ(1)

R015 ³ Unsat. zone 1, field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCUZ(1)

R015 ³ Unsat. zone 1, soil-specific b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BUZ(1)

R015 ³ Unsat. zone 1, hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCUZ(1)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for Nb-94 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 3.310E+03 ³ 0.000E+00 ³ --- ³ DCNUCC( 1)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 3.800E+02 ³ 0.000E+00 ³ --- ³ DCNUCU( 1,1)

R016 ³ Saturated zone (cm**3/g) ³ 3.800E+02 ³ 0.000E+00 ³ --- ³ DCNUCS( 1)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 3.475E-05 ³ ALEACH( 1)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 1)

³ ³ ³ ³ ³ R017 ³ Inhalation rate (m**3/yr) ³ 8.400E+03 ³ 8.400E+03 ³ --- ³ INHALR R017 ³ Mass loading for inhalation (g/m**3) ³ 2.330E-05 ³ 1.000E-04 ³ --- ³ MLINH R017 ³ Exposure duration ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ ED R017 ³ Shielding factor, inhalation ³ 5.500E-01 ³ 4.000E-01 ³ --- ³ SHF3 R017 ³ Shielding factor, external gamma ³ 3.980E-01 ³ 7.000E-01 ³ --- ³ SHF1 R017 ³ Fraction of time spent indoors ³ 6.571E-01 ³ 5.000E-01 ³ --- ³ FIND R017 ³ Fraction of time spent outdoors (on site) ³ 1.181E-01 ³ 2.500E-01 ³ --- ³ FOTD R017 ³ Shape factor flag, external gamma ³ 1.000E+00 ³ 1.000E+00 ³ >0 shows circular AREA. ³ FS R017 ³ Radii of shape factor array (used if FS = -1): ³ ³ ³ ³ R017 ³ Outer annular radius (m), ring 1: ³ not used ³ 5.000E+01 ³ --- ³ RAD_SHAPE(

1)

R017 ³ Outer annular radius (m), ring 2: ³ not used ³ 7.071E+01 ³ --- ³ RAD_SHAPE(

2)

R017 ³ Outer annular radius (m), ring 3: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

3)

R017 ³ Outer annular radius (m), ring 4: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

4)

R017 ³ Outer annular radius (m), ring 5: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

5)

R017 ³ Outer annular radius (m), ring 6: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

6)

R017 ³ Outer annular radius (m), ring 7: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

7)

R017 ³ Outer annular radius (m), ring 8: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

8)

R017 ³ Outer annular radius (m), ring 9: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

9)

R017 ³ Outer annular radius (m), ring 10: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (10)

R017 ³ Outer annular radius (m), ring 11: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (11)

R017 ³ Outer annular radius (m), ring 12: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (12)

³ ³ ³ ³ ³ R017 ³ Fractions of annular areas within AREA: ³ ³ ³ ³ R017 ³ Ring 1 ³ not used ³ 1.000E+00 ³ --- ³ FRACA( 1)

R017 ³ Ring 2 ³ not used ³ 2.732E-01 ³ --- ³ FRACA( 2)

R017 ³ Ring 3 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 3)

R017 ³ Ring 4 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 4)

R017 ³ Ring 5 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 5)

R017 ³ Ring 6 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 6)

R017 ³ Ring 7 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 7)

R017 ³ Ring 8 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 8)

R017 ³ Ring 9 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 9)

R017 ³ Ring 10 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(10)

R017 ³ Ring 11 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(11)

R017 ³ Ring 12 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(12)

³ ³ ³ ³ ³ 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 08:16 Page 5 Summary : Yankee Rowe Sensitivity Analysis=soil File: Nb-94_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R018 ³ Fruits, vegetables and grain consumption (kg/yr) ³ 1.120E+02 ³ 1.600E+02 ³ --- ³ DIET(1)

R018 ³ Leafy vegetable consumption (kg/yr) ³ 2.140E+01 ³ 1.400E+01 ³ --- ³ DIET(2)

R018 ³ Milk consumption (L/yr) ³ 2.330E+02 ³ 9.200E+01 ³ --- ³ DIET(3)

R018 ³ Meat and poultry consumption (kg/yr) ³ 6.510E+01 ³ 6.300E+01 ³ --- ³ DIET(4)

R018 ³ Fish consumption (kg/yr) ³ 2.060E+01 ³ 5.400E+00 ³ --- ³ DIET(5)

R018 ³ Other seafood consumption (kg/yr) ³ 9.000E-01 ³ 9.000E-01 ³ --- ³ DIET(6)

R018 ³ Soil ingestion rate (g/yr) ³ 1.826E+01 ³ 3.650E+01 ³ --- ³ SOIL R018 ³ Drinking water intake (L/yr) ³ 4.785E+02 ³ 5.100E+02 ³ --- ³ DWI R018 ³ Contamination fraction of drinking water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FDW R018 ³ Contamination fraction of household water ³ not used ³ 1.000E+00 ³ --- ³ FHHW R018 ³ Contamination fraction of livestock water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FLW R018 ³ Contamination fraction of irrigation water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FIRW R018 ³ Contamination fraction of aquatic food ³ 1.000E+00 ³ 5.000E-01 ³ --- ³ FR9 R018 ³ Contamination fraction of plant food ³ 1.000E+00 ³-1 ³ --- ³ FPLANT R018 ³ Contamination fraction of meat ³ 1.000E+00 ³-1 ³ --- ³ FMEAT R018 ³ Contamination fraction of milk ³ 1.000E+00 ³-1 ³ --- ³ FMILK

³ ³ ³ ³ ³ R019 ³ Livestock fodder intake for meat (kg/day) ³ 2.710E+01 ³ 6.800E+01 ³ --- ³ LFI5 R019 ³ Livestock fodder intake for milk (kg/day) ³ 6.320E+01 ³ 5.500E+01 ³ --- ³ LFI6 R019 ³ Livestock water intake for meat (L/day) ³ 5.060E+01 ³ 5.000E+01 ³ --- ³ LWI5 R019 ³ Livestock water intake for milk (L/day) ³ 6.000E+01 ³ 1.600E+02 ³ --- ³ LWI6 R019 ³ Livestock soil intake (kg/day) ³ 5.000E-01 ³ 5.000E-01 ³ --- ³ LSI R019 ³ Mass loading for foliar deposition (g/m**3) ³ 4.000E-04 ³ 1.000E-04 ³ --- ³ MLFD R019 ³ Depth of soil mixing layer (m) ³ 2.300E-01 ³ 1.500E-01 ³ --- ³ DM R019 ³ Depth of roots (m) ³ 2.050E+00 ³ 9.000E-01 ³ --- ³ DROOT R019 ³ Drinking water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWDW R019 ³ Household water fraction from ground water ³ not used ³ 1.000E+00 ³ --- ³ FGWHH R019 ³ Livestock water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWLW R019 ³ Irrigation fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWIR

³ ³ ³ ³ ³ R19B ³ Wet weight crop yield for Non-Leafy (kg/m**2) ³ 1.750E+00 ³ 7.000E-01 ³ --- ³ YV(1)

R19B ³ Wet weight crop yield for Leafy (kg/m**2) ³ 2.889E+00 ³ 1.500E+00 ³ --- ³ YV(2)

R19B ³ Wet weight crop yield for Fodder (kg/m**2) ³ 1.887E+00 ³ 1.100E+00 ³ --- ³ YV(3)

R19B ³ Growing Season for Non-Leafy (years) ³ 2.460E-01 ³ 1.700E-01 ³ --- ³ TE(1)

R19B ³ Growing Season for Leafy (years) ³ 1.230E-01 ³ 2.500E-01 ³ --- ³ TE(2)

R19B ³ Growing Season for Fodder (years) ³ 8.200E-02 ³ 8.000E-02 ³ --- ³ TE(3)

R19B ³ Translocation Factor for Non-Leafy ³ 1.000E-01 ³ 1.000E-01 ³ --- ³ TIV(1)

R19B ³ Translocation Factor for Leafy ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(2)

R19B ³ Translocation Factor for Fodder ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(3)

R19B ³ Dry Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(1)

R19B ³ Dry Foliar Interception Fraction for Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(2)

R19B ³ Dry Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(3)

R19B ³ Wet Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(1)

R19B ³ Wet Foliar Interception Fraction for Leafy ³ 5.800E-01 ³ 2.500E-01 ³ --- ³ RWET(2)

R19B ³ Wet Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(3)

R19B ³ Weathering Removal Constant for Vegetation ³ 3.300E+01 ³ 2.000E+01 ³ --- ³ WLAM

³ ³ ³ ³ ³ C14 ³ C-12 concentration in water (g/cm**3) ³ not used ³ 2.000E-05 ³ --- ³ C12WTR C14 ³ C-12 concentration in contaminated soil (g/g) ³ not used ³ 3.000E-02 ³ --- ³ C12CZ C14 ³ Fraction of vegetation carbon from soil ³ not used ³ 2.000E-02 ³ --- ³ CSOIL C14 ³ Fraction of vegetation carbon from air ³ not used ³ 9.800E-01 ³ --- ³ CAIR 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 08:16 Page 6 Summary : Yankee Rowe Sensitivity Analysis=soil File: Nb-94_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ C14 ³ C-14 evasion layer thickness in soil (m) ³ not used ³ 3.000E-01 ³ --- ³ DMC C14 ³ C-14 evasion flux rate from soil (1/sec) ³ not used ³ 7.000E-07 ³ --- ³ EVSN C14 ³ C-12 evasion flux rate from soil (1/sec) ³ not used ³ 1.000E-10 ³ --- ³ REVSN C14 ³ Fraction of grain in beef cattle feed ³ not used ³ 8.000E-01 ³ --- ³ AVFG4 C14 ³ Fraction of grain in milk cow feed ³ not used ³ 2.000E-01 ³ --- ³ AVFG5 C14 ³ DCF correction factor for gaseous forms of C14 ³ not used ³ 8.894E+01 ³ --- ³ CO2F

³ ³ ³ ³ ³ STOR ³ Storage times of contaminated foodstuffs (days): ³ ³ ³ ³ STOR ³ Fruits, non-leafy vegetables, and grain ³ 1.400E+01 ³ 1.400E+01 ³ --- ³ STOR_T(1)

STOR ³ Leafy vegetables ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(2)

STOR ³ Milk ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(3)

STOR ³ Meat and poultry ³ 2.000E+01 ³ 2.000E+01 ³ --- ³ STOR_T(4)

STOR ³ Fish ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(5)

STOR ³ Crustacea and mollusks ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(6)

STOR ³ Well water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(7)

STOR ³ Surface water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(8)

STOR ³ Livestock fodder ³ 4.500E+01 ³ 4.500E+01 ³ --- ³ STOR_T(9)

³ ³ ³ ³ ³ R021 ³ Thickness of building foundation (m) ³ not used ³ 1.500E-01 ³ --- ³ FLOOR1 R021 ³ Bulk density of building foundation (g/cm**3) ³ not used ³ 2.400E+00 ³ --- ³ DENSFL R021 ³ Total porosity of the cover material ³ not used ³ 4.000E-01 ³ --- ³ TPCV R021 ³ Total porosity of the building foundation ³ not used ³ 1.000E-01 ³ --- ³ TPFL R021 ³ Volumetric water content of the cover material ³ not used ³ 5.000E-02 ³ --- ³ PH2OCV R021 ³ Volumetric water content of the foundation ³ not used ³ 3.000E-02 ³ --- ³ PH2OFL R021 ³ Diffusion coefficient for radon gas (m/sec): ³ ³ ³ ³ R021 ³ in cover material ³ not used ³ 2.000E-06 ³ --- ³ DIFCV R021 ³ in foundation material ³ not used ³ 3.000E-07 ³ --- ³ DIFFL R021 ³ in contaminated zone soil ³ not used ³ 2.000E-06 ³ --- ³ DIFCZ R021 ³ Radon vertical dimension of mixing (m) ³ not used ³ 2.000E+00 ³ --- ³ HMIX R021 ³ Average building air exchange rate (1/hr) ³ not used ³ 5.000E-01 ³ --- ³ REXG R021 ³ Height of the building (room) (m) ³ not used ³ 2.500E+00 ³ --- ³ HRM R021 ³ Building interior area factor ³ not used ³ 0.000E+00 ³ --- ³ FAI R021 ³ Building depth below ground surface (m) ³ not used ³-1.000E+00 ³ --- ³ DMFL R021 ³ Emanating power of Rn-222 gas ³ not used ³ 2.500E-01 ³ --- ³ EMANA(1)

R021 ³ Emanating power of Rn-220 gas ³ not used ³ 1.500E-01 ³ --- ³ EMANA(2)

³ ³ ³ ³ ³ TITL ³ Number of graphical time points ³ 32 ³ --- ³ --- ³ NPTS TITL ³ Maximum number of integration points for dose ³ 17 ³ --- ³ --- ³ LYMAX TITL ³ Maximum number of integration points for risk ³ 1 ³ --- ³ --- ³ KYMAX

1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 08:16 Page 7 Summary : Yankee Rowe Sensitivity Analysis=soil File: Nb-94_DCGL.RAD Summary of Pathway Selections Pathway ³ User Selection

Å 1 -- external gamma ³ active 2 -- inhalation (w/o radon)³ active 3 -- plant ingestion ³ active 4 -- meat ingestion ³ active 5 -- milk ingestion ³ active 6 -- aquatic foods ³ active 7 -- drinking water ³ active 8 -- soil ingestion ³ active 9 -- radon ³ suppressed Find peak pathway doses ³ active

1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 08:37 Page 2 Summary : Yankee Rowe Sensitivity Analysis=soil File: Ni-63_DCGL.RAD Dose Conversion Factor (and Related) Parameter Summary File: YR soil DCGL lib 0 ³ ³ Current ³ ³ Parameter Menu ³ Parameter ³ Value ³ Default ³ Name

ÅÅÅÅ B-1 ³ Dose conversion factors for inhalation, mrem/pCi: ³ ³ ³ B-1 ³ Ni-63 ³ 6.290E-06 ³ 6.290E-06 ³ DCF2( 1)

³ ³ ³ ³ D-1 ³ Dose conversion factors for ingestion, mrem/pCi: ³ ³ ³ D-1 ³ Ni-63 ³ 5.770E-07 ³ 5.770E-07 ³ DCF3( 1)

³ ³ ³ ³ D-34 ³ Food transfer factors: ³ ³ ³ D-34 ³ Ni-63, plant/soil concentration ratio, dimensionless ³ 9.110E-02 ³ 5.000E-02 ³ RTF( 1,1)

D-34 ³ Ni-63, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 5.000E-03 ³ 5.000E-03 ³ RTF( 1,2)

D-34 ³ Ni-63, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 3.210E-02 ³ 2.000E-02 ³ RTF( 1,3)

³ ³ ³ ³ D-5 ³ Bioaccumulation factors, fresh water, L/kg: ³ ³ ³ D-5 ³ Ni-63, fish ³ 1.000E+02 ³ 1.000E+02 ³ BIOFAC( 1,1)

D-5 ³ Ni-63, crustacea and mollusks ³ 1.000E+02 ³ 1.000E+02 ³ BIOFAC( 1,2) 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 08:37 Page 3 Summary : Yankee Rowe Sensitivity Analysis=soil File: Ni-63_DCGL.RAD Site-Specific Parameter Summary 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R011 ³ Area of contaminated zone (m**2) ³ 1.302E+04 ³ 1.000E+04 ³ --- ³ AREA R011 ³ Thickness of contaminated zone (m) ³ 1.975E+00 ³ 2.000E+00 ³ --- ³ THICK0 R011 ³ Length parallel to aquifer flow (m) ³ 1.290E+02 ³ 1.000E+02 ³ --- ³ LCZPAQ R011 ³ Basic radiation dose limit (mrem/yr) ³ 2.500E+01 ³ 2.500E+01 ³ --- ³ BRDL R011 ³ Time since placement of material (yr) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ TI R011 ³ Times for calculations (yr) ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ T( 2)

R011 ³ Times for calculations (yr) ³ 3.000E+00 ³ 3.000E+00 ³ --- ³ T( 3)

R011 ³ Times for calculations (yr) ³ 1.000E+01 ³ 1.000E+01 ³ --- ³ T( 4)

R011 ³ Times for calculations (yr) ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ T( 5)

R011 ³ Times for calculations (yr) ³ 1.000E+02 ³ 1.000E+02 ³ --- ³ T( 6)

R011 ³ Times for calculations (yr) ³ 3.000E+02 ³ 3.000E+02 ³ --- ³ T( 7)

R011 ³ Times for calculations (yr) ³ 1.000E+03 ³ 1.000E+03 ³ --- ³ T( 8)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T( 9)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T(10)

³ ³ ³ ³ ³ R012 ³ Initial principal radionuclide (pCi/g): Ni-63 ³ 1.000E+00 ³ 0.000E+00 ³ --- ³ S1( 1)

R012 ³ Concentration in groundwater (pCi/L): Ni-63 ³ not used ³ 0.000E+00 ³ --- ³ W1( 1)

³ ³ ³ ³ ³ R013 ³ Cover depth (m) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ COVER0 R013 ³ Density of cover material (g/cm**3) ³ not used ³ 1.500E+00 ³ --- ³ DENSCV R013 ³ Cover depth erosion rate (m/yr) ³ not used ³ 1.000E-03 ³ --- ³ VCV R013 ³ Density of contaminated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSCZ R013 ³ Contaminated zone erosion rate (m/yr) ³ 8.500E-04 ³ 1.000E-03 ³ --- ³ VCZ R013 ³ Contaminated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPCZ R013 ³ Contaminated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCCZ R013 ³ Contaminated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCCZ R013 ³ Contaminated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BCZ R013 ³ Average annual wind speed (m/sec) ³ 2.030E+00 ³ 2.000E+00 ³ --- ³ WIND R013 ³ Humidity in air (g/m**3) ³ not used ³ 8.000E+00 ³ --- ³ HUMID R013 ³ Evapotranspiration coefficient ³ 6.250E-01 ³ 5.000E-01 ³ --- ³ EVAPTR R013 ³ Precipitation (m/yr) ³ 1.200E+00 ³ 1.000E+00 ³ --- ³ PRECIP R013 ³ Irrigation (m/yr) ³ 4.350E-01 ³ 2.000E-01 ³ --- ³ RI R013 ³ Irrigation mode ³ overhead ³ overhead ³ --- ³ IDITCH R013 ³ Runoff coefficient ³ 6.000E-01 ³ 2.000E-01 ³ --- ³ RUNOFF R013 ³ Watershed area for nearby stream or pond (m**2) ³ 7.770E+05 ³ 1.000E+06 ³ --- ³ WAREA R013 ³ Accuracy for water/soil computations ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ EPS

³ ³ ³ ³ ³ R014 ³ Density of saturated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSAQ R014 ³ Saturated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPSZ R014 ³ Saturated zone effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPSZ R014 ³ Saturated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCSZ R014 ³ Saturated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+02 ³ --- ³ HCSZ R014 ³ Saturated zone hydraulic gradient ³ 1.000E-01 ³ 2.000E-02 ³ --- ³ HGWT R014 ³ Saturated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BSZ R014 ³ Water table drop rate (m/yr) ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ VWT R014 ³ Well pump intake depth (m below water table) ³ 1.451E+01 ³ 1.000E+01 ³ --- ³ DWIBWT R014 ³ Model: Nondispersion (ND) or Mass-Balance (MB) ³ ND ³ ND ³ --- ³ MODEL R014 ³ Well pumping rate (m**3/yr) ³ 1.323E+03 ³ 2.500E+02 ³ --- ³ UW

³ ³ ³ ³ ³ R015 ³ Number of unsaturated zone strata ³ 1 ³ 1 ³ --- ³ NS 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 08:37 Page 4 Summary : Yankee Rowe Sensitivity Analysis=soil File: Ni-63_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R015 ³ Unsat. zone 1, thickness (m) ³ 1.820E+00 ³ 4.000E+00 ³ --- ³ H(1)

R015 ³ Unsat. zone 1, soil density (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSUZ(1)

R015 ³ Unsat. zone 1, total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPUZ(1)

R015 ³ Unsat. zone 1, effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPUZ(1)

R015 ³ Unsat. zone 1, field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCUZ(1)

R015 ³ Unsat. zone 1, soil-specific b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BUZ(1)

R015 ³ Unsat. zone 1, hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCUZ(1)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for Ni-63 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 4.240E+02 ³ 1.000E+03 ³ --- ³ DCNUCC( 1)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 4.240E+02 ³ 1.000E+03 ³ --- ³ DCNUCU( 1,1)

R016 ³ Saturated zone (cm**3/g) ³ 4.240E+02 ³ 1.000E+03 ³ --- ³ DCNUCS( 1)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 2.712E-04 ³ ALEACH( 1)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 1)

³ ³ ³ ³ ³ R017 ³ Inhalation rate (m**3/yr) ³ 8.400E+03 ³ 8.400E+03 ³ --- ³ INHALR R017 ³ Mass loading for inhalation (g/m**3) ³ 2.330E-05 ³ 1.000E-04 ³ --- ³ MLINH R017 ³ Exposure duration ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ ED R017 ³ Shielding factor, inhalation ³ 5.500E-01 ³ 4.000E-01 ³ --- ³ SHF3 R017 ³ Shielding factor, external gamma ³ 2.725E-01 ³ 7.000E-01 ³ --- ³ SHF1 R017 ³ Fraction of time spent indoors ³ 6.571E-01 ³ 5.000E-01 ³ --- ³ FIND R017 ³ Fraction of time spent outdoors (on site) ³ 1.181E-01 ³ 2.500E-01 ³ --- ³ FOTD R017 ³ Shape factor flag, external gamma ³ 1.000E+00 ³ 1.000E+00 ³ >0 shows circular AREA. ³ FS R017 ³ Radii of shape factor array (used if FS = -1): ³ ³ ³ ³ R017 ³ Outer annular radius (m), ring 1: ³ not used ³ 5.000E+01 ³ --- ³ RAD_SHAPE(

1)

R017 ³ Outer annular radius (m), ring 2: ³ not used ³ 7.071E+01 ³ --- ³ RAD_SHAPE(

2)

R017 ³ Outer annular radius (m), ring 3: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

3)

R017 ³ Outer annular radius (m), ring 4: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

4)

R017 ³ Outer annular radius (m), ring 5: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

5)

R017 ³ Outer annular radius (m), ring 6: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

6)

R017 ³ Outer annular radius (m), ring 7: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

7)

R017 ³ Outer annular radius (m), ring 8: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

8)

R017 ³ Outer annular radius (m), ring 9: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

9)

R017 ³ Outer annular radius (m), ring 10: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (10)

R017 ³ Outer annular radius (m), ring 11: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (11)

R017 ³ Outer annular radius (m), ring 12: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (12)

³ ³ ³ ³ ³ R017 ³ Fractions of annular areas within AREA: ³ ³ ³ ³ R017 ³ Ring 1 ³ not used ³ 1.000E+00 ³ --- ³ FRACA( 1)

R017 ³ Ring 2 ³ not used ³ 2.732E-01 ³ --- ³ FRACA( 2)

R017 ³ Ring 3 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 3)

R017 ³ Ring 4 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 4)

R017 ³ Ring 5 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 5)

R017 ³ Ring 6 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 6)

R017 ³ Ring 7 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 7)

R017 ³ Ring 8 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 8)

R017 ³ Ring 9 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 9)

R017 ³ Ring 10 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(10)

R017 ³ Ring 11 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(11)

R017 ³ Ring 12 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(12)

³ ³ ³ ³ ³ 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 08:37 Page 5 Summary : Yankee Rowe Sensitivity Analysis=soil File: Ni-63_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R018 ³ Fruits, vegetables and grain consumption (kg/yr) ³ 1.120E+02 ³ 1.600E+02 ³ --- ³ DIET(1)

R018 ³ Leafy vegetable consumption (kg/yr) ³ 2.140E+01 ³ 1.400E+01 ³ --- ³ DIET(2)

R018 ³ Milk consumption (L/yr) ³ 2.330E+02 ³ 9.200E+01 ³ --- ³ DIET(3)

R018 ³ Meat and poultry consumption (kg/yr) ³ 6.510E+01 ³ 6.300E+01 ³ --- ³ DIET(4)

R018 ³ Fish consumption (kg/yr) ³ 2.060E+01 ³ 5.400E+00 ³ --- ³ DIET(5)

R018 ³ Other seafood consumption (kg/yr) ³ 9.000E-01 ³ 9.000E-01 ³ --- ³ DIET(6)

R018 ³ Soil ingestion rate (g/yr) ³ 1.826E+01 ³ 3.650E+01 ³ --- ³ SOIL R018 ³ Drinking water intake (L/yr) ³ 4.785E+02 ³ 5.100E+02 ³ --- ³ DWI R018 ³ Contamination fraction of drinking water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FDW R018 ³ Contamination fraction of household water ³ not used ³ 1.000E+00 ³ --- ³ FHHW R018 ³ Contamination fraction of livestock water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FLW R018 ³ Contamination fraction of irrigation water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FIRW R018 ³ Contamination fraction of aquatic food ³ 1.000E+00 ³ 5.000E-01 ³ --- ³ FR9 R018 ³ Contamination fraction of plant food ³ 1.000E+00 ³-1 ³ --- ³ FPLANT R018 ³ Contamination fraction of meat ³ 1.000E+00 ³-1 ³ --- ³ FMEAT R018 ³ Contamination fraction of milk ³ 1.000E+00 ³-1 ³ --- ³ FMILK

³ ³ ³ ³ ³ R019 ³ Livestock fodder intake for meat (kg/day) ³ 2.710E+01 ³ 6.800E+01 ³ --- ³ LFI5 R019 ³ Livestock fodder intake for milk (kg/day) ³ 6.320E+01 ³ 5.500E+01 ³ --- ³ LFI6 R019 ³ Livestock water intake for meat (L/day) ³ 5.060E+01 ³ 5.000E+01 ³ --- ³ LWI5 R019 ³ Livestock water intake for milk (L/day) ³ 6.000E+01 ³ 1.600E+02 ³ --- ³ LWI6 R019 ³ Livestock soil intake (kg/day) ³ 5.000E-01 ³ 5.000E-01 ³ --- ³ LSI R019 ³ Mass loading for foliar deposition (g/m**3) ³ 4.000E-04 ³ 1.000E-04 ³ --- ³ MLFD R019 ³ Depth of soil mixing layer (m) ³ 2.300E-01 ³ 1.500E-01 ³ --- ³ DM R019 ³ Depth of roots (m) ³ 1.170E+00 ³ 9.000E-01 ³ --- ³ DROOT R019 ³ Drinking water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWDW R019 ³ Household water fraction from ground water ³ not used ³ 1.000E+00 ³ --- ³ FGWHH R019 ³ Livestock water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWLW R019 ³ Irrigation fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWIR

³ ³ ³ ³ ³ R19B ³ Wet weight crop yield for Non-Leafy (kg/m**2) ³ 1.750E+00 ³ 7.000E-01 ³ --- ³ YV(1)

R19B ³ Wet weight crop yield for Leafy (kg/m**2) ³ 2.889E+00 ³ 1.500E+00 ³ --- ³ YV(2)

R19B ³ Wet weight crop yield for Fodder (kg/m**2) ³ 1.887E+00 ³ 1.100E+00 ³ --- ³ YV(3)

R19B ³ Growing Season for Non-Leafy (years) ³ 2.460E-01 ³ 1.700E-01 ³ --- ³ TE(1)

R19B ³ Growing Season for Leafy (years) ³ 1.230E-01 ³ 2.500E-01 ³ --- ³ TE(2)

R19B ³ Growing Season for Fodder (years) ³ 8.200E-02 ³ 8.000E-02 ³ --- ³ TE(3)

R19B ³ Translocation Factor for Non-Leafy ³ 1.000E-01 ³ 1.000E-01 ³ --- ³ TIV(1)

R19B ³ Translocation Factor for Leafy ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(2)

R19B ³ Translocation Factor for Fodder ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(3)

R19B ³ Dry Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(1)

R19B ³ Dry Foliar Interception Fraction for Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(2)

R19B ³ Dry Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(3)

R19B ³ Wet Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(1)

R19B ³ Wet Foliar Interception Fraction for Leafy ³ 5.800E-01 ³ 2.500E-01 ³ --- ³ RWET(2)

R19B ³ Wet Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(3)

R19B ³ Weathering Removal Constant for Vegetation ³ 3.300E+01 ³ 2.000E+01 ³ --- ³ WLAM

³ ³ ³ ³ ³ C14 ³ C-12 concentration in water (g/cm**3) ³ not used ³ 2.000E-05 ³ --- ³ C12WTR C14 ³ C-12 concentration in contaminated soil (g/g) ³ not used ³ 3.000E-02 ³ --- ³ C12CZ C14 ³ Fraction of vegetation carbon from soil ³ not used ³ 2.000E-02 ³ --- ³ CSOIL C14 ³ Fraction of vegetation carbon from air ³ not used ³ 9.800E-01 ³ --- ³ CAIR 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 08:37 Page 6 Summary : Yankee Rowe Sensitivity Analysis=soil File: Ni-63_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ C14 ³ C-14 evasion layer thickness in soil (m) ³ not used ³ 3.000E-01 ³ --- ³ DMC C14 ³ C-14 evasion flux rate from soil (1/sec) ³ not used ³ 7.000E-07 ³ --- ³ EVSN C14 ³ C-12 evasion flux rate from soil (1/sec) ³ not used ³ 1.000E-10 ³ --- ³ REVSN C14 ³ Fraction of grain in beef cattle feed ³ not used ³ 8.000E-01 ³ --- ³ AVFG4 C14 ³ Fraction of grain in milk cow feed ³ not used ³ 2.000E-01 ³ --- ³ AVFG5 C14 ³ DCF correction factor for gaseous forms of C14 ³ not used ³ 8.894E+01 ³ --- ³ CO2F

³ ³ ³ ³ ³ STOR ³ Storage times of contaminated foodstuffs (days): ³ ³ ³ ³ STOR ³ Fruits, non-leafy vegetables, and grain ³ 1.400E+01 ³ 1.400E+01 ³ --- ³ STOR_T(1)

STOR ³ Leafy vegetables ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(2)

STOR ³ Milk ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(3)

STOR ³ Meat and poultry ³ 2.000E+01 ³ 2.000E+01 ³ --- ³ STOR_T(4)

STOR ³ Fish ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(5)

STOR ³ Crustacea and mollusks ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(6)

STOR ³ Well water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(7)

STOR ³ Surface water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(8)

STOR ³ Livestock fodder ³ 4.500E+01 ³ 4.500E+01 ³ --- ³ STOR_T(9)

³ ³ ³ ³ ³ R021 ³ Thickness of building foundation (m) ³ not used ³ 1.500E-01 ³ --- ³ FLOOR1 R021 ³ Bulk density of building foundation (g/cm**3) ³ not used ³ 2.400E+00 ³ --- ³ DENSFL R021 ³ Total porosity of the cover material ³ not used ³ 4.000E-01 ³ --- ³ TPCV R021 ³ Total porosity of the building foundation ³ not used ³ 1.000E-01 ³ --- ³ TPFL R021 ³ Volumetric water content of the cover material ³ not used ³ 5.000E-02 ³ --- ³ PH2OCV R021 ³ Volumetric water content of the foundation ³ not used ³ 3.000E-02 ³ --- ³ PH2OFL R021 ³ Diffusion coefficient for radon gas (m/sec): ³ ³ ³ ³ R021 ³ in cover material ³ not used ³ 2.000E-06 ³ --- ³ DIFCV R021 ³ in foundation material ³ not used ³ 3.000E-07 ³ --- ³ DIFFL R021 ³ in contaminated zone soil ³ not used ³ 2.000E-06 ³ --- ³ DIFCZ R021 ³ Radon vertical dimension of mixing (m) ³ not used ³ 2.000E+00 ³ --- ³ HMIX R021 ³ Average building air exchange rate (1/hr) ³ not used ³ 5.000E-01 ³ --- ³ REXG R021 ³ Height of the building (room) (m) ³ not used ³ 2.500E+00 ³ --- ³ HRM R021 ³ Building interior area factor ³ not used ³ 0.000E+00 ³ --- ³ FAI R021 ³ Building depth below ground surface (m) ³ not used ³-1.000E+00 ³ --- ³ DMFL R021 ³ Emanating power of Rn-222 gas ³ not used ³ 2.500E-01 ³ --- ³ EMANA(1)

R021 ³ Emanating power of Rn-220 gas ³ not used ³ 1.500E-01 ³ --- ³ EMANA(2)

³ ³ ³ ³ ³ TITL ³ Number of graphical time points ³ 32 ³ --- ³ --- ³ NPTS TITL ³ Maximum number of integration points for dose ³ 17 ³ --- ³ --- ³ LYMAX TITL ³ Maximum number of integration points for risk ³ 1 ³ --- ³ --- ³ KYMAX

1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 08:37 Page 7 Summary : Yankee Rowe Sensitivity Analysis=soil File: Ni-63_DCGL.RAD Summary of Pathway Selections Pathway ³ User Selection

Å 1 -- external gamma ³ active 2 -- inhalation (w/o radon)³ active 3 -- plant ingestion ³ active 4 -- meat ingestion ³ active 5 -- milk ingestion ³ active 6 -- aquatic foods ³ active 7 -- drinking water ³ active 8 -- soil ingestion ³ active 9 -- radon ³ suppressed Find peak pathway doses ³ active

1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/01/2003 10:12 Page 2 Summary : Yankee Rowe Sensitivity Analysis=soil File: Pu-238_DCGL.RAD Dose Conversion Factor (and Related) Parameter Summary File: YR soil DCGL lib 0 ³ ³ Current ³ ³ Parameter Menu ³ Parameter ³ Value ³ Default ³ Name

ÅÅÅÅ B-1 ³ Dose conversion factors for inhalation, mrem/pCi: ³ ³ ³ B-1 ³ Pb-210+D ³ 2.320E-02 ³ 2.320E-02 ³ DCF2( 1)

B-1 ³ Pu-238 ³ 3.920E-01 ³ 3.920E-01 ³ DCF2( 2)

B-1 ³ Ra-226+D ³ 8.600E-03 ³ 8.600E-03 ³ DCF2( 3)

B-1 ³ Th-230 ³ 3.260E-01 ³ 3.260E-01 ³ DCF2( 4)

B-1 ³ U-234 ³ 1.320E-01 ³ 1.320E-01 ³ DCF2( 5)

³ ³ ³ ³ D-1 ³ Dose conversion factors for ingestion, mrem/pCi: ³ ³ ³ D-1 ³ Pb-210+D ³ 7.270E-03 ³ 7.270E-03 ³ DCF3( 1)

D-1 ³ Pu-238 ³ 3.200E-03 ³ 3.200E-03 ³ DCF3( 2)

D-1 ³ Ra-226+D ³ 1.330E-03 ³ 1.330E-03 ³ DCF3( 3)

D-1 ³ Th-230 ³ 5.480E-04 ³ 5.480E-04 ³ DCF3( 4)

D-1 ³ U-234 ³ 2.830E-04 ³ 2.830E-04 ³ DCF3( 5)

³ ³ ³ ³ D-34 ³ Food transfer factors: ³ ³ ³ D-34 ³ Pb-210+D, plant/soil concentration ratio, dimensionless ³ 1.000E-02 ³ 1.000E-02 ³ RTF( 1,1)

D-34 ³ Pb-210+D, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 8.000E-04 ³ 8.000E-04 ³ RTF( 1,2)

D-34 ³ Pb-210+D, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 3.000E-04 ³ 3.000E-04 ³ RTF( 1,3)

D-34 ³ ³ ³ ³ D-34 ³ Pu-238, plant/soil concentration ratio, dimensionless ³ 1.830E-03 ³ 1.000E-03 ³ RTF( 2,1)

D-34 ³ Pu-238, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 1.000E-04 ³ 1.000E-04 ³ RTF( 2,2)

D-34 ³ Pu-238, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 1.000E-06 ³ 1.000E-06 ³ RTF( 2,3)

D-34 ³ ³ ³ ³ D-34 ³ Ra-226+D, plant/soil concentration ratio, dimensionless ³ 4.000E-02 ³ 4.000E-02 ³ RTF( 3,1)

D-34 ³ Ra-226+D, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 1.000E-03 ³ 1.000E-03 ³ RTF( 3,2)

D-34 ³ Ra-226+D, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 1.000E-03 ³ 1.000E-03 ³ RTF( 3,3)

D-34 ³ ³ ³ ³ D-34 ³ Th-230, plant/soil concentration ratio, dimensionless ³ 1.000E-03 ³ 1.000E-03 ³ RTF( 4,1)

D-34 ³ Th-230, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 1.000E-04 ³ 1.000E-04 ³ RTF( 4,2)

D-34 ³ Th-230, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 5.000E-06 ³ 5.000E-06 ³ RTF( 4,3)

D-34 ³ ³ ³ ³ D-34 ³ U-234, plant/soil concentration ratio, dimensionless ³ 2.500E-03 ³ 2.500E-03 ³ RTF( 5,1)

D-34 ³ U-234, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 3.400E-04 ³ 3.400E-04 ³ RTF( 5,2)

D-34 ³ U-234, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 6.000E-04 ³ 6.000E-04 ³ RTF( 5,3)

³ ³ ³ ³ D-5 ³ Bioaccumulation factors, fresh water, L/kg: ³ ³ ³ D-5 ³ Pb-210+D, fish ³ 3.000E+02 ³ 3.000E+02 ³ BIOFAC( 1,1)

D-5 ³ Pb-210+D, crustacea and mollusks ³ 1.000E+02 ³ 1.000E+02 ³ BIOFAC( 1,2)

D-5 ³ ³ ³ ³ D-5 ³ Pu-238, fish ³ 3.000E+01 ³ 3.000E+01 ³ BIOFAC( 2,1)

D-5 ³ Pu-238, crustacea and mollusks ³ 1.000E+02 ³ 1.000E+02 ³ BIOFAC( 2,2)

D-5 ³ ³ ³ ³ D-5 ³ Ra-226+D, fish ³ 5.000E+01 ³ 5.000E+01 ³ BIOFAC( 3,1)

D-5 ³ Ra-226+D, crustacea and mollusks ³ 2.500E+02 ³ 2.500E+02 ³ BIOFAC( 3,2)

D-5 ³ ³ ³ ³ D-5 ³ Th-230, fish ³ 1.000E+02 ³ 1.000E+02 ³ BIOFAC( 4,1)

D-5 ³ Th-230, crustacea and mollusks ³ 5.000E+02 ³ 5.000E+02 ³ BIOFAC( 4,2)

D-5 ³ ³ ³ ³ D-5 ³ U-234, fish ³ 1.000E+01 ³ 1.000E+01 ³ BIOFAC( 5,1)

D-5 ³ U-234, crustacea and mollusks ³ 6.000E+01 ³ 6.000E+01 ³ BIOFAC( 5,2) 1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/01/2003 10:12 Page 3 Summary : Yankee Rowe Sensitivity Analysis=soil File: Pu-238_DCGL.RAD Site-Specific Parameter Summary 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R011 ³ Area of contaminated zone (m**2) ³ 1.302E+04 ³ 1.000E+04 ³ --- ³ AREA R011 ³ Thickness of contaminated zone (m) ³ 1.975E+00 ³ 2.000E+00 ³ --- ³ THICK0 R011 ³ Length parallel to aquifer flow (m) ³ 1.290E+02 ³ 1.000E+02 ³ --- ³ LCZPAQ R011 ³ Basic radiation dose limit (mrem/yr) ³ 2.500E+01 ³ 2.500E+01 ³ --- ³ BRDL R011 ³ Time since placement of material (yr) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ TI R011 ³ Times for calculations (yr) ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ T( 2)

R011 ³ Times for calculations (yr) ³ 3.000E+00 ³ 3.000E+00 ³ --- ³ T( 3)

R011 ³ Times for calculations (yr) ³ 1.000E+01 ³ 1.000E+01 ³ --- ³ T( 4)

R011 ³ Times for calculations (yr) ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ T( 5)

R011 ³ Times for calculations (yr) ³ 1.000E+02 ³ 1.000E+02 ³ --- ³ T( 6)

R011 ³ Times for calculations (yr) ³ 3.000E+02 ³ 3.000E+02 ³ --- ³ T( 7)

R011 ³ Times for calculations (yr) ³ 1.000E+03 ³ 1.000E+03 ³ --- ³ T( 8)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T( 9)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T(10)

³ ³ ³ ³ ³ R012 ³ Initial principal radionuclide (pCi/g): Pu-238 ³ 1.000E+00 ³ 0.000E+00 ³ --- ³ S1( 2)

R012 ³ Concentration in groundwater (pCi/L): Pu-238 ³ not used ³ 0.000E+00 ³ --- ³ W1( 2)

³ ³ ³ ³ ³ R013 ³ Cover depth (m) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ COVER0 R013 ³ Density of cover material (g/cm**3) ³ not used ³ 1.500E+00 ³ --- ³ DENSCV R013 ³ Cover depth erosion rate (m/yr) ³ not used ³ 1.000E-03 ³ --- ³ VCV R013 ³ Density of contaminated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSCZ R013 ³ Contaminated zone erosion rate (m/yr) ³ 8.500E-04 ³ 1.000E-03 ³ --- ³ VCZ R013 ³ Contaminated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPCZ R013 ³ Contaminated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCCZ R013 ³ Contaminated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCCZ R013 ³ Contaminated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BCZ R013 ³ Average annual wind speed (m/sec) ³ 2.030E+00 ³ 2.000E+00 ³ --- ³ WIND R013 ³ Humidity in air (g/m**3) ³ not used ³ 8.000E+00 ³ --- ³ HUMID

R013 ³ Evapotranspiration coefficient ³ 6.250E-01 ³ 5.000E-01 ³ --- ³ EVAPTR R013 ³ Precipitation (m/yr) ³ 1.200E+00 ³ 1.000E+00 ³ --- ³ PRECIP R013 ³ Irrigation (m/yr) ³ 4.350E-01 ³ 2.000E-01 ³ --- ³ RI R013 ³ Irrigation mode ³ overhead ³ overhead ³ --- ³ IDITCH R013 ³ Runoff coefficient ³ 6.000E-01 ³ 2.000E-01 ³ --- ³ RUNOFF R013 ³ Watershed area for nearby stream or pond (m**2) ³ 7.770E+05 ³ 1.000E+06 ³ --- ³ WAREA R013 ³ Accuracy for water/soil computations ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ EPS

³ ³ ³ ³ ³ R014 ³ Density of saturated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSAQ R014 ³ Saturated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPSZ R014 ³ Saturated zone effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPSZ R014 ³ Saturated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCSZ R014 ³ Saturated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+02 ³ --- ³ HCSZ R014 ³ Saturated zone hydraulic gradient ³ 1.000E-01 ³ 2.000E-02 ³ --- ³ HGWT R014 ³ Saturated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BSZ R014 ³ Water table drop rate (m/yr) ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ VWT R014 ³ Well pump intake depth (m below water table) ³ 1.451E+01 ³ 1.000E+01 ³ --- ³ DWIBWT R014 ³ Model: Nondispersion (ND) or Mass-Balance (MB) ³ ND ³ ND ³ --- ³ MODEL R014 ³ Well pumping rate (m**3/yr) ³ 1.323E+03 ³ 2.500E+02 ³ --- ³ UW

³ ³ ³ ³ ³ R015 ³ Number of unsaturated zone strata ³ 1 ³ 1 ³ --- ³ NS 1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/01/2003 10:12 Page 4 Summary : Yankee Rowe Sensitivity Analysis=soil File: Pu-238_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R015 ³ Unsat. zone 1, thickness (m) ³ 1.820E+00 ³ 4.000E+00 ³ --- ³ H(1)

R015 ³ Unsat. zone 1, soil density (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSUZ(1)

R015 ³ Unsat. zone 1, total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPUZ(1)

R015 ³ Unsat. zone 1, effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPUZ(1)

R015 ³ Unsat. zone 1, field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCUZ(1)

R015 ³ Unsat. zone 1, soil-specific b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BUZ(1)

R015 ³ Unsat. zone 1, hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCUZ(1)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for Pu-238 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 9.530E+02 ³ 2.000E+03 ³ --- ³ DCNUCC( 2)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 9.530E+02 ³ 2.000E+03 ³ --- ³ DCNUCU( 2,1)

R016 ³ Saturated zone (cm**3/g) ³ 9.530E+02 ³ 2.000E+03 ³ --- ³ DCNUCS( 2)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 1.207E-04 ³ ALEACH( 2)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 2)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for daughter Pb-210 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 2.392E+03 ³ 1.000E+02 ³ --- ³ DCNUCC( 1)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 2.392E+03 ³ 1.000E+02 ³ --- ³ DCNUCU( 1,1)

R016 ³ Saturated zone (cm**3/g) ³ 2.392E+03 ³ 1.000E+02 ³ --- ³ DCNUCS( 1)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 4.808E-05 ³ ALEACH( 1)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 1)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for daughter Ra-226 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 3.533E+03 ³ 7.000E+01 ³ --- ³ DCNUCC( 3)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 3.533E+03 ³ 7.000E+01 ³ --- ³ DCNUCU( 3,1)

R016 ³ Saturated zone (cm**3/g) ³ 3.533E+03 ³ 7.000E+01 ³ --- ³ DCNUCS( 3)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 3.255E-05 ³ ALEACH( 3)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 3)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for daughter Th-230 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 5.884E+03 ³ 6.000E+04 ³ --- ³ DCNUCC( 4)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 5.884E+03 ³ 6.000E+04 ³ --- ³ DCNUCU( 4,1)

R016 ³ Saturated zone (cm**3/g) ³ 5.884E+03 ³ 6.000E+04 ³ --- ³ DCNUCS( 4)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 1.955E-05 ³ ALEACH( 4)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 4)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for daughter U-234 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 1.260E+02 ³ 5.000E+01 ³ --- ³ DCNUCC( 5)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 1.260E+02 ³ 5.000E+01 ³ --- ³ DCNUCU( 5,1)

R016 ³ Saturated zone (cm**3/g) ³ 1.260E+02 ³ 5.000E+01 ³ --- ³ DCNUCS( 5)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 9.125E-04 ³ ALEACH( 5)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 5)

³ ³ ³ ³ ³ R017 ³ Inhalation rate (m**3/yr) ³ 8.400E+03 ³ 8.400E+03 ³ --- ³ INHALR R017 ³ Mass loading for inhalation (g/m**3) ³ 2.330E-05 ³ 1.000E-04 ³ --- ³ MLINH R017 ³ Exposure duration ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ ED R017 ³ Shielding factor, inhalation ³ 5.500E-01 ³ 4.000E-01 ³ --- ³ SHF3 R017 ³ Shielding factor, external gamma ³ 2.725E-01 ³ 7.000E-01 ³ --- ³ SHF1 R017 ³ Fraction of time spent indoors ³ 6.571E-01 ³ 5.000E-01 ³ --- ³ FIND R017 ³ Fraction of time spent outdoors (on site) ³ 1.181E-01 ³ 2.500E-01 ³ --- ³ FOTD R017 ³ Shape factor flag, external gamma ³ 1.000E+00 ³ 1.000E+00 ³ >0 shows circular AREA. ³ FS 1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/01/2003 10:12 Page 5 Summary : Yankee Rowe Sensitivity Analysis=soil File: Pu-238_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R017 ³ Radii of shape factor array (used if FS = -1): ³ ³ ³ ³ R017 ³ Outer annular radius (m), ring 1: ³ not used ³ 5.000E+01 ³ --- ³ RAD_SHAPE(

1)

R017 ³ Outer annular radius (m), ring 2: ³ not used ³ 7.071E+01 ³ --- ³ RAD_SHAPE(

2)

R017 ³ Outer annular radius (m), ring 3: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

3)

R017 ³ Outer annular radius (m), ring 4: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

4)

R017 ³ Outer annular radius (m), ring 5: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

5)

R017 ³ Outer annular radius (m), ring 6: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

6)

R017 ³ Outer annular radius (m), ring 7: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

7)

R017 ³ Outer annular radius (m), ring 8: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

8)

R017 ³ Outer annular radius (m), ring 9: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

9)

R017 ³ Outer annular radius (m), ring 10: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (10)

R017 ³ Outer annular radius (m), ring 11: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (11)

R017 ³ Outer annular radius (m), ring 12: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (12)

³ ³ ³ ³ ³ R017 ³ Fractions of annular areas within AREA: ³ ³ ³ ³ R017 ³ Ring 1 ³ not used ³ 1.000E+00 ³ --- ³ FRACA( 1)

R017 ³ Ring 2 ³ not used ³ 2.732E-01 ³ --- ³ FRACA( 2)

R017 ³ Ring 3 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 3)

R017 ³ Ring 4 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 4)

R017 ³ Ring 5 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 5)

R017 ³ Ring 6 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 6)

R017 ³ Ring 7 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 7)

R017 ³ Ring 8 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 8)

R017 ³ Ring 9 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 9)

R017 ³ Ring 10 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(10)

R017 ³ Ring 11 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(11)

R017 ³ Ring 12 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(12)

³ ³ ³ ³ ³ R018 ³ Fruits, vegetables and grain consumption (kg/yr) ³ 1.120E+02 ³ 1.600E+02 ³ --- ³ DIET(1)

R018 ³ Leafy vegetable consumption (kg/yr) ³ 2.140E+01 ³ 1.400E+01 ³ --- ³ DIET(2)

R018 ³ Milk consumption (L/yr) ³ 2.330E+02 ³ 9.200E+01 ³ --- ³ DIET(3)

R018 ³ Meat and poultry consumption (kg/yr) ³ 6.510E+01 ³ 6.300E+01 ³ --- ³ DIET(4)

R018 ³ Fish consumption (kg/yr) ³ 2.060E+01 ³ 5.400E+00 ³ --- ³ DIET(5)

R018 ³ Other seafood consumption (kg/yr) ³ 9.000E-01 ³ 9.000E-01 ³ --- ³ DIET(6)

R018 ³ Soil ingestion rate (g/yr) ³ 1.826E+01 ³ 3.650E+01 ³ --- ³ SOIL R018 ³ Drinking water intake (L/yr) ³ 4.785E+02 ³ 5.100E+02 ³ --- ³ DWI R018 ³ Contamination fraction of drinking water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FDW R018 ³ Contamination fraction of household water ³ not used ³ 1.000E+00 ³ --- ³ FHHW R018 ³ Contamination fraction of livestock water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FLW R018 ³ Contamination fraction of irrigation water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FIRW R018 ³ Contamination fraction of aquatic food ³ 1.000E+00 ³ 5.000E-01 ³ --- ³ FR9 R018 ³ Contamination fraction of plant food ³ 1.000E+00 ³-1 ³ --- ³ FPLANT R018 ³ Contamination fraction of meat ³ 1.000E+00 ³-1 ³ --- ³ FMEAT R018 ³ Contamination fraction of milk ³ 1.000E+00 ³-1 ³ --- ³ FMILK

³ ³ ³ ³ ³ R019 ³ Livestock fodder intake for meat (kg/day) ³ 2.710E+01 ³ 6.800E+01 ³ --- ³ LFI5 R019 ³ Livestock fodder intake for milk (kg/day) ³ 6.320E+01 ³ 5.500E+01 ³ --- ³ LFI6 R019 ³ Livestock water intake for meat (L/day) ³ 5.060E+01 ³ 5.000E+01 ³ --- ³ LWI5 R019 ³ Livestock water intake for milk (L/day) ³ 6.000E+01 ³ 1.600E+02 ³ --- ³ LWI6 R019 ³ Livestock soil intake (kg/day) ³ 5.000E-01 ³ 5.000E-01 ³ --- ³ LSI R019 ³ Mass loading for foliar deposition (g/m**3) ³ 4.000E-04 ³ 1.000E-04 ³ --- ³ MLFD 1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/01/2003 10:12 Page 6 Summary : Yankee Rowe Sensitivity Analysis=soil File: Pu-238_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R019 ³ Depth of soil mixing layer (m) ³ 2.300E-01 ³ 1.500E-01 ³ --- ³ DM R019 ³ Depth of roots (m) ³ 1.170E+00 ³ 9.000E-01 ³ --- ³ DROOT R019 ³ Drinking water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWDW R019 ³ Household water fraction from ground water ³ not used ³ 1.000E+00 ³ --- ³ FGWHH R019 ³ Livestock water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWLW R019 ³ Irrigation fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWIR

³ ³ ³ ³ ³ R19B ³ Wet weight crop yield for Non-Leafy (kg/m**2) ³ 1.750E+00 ³ 7.000E-01 ³ --- ³ YV(1)

R19B ³ Wet weight crop yield for Leafy (kg/m**2) ³ 2.889E+00 ³ 1.500E+00 ³ --- ³ YV(2)

R19B ³ Wet weight crop yield for Fodder (kg/m**2) ³ 1.887E+00 ³ 1.100E+00 ³ --- ³ YV(3)

R19B ³ Growing Season for Non-Leafy (years) ³ 2.460E-01 ³ 1.700E-01 ³ --- ³ TE(1)

R19B ³ Growing Season for Leafy (years) ³ 1.230E-01 ³ 2.500E-01 ³ --- ³ TE(2)

R19B ³ Growing Season for Fodder (years) ³ 8.200E-02 ³ 8.000E-02 ³ --- ³ TE(3)

R19B ³ Translocation Factor for Non-Leafy ³ 1.000E-01 ³ 1.000E-01 ³ --- ³ TIV(1)

R19B ³ Translocation Factor for Leafy ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(2)

R19B ³ Translocation Factor for Fodder ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(3)

R19B ³ Dry Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(1)

R19B ³ Dry Foliar Interception Fraction for Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(2)

R19B ³ Dry Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(3)

R19B ³ Wet Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(1)

R19B ³ Wet Foliar Interception Fraction for Leafy ³ 5.800E-01 ³ 2.500E-01 ³ --- ³ RWET(2)

R19B ³ Wet Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(3)

R19B ³ Weathering Removal Constant for Vegetation ³ 3.300E+01 ³ 2.000E+01 ³ --- ³ WLAM

³ ³ ³ ³ ³ C14 ³ C-12 concentration in water (g/cm**3) ³ not used ³ 2.000E-05 ³ --- ³ C12WTR C14 ³ C-12 concentration in contaminated soil (g/g) ³ not used ³ 3.000E-02 ³ --- ³ C12CZ C14 ³ Fraction of vegetation carbon from soil ³ not used ³ 2.000E-02 ³ --- ³ CSOIL C14 ³ Fraction of vegetation carbon from air ³ not used ³ 9.800E-01 ³ --- ³ CAIR C14 ³ C-14 evasion layer thickness in soil (m) ³ not used ³ 3.000E-01 ³ --- ³ DMC C14 ³ C-14 evasion flux rate from soil (1/sec) ³ not used ³ 7.000E-07 ³ --- ³ EVSN C14 ³ C-12 evasion flux rate from soil (1/sec) ³ not used ³ 1.000E-10 ³ --- ³ REVSN C14 ³ Fraction of grain in beef cattle feed ³ not used ³ 8.000E-01 ³ --- ³ AVFG4 C14 ³ Fraction of grain in milk cow feed ³ not used ³ 2.000E-01 ³ --- ³ AVFG5

C14 ³ DCF correction factor for gaseous forms of C14 ³ not used ³ 8.894E+01 ³ --- ³ CO2F

³ ³ ³ ³ ³ STOR ³ Storage times of contaminated foodstuffs (days): ³ ³ ³ ³ STOR ³ Fruits, non-leafy vegetables, and grain ³ 1.400E+01 ³ 1.400E+01 ³ --- ³ STOR_T(1)

STOR ³ Leafy vegetables ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(2)

STOR ³ Milk ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(3)

STOR ³ Meat and poultry ³ 2.000E+01 ³ 2.000E+01 ³ --- ³ STOR_T(4)

STOR ³ Fish ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(5)

STOR ³ Crustacea and mollusks ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(6)

STOR ³ Well water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(7)

STOR ³ Surface water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(8)

STOR ³ Livestock fodder ³ 4.500E+01 ³ 4.500E+01 ³ --- ³ STOR_T(9)

³ ³ ³ ³ ³ R021 ³ Thickness of building foundation (m) ³ not used ³ 1.500E-01 ³ --- ³ FLOOR1 R021 ³ Bulk density of building foundation (g/cm**3) ³ not used ³ 2.400E+00 ³ --- ³ DENSFL R021 ³ Total porosity of the cover material ³ not used ³ 4.000E-01 ³ --- ³ TPCV R021 ³ Total porosity of the building foundation ³ not used ³ 1.000E-01 ³ --- ³ TPFL R021 ³ Volumetric water content of the cover material ³ not used ³ 5.000E-02 ³ --- ³ PH2OCV 1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/01/2003 10:12 Page 7 Summary : Yankee Rowe Sensitivity Analysis=soil File: Pu-238_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R021 ³ Volumetric water content of the foundation ³ not used ³ 3.000E-02 ³ --- ³ PH2OFL R021 ³ Diffusion coefficient for radon gas (m/sec): ³ ³ ³ ³ R021 ³ in cover material ³ not used ³ 2.000E-06 ³ --- ³ DIFCV R021 ³ in foundation material ³ not used ³ 3.000E-07 ³ --- ³ DIFFL R021 ³ in contaminated zone soil ³ not used ³ 2.000E-06 ³ --- ³ DIFCZ R021 ³ Radon vertical dimension of mixing (m) ³ not used ³ 2.000E+00 ³ --- ³ HMIX R021 ³ Average building air exchange rate (1/hr) ³ not used ³ 5.000E-01 ³ --- ³ REXG R021 ³ Height of the building (room) (m) ³ not used ³ 2.500E+00 ³ --- ³ HRM R021 ³ Building interior area factor ³ not used ³ 0.000E+00 ³ --- ³ FAI R021 ³ Building depth below ground surface (m) ³ not used ³-1.000E+00 ³ --- ³ DMFL R021 ³ Emanating power of Rn-222 gas ³ not used ³ 2.500E-01 ³ --- ³ EMANA(1)

R021 ³ Emanating power of Rn-220 gas ³ not used ³ 1.500E-01 ³ --- ³ EMANA(2)

³ ³ ³ ³ ³ TITL ³ Number of graphical time points ³ 32 ³ --- ³ --- ³ NPTS TITL ³ Maximum number of integration points for dose ³ 17 ³ --- ³ --- ³ LYMAX TITL ³ Maximum number of integration points for risk ³ 1 ³ --- ³ --- ³ KYMAX

Summary of Pathway Selections Pathway ³ User Selection

Å 1 -- external gamma ³ active 2 -- inhalation (w/o radon)³ active 3 -- plant ingestion ³ active 4 -- meat ingestion ³ active 5 -- milk ingestion ³ active 6 -- aquatic foods ³ active 7 -- drinking water ³ active 8 -- soil ingestion ³ active 9 -- radon ³ suppressed Find peak pathway doses ³ active

1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/01/2003 10:51 Page 2 Summary : Yankee Rowe Sensitivity Analysis=soil File: Pu-239_DCGL.RAD Dose Conversion Factor (and Related) Parameter Summary File: YR soil DCGL lib 0 ³ ³ Current ³ ³ Parameter Menu ³ Parameter ³ Value ³ Default ³ Name

ÅÅÅÅ B-1 ³ Dose conversion factors for inhalation, mrem/pCi: ³ ³ ³ B-1 ³ Ac-227+D ³ 6.720E+00 ³ 6.720E+00 ³ DCF2( 1)

B-1 ³ Pa-231 ³ 1.280E+00 ³ 1.280E+00 ³ DCF2( 2)

B-1 ³ Pu-239 ³ 4.290E-01 ³ 4.290E-01 ³ DCF2( 3)

B-1 ³ U-235+D ³ 1.230E-01 ³ 1.230E-01 ³ DCF2( 4)

³ ³ ³ ³ D-1 ³ Dose conversion factors for ingestion, mrem/pCi: ³ ³ ³ D-1 ³ Ac-227+D ³ 1.480E-02 ³ 1.480E-02 ³ DCF3( 1)

D-1 ³ Pa-231 ³ 1.060E-02 ³ 1.060E-02 ³ DCF3( 2)

D-1 ³ Pu-239 ³ 3.540E-03 ³ 3.540E-03 ³ DCF3( 3)

D-1 ³ U-235+D ³ 2.670E-04 ³ 2.670E-04 ³ DCF3( 4)

³ ³ ³ ³ D-34 ³ Food transfer factors: ³ ³ ³ D-34 ³ Ac-227+D, plant/soil concentration ratio, dimensionless ³ 2.500E-03 ³ 2.500E-03 ³ RTF( 1,1)

D-34 ³ Ac-227+D, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 2.000E-05 ³ 2.000E-05 ³ RTF( 1,2)

D-34 ³ Ac-227+D, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 2.000E-05 ³ 2.000E-05 ³ RTF( 1,3)

D-34 ³ ³ ³ ³ D-34 ³ Pa-231, plant/soil concentration ratio, dimensionless ³ 1.000E-02 ³ 1.000E-02 ³ RTF( 2,1)

D-34 ³ Pa-231, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 5.000E-03 ³ 5.000E-03 ³ RTF( 2,2)

D-34 ³ Pa-231, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 5.000E-06 ³ 5.000E-06 ³ RTF( 2,3)

D-34 ³ ³ ³ ³ D-34 ³ Pu-239, plant/soil concentration ratio, dimensionless ³ 1.830E-03 ³ 1.000E-03 ³ RTF( 3,1)

D-34 ³ Pu-239, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 1.000E-04 ³ 1.000E-04 ³ RTF( 3,2)

D-34 ³ Pu-239, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 1.000E-06 ³ 1.000E-06 ³ RTF( 3,3)

D-34 ³ ³ ³ ³ D-34 ³ U-235+D, plant/soil concentration ratio, dimensionless ³ 2.500E-03 ³ 2.500E-03 ³ RTF( 4,1)

D-34 ³ U-235+D, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 3.400E-04 ³ 3.400E-04 ³ RTF( 4,2)

D-34 ³ U-235+D, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 6.000E-04 ³ 6.000E-04 ³ RTF( 4,3)

³ ³ ³ ³ D-5 ³ Bioaccumulation factors, fresh water, L/kg: ³ ³ ³ D-5 ³ Ac-227+D, fish ³ 1.500E+01 ³ 1.500E+01 ³ BIOFAC( 1,1)

D-5 ³ Ac-227+D, crustacea and mollusks ³ 1.000E+03 ³ 1.000E+03 ³ BIOFAC( 1,2)

D-5 ³ ³ ³ ³ D-5 ³ Pa-231, fish ³ 1.000E+01 ³ 1.000E+01 ³ BIOFAC( 2,1)

D-5 ³ Pa-231, crustacea and mollusks ³ 1.100E+02 ³ 1.100E+02 ³ BIOFAC( 2,2)

D-5 ³ ³ ³ ³ D-5 ³ Pu-239, fish ³ 3.000E+01 ³ 3.000E+01 ³ BIOFAC( 3,1)

D-5 ³ Pu-239, crustacea and mollusks ³ 1.000E+02 ³ 1.000E+02 ³ BIOFAC( 3,2)

D-5 ³ ³ ³ ³ D-5 ³ U-235+D, fish ³ 1.000E+01 ³ 1.000E+01 ³ BIOFAC( 4,1)

D-5 ³ U-235+D, crustacea and mollusks ³ 6.000E+01 ³ 6.000E+01 ³ BIOFAC( 4,2) 1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/01/2003 10:51 Page 3 Summary : Yankee Rowe Sensitivity Analysis=soil File: Pu-239_DCGL.RAD Site-Specific Parameter Summary 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R011 ³ Area of contaminated zone (m**2) ³ 1.302E+04 ³ 1.000E+04 ³ --- ³ AREA R011 ³ Thickness of contaminated zone (m) ³ 1.975E+00 ³ 2.000E+00 ³ --- ³ THICK0 R011 ³ Length parallel to aquifer flow (m) ³ 1.290E+02 ³ 1.000E+02 ³ --- ³ LCZPAQ R011 ³ Basic radiation dose limit (mrem/yr) ³ 2.500E+01 ³ 2.500E+01 ³ --- ³ BRDL R011 ³ Time since placement of material (yr) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ TI R011 ³ Times for calculations (yr) ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ T( 2)

R011 ³ Times for calculations (yr) ³ 3.000E+00 ³ 3.000E+00 ³ --- ³ T( 3)

R011 ³ Times for calculations (yr) ³ 1.000E+01 ³ 1.000E+01 ³ --- ³ T( 4)

R011 ³ Times for calculations (yr) ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ T( 5)

R011 ³ Times for calculations (yr) ³ 1.000E+02 ³ 1.000E+02 ³ --- ³ T( 6)

R011 ³ Times for calculations (yr) ³ 3.000E+02 ³ 3.000E+02 ³ --- ³ T( 7)

R011 ³ Times for calculations (yr) ³ 1.000E+03 ³ 1.000E+03 ³ --- ³ T( 8)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T( 9)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T(10)

³ ³ ³ ³ ³ R012 ³ Initial principal radionuclide (pCi/g): Pu-239 ³ 1.000E+00 ³ 0.000E+00 ³ --- ³ S1( 3)

R012 ³ Concentration in groundwater (pCi/L): Pu-239 ³ not used ³ 0.000E+00 ³ --- ³ W1( 3)

³ ³ ³ ³ ³ R013 ³ Cover depth (m) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ COVER0 R013 ³ Density of cover material (g/cm**3) ³ not used ³ 1.500E+00 ³ --- ³ DENSCV R013 ³ Cover depth erosion rate (m/yr) ³ not used ³ 1.000E-03 ³ --- ³ VCV R013 ³ Density of contaminated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSCZ R013 ³ Contaminated zone erosion rate (m/yr) ³ 8.500E-04 ³ 1.000E-03 ³ --- ³ VCZ R013 ³ Contaminated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPCZ R013 ³ Contaminated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCCZ R013 ³ Contaminated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCCZ R013 ³ Contaminated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BCZ R013 ³ Average annual wind speed (m/sec) ³ 2.030E+00 ³ 2.000E+00 ³ --- ³ WIND R013 ³ Humidity in air (g/m**3) ³ not used ³ 8.000E+00 ³ --- ³ HUMID R013 ³ Evapotranspiration coefficient ³ 6.250E-01 ³ 5.000E-01 ³ --- ³ EVAPTR R013 ³ Precipitation (m/yr) ³ 1.200E+00 ³ 1.000E+00 ³ --- ³ PRECIP R013 ³ Irrigation (m/yr) ³ 4.350E-01 ³ 2.000E-01 ³ --- ³ RI R013 ³ Irrigation mode ³ overhead ³ overhead ³ --- ³ IDITCH R013 ³ Runoff coefficient ³ 6.000E-01 ³ 2.000E-01 ³ --- ³ RUNOFF R013 ³ Watershed area for nearby stream or pond (m**2) ³ 7.770E+05 ³ 1.000E+06 ³ --- ³ WAREA R013 ³ Accuracy for water/soil computations ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ EPS

³ ³ ³ ³ ³ R014 ³ Density of saturated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSAQ

R014 ³ Saturated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPSZ R014 ³ Saturated zone effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPSZ R014 ³ Saturated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCSZ R014 ³ Saturated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+02 ³ --- ³ HCSZ R014 ³ Saturated zone hydraulic gradient ³ 1.000E-01 ³ 2.000E-02 ³ --- ³ HGWT R014 ³ Saturated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BSZ R014 ³ Water table drop rate (m/yr) ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ VWT R014 ³ Well pump intake depth (m below water table) ³ 1.451E+01 ³ 1.000E+01 ³ --- ³ DWIBWT R014 ³ Model: Nondispersion (ND) or Mass-Balance (MB) ³ ND ³ ND ³ --- ³ MODEL R014 ³ Well pumping rate (m**3/yr) ³ 1.323E+03 ³ 2.500E+02 ³ --- ³ UW

³ ³ ³ ³ ³ R015 ³ Number of unsaturated zone strata ³ 1 ³ 1 ³ --- ³ NS 1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/01/2003 10:51 Page 4 Summary : Yankee Rowe Sensitivity Analysis=soil File: Pu-239_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R015 ³ Unsat. zone 1, thickness (m) ³ 1.820E+00 ³ 4.000E+00 ³ --- ³ H(1)

R015 ³ Unsat. zone 1, soil density (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSUZ(1)

R015 ³ Unsat. zone 1, total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPUZ(1)

R015 ³ Unsat. zone 1, effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPUZ(1)

R015 ³ Unsat. zone 1, field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCUZ(1)

R015 ³ Unsat. zone 1, soil-specific b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BUZ(1)

R015 ³ Unsat. zone 1, hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCUZ(1)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for Pu-239 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 9.530E+02 ³ 2.000E+03 ³ --- ³ DCNUCC( 3)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 9.530E+02 ³ 2.000E+03 ³ --- ³ DCNUCU( 3,1)

R016 ³ Saturated zone (cm**3/g) ³ 9.530E+02 ³ 2.000E+03 ³ --- ³ DCNUCS( 3)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 1.207E-04 ³ ALEACH( 3)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 3)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for daughter Ac-227 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 8.250E+02 ³ 2.000E+01 ³ --- ³ DCNUCC( 1)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 8.250E+02 ³ 2.000E+01 ³ --- ³ DCNUCU( 1,1)

R016 ³ Saturated zone (cm**3/g) ³ 8.250E+02 ³ 2.000E+01 ³ --- ³ DCNUCS( 1)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 1.394E-04 ³ ALEACH( 1)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 1)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for daughter Pa-231 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 3.800E+02 ³ 5.000E+01 ³ --- ³ DCNUCC( 2)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 3.800E+02 ³ 5.000E+01 ³ --- ³ DCNUCU( 2,1)

R016 ³ Saturated zone (cm**3/g) ³ 3.800E+02 ³ 5.000E+01 ³ --- ³ DCNUCS( 2)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 3.026E-04 ³ ALEACH( 2)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 2)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for daughter U-235 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 1.260E+02 ³ 5.000E+01 ³ --- ³ DCNUCC( 4)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 1.260E+02 ³ 5.000E+01 ³ --- ³ DCNUCU( 4,1)

R016 ³ Saturated zone (cm**3/g) ³ 1.260E+02 ³ 5.000E+01 ³ --- ³ DCNUCS( 4)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 9.125E-04 ³ ALEACH( 4)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 4)

³ ³ ³ ³ ³ R017 ³ Inhalation rate (m**3/yr) ³ 8.400E+03 ³ 8.400E+03 ³ --- ³ INHALR R017 ³ Mass loading for inhalation (g/m**3) ³ 2.330E-05 ³ 1.000E-04 ³ --- ³ MLINH R017 ³ Exposure duration ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ ED R017 ³ Shielding factor, inhalation ³ 5.500E-01 ³ 4.000E-01 ³ --- ³ SHF3 R017 ³ Shielding factor, external gamma ³ 2.725E-01 ³ 7.000E-01 ³ --- ³ SHF1 R017 ³ Fraction of time spent indoors ³ 6.571E-01 ³ 5.000E-01 ³ --- ³ FIND R017 ³ Fraction of time spent outdoors (on site) ³ 1.181E-01 ³ 2.500E-01 ³ --- ³ FOTD R017 ³ Shape factor flag, external gamma ³ 1.000E+00 ³ 1.000E+00 ³ >0 shows circular AREA. ³ FS 1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/01/2003 10:51 Page 5 Summary : Yankee Rowe Sensitivity Analysis=soil File: Pu-239_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R017 ³ Radii of shape factor array (used if FS = -1): ³ ³ ³ ³ R017 ³ Outer annular radius (m), ring 1: ³ not used ³ 5.000E+01 ³ --- ³ RAD_SHAPE(

1)

R017 ³ Outer annular radius (m), ring 2: ³ not used ³ 7.071E+01 ³ --- ³ RAD_SHAPE(

2)

R017 ³ Outer annular radius (m), ring 3: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

3)

R017 ³ Outer annular radius (m), ring 4: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

4)

R017 ³ Outer annular radius (m), ring 5: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

5)

R017 ³ Outer annular radius (m), ring 6: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

6)

R017 ³ Outer annular radius (m), ring 7: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

7)

R017 ³ Outer annular radius (m), ring 8: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

8)

R017 ³ Outer annular radius (m), ring 9: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

9)

R017 ³ Outer annular radius (m), ring 10: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (10)

R017 ³ Outer annular radius (m), ring 11: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (11)

R017 ³ Outer annular radius (m), ring 12: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE

(12)

³ ³ ³ ³ ³ R017 ³ Fractions of annular areas within AREA: ³ ³ ³ ³ R017 ³ Ring 1 ³ not used ³ 1.000E+00 ³ --- ³ FRACA( 1)

R017 ³ Ring 2 ³ not used ³ 2.732E-01 ³ --- ³ FRACA( 2)

R017 ³ Ring 3 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 3)

R017 ³ Ring 4 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 4)

R017 ³ Ring 5 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 5)

R017 ³ Ring 6 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 6)

R017 ³ Ring 7 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 7)

R017 ³ Ring 8 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 8)

R017 ³ Ring 9 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 9)

R017 ³ Ring 10 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(10)

R017 ³ Ring 11 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(11)

R017 ³ Ring 12 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(12)

³ ³ ³ ³ ³ R018 ³ Fruits, vegetables and grain consumption (kg/yr) ³ 1.120E+02 ³ 1.600E+02 ³ --- ³ DIET(1)

R018 ³ Leafy vegetable consumption (kg/yr) ³ 2.140E+01 ³ 1.400E+01 ³ --- ³ DIET(2)

R018 ³ Milk consumption (L/yr) ³ 2.330E+02 ³ 9.200E+01 ³ --- ³ DIET(3)

R018 ³ Meat and poultry consumption (kg/yr) ³ 6.510E+01 ³ 6.300E+01 ³ --- ³ DIET(4)

R018 ³ Fish consumption (kg/yr) ³ 2.060E+01 ³ 5.400E+00 ³ --- ³ DIET(5)

R018 ³ Other seafood consumption (kg/yr) ³ 9.000E-01 ³ 9.000E-01 ³ --- ³ DIET(6)

R018 ³ Soil ingestion rate (g/yr) ³ 1.826E+01 ³ 3.650E+01 ³ --- ³ SOIL R018 ³ Drinking water intake (L/yr) ³ 4.785E+02 ³ 5.100E+02 ³ --- ³ DWI R018 ³ Contamination fraction of drinking water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FDW R018 ³ Contamination fraction of household water ³ not used ³ 1.000E+00 ³ --- ³ FHHW R018 ³ Contamination fraction of livestock water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FLW R018 ³ Contamination fraction of irrigation water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FIRW R018 ³ Contamination fraction of aquatic food ³ 1.000E+00 ³ 5.000E-01 ³ --- ³ FR9 R018 ³ Contamination fraction of plant food ³ 1.000E+00 ³-1 ³ --- ³ FPLANT R018 ³ Contamination fraction of meat ³ 1.000E+00 ³-1 ³ --- ³ FMEAT R018 ³ Contamination fraction of milk ³ 1.000E+00 ³-1 ³ --- ³ FMILK

³ ³ ³ ³ ³ R019 ³ Livestock fodder intake for meat (kg/day) ³ 2.710E+01 ³ 6.800E+01 ³ --- ³ LFI5 R019 ³ Livestock fodder intake for milk (kg/day) ³ 6.320E+01 ³ 5.500E+01 ³ --- ³ LFI6 R019 ³ Livestock water intake for meat (L/day) ³ 5.060E+01 ³ 5.000E+01 ³ --- ³ LWI5 R019 ³ Livestock water intake for milk (L/day) ³ 6.000E+01 ³ 1.600E+02 ³ --- ³ LWI6 R019 ³ Livestock soil intake (kg/day) ³ 5.000E-01 ³ 5.000E-01 ³ --- ³ LSI R019 ³ Mass loading for foliar deposition (g/m**3) ³ 4.000E-04 ³ 1.000E-04 ³ --- ³ MLFD 1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/01/2003 10:51 Page 6 Summary : Yankee Rowe Sensitivity Analysis=soil File: Pu-239_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R019 ³ Depth of soil mixing layer (m) ³ 2.300E-01 ³ 1.500E-01 ³ --- ³ DM R019 ³ Depth of roots (m) ³ 1.170E+00 ³ 9.000E-01 ³ --- ³ DROOT R019 ³ Drinking water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWDW R019 ³ Household water fraction from ground water ³ not used ³ 1.000E+00 ³ --- ³ FGWHH R019 ³ Livestock water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWLW R019 ³ Irrigation fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWIR

³ ³ ³ ³ ³ R19B ³ Wet weight crop yield for Non-Leafy (kg/m**2) ³ 1.750E+00 ³ 7.000E-01 ³ --- ³ YV(1)

R19B ³ Wet weight crop yield for Leafy (kg/m**2) ³ 2.889E+00 ³ 1.500E+00 ³ --- ³ YV(2)

R19B ³ Wet weight crop yield for Fodder (kg/m**2) ³ 1.887E+00 ³ 1.100E+00 ³ --- ³ YV(3)

R19B ³ Growing Season for Non-Leafy (years) ³ 2.460E-01 ³ 1.700E-01 ³ --- ³ TE(1)

R19B ³ Growing Season for Leafy (years) ³ 1.230E-01 ³ 2.500E-01 ³ --- ³ TE(2)

R19B ³ Growing Season for Fodder (years) ³ 8.200E-02 ³ 8.000E-02 ³ --- ³ TE(3)

R19B ³ Translocation Factor for Non-Leafy ³ 1.000E-01 ³ 1.000E-01 ³ --- ³ TIV(1)

R19B ³ Translocation Factor for Leafy ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(2)

R19B ³ Translocation Factor for Fodder ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(3)

R19B ³ Dry Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(1)

R19B ³ Dry Foliar Interception Fraction for Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(2)

R19B ³ Dry Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(3)

R19B ³ Wet Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(1)

R19B ³ Wet Foliar Interception Fraction for Leafy ³ 5.800E-01 ³ 2.500E-01 ³ --- ³ RWET(2)

R19B ³ Wet Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(3)

R19B ³ Weathering Removal Constant for Vegetation ³ 3.300E+01 ³ 2.000E+01 ³ --- ³ WLAM

³ ³ ³ ³ ³ C14 ³ C-12 concentration in water (g/cm**3) ³ not used ³ 2.000E-05 ³ --- ³ C12WTR C14 ³ C-12 concentration in contaminated soil (g/g) ³ not used ³ 3.000E-02 ³ --- ³ C12CZ C14 ³ Fraction of vegetation carbon from soil ³ not used ³ 2.000E-02 ³ --- ³ CSOIL C14 ³ Fraction of vegetation carbon from air ³ not used ³ 9.800E-01 ³ --- ³ CAIR C14 ³ C-14 evasion layer thickness in soil (m) ³ not used ³ 3.000E-01 ³ --- ³ DMC C14 ³ C-14 evasion flux rate from soil (1/sec) ³ not used ³ 7.000E-07 ³ --- ³ EVSN C14 ³ C-12 evasion flux rate from soil (1/sec) ³ not used ³ 1.000E-10 ³ --- ³ REVSN C14 ³ Fraction of grain in beef cattle feed ³ not used ³ 8.000E-01 ³ --- ³ AVFG4 C14 ³ Fraction of grain in milk cow feed ³ not used ³ 2.000E-01 ³ --- ³ AVFG5 C14 ³ DCF correction factor for gaseous forms of C14 ³ not used ³ 8.894E+01 ³ --- ³ CO2F

³ ³ ³ ³ ³ STOR ³ Storage times of contaminated foodstuffs (days): ³ ³ ³ ³ STOR ³ Fruits, non-leafy vegetables, and grain ³ 1.400E+01 ³ 1.400E+01 ³ --- ³ STOR_T(1)

STOR ³ Leafy vegetables ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(2)

STOR ³ Milk ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(3)

STOR ³ Meat and poultry ³ 2.000E+01 ³ 2.000E+01 ³ --- ³ STOR_T(4)

STOR ³ Fish ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(5)

STOR ³ Crustacea and mollusks ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(6)

STOR ³ Well water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(7)

STOR ³ Surface water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(8)

STOR ³ Livestock fodder ³ 4.500E+01 ³ 4.500E+01 ³ --- ³ STOR_T(9)

³ ³ ³ ³ ³ R021 ³ Thickness of building foundation (m) ³ not used ³ 1.500E-01 ³ --- ³ FLOOR1 R021 ³ Bulk density of building foundation (g/cm**3) ³ not used ³ 2.400E+00 ³ --- ³ DENSFL R021 ³ Total porosity of the cover material ³ not used ³ 4.000E-01 ³ --- ³ TPCV

R021 ³ Total porosity of the building foundation ³ not used ³ 1.000E-01 ³ --- ³ TPFL R021 ³ Volumetric water content of the cover material ³ not used ³ 5.000E-02 ³ --- ³ PH2OCV 1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/01/2003 10:51 Page 7 Summary : Yankee Rowe Sensitivity Analysis=soil File: Pu-239_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R021 ³ Volumetric water content of the foundation ³ not used ³ 3.000E-02 ³ --- ³ PH2OFL R021 ³ Diffusion coefficient for radon gas (m/sec): ³ ³ ³ ³ R021 ³ in cover material ³ not used ³ 2.000E-06 ³ --- ³ DIFCV R021 ³ in foundation material ³ not used ³ 3.000E-07 ³ --- ³ DIFFL R021 ³ in contaminated zone soil ³ not used ³ 2.000E-06 ³ --- ³ DIFCZ R021 ³ Radon vertical dimension of mixing (m) ³ not used ³ 2.000E+00 ³ --- ³ HMIX R021 ³ Average building air exchange rate (1/hr) ³ not used ³ 5.000E-01 ³ --- ³ REXG R021 ³ Height of the building (room) (m) ³ not used ³ 2.500E+00 ³ --- ³ HRM R021 ³ Building interior area factor ³ not used ³ 0.000E+00 ³ --- ³ FAI R021 ³ Building depth below ground surface (m) ³ not used ³-1.000E+00 ³ --- ³ DMFL R021 ³ Emanating power of Rn-222 gas ³ not used ³ 2.500E-01 ³ --- ³ EMANA(1)

R021 ³ Emanating power of Rn-220 gas ³ not used ³ 1.500E-01 ³ --- ³ EMANA(2)

³ ³ ³ ³ ³ TITL ³ Number of graphical time points ³ 32 ³ --- ³ --- ³ NPTS TITL ³ Maximum number of integration points for dose ³ 17 ³ --- ³ --- ³ LYMAX TITL ³ Maximum number of integration points for risk ³ 1 ³ --- ³ --- ³ KYMAX

Summary of Pathway Selections Pathway ³ User Selection

Å 1 -- external gamma ³ active 2 -- inhalation (w/o radon)³ active 3 -- plant ingestion ³ active 4 -- meat ingestion ³ active 5 -- milk ingestion ³ active 6 -- aquatic foods ³ active 7 -- drinking water ³ active 8 -- soil ingestion ³ active 9 -- radon ³ suppressed Find peak pathway doses ³ active

1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/01/2003 11:46 Page 2 Summary : Yankee Rowe Sensitivity Analysis=soil File: Pu-241_DCGL.RAD Dose Conversion Factor (and Related) Parameter Summary File: YR soil DCGL Pu241 lib 0 ³ ³ Current ³ ³ Parameter Menu ³ Parameter ³ Value ³ Default ³ Name

ÅÅÅÅ B-1 ³ Dose conversion factors for inhalation, mrem/pCi: ³ ³ ³ B-1 ³ Am-241 ³ 4.440E-01 ³ 4.440E-01 ³ DCF2( 1)

B-1 ³ Np-237+D ³ 5.400E-01 ³ 5.400E-01 ³ DCF2( 2)

B-1 ³ Pu-241+D ³ 8.250E-03 ³ 8.250E-03 ³ DCF2( 3)

B-1 ³ Th-229+D ³ 2.160E+00 ³ 2.160E+00 ³ DCF2( 5)

B-1 ³ U-233 ³ 1.350E-01 ³ 1.350E-01 ³ DCF2( 6)

³ ³ ³ ³ D-1 ³ Dose conversion factors for ingestion, mrem/pCi: ³ ³ ³ D-1 ³ Am-241 ³ 3.640E-03 ³ 3.640E-03 ³ DCF3( 1)

D-1 ³ Np-237+D ³ 4.440E-03 ³ 4.440E-03 ³ DCF3( 2)

D-1 ³ Pu-241+D ³ 6.850E-05 ³ 6.850E-05 ³ DCF3( 3)

D-1 ³ Th-229+D ³ 4.030E-03 ³ 4.030E-03 ³ DCF3( 5)

D-1 ³ U-233 ³ 2.890E-04 ³ 2.890E-04 ³ DCF3( 6)

³ ³ ³ ³ D-34 ³ Food transfer factors: ³ ³ ³ D-34 ³ Am-241, plant/soil concentration ratio, dimensionless ³ 1.830E-03 ³ 1.000E-03 ³ RTF( 1,1)

D-34 ³ Am-241, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 5.000E-05 ³ 5.000E-05 ³ RTF( 1,2)

D-34 ³ Am-241, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 2.000E-06 ³ 2.000E-06 ³ RTF( 1,3)

D-34 ³ ³ ³ ³ D-34 ³ Np-237+D, plant/soil concentration ratio, dimensionless ³ 2.000E-02 ³ 2.000E-02 ³ RTF( 2,1)

D-34 ³ Np-237+D, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 1.000E-03 ³ 1.000E-03 ³ RTF( 2,2)

D-34 ³ Np-237+D, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 5.000E-06 ³ 5.000E-06 ³ RTF( 2,3)

D-34 ³ ³ ³ ³ D-34 ³ Pu-241+D, plant/soil concentration ratio, dimensionless ³ 1.000E-03 ³ 1.000E-03 ³ RTF( 3,1)

D-34 ³ Pu-241+D, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 1.000E-04 ³ 1.000E-04 ³ RTF( 3,2)

D-34 ³ Pu-241+D, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 1.000E-06 ³ 1.000E-06 ³ RTF( 3,3)

D-34 ³ ³ ³ ³ D-34 ³ Th-229+D, plant/soil concentration ratio, dimensionless ³ 1.000E-03 ³ 1.000E-03 ³ RTF( 5,1)

D-34 ³ Th-229+D, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 1.000E-04 ³ 1.000E-04 ³ RTF( 5,2)

D-34 ³ Th-229+D, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 5.000E-06 ³ 5.000E-06 ³ RTF( 5,3)

D-34 ³ ³ ³ ³ D-34 ³ U-233, plant/soil concentration ratio, dimensionless ³ 2.500E-03 ³ 2.500E-03 ³ RTF( 6,1)

D-34 ³ U-233, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 3.400E-04 ³ 3.400E-04 ³ RTF( 6,2)

D-34 ³ U-233, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 6.000E-04 ³ 6.000E-04 ³ RTF( 6,3)

³ ³ ³ ³ D-5 ³ Bioaccumulation factors, fresh water, L/kg: ³ ³ ³ D-5 ³ Am-241, fish ³ 3.000E+01 ³ 3.000E+01 ³ BIOFAC( 1,1)

D-5 ³ Am-241, crustacea and mollusks ³ 1.000E+03 ³ 1.000E+03 ³ BIOFAC( 1,2)

D-5 ³ ³ ³ ³ D-5 ³ Np-237+D, fish ³ 3.000E+01 ³ 3.000E+01 ³ BIOFAC( 2,1)

D-5 ³ Np-237+D, crustacea and mollusks ³ 4.000E+02 ³ 4.000E+02 ³ BIOFAC( 2,2)

D-5 ³ ³ ³ ³ D-5 ³ Pu-241+D, fish ³ 3.000E+01 ³ 3.000E+01 ³ BIOFAC( 3,1)

D-5 ³ Pu-241+D, crustacea and mollusks ³ 1.000E+02 ³ 1.000E+02 ³ BIOFAC( 3,2)

D-5 ³ ³ ³ ³ D-5 ³ Th-229+D, fish ³ 1.000E+02 ³ 1.000E+02 ³ BIOFAC( 5,1)

D-5 ³ Th-229+D, crustacea and mollusks ³ 5.000E+02 ³ 5.000E+02 ³ BIOFAC( 5,2)

D-5 ³ ³ ³ ³ D-5 ³ U-233, fish ³ 1.000E+01 ³ 1.000E+01 ³ BIOFAC( 6,1)

D-5 ³ U-233, crustacea and mollusks ³ 6.000E+01 ³ 6.000E+01 ³ BIOFAC( 6,2) 1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/01/2003 11:46 Page 3 Summary : Yankee Rowe Sensitivity Analysis=soil File: Pu-241_DCGL.RAD Site-Specific Parameter Summary 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R011 ³ Area of contaminated zone (m**2) ³ 1.302E+04 ³ 1.000E+04 ³ --- ³ AREA R011 ³ Thickness of contaminated zone (m) ³ 1.975E+00 ³ 2.000E+00 ³ --- ³ THICK0 R011 ³ Length parallel to aquifer flow (m) ³ 1.290E+02 ³ 1.000E+02 ³ --- ³ LCZPAQ R011 ³ Basic radiation dose limit (mrem/yr) ³ 2.500E+01 ³ 2.500E+01 ³ --- ³ BRDL R011 ³ Time since placement of material (yr) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ TI R011 ³ Times for calculations (yr) ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ T( 2)

R011 ³ Times for calculations (yr) ³ 3.000E+00 ³ 3.000E+00 ³ --- ³ T( 3)

R011 ³ Times for calculations (yr) ³ 1.000E+01 ³ 1.000E+01 ³ --- ³ T( 4)

R011 ³ Times for calculations (yr) ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ T( 5)

R011 ³ Times for calculations (yr) ³ 1.000E+02 ³ 1.000E+02 ³ --- ³ T( 6)

R011 ³ Times for calculations (yr) ³ 3.000E+02 ³ 3.000E+02 ³ --- ³ T( 7)

R011 ³ Times for calculations (yr) ³ 1.000E+03 ³ 1.000E+03 ³ --- ³ T( 8)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T( 9)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T(10)

³ ³ ³ ³ ³ R012 ³ Initial principal radionuclide (pCi/g): Pu-241 ³ 1.000E+00 ³ 0.000E+00 ³ --- ³ S1( 3)

R012 ³ Concentration in groundwater (pCi/L): Pu-241 ³ not used ³ 0.000E+00 ³ --- ³ W1( 3)

³ ³ ³ ³ ³ R013 ³ Cover depth (m) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ COVER0 R013 ³ Density of cover material (g/cm**3) ³ not used ³ 1.500E+00 ³ --- ³ DENSCV R013 ³ Cover depth erosion rate (m/yr) ³ not used ³ 1.000E-03 ³ --- ³ VCV R013 ³ Density of contaminated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSCZ R013 ³ Contaminated zone erosion rate (m/yr) ³ 8.500E-04 ³ 1.000E-03 ³ --- ³ VCZ R013 ³ Contaminated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPCZ R013 ³ Contaminated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCCZ R013 ³ Contaminated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCCZ R013 ³ Contaminated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BCZ R013 ³ Average annual wind speed (m/sec) ³ 2.030E+00 ³ 2.000E+00 ³ --- ³ WIND R013 ³ Humidity in air (g/m**3) ³ not used ³ 8.000E+00 ³ --- ³ HUMID

R013 ³ Evapotranspiration coefficient ³ 6.250E-01 ³ 5.000E-01 ³ --- ³ EVAPTR R013 ³ Precipitation (m/yr) ³ 1.200E+00 ³ 1.000E+00 ³ --- ³ PRECIP R013 ³ Irrigation (m/yr) ³ 4.350E-01 ³ 2.000E-01 ³ --- ³ RI R013 ³ Irrigation mode ³ overhead ³ overhead ³ --- ³ IDITCH R013 ³ Runoff coefficient ³ 6.000E-01 ³ 2.000E-01 ³ --- ³ RUNOFF R013 ³ Watershed area for nearby stream or pond (m**2) ³ 7.770E+05 ³ 1.000E+06 ³ --- ³ WAREA R013 ³ Accuracy for water/soil computations ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ EPS

³ ³ ³ ³ ³ R014 ³ Density of saturated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSAQ R014 ³ Saturated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPSZ R014 ³ Saturated zone effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPSZ R014 ³ Saturated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCSZ R014 ³ Saturated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+02 ³ --- ³ HCSZ R014 ³ Saturated zone hydraulic gradient ³ 1.000E-01 ³ 2.000E-02 ³ --- ³ HGWT R014 ³ Saturated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BSZ R014 ³ Water table drop rate (m/yr) ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ VWT R014 ³ Well pump intake depth (m below water table) ³ 1.451E+01 ³ 1.000E+01 ³ --- ³ DWIBWT R014 ³ Model: Nondispersion (ND) or Mass-Balance (MB) ³ ND ³ ND ³ --- ³ MODEL R014 ³ Well pumping rate (m**3/yr) ³ 1.323E+03 ³ 2.500E+02 ³ --- ³ UW

³ ³ ³ ³ ³ R015 ³ Number of unsaturated zone strata ³ 1 ³ 1 ³ --- ³ NS 1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/01/2003 11:46 Page 4 Summary : Yankee Rowe Sensitivity Analysis=soil File: Pu-241_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R015 ³ Unsat. zone 1, thickness (m) ³ 1.820E+00 ³ 4.000E+00 ³ --- ³ H(1)

R015 ³ Unsat. zone 1, soil density (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSUZ(1)

R015 ³ Unsat. zone 1, total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPUZ(1)

R015 ³ Unsat. zone 1, effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPUZ(1)

R015 ³ Unsat. zone 1, field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCUZ(1)

R015 ³ Unsat. zone 1, soil-specific b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BUZ(1)

R015 ³ Unsat. zone 1, hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCUZ(1)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for Pu-241 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 9.530E+02 ³ 2.000E+03 ³ --- ³ DCNUCC( 3)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 9.530E+02 ³ 2.000E+03 ³ --- ³ DCNUCU( 3,1)

R016 ³ Saturated zone (cm**3/g) ³ 9.530E+02 ³ 2.000E+03 ³ --- ³ DCNUCS( 3)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 1.207E-04 ³ ALEACH( 3)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 3)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for daughter Am-241 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 1.200E+04 ³ 2.000E+01 ³ --- ³ DCNUCC( 1)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 1.445E+03 ³ 2.000E+01 ³ --- ³ DCNUCU( 1,1)

R016 ³ Saturated zone (cm**3/g) ³ 1.445E+03 ³ 2.000E+01 ³ --- ³ DCNUCS( 1)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 9.585E-06 ³ ALEACH( 1)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 1)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for daughter Np-237 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 1.700E+01 ³-1.000E+00 ³ --- ³ DCNUCC( 2)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 1.700E+01 ³-1.000E+00 ³ --- ³ DCNUCU( 2,1)

R016 ³ Saturated zone (cm**3/g) ³ 1.700E+01 ³-1.000E+00 ³ --- ³ DCNUCS( 2)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 6.747E-03 ³ ALEACH( 2)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 2)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for daughter Th-229 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 5.884E+03 ³ 6.000E+04 ³ --- ³ DCNUCC( 5)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 5.884E+03 ³ 6.000E+04 ³ --- ³ DCNUCU( 5,1)

R016 ³ Saturated zone (cm**3/g) ³ 5.884E+03 ³ 6.000E+04 ³ --- ³ DCNUCS( 5)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 1.955E-05 ³ ALEACH( 5)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 5)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for daughter U-233 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 1.260E+02 ³ 5.000E+01 ³ --- ³ DCNUCC( 6)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 1.260E+02 ³ 5.000E+01 ³ --- ³ DCNUCU( 6,1)

R016 ³ Saturated zone (cm**3/g) ³ 1.260E+02 ³ 5.000E+01 ³ --- ³ DCNUCS( 6)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 9.125E-04 ³ ALEACH( 6)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 6)

³ ³ ³ ³ ³ R017 ³ Inhalation rate (m**3/yr) ³ 8.400E+03 ³ 8.400E+03 ³ --- ³ INHALR R017 ³ Mass loading for inhalation (g/m**3) ³ 2.330E-05 ³ 1.000E-04 ³ --- ³ MLINH R017 ³ Exposure duration ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ ED R017 ³ Shielding factor, inhalation ³ 5.500E-01 ³ 4.000E-01 ³ --- ³ SHF3 R017 ³ Shielding factor, external gamma ³ 2.725E-01 ³ 7.000E-01 ³ --- ³ SHF1 R017 ³ Fraction of time spent indoors ³ 6.571E-01 ³ 5.000E-01 ³ --- ³ FIND R017 ³ Fraction of time spent outdoors (on site) ³ 1.181E-01 ³ 2.500E-01 ³ --- ³ FOTD R017 ³ Shape factor flag, external gamma ³ 1.000E+00 ³ 1.000E+00 ³ >0 shows circular AREA. ³ FS 1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/01/2003 11:46 Page 5 Summary : Yankee Rowe Sensitivity Analysis=soil File: Pu-241_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R017 ³ Radii of shape factor array (used if FS = -1): ³ ³ ³ ³ R017 ³ Outer annular radius (m), ring 1: ³ not used ³ 5.000E+01 ³ --- ³ RAD_SHAPE(

1)

R017 ³ Outer annular radius (m), ring 2: ³ not used ³ 7.071E+01 ³ --- ³ RAD_SHAPE(

2)

R017 ³ Outer annular radius (m), ring 3: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

3)

R017 ³ Outer annular radius (m), ring 4: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

4)

R017 ³ Outer annular radius (m), ring 5: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

5)

R017 ³ Outer annular radius (m), ring 6: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

6)

R017 ³ Outer annular radius (m), ring 7: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

7)

R017 ³ Outer annular radius (m), ring 8: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

8)

R017 ³ Outer annular radius (m), ring 9: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

9)

R017 ³ Outer annular radius (m), ring 10: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (10)

R017 ³ Outer annular radius (m), ring 11: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (11)

R017 ³ Outer annular radius (m), ring 12: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (12)

³ ³ ³ ³ ³ R017 ³ Fractions of annular areas within AREA: ³ ³ ³ ³ R017 ³ Ring 1 ³ not used ³ 1.000E+00 ³ --- ³ FRACA( 1)

R017 ³ Ring 2 ³ not used ³ 2.732E-01 ³ --- ³ FRACA( 2)

R017 ³ Ring 3 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 3)

R017 ³ Ring 4 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 4)

R017 ³ Ring 5 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 5)

R017 ³ Ring 6 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 6)

R017 ³ Ring 7 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 7)

R017 ³ Ring 8 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 8)

R017 ³ Ring 9 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 9)

R017 ³ Ring 10 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(10)

R017 ³ Ring 11 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(11)

R017 ³ Ring 12 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(12)

³ ³ ³ ³ ³ R018 ³ Fruits, vegetables and grain consumption (kg/yr) ³ 1.120E+02 ³ 1.600E+02 ³ --- ³ DIET(1)

R018 ³ Leafy vegetable consumption (kg/yr) ³ 2.140E+01 ³ 1.400E+01 ³ --- ³ DIET(2)

R018 ³ Milk consumption (L/yr) ³ 2.330E+02 ³ 9.200E+01 ³ --- ³ DIET(3)

R018 ³ Meat and poultry consumption (kg/yr) ³ 6.510E+01 ³ 6.300E+01 ³ --- ³ DIET(4)

R018 ³ Fish consumption (kg/yr) ³ 2.060E+01 ³ 5.400E+00 ³ --- ³ DIET(5)

R018 ³ Other seafood consumption (kg/yr) ³ 9.000E-01 ³ 9.000E-01 ³ --- ³ DIET(6)

R018 ³ Soil ingestion rate (g/yr) ³ 1.826E+01 ³ 3.650E+01 ³ --- ³ SOIL R018 ³ Drinking water intake (L/yr) ³ 4.785E+02 ³ 5.100E+02 ³ --- ³ DWI R018 ³ Contamination fraction of drinking water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FDW R018 ³ Contamination fraction of household water ³ not used ³ 1.000E+00 ³ --- ³ FHHW R018 ³ Contamination fraction of livestock water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FLW R018 ³ Contamination fraction of irrigation water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FIRW R018 ³ Contamination fraction of aquatic food ³ 1.000E+00 ³ 5.000E-01 ³ --- ³ FR9 R018 ³ Contamination fraction of plant food ³ 1.000E+00 ³-1 ³ --- ³ FPLANT R018 ³ Contamination fraction of meat ³ 1.000E+00 ³-1 ³ --- ³ FMEAT R018 ³ Contamination fraction of milk ³ 1.000E+00 ³-1 ³ --- ³ FMILK

³ ³ ³ ³ ³ R019 ³ Livestock fodder intake for meat (kg/day) ³ 2.710E+01 ³ 6.800E+01 ³ --- ³ LFI5 R019 ³ Livestock fodder intake for milk (kg/day) ³ 6.320E+01 ³ 5.500E+01 ³ --- ³ LFI6 R019 ³ Livestock water intake for meat (L/day) ³ 5.060E+01 ³ 5.000E+01 ³ --- ³ LWI5 R019 ³ Livestock water intake for milk (L/day) ³ 6.000E+01 ³ 1.600E+02 ³ --- ³ LWI6 R019 ³ Livestock soil intake (kg/day) ³ 5.000E-01 ³ 5.000E-01 ³ --- ³ LSI R019 ³ Mass loading for foliar deposition (g/m**3) ³ 4.000E-04 ³ 1.000E-04 ³ --- ³ MLFD 1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/01/2003 11:46 Page 6 Summary : Yankee Rowe Sensitivity Analysis=soil File: Pu-241_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R019 ³ Depth of soil mixing layer (m) ³ 2.300E-01 ³ 1.500E-01 ³ --- ³ DM R019 ³ Depth of roots (m) ³ 1.170E+00 ³ 9.000E-01 ³ --- ³ DROOT R019 ³ Drinking water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWDW R019 ³ Household water fraction from ground water ³ not used ³ 1.000E+00 ³ --- ³ FGWHH R019 ³ Livestock water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWLW R019 ³ Irrigation fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWIR

³ ³ ³ ³ ³ R19B ³ Wet weight crop yield for Non-Leafy (kg/m**2) ³ 1.750E+00 ³ 7.000E-01 ³ --- ³ YV(1)

R19B ³ Wet weight crop yield for Leafy (kg/m**2) ³ 2.889E+00 ³ 1.500E+00 ³ --- ³ YV(2)

R19B ³ Wet weight crop yield for Fodder (kg/m**2) ³ 1.887E+00 ³ 1.100E+00 ³ --- ³ YV(3)

R19B ³ Growing Season for Non-Leafy (years) ³ 2.460E-01 ³ 1.700E-01 ³ --- ³ TE(1)

R19B ³ Growing Season for Leafy (years) ³ 1.230E-01 ³ 2.500E-01 ³ --- ³ TE(2)

R19B ³ Growing Season for Fodder (years) ³ 8.200E-02 ³ 8.000E-02 ³ --- ³ TE(3)

R19B ³ Translocation Factor for Non-Leafy ³ 1.000E-01 ³ 1.000E-01 ³ --- ³ TIV(1)

R19B ³ Translocation Factor for Leafy ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(2)

R19B ³ Translocation Factor for Fodder ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(3)

R19B ³ Dry Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(1)

R19B ³ Dry Foliar Interception Fraction for Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(2)

R19B ³ Dry Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(3)

R19B ³ Wet Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(1)

R19B ³ Wet Foliar Interception Fraction for Leafy ³ 5.800E-01 ³ 2.500E-01 ³ --- ³ RWET(2)

R19B ³ Wet Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(3)

R19B ³ Weathering Removal Constant for Vegetation ³ 3.300E+01 ³ 2.000E+01 ³ --- ³ WLAM

³ ³ ³ ³ ³ C14 ³ C-12 concentration in water (g/cm**3) ³ not used ³ 2.000E-05 ³ --- ³ C12WTR C14 ³ C-12 concentration in contaminated soil (g/g) ³ not used ³ 3.000E-02 ³ --- ³ C12CZ C14 ³ Fraction of vegetation carbon from soil ³ not used ³ 2.000E-02 ³ --- ³ CSOIL C14 ³ Fraction of vegetation carbon from air ³ not used ³ 9.800E-01 ³ --- ³ CAIR C14 ³ C-14 evasion layer thickness in soil (m) ³ not used ³ 3.000E-01 ³ --- ³ DMC C14 ³ C-14 evasion flux rate from soil (1/sec) ³ not used ³ 7.000E-07 ³ --- ³ EVSN C14 ³ C-12 evasion flux rate from soil (1/sec) ³ not used ³ 1.000E-10 ³ --- ³ REVSN C14 ³ Fraction of grain in beef cattle feed ³ not used ³ 8.000E-01 ³ --- ³ AVFG4 C14 ³ Fraction of grain in milk cow feed ³ not used ³ 2.000E-01 ³ --- ³ AVFG5

C14 ³ DCF correction factor for gaseous forms of C14 ³ not used ³ 8.894E+01 ³ --- ³ CO2F

³ ³ ³ ³ ³ STOR ³ Storage times of contaminated foodstuffs (days): ³ ³ ³ ³ STOR ³ Fruits, non-leafy vegetables, and grain ³ 1.400E+01 ³ 1.400E+01 ³ --- ³ STOR_T(1)

STOR ³ Leafy vegetables ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(2)

STOR ³ Milk ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(3)

STOR ³ Meat and poultry ³ 2.000E+01 ³ 2.000E+01 ³ --- ³ STOR_T(4)

STOR ³ Fish ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(5)

STOR ³ Crustacea and mollusks ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(6)

STOR ³ Well water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(7)

STOR ³ Surface water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(8)

STOR ³ Livestock fodder ³ 4.500E+01 ³ 4.500E+01 ³ --- ³ STOR_T(9)

³ ³ ³ ³ ³ R021 ³ Thickness of building foundation (m) ³ not used ³ 1.500E-01 ³ --- ³ FLOOR1 R021 ³ Bulk density of building foundation (g/cm**3) ³ not used ³ 2.400E+00 ³ --- ³ DENSFL R021 ³ Total porosity of the cover material ³ not used ³ 4.000E-01 ³ --- ³ TPCV R021 ³ Total porosity of the building foundation ³ not used ³ 1.000E-01 ³ --- ³ TPFL R021 ³ Volumetric water content of the cover material ³ not used ³ 5.000E-02 ³ --- ³ PH2OCV 1RESRAD, Version 6.21 T<< Limit = 0.5 year 12/01/2003 11:46 Page 7 Summary : Yankee Rowe Sensitivity Analysis=soil File: Pu-241_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R021 ³ Volumetric water content of the foundation ³ not used ³ 3.000E-02 ³ --- ³ PH2OFL R021 ³ Diffusion coefficient for radon gas (m/sec): ³ ³ ³ ³ R021 ³ in cover material ³ not used ³ 2.000E-06 ³ --- ³ DIFCV R021 ³ in foundation material ³ not used ³ 3.000E-07 ³ --- ³ DIFFL R021 ³ in contaminated zone soil ³ not used ³ 2.000E-06 ³ --- ³ DIFCZ R021 ³ Radon vertical dimension of mixing (m) ³ not used ³ 2.000E+00 ³ --- ³ HMIX R021 ³ Average building air exchange rate (1/hr) ³ not used ³ 5.000E-01 ³ --- ³ REXG R021 ³ Height of the building (room) (m) ³ not used ³ 2.500E+00 ³ --- ³ HRM R021 ³ Building interior area factor ³ not used ³ 0.000E+00 ³ --- ³ FAI R021 ³ Building depth below ground surface (m) ³ not used ³-1.000E+00 ³ --- ³ DMFL R021 ³ Emanating power of Rn-222 gas ³ not used ³ 2.500E-01 ³ --- ³ EMANA(1)

R021 ³ Emanating power of Rn-220 gas ³ not used ³ 1.500E-01 ³ --- ³ EMANA(2)

³ ³ ³ ³ ³ TITL ³ Number of graphical time points ³ 32 ³ --- ³ --- ³ NPTS TITL ³ Maximum number of integration points for dose ³ 17 ³ --- ³ --- ³ LYMAX TITL ³ Maximum number of integration points for risk ³ 1 ³ --- ³ --- ³ KYMAX

Summary of Pathway Selections Pathway ³ User Selection

Å 1 -- external gamma ³ active 2 -- inhalation (w/o radon)³ active 3 -- plant ingestion ³ active 4 -- meat ingestion ³ active 5 -- milk ingestion ³ active 6 -- aquatic foods ³ active 7 -- drinking water ³ active 8 -- soil ingestion ³ active 9 -- radon ³ suppressed Find peak pathway doses ³ active

1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 08:30 Page 2 Summary : Yankee Rowe Sensitivity Analysis=soil File: Sb-125_DCGL.RAD Dose Conversion Factor (and Related) Parameter Summary File: FGR 13 Morbidity 0 ³ ³ Current ³ ³ Parameter Menu ³ Parameter ³ Value ³ Default ³ Name

ÅÅÅÅ B-1 ³ Dose conversion factors for inhalation, mrem/pCi: ³ ³ ³ B-1 ³ Sb-125+D ³ 1.386E-05 ³ 1.386E-05 ³ DCF2( 1)

³ ³ ³ ³ D-1 ³ Dose conversion factors for ingestion, mrem/pCi: ³ ³ ³ D-1 ³ Sb-125+D ³ 3.647E-06 ³ 3.647E-06 ³ DCF3( 1)

³ ³ ³ ³ D-34 ³ Food transfer factors: ³ ³ ³ D-34 ³ Sb-125+D, plant/soil concentration ratio, dimensionless ³ 1.000E-02 ³ 1.000E-02 ³ RTF( 1,1)

D-34 ³ Sb-125+D, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 1.000E-03 ³ 1.000E-03 ³ RTF( 1,2)

D-34 ³ Sb-125+D, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 1.000E-04 ³ 1.000E-04 ³ RTF( 1,3)

³ ³ ³ ³ D-5 ³ Bioaccumulation factors, fresh water, L/kg: ³ ³ ³ D-5 ³ Sb-125+D, fish ³ 1.000E+02 ³ 1.000E+02 ³ BIOFAC( 1,1)

D-5 ³ Sb-125+D, crustacea and mollusks ³ 1.000E+01 ³ 1.000E+01 ³ BIOFAC( 1,2) 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 08:30 Page 3 Summary : Yankee Rowe Sensitivity Analysis=soil File: Sb-125_DCGL.RAD Site-Specific Parameter Summary 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R011 ³ Area of contaminated zone (m**2) ³ 1.302E+04 ³ 1.000E+04 ³ --- ³ AREA R011 ³ Thickness of contaminated zone (m) ³ 1.975E+00 ³ 2.000E+00 ³ --- ³ THICK0 R011 ³ Length parallel to aquifer flow (m) ³ 1.290E+02 ³ 1.000E+02 ³ --- ³ LCZPAQ R011 ³ Basic radiation dose limit (mrem/yr) ³ 2.500E+01 ³ 2.500E+01 ³ --- ³ BRDL R011 ³ Time since placement of material (yr) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ TI R011 ³ Times for calculations (yr) ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ T( 2)

R011 ³ Times for calculations (yr) ³ 3.000E+00 ³ 3.000E+00 ³ --- ³ T( 3)

R011 ³ Times for calculations (yr) ³ 1.000E+01 ³ 1.000E+01 ³ --- ³ T( 4)

R011 ³ Times for calculations (yr) ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ T( 5)

R011 ³ Times for calculations (yr) ³ 1.000E+02 ³ 1.000E+02 ³ --- ³ T( 6)

R011 ³ Times for calculations (yr) ³ 3.000E+02 ³ 3.000E+02 ³ --- ³ T( 7)

R011 ³ Times for calculations (yr) ³ 1.000E+03 ³ 1.000E+03 ³ --- ³ T( 8)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T( 9)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T(10)

³ ³ ³ ³ ³ R012 ³ Initial principal radionuclide (pCi/g): Sb-125 ³ 1.000E+00 ³ 0.000E+00 ³ --- ³ S1( 1)

R012 ³ Concentration in groundwater (pCi/L): Sb-125 ³ not used ³ 0.000E+00 ³ --- ³ W1( 1)

³ ³ ³ ³ ³ R013 ³ Cover depth (m) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ COVER0 R013 ³ Density of cover material (g/cm**3) ³ not used ³ 1.500E+00 ³ --- ³ DENSCV R013 ³ Cover depth erosion rate (m/yr) ³ not used ³ 1.000E-03 ³ --- ³ VCV R013 ³ Density of contaminated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSCZ R013 ³ Contaminated zone erosion rate (m/yr) ³ 8.500E-04 ³ 1.000E-03 ³ --- ³ VCZ R013 ³ Contaminated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPCZ R013 ³ Contaminated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCCZ R013 ³ Contaminated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCCZ R013 ³ Contaminated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BCZ R013 ³ Average annual wind speed (m/sec) ³ 2.030E+00 ³ 2.000E+00 ³ --- ³ WIND R013 ³ Humidity in air (g/m**3) ³ not used ³ 8.000E+00 ³ --- ³ HUMID R013 ³ Evapotranspiration coefficient ³ 6.250E-01 ³ 5.000E-01 ³ --- ³ EVAPTR R013 ³ Precipitation (m/yr) ³ 1.200E+00 ³ 1.000E+00 ³ --- ³ PRECIP R013 ³ Irrigation (m/yr) ³ 4.350E-01 ³ 2.000E-01 ³ --- ³ RI R013 ³ Irrigation mode ³ overhead ³ overhead ³ --- ³ IDITCH R013 ³ Runoff coefficient ³ 6.000E-01 ³ 2.000E-01 ³ --- ³ RUNOFF R013 ³ Watershed area for nearby stream or pond (m**2) ³ 7.770E+05 ³ 1.000E+06 ³ --- ³ WAREA R013 ³ Accuracy for water/soil computations ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ EPS

³ ³ ³ ³ ³ R014 ³ Density of saturated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSAQ R014 ³ Saturated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPSZ R014 ³ Saturated zone effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPSZ R014 ³ Saturated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCSZ R014 ³ Saturated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+02 ³ --- ³ HCSZ R014 ³ Saturated zone hydraulic gradient ³ 1.000E-01 ³ 2.000E-02 ³ --- ³ HGWT R014 ³ Saturated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BSZ R014 ³ Water table drop rate (m/yr) ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ VWT R014 ³ Well pump intake depth (m below water table) ³ 1.451E+01 ³ 1.000E+01 ³ --- ³ DWIBWT R014 ³ Model: Nondispersion (ND) or Mass-Balance (MB) ³ ND ³ ND ³ --- ³ MODEL R014 ³ Well pumping rate (m**3/yr) ³ 1.323E+03 ³ 2.500E+02 ³ --- ³ UW

³ ³ ³ ³ ³ R015 ³ Number of unsaturated zone strata ³ 1 ³ 1 ³ --- ³ NS 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 08:30 Page 4 Summary : Yankee Rowe Sensitivity Analysis=soil File: Sb-125_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R015 ³ Unsat. zone 1, thickness (m) ³ 1.820E+00 ³ 4.000E+00 ³ --- ³ H(1)

R015 ³ Unsat. zone 1, soil density (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSUZ(1)

R015 ³ Unsat. zone 1, total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPUZ(1)

R015 ³ Unsat. zone 1, effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPUZ(1)

R015 ³ Unsat. zone 1, field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCUZ(1)

R015 ³ Unsat. zone 1, soil-specific b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BUZ(1)

R015 ³ Unsat. zone 1, hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCUZ(1)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for Sb-125 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 3.310E+03 ³ 0.000E+00 ³ --- ³ DCNUCC( 1)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 3.800E+02 ³ 0.000E+00 ³ --- ³ DCNUCU( 1,1)

R016 ³ Saturated zone (cm**3/g) ³ 3.800E+02 ³ 0.000E+00 ³ --- ³ DCNUCS( 1)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 3.475E-05 ³ ALEACH( 1)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 1)

³ ³ ³ ³ ³ R017 ³ Inhalation rate (m**3/yr) ³ 8.400E+03 ³ 8.400E+03 ³ --- ³ INHALR R017 ³ Mass loading for inhalation (g/m**3) ³ 2.330E-05 ³ 1.000E-04 ³ --- ³ MLINH R017 ³ Exposure duration ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ ED R017 ³ Shielding factor, inhalation ³ 5.500E-01 ³ 4.000E-01 ³ --- ³ SHF3 R017 ³ Shielding factor, external gamma ³ 3.980E-01 ³ 7.000E-01 ³ --- ³ SHF1 R017 ³ Fraction of time spent indoors ³ 6.571E-01 ³ 5.000E-01 ³ --- ³ FIND R017 ³ Fraction of time spent outdoors (on site) ³ 1.181E-01 ³ 2.500E-01 ³ --- ³ FOTD R017 ³ Shape factor flag, external gamma ³ 1.000E+00 ³ 1.000E+00 ³ >0 shows circular AREA. ³ FS R017 ³ Radii of shape factor array (used if FS = -1): ³ ³ ³ ³ R017 ³ Outer annular radius (m), ring 1: ³ not used ³ 5.000E+01 ³ --- ³ RAD_SHAPE(

1)

R017 ³ Outer annular radius (m), ring 2: ³ not used ³ 7.071E+01 ³ --- ³ RAD_SHAPE(

2)

R017 ³ Outer annular radius (m), ring 3: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

3)

R017 ³ Outer annular radius (m), ring 4: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

4)

R017 ³ Outer annular radius (m), ring 5: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

5)

R017 ³ Outer annular radius (m), ring 6: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

6)

R017 ³ Outer annular radius (m), ring 7: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

7)

R017 ³ Outer annular radius (m), ring 8: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

8)

R017 ³ Outer annular radius (m), ring 9: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

9)

R017 ³ Outer annular radius (m), ring 10: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (10)

R017 ³ Outer annular radius (m), ring 11: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (11)

R017 ³ Outer annular radius (m), ring 12: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (12)

³ ³ ³ ³ ³ R017 ³ Fractions of annular areas within AREA: ³ ³ ³ ³ R017 ³ Ring 1 ³ not used ³ 1.000E+00 ³ --- ³ FRACA( 1)

R017 ³ Ring 2 ³ not used ³ 2.732E-01 ³ --- ³ FRACA( 2)

R017 ³ Ring 3 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 3)

R017 ³ Ring 4 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 4)

R017 ³ Ring 5 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 5)

R017 ³ Ring 6 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 6)

R017 ³ Ring 7 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 7)

R017 ³ Ring 8 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 8)

R017 ³ Ring 9 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 9)

R017 ³ Ring 10 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(10)

R017 ³ Ring 11 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(11)

R017 ³ Ring 12 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(12)

³ ³ ³ ³ ³ 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 08:30 Page 5 Summary : Yankee Rowe Sensitivity Analysis=soil File: Sb-125_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R018 ³ Fruits, vegetables and grain consumption (kg/yr) ³ 1.120E+02 ³ 1.600E+02 ³ --- ³ DIET(1)

R018 ³ Leafy vegetable consumption (kg/yr) ³ 2.140E+01 ³ 1.400E+01 ³ --- ³ DIET(2)

R018 ³ Milk consumption (L/yr) ³ 2.330E+02 ³ 9.200E+01 ³ --- ³ DIET(3)

R018 ³ Meat and poultry consumption (kg/yr) ³ 6.510E+01 ³ 6.300E+01 ³ --- ³ DIET(4)

R018 ³ Fish consumption (kg/yr) ³ 2.060E+01 ³ 5.400E+00 ³ --- ³ DIET(5)

R018 ³ Other seafood consumption (kg/yr) ³ 9.000E-01 ³ 9.000E-01 ³ --- ³ DIET(6)

R018 ³ Soil ingestion rate (g/yr) ³ 1.826E+01 ³ 3.650E+01 ³ --- ³ SOIL R018 ³ Drinking water intake (L/yr) ³ 4.785E+02 ³ 5.100E+02 ³ --- ³ DWI R018 ³ Contamination fraction of drinking water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FDW R018 ³ Contamination fraction of household water ³ not used ³ 1.000E+00 ³ --- ³ FHHW R018 ³ Contamination fraction of livestock water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FLW R018 ³ Contamination fraction of irrigation water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FIRW R018 ³ Contamination fraction of aquatic food ³ 1.000E+00 ³ 5.000E-01 ³ --- ³ FR9 R018 ³ Contamination fraction of plant food ³ 1.000E+00 ³-1 ³ --- ³ FPLANT R018 ³ Contamination fraction of meat ³ 1.000E+00 ³-1 ³ --- ³ FMEAT R018 ³ Contamination fraction of milk ³ 1.000E+00 ³-1 ³ --- ³ FMILK

³ ³ ³ ³ ³ R019 ³ Livestock fodder intake for meat (kg/day) ³ 2.710E+01 ³ 6.800E+01 ³ --- ³ LFI5 R019 ³ Livestock fodder intake for milk (kg/day) ³ 6.320E+01 ³ 5.500E+01 ³ --- ³ LFI6 R019 ³ Livestock water intake for meat (L/day) ³ 5.060E+01 ³ 5.000E+01 ³ --- ³ LWI5 R019 ³ Livestock water intake for milk (L/day) ³ 6.000E+01 ³ 1.600E+02 ³ --- ³ LWI6 R019 ³ Livestock soil intake (kg/day) ³ 5.000E-01 ³ 5.000E-01 ³ --- ³ LSI R019 ³ Mass loading for foliar deposition (g/m**3) ³ 4.000E-04 ³ 1.000E-04 ³ --- ³ MLFD R019 ³ Depth of soil mixing layer (m) ³ 2.300E-01 ³ 1.500E-01 ³ --- ³ DM R019 ³ Depth of roots (m) ³ 2.050E+00 ³ 9.000E-01 ³ --- ³ DROOT R019 ³ Drinking water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWDW R019 ³ Household water fraction from ground water ³ not used ³ 1.000E+00 ³ --- ³ FGWHH R019 ³ Livestock water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWLW R019 ³ Irrigation fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWIR

³ ³ ³ ³ ³ R19B ³ Wet weight crop yield for Non-Leafy (kg/m**2) ³ 1.750E+00 ³ 7.000E-01 ³ --- ³ YV(1)

R19B ³ Wet weight crop yield for Leafy (kg/m**2) ³ 2.889E+00 ³ 1.500E+00 ³ --- ³ YV(2)

R19B ³ Wet weight crop yield for Fodder (kg/m**2) ³ 1.887E+00 ³ 1.100E+00 ³ --- ³ YV(3)

R19B ³ Growing Season for Non-Leafy (years) ³ 2.460E-01 ³ 1.700E-01 ³ --- ³ TE(1)

R19B ³ Growing Season for Leafy (years) ³ 1.230E-01 ³ 2.500E-01 ³ --- ³ TE(2)

R19B ³ Growing Season for Fodder (years) ³ 8.200E-02 ³ 8.000E-02 ³ --- ³ TE(3)

R19B ³ Translocation Factor for Non-Leafy ³ 1.000E-01 ³ 1.000E-01 ³ --- ³ TIV(1)

R19B ³ Translocation Factor for Leafy ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(2)

R19B ³ Translocation Factor for Fodder ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(3)

R19B ³ Dry Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(1)

R19B ³ Dry Foliar Interception Fraction for Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(2)

R19B ³ Dry Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(3)

R19B ³ Wet Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(1)

R19B ³ Wet Foliar Interception Fraction for Leafy ³ 5.800E-01 ³ 2.500E-01 ³ --- ³ RWET(2)

R19B ³ Wet Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(3)

R19B ³ Weathering Removal Constant for Vegetation ³ 3.300E+01 ³ 2.000E+01 ³ --- ³ WLAM

³ ³ ³ ³ ³ C14 ³ C-12 concentration in water (g/cm**3) ³ not used ³ 2.000E-05 ³ --- ³ C12WTR C14 ³ C-12 concentration in contaminated soil (g/g) ³ not used ³ 3.000E-02 ³ --- ³ C12CZ C14 ³ Fraction of vegetation carbon from soil ³ not used ³ 2.000E-02 ³ --- ³ CSOIL C14 ³ Fraction of vegetation carbon from air ³ not used ³ 9.800E-01 ³ --- ³ CAIR 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 08:30 Page 6 Summary : Yankee Rowe Sensitivity Analysis=soil File: Sb-125_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ C14 ³ C-14 evasion layer thickness in soil (m) ³ not used ³ 3.000E-01 ³ --- ³ DMC C14 ³ C-14 evasion flux rate from soil (1/sec) ³ not used ³ 7.000E-07 ³ --- ³ EVSN C14 ³ C-12 evasion flux rate from soil (1/sec) ³ not used ³ 1.000E-10 ³ --- ³ REVSN C14 ³ Fraction of grain in beef cattle feed ³ not used ³ 8.000E-01 ³ --- ³ AVFG4 C14 ³ Fraction of grain in milk cow feed ³ not used ³ 2.000E-01 ³ --- ³ AVFG5 C14 ³ DCF correction factor for gaseous forms of C14 ³ not used ³ 8.894E+01 ³ --- ³ CO2F

³ ³ ³ ³ ³ STOR ³ Storage times of contaminated foodstuffs (days): ³ ³ ³ ³ STOR ³ Fruits, non-leafy vegetables, and grain ³ 1.400E+01 ³ 1.400E+01 ³ --- ³ STOR_T(1)

STOR ³ Leafy vegetables ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(2)

STOR ³ Milk ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(3)

STOR ³ Meat and poultry ³ 2.000E+01 ³ 2.000E+01 ³ --- ³ STOR_T(4)

STOR ³ Fish ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(5)

STOR ³ Crustacea and mollusks ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(6)

STOR ³ Well water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(7)

STOR ³ Surface water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(8)

STOR ³ Livestock fodder ³ 4.500E+01 ³ 4.500E+01 ³ --- ³ STOR_T(9)

³ ³ ³ ³ ³ R021 ³ Thickness of building foundation (m) ³ not used ³ 1.500E-01 ³ --- ³ FLOOR1 R021 ³ Bulk density of building foundation (g/cm**3) ³ not used ³ 2.400E+00 ³ --- ³ DENSFL R021 ³ Total porosity of the cover material ³ not used ³ 4.000E-01 ³ --- ³ TPCV R021 ³ Total porosity of the building foundation ³ not used ³ 1.000E-01 ³ --- ³ TPFL R021 ³ Volumetric water content of the cover material ³ not used ³ 5.000E-02 ³ --- ³ PH2OCV R021 ³ Volumetric water content of the foundation ³ not used ³ 3.000E-02 ³ --- ³ PH2OFL R021 ³ Diffusion coefficient for radon gas (m/sec): ³ ³ ³ ³ R021 ³ in cover material ³ not used ³ 2.000E-06 ³ --- ³ DIFCV R021 ³ in foundation material ³ not used ³ 3.000E-07 ³ --- ³ DIFFL R021 ³ in contaminated zone soil ³ not used ³ 2.000E-06 ³ --- ³ DIFCZ R021 ³ Radon vertical dimension of mixing (m) ³ not used ³ 2.000E+00 ³ --- ³ HMIX R021 ³ Average building air exchange rate (1/hr) ³ not used ³ 5.000E-01 ³ --- ³ REXG R021 ³ Height of the building (room) (m) ³ not used ³ 2.500E+00 ³ --- ³ HRM R021 ³ Building interior area factor ³ not used ³ 0.000E+00 ³ --- ³ FAI R021 ³ Building depth below ground surface (m) ³ not used ³-1.000E+00 ³ --- ³ DMFL R021 ³ Emanating power of Rn-222 gas ³ not used ³ 2.500E-01 ³ --- ³ EMANA(1)

R021 ³ Emanating power of Rn-220 gas ³ not used ³ 1.500E-01 ³ --- ³ EMANA(2)

³ ³ ³ ³ ³ TITL ³ Number of graphical time points ³ 32 ³ --- ³ --- ³ NPTS TITL ³ Maximum number of integration points for dose ³ 17 ³ --- ³ --- ³ LYMAX TITL ³ Maximum number of integration points for risk ³ 1 ³ --- ³ --- ³ KYMAX

1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 08:30 Page 7 Summary : Yankee Rowe Sensitivity Analysis=soil File: Sb-125_DCGL.RAD Summary of Pathway Selections Pathway ³ User Selection

Å 1 -- external gamma ³ active 2 -- inhalation (w/o radon)³ active 3 -- plant ingestion ³ active 4 -- meat ingestion ³ active 5 -- milk ingestion ³ active 6 -- aquatic foods ³ active 7 -- drinking water ³ active 8 -- soil ingestion ³ active 9 -- radon ³ suppressed Find peak pathway doses ³ active

1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 08:49 Page 2 Summary : Yankee Rowe Sensitivity Analysis=soil File: Sr-90_DCGL.RAD Dose Conversion Factor (and Related) Parameter Summary File: YR soil DCGL lib 0 ³ ³ Current ³ ³ Parameter Menu ³ Parameter ³ Value ³ Default ³ Name

ÅÅÅÅ B-1 ³ Dose conversion factors for inhalation, mrem/pCi: ³ ³ ³ B-1 ³ Sr-90+D ³ 1.310E-03 ³ 1.310E-03 ³ DCF2( 1)

³ ³ ³ ³ D-1 ³ Dose conversion factors for ingestion, mrem/pCi: ³ ³ ³ D-1 ³ Sr-90+D ³ 1.530E-04 ³ 1.530E-04 ³ DCF3( 1)

³ ³ ³ ³ D-34 ³ Food transfer factors: ³ ³ ³ D-34 ³ Sr-90+D, plant/soil concentration ratio, dimensionless ³ 5.900E-01 ³ 3.000E-01 ³ RTF( 1,1)

D-34 ³ Sr-90+D, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 8.000E-03 ³ 8.000E-03 ³ RTF( 1,2)

D-34 ³ Sr-90+D, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 2.000E-03 ³ 2.000E-03 ³ RTF( 1,3)

³ ³ ³ ³ D-5 ³ Bioaccumulation factors, fresh water, L/kg: ³ ³ ³ D-5 ³ Sr-90+D, fish ³ 6.000E+01 ³ 6.000E+01 ³ BIOFAC( 1,1)

D-5 ³ Sr-90+D, crustacea and mollusks ³ 1.000E+02 ³ 1.000E+02 ³ BIOFAC( 1,2) 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 08:49 Page 3 Summary : Yankee Rowe Sensitivity Analysis=soil File: Sr-90_DCGL.RAD Site-Specific Parameter Summary 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R011 ³ Area of contaminated zone (m**2) ³ 1.302E+04 ³ 1.000E+04 ³ --- ³ AREA R011 ³ Thickness of contaminated zone (m) ³ 1.975E+00 ³ 2.000E+00 ³ --- ³ THICK0 R011 ³ Length parallel to aquifer flow (m) ³ 1.290E+02 ³ 1.000E+02 ³ --- ³ LCZPAQ R011 ³ Basic radiation dose limit (mrem/yr) ³ 2.500E+01 ³ 2.500E+01 ³ --- ³ BRDL R011 ³ Time since placement of material (yr) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ TI R011 ³ Times for calculations (yr) ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ T( 2)

R011 ³ Times for calculations (yr) ³ 3.000E+00 ³ 3.000E+00 ³ --- ³ T( 3)

R011 ³ Times for calculations (yr) ³ 1.000E+01 ³ 1.000E+01 ³ --- ³ T( 4)

R011 ³ Times for calculations (yr) ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ T( 5)

R011 ³ Times for calculations (yr) ³ 1.000E+02 ³ 1.000E+02 ³ --- ³ T( 6)

R011 ³ Times for calculations (yr) ³ 3.000E+02 ³ 3.000E+02 ³ --- ³ T( 7)

R011 ³ Times for calculations (yr) ³ 1.000E+03 ³ 1.000E+03 ³ --- ³ T( 8)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T( 9)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T(10)

³ ³ ³ ³ ³ R012 ³ Initial principal radionuclide (pCi/g): Sr-90 ³ 1.000E+00 ³ 0.000E+00 ³ --- ³ S1( 1)

R012 ³ Concentration in groundwater (pCi/L): Sr-90 ³ not used ³ 0.000E+00 ³ --- ³ W1( 1)

³ ³ ³ ³ ³ R013 ³ Cover depth (m) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ COVER0 R013 ³ Density of cover material (g/cm**3) ³ not used ³ 1.500E+00 ³ --- ³ DENSCV R013 ³ Cover depth erosion rate (m/yr) ³ not used ³ 1.000E-03 ³ --- ³ VCV R013 ³ Density of contaminated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSCZ R013 ³ Contaminated zone erosion rate (m/yr) ³ 8.500E-04 ³ 1.000E-03 ³ --- ³ VCZ R013 ³ Contaminated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPCZ R013 ³ Contaminated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCCZ R013 ³ Contaminated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCCZ R013 ³ Contaminated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BCZ R013 ³ Average annual wind speed (m/sec) ³ 2.030E+00 ³ 2.000E+00 ³ --- ³ WIND R013 ³ Humidity in air (g/m**3) ³ not used ³ 8.000E+00 ³ --- ³ HUMID R013 ³ Evapotranspiration coefficient ³ 6.250E-01 ³ 5.000E-01 ³ --- ³ EVAPTR R013 ³ Precipitation (m/yr) ³ 1.200E+00 ³ 1.000E+00 ³ --- ³ PRECIP R013 ³ Irrigation (m/yr) ³ 4.350E-01 ³ 2.000E-01 ³ --- ³ RI R013 ³ Irrigation mode ³ overhead ³ overhead ³ --- ³ IDITCH R013 ³ Runoff coefficient ³ 6.000E-01 ³ 2.000E-01 ³ --- ³ RUNOFF R013 ³ Watershed area for nearby stream or pond (m**2) ³ 7.770E+05 ³ 1.000E+06 ³ --- ³ WAREA R013 ³ Accuracy for water/soil computations ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ EPS

³ ³ ³ ³ ³ R014 ³ Density of saturated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSAQ R014 ³ Saturated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPSZ R014 ³ Saturated zone effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPSZ R014 ³ Saturated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCSZ R014 ³ Saturated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+02 ³ --- ³ HCSZ R014 ³ Saturated zone hydraulic gradient ³ 1.000E-01 ³ 2.000E-02 ³ --- ³ HGWT R014 ³ Saturated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BSZ R014 ³ Water table drop rate (m/yr) ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ VWT R014 ³ Well pump intake depth (m below water table) ³ 1.451E+01 ³ 1.000E+01 ³ --- ³ DWIBWT R014 ³ Model: Nondispersion (ND) or Mass-Balance (MB) ³ ND ³ ND ³ --- ³ MODEL R014 ³ Well pumping rate (m**3/yr) ³ 1.323E+03 ³ 2.500E+02 ³ --- ³ UW

³ ³ ³ ³ ³ R015 ³ Number of unsaturated zone strata ³ 1 ³ 1 ³ --- ³ NS 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 08:49 Page 4 Summary : Yankee Rowe Sensitivity Analysis=soil File: Sr-90_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R015 ³ Unsat. zone 1, thickness (m) ³ 1.820E+00 ³ 4.000E+00 ³ --- ³ H(1)

R015 ³ Unsat. zone 1, soil density (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSUZ(1)

R015 ³ Unsat. zone 1, total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPUZ(1)

R015 ³ Unsat. zone 1, effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPUZ(1)

R015 ³ Unsat. zone 1, field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCUZ(1)

R015 ³ Unsat. zone 1, soil-specific b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BUZ(1)

R015 ³ Unsat. zone 1, hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCUZ(1)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for Sr-90 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 3.200E+01 ³ 3.000E+01 ³ --- ³ DCNUCC( 1)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 3.200E+01 ³ 3.000E+01 ³ --- ³ DCNUCU( 1,1)

R016 ³ Saturated zone (cm**3/g) ³ 3.200E+01 ³ 3.000E+01 ³ --- ³ DCNUCS( 1)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 3.589E-03 ³ ALEACH( 1)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 1)

³ ³ ³ ³ ³ R017 ³ Inhalation rate (m**3/yr) ³ 8.400E+03 ³ 8.400E+03 ³ --- ³ INHALR R017 ³ Mass loading for inhalation (g/m**3) ³ 2.330E-05 ³ 1.000E-04 ³ --- ³ MLINH R017 ³ Exposure duration ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ ED R017 ³ Shielding factor, inhalation ³ 5.500E-01 ³ 4.000E-01 ³ --- ³ SHF3 R017 ³ Shielding factor, external gamma ³ 2.725E-01 ³ 7.000E-01 ³ --- ³ SHF1 R017 ³ Fraction of time spent indoors ³ 6.571E-01 ³ 5.000E-01 ³ --- ³ FIND R017 ³ Fraction of time spent outdoors (on site) ³ 1.181E-01 ³ 2.500E-01 ³ --- ³ FOTD R017 ³ Shape factor flag, external gamma ³ 1.000E+00 ³ 1.000E+00 ³ >0 shows circular AREA. ³ FS R017 ³ Radii of shape factor array (used if FS = -1): ³ ³ ³ ³ R017 ³ Outer annular radius (m), ring 1: ³ not used ³ 5.000E+01 ³ --- ³ RAD_SHAPE(

1)

R017 ³ Outer annular radius (m), ring 2: ³ not used ³ 7.071E+01 ³ --- ³ RAD_SHAPE(

2)

R017 ³ Outer annular radius (m), ring 3: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

3)

R017 ³ Outer annular radius (m), ring 4: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

4)

R017 ³ Outer annular radius (m), ring 5: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

5)

R017 ³ Outer annular radius (m), ring 6: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

6)

R017 ³ Outer annular radius (m), ring 7: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

7)

R017 ³ Outer annular radius (m), ring 8: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

8)

R017 ³ Outer annular radius (m), ring 9: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

9)

R017 ³ Outer annular radius (m), ring 10: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (10)

R017 ³ Outer annular radius (m), ring 11: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (11)

R017 ³ Outer annular radius (m), ring 12: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (12)

³ ³ ³ ³ ³ R017 ³ Fractions of annular areas within AREA: ³ ³ ³ ³ R017 ³ Ring 1 ³ not used ³ 1.000E+00 ³ --- ³ FRACA( 1)

R017 ³ Ring 2 ³ not used ³ 2.732E-01 ³ --- ³ FRACA( 2)

R017 ³ Ring 3 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 3)

R017 ³ Ring 4 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 4)

R017 ³ Ring 5 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 5)

R017 ³ Ring 6 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 6)

R017 ³ Ring 7 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 7)

R017 ³ Ring 8 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 8)

R017 ³ Ring 9 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 9)

R017 ³ Ring 10 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(10)

R017 ³ Ring 11 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(11)

R017 ³ Ring 12 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(12)

³ ³ ³ ³ ³ 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 08:49 Page 5 Summary : Yankee Rowe Sensitivity Analysis=soil File: Sr-90_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R018 ³ Fruits, vegetables and grain consumption (kg/yr) ³ 1.120E+02 ³ 1.600E+02 ³ --- ³ DIET(1)

R018 ³ Leafy vegetable consumption (kg/yr) ³ 2.140E+01 ³ 1.400E+01 ³ --- ³ DIET(2)

R018 ³ Milk consumption (L/yr) ³ 2.330E+02 ³ 9.200E+01 ³ --- ³ DIET(3)

R018 ³ Meat and poultry consumption (kg/yr) ³ 6.510E+01 ³ 6.300E+01 ³ --- ³ DIET(4)

R018 ³ Fish consumption (kg/yr) ³ 2.060E+01 ³ 5.400E+00 ³ --- ³ DIET(5)

R018 ³ Other seafood consumption (kg/yr) ³ 9.000E-01 ³ 9.000E-01 ³ --- ³ DIET(6)

R018 ³ Soil ingestion rate (g/yr) ³ 1.826E+01 ³ 3.650E+01 ³ --- ³ SOIL R018 ³ Drinking water intake (L/yr) ³ 4.785E+02 ³ 5.100E+02 ³ --- ³ DWI R018 ³ Contamination fraction of drinking water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FDW R018 ³ Contamination fraction of household water ³ not used ³ 1.000E+00 ³ --- ³ FHHW R018 ³ Contamination fraction of livestock water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FLW R018 ³ Contamination fraction of irrigation water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FIRW R018 ³ Contamination fraction of aquatic food ³ 1.000E+00 ³ 5.000E-01 ³ --- ³ FR9 R018 ³ Contamination fraction of plant food ³ 1.000E+00 ³-1 ³ --- ³ FPLANT R018 ³ Contamination fraction of meat ³ 1.000E+00 ³-1 ³ --- ³ FMEAT R018 ³ Contamination fraction of milk ³ 1.000E+00 ³-1 ³ --- ³ FMILK

³ ³ ³ ³ ³ R019 ³ Livestock fodder intake for meat (kg/day) ³ 2.710E+01 ³ 6.800E+01 ³ --- ³ LFI5 R019 ³ Livestock fodder intake for milk (kg/day) ³ 6.320E+01 ³ 5.500E+01 ³ --- ³ LFI6 R019 ³ Livestock water intake for meat (L/day) ³ 5.060E+01 ³ 5.000E+01 ³ --- ³ LWI5 R019 ³ Livestock water intake for milk (L/day) ³ 6.000E+01 ³ 1.600E+02 ³ --- ³ LWI6 R019 ³ Livestock soil intake (kg/day) ³ 5.000E-01 ³ 5.000E-01 ³ --- ³ LSI R019 ³ Mass loading for foliar deposition (g/m**3) ³ 4.000E-04 ³ 1.000E-04 ³ --- ³ MLFD R019 ³ Depth of soil mixing layer (m) ³ 2.300E-01 ³ 1.500E-01 ³ --- ³ DM R019 ³ Depth of roots (m) ³ 1.170E+00 ³ 9.000E-01 ³ --- ³ DROOT R019 ³ Drinking water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWDW R019 ³ Household water fraction from ground water ³ not used ³ 1.000E+00 ³ --- ³ FGWHH R019 ³ Livestock water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWLW R019 ³ Irrigation fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWIR

³ ³ ³ ³ ³ R19B ³ Wet weight crop yield for Non-Leafy (kg/m**2) ³ 1.750E+00 ³ 7.000E-01 ³ --- ³ YV(1)

R19B ³ Wet weight crop yield for Leafy (kg/m**2) ³ 2.889E+00 ³ 1.500E+00 ³ --- ³ YV(2)

R19B ³ Wet weight crop yield for Fodder (kg/m**2) ³ 1.887E+00 ³ 1.100E+00 ³ --- ³ YV(3)

R19B ³ Growing Season for Non-Leafy (years) ³ 2.460E-01 ³ 1.700E-01 ³ --- ³ TE(1)

R19B ³ Growing Season for Leafy (years) ³ 1.230E-01 ³ 2.500E-01 ³ --- ³ TE(2)

R19B ³ Growing Season for Fodder (years) ³ 8.200E-02 ³ 8.000E-02 ³ --- ³ TE(3)

R19B ³ Translocation Factor for Non-Leafy ³ 1.000E-01 ³ 1.000E-01 ³ --- ³ TIV(1)

R19B ³ Translocation Factor for Leafy ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(2)

R19B ³ Translocation Factor for Fodder ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(3)

R19B ³ Dry Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(1)

R19B ³ Dry Foliar Interception Fraction for Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(2)

R19B ³ Dry Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(3)

R19B ³ Wet Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(1)

R19B ³ Wet Foliar Interception Fraction for Leafy ³ 5.800E-01 ³ 2.500E-01 ³ --- ³ RWET(2)

R19B ³ Wet Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(3)

R19B ³ Weathering Removal Constant for Vegetation ³ 3.300E+01 ³ 2.000E+01 ³ --- ³ WLAM

³ ³ ³ ³ ³ C14 ³ C-12 concentration in water (g/cm**3) ³ not used ³ 2.000E-05 ³ --- ³ C12WTR C14 ³ C-12 concentration in contaminated soil (g/g) ³ not used ³ 3.000E-02 ³ --- ³ C12CZ C14 ³ Fraction of vegetation carbon from soil ³ not used ³ 2.000E-02 ³ --- ³ CSOIL C14 ³ Fraction of vegetation carbon from air ³ not used ³ 9.800E-01 ³ --- ³ CAIR 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 08:49 Page 6 Summary : Yankee Rowe Sensitivity Analysis=soil File: Sr-90_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ C14 ³ C-14 evasion layer thickness in soil (m) ³ not used ³ 3.000E-01 ³ --- ³ DMC C14 ³ C-14 evasion flux rate from soil (1/sec) ³ not used ³ 7.000E-07 ³ --- ³ EVSN C14 ³ C-12 evasion flux rate from soil (1/sec) ³ not used ³ 1.000E-10 ³ --- ³ REVSN C14 ³ Fraction of grain in beef cattle feed ³ not used ³ 8.000E-01 ³ --- ³ AVFG4 C14 ³ Fraction of grain in milk cow feed ³ not used ³ 2.000E-01 ³ --- ³ AVFG5 C14 ³ DCF correction factor for gaseous forms of C14 ³ not used ³ 8.894E+01 ³ --- ³ CO2F

³ ³ ³ ³ ³ STOR ³ Storage times of contaminated foodstuffs (days): ³ ³ ³ ³ STOR ³ Fruits, non-leafy vegetables, and grain ³ 1.400E+01 ³ 1.400E+01 ³ --- ³ STOR_T(1)

STOR ³ Leafy vegetables ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(2)

STOR ³ Milk ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(3)

STOR ³ Meat and poultry ³ 2.000E+01 ³ 2.000E+01 ³ --- ³ STOR_T(4)

STOR ³ Fish ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(5)

STOR ³ Crustacea and mollusks ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(6)

STOR ³ Well water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(7)

STOR ³ Surface water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(8)

STOR ³ Livestock fodder ³ 4.500E+01 ³ 4.500E+01 ³ --- ³ STOR_T(9)

³ ³ ³ ³ ³ R021 ³ Thickness of building foundation (m) ³ not used ³ 1.500E-01 ³ --- ³ FLOOR1 R021 ³ Bulk density of building foundation (g/cm**3) ³ not used ³ 2.400E+00 ³ --- ³ DENSFL R021 ³ Total porosity of the cover material ³ not used ³ 4.000E-01 ³ --- ³ TPCV R021 ³ Total porosity of the building foundation ³ not used ³ 1.000E-01 ³ --- ³ TPFL R021 ³ Volumetric water content of the cover material ³ not used ³ 5.000E-02 ³ --- ³ PH2OCV R021 ³ Volumetric water content of the foundation ³ not used ³ 3.000E-02 ³ --- ³ PH2OFL R021 ³ Diffusion coefficient for radon gas (m/sec): ³ ³ ³ ³ R021 ³ in cover material ³ not used ³ 2.000E-06 ³ --- ³ DIFCV R021 ³ in foundation material ³ not used ³ 3.000E-07 ³ --- ³ DIFFL R021 ³ in contaminated zone soil ³ not used ³ 2.000E-06 ³ --- ³ DIFCZ R021 ³ Radon vertical dimension of mixing (m) ³ not used ³ 2.000E+00 ³ --- ³ HMIX R021 ³ Average building air exchange rate (1/hr) ³ not used ³ 5.000E-01 ³ --- ³ REXG R021 ³ Height of the building (room) (m) ³ not used ³ 2.500E+00 ³ --- ³ HRM R021 ³ Building interior area factor ³ not used ³ 0.000E+00 ³ --- ³ FAI R021 ³ Building depth below ground surface (m) ³ not used ³-1.000E+00 ³ --- ³ DMFL R021 ³ Emanating power of Rn-222 gas ³ not used ³ 2.500E-01 ³ --- ³ EMANA(1)

R021 ³ Emanating power of Rn-220 gas ³ not used ³ 1.500E-01 ³ --- ³ EMANA(2)

³ ³ ³ ³ ³ TITL ³ Number of graphical time points ³ 32 ³ --- ³ --- ³ NPTS TITL ³ Maximum number of integration points for dose ³ 17 ³ --- ³ --- ³ LYMAX TITL ³ Maximum number of integration points for risk ³ 1 ³ --- ³ --- ³ KYMAX

1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 08:49 Page 7 Summary : Yankee Rowe Sensitivity Analysis=soil File: Sr-90_DCGL.RAD Summary of Pathway Selections Pathway ³ User Selection

Å 1 -- external gamma ³ active 2 -- inhalation (w/o radon)³ active 3 -- plant ingestion ³ active 4 -- meat ingestion ³ active 5 -- milk ingestion ³ active 6 -- aquatic foods ³ active 7 -- drinking water ³ active 8 -- soil ingestion ³ active 9 -- radon ³ suppressed Find peak pathway doses ³ active

1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 08:59 Page 2 Summary : Yankee Rowe Sensitivity Analysis=soil File: Tc-99_DCGL.RAD Dose Conversion Factor (and Related) Parameter Summary File: YR soil DCGL lib 0 ³ ³ Current ³ ³ Parameter Menu ³ Parameter ³ Value ³ Default ³ Name

ÅÅÅÅ B-1 ³ Dose conversion factors for inhalation, mrem/pCi: ³ ³ ³ B-1 ³ Tc-99 ³ 8.330E-06 ³ 8.330E-06 ³ DCF2( 1)

³ ³ ³ ³ D-1 ³ Dose conversion factors for ingestion, mrem/pCi: ³ ³ ³ D-1 ³ Tc-99 ³ 1.460E-06 ³ 1.460E-06 ³ DCF3( 1)

³ ³ ³ ³ D-34 ³ Food transfer factors: ³ ³ ³ D-34 ³ Tc-99, plant/soil concentration ratio, dimensionless ³ 9.160E+00 ³ 5.000E+00 ³ RTF( 1,1)

D-34 ³ Tc-99, beef/livestock-intake ratio, (pCi/kg)/(pCi/d) ³ 1.000E-04 ³ 1.000E-04 ³ RTF( 1,2)

D-34 ³ Tc-99, milk/livestock-intake ratio, (pCi/L)/(pCi/d) ³ 1.000E-03 ³ 1.000E-03 ³ RTF( 1,3)

³ ³ ³ ³ D-5 ³ Bioaccumulation factors, fresh water, L/kg: ³ ³ ³ D-5 ³ Tc-99, fish ³ 2.000E+01 ³ 2.000E+01 ³ BIOFAC( 1,1)

D-5 ³ Tc-99, crustacea and mollusks ³ 5.000E+00 ³ 5.000E+00 ³ BIOFAC( 1,2) 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 08:59 Page 3 Summary : Yankee Rowe Sensitivity Analysis=soil File: Tc-99_DCGL.RAD Site-Specific Parameter Summary 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R011 ³ Area of contaminated zone (m**2) ³ 1.302E+04 ³ 1.000E+04 ³ --- ³ AREA R011 ³ Thickness of contaminated zone (m) ³ 1.975E+00 ³ 2.000E+00 ³ --- ³ THICK0 R011 ³ Length parallel to aquifer flow (m) ³ 1.290E+02 ³ 1.000E+02 ³ --- ³ LCZPAQ R011 ³ Basic radiation dose limit (mrem/yr) ³ 2.500E+01 ³ 2.500E+01 ³ --- ³ BRDL R011 ³ Time since placement of material (yr) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ TI R011 ³ Times for calculations (yr) ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ T( 2)

R011 ³ Times for calculations (yr) ³ 3.000E+00 ³ 3.000E+00 ³ --- ³ T( 3)

R011 ³ Times for calculations (yr) ³ 1.000E+01 ³ 1.000E+01 ³ --- ³ T( 4)

R011 ³ Times for calculations (yr) ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ T( 5)

R011 ³ Times for calculations (yr) ³ 1.000E+02 ³ 1.000E+02 ³ --- ³ T( 6)

R011 ³ Times for calculations (yr) ³ 3.000E+02 ³ 3.000E+02 ³ --- ³ T( 7)

R011 ³ Times for calculations (yr) ³ 1.000E+03 ³ 1.000E+03 ³ --- ³ T( 8)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T( 9)

R011 ³ Times for calculations (yr) ³ not used ³ 0.000E+00 ³ --- ³ T(10)

³ ³ ³ ³ ³ R012 ³ Initial principal radionuclide (pCi/g): Tc-99 ³ 1.000E+00 ³ 0.000E+00 ³ --- ³ S1( 1)

R012 ³ Concentration in groundwater (pCi/L): Tc-99 ³ not used ³ 0.000E+00 ³ --- ³ W1( 1)

³ ³ ³ ³ ³ R013 ³ Cover depth (m) ³ 0.000E+00 ³ 0.000E+00 ³ --- ³ COVER0 R013 ³ Density of cover material (g/cm**3) ³ not used ³ 1.500E+00 ³ --- ³ DENSCV R013 ³ Cover depth erosion rate (m/yr) ³ not used ³ 1.000E-03 ³ --- ³ VCV R013 ³ Density of contaminated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSCZ R013 ³ Contaminated zone erosion rate (m/yr) ³ 8.500E-04 ³ 1.000E-03 ³ --- ³ VCZ R013 ³ Contaminated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPCZ R013 ³ Contaminated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCCZ R013 ³ Contaminated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCCZ R013 ³ Contaminated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BCZ R013 ³ Average annual wind speed (m/sec) ³ 2.030E+00 ³ 2.000E+00 ³ --- ³ WIND R013 ³ Humidity in air (g/m**3) ³ not used ³ 8.000E+00 ³ --- ³ HUMID R013 ³ Evapotranspiration coefficient ³ 6.250E-01 ³ 5.000E-01 ³ --- ³ EVAPTR R013 ³ Precipitation (m/yr) ³ 1.200E+00 ³ 1.000E+00 ³ --- ³ PRECIP R013 ³ Irrigation (m/yr) ³ 4.350E-01 ³ 2.000E-01 ³ --- ³ RI R013 ³ Irrigation mode ³ overhead ³ overhead ³ --- ³ IDITCH R013 ³ Runoff coefficient ³ 6.000E-01 ³ 2.000E-01 ³ --- ³ RUNOFF R013 ³ Watershed area for nearby stream or pond (m**2) ³ 7.770E+05 ³ 1.000E+06 ³ --- ³ WAREA R013 ³ Accuracy for water/soil computations ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ EPS

³ ³ ³ ³ ³ R014 ³ Density of saturated zone (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSAQ R014 ³ Saturated zone total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPSZ R014 ³ Saturated zone effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPSZ R014 ³ Saturated zone field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCSZ R014 ³ Saturated zone hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+02 ³ --- ³ HCSZ R014 ³ Saturated zone hydraulic gradient ³ 1.000E-01 ³ 2.000E-02 ³ --- ³ HGWT R014 ³ Saturated zone b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BSZ R014 ³ Water table drop rate (m/yr) ³ 1.000E-03 ³ 1.000E-03 ³ --- ³ VWT R014 ³ Well pump intake depth (m below water table) ³ 1.451E+01 ³ 1.000E+01 ³ --- ³ DWIBWT R014 ³ Model: Nondispersion (ND) or Mass-Balance (MB) ³ ND ³ ND ³ --- ³ MODEL R014 ³ Well pumping rate (m**3/yr) ³ 1.323E+03 ³ 2.500E+02 ³ --- ³ UW

³ ³ ³ ³ ³ R015 ³ Number of unsaturated zone strata ³ 1 ³ 1 ³ --- ³ NS 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 08:59 Page 4 Summary : Yankee Rowe Sensitivity Analysis=soil File: Tc-99_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R015 ³ Unsat. zone 1, thickness (m) ³ 1.820E+00 ³ 4.000E+00 ³ --- ³ H(1)

R015 ³ Unsat. zone 1, soil density (g/cm**3) ³ 1.510E+00 ³ 1.500E+00 ³ --- ³ DENSUZ(1)

R015 ³ Unsat. zone 1, total porosity ³ 4.300E-01 ³ 4.000E-01 ³ --- ³ TPUZ(1)

R015 ³ Unsat. zone 1, effective porosity ³ 3.830E-01 ³ 2.000E-01 ³ --- ³ EPUZ(1)

R015 ³ Unsat. zone 1, field capacity ³ 5.000E-02 ³ 2.000E-01 ³ --- ³ FCUZ(1)

R015 ³ Unsat. zone 1, soil-specific b parameter ³ 9.750E-01 ³ 5.300E+00 ³ --- ³ BUZ(1)

R015 ³ Unsat. zone 1, hydraulic conductivity (m/yr) ³ 2.506E+03 ³ 1.000E+01 ³ --- ³ HCUZ(1)

³ ³ ³ ³ ³ R016 ³ Distribution coefficients for Tc-99 ³ ³ ³ ³ R016 ³ Contaminated zone (cm**3/g) ³ 4.280E+00 ³ 0.000E+00 ³ --- ³ DCNUCC( 1)

R016 ³ Unsaturated zone 1 (cm**3/g) ³ 5.100E-01 ³ 0.000E+00 ³ --- ³ DCNUCU( 1,1)

R016 ³ Saturated zone (cm**3/g) ³ 5.100E-01 ³ 0.000E+00 ³ --- ³ DCNUCS( 1)

R016 ³ Leach rate (/yr) ³ 0.000E+00 ³ 0.000E+00 ³ 2.658E-02 ³ ALEACH( 1)

R016 ³ Solubility constant ³ 0.000E+00 ³ 0.000E+00 ³ not used ³ SOLUBK( 1)

³ ³ ³ ³ ³ R017 ³ Inhalation rate (m**3/yr) ³ 8.400E+03 ³ 8.400E+03 ³ --- ³ INHALR R017 ³ Mass loading for inhalation (g/m**3) ³ 2.330E-05 ³ 1.000E-04 ³ --- ³ MLINH R017 ³ Exposure duration ³ 3.000E+01 ³ 3.000E+01 ³ --- ³ ED R017 ³ Shielding factor, inhalation ³ 5.500E-01 ³ 4.000E-01 ³ --- ³ SHF3 R017 ³ Shielding factor, external gamma ³ 2.725E-01 ³ 7.000E-01 ³ --- ³ SHF1 R017 ³ Fraction of time spent indoors ³ 6.571E-01 ³ 5.000E-01 ³ --- ³ FIND R017 ³ Fraction of time spent outdoors (on site) ³ 1.181E-01 ³ 2.500E-01 ³ --- ³ FOTD R017 ³ Shape factor flag, external gamma ³ 1.000E+00 ³ 1.000E+00 ³ >0 shows circular AREA. ³ FS R017 ³ Radii of shape factor array (used if FS = -1): ³ ³ ³ ³ R017 ³ Outer annular radius (m), ring 1: ³ not used ³ 5.000E+01 ³ --- ³ RAD_SHAPE(

1)

R017 ³ Outer annular radius (m), ring 2: ³ not used ³ 7.071E+01 ³ --- ³ RAD_SHAPE(

2)

R017 ³ Outer annular radius (m), ring 3: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

3)

R017 ³ Outer annular radius (m), ring 4: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

4)

R017 ³ Outer annular radius (m), ring 5: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

5)

R017 ³ Outer annular radius (m), ring 6: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

6)

R017 ³ Outer annular radius (m), ring 7: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

7)

R017 ³ Outer annular radius (m), ring 8: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

8)

R017 ³ Outer annular radius (m), ring 9: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE(

9)

R017 ³ Outer annular radius (m), ring 10: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (10)

R017 ³ Outer annular radius (m), ring 11: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (11)

R017 ³ Outer annular radius (m), ring 12: ³ not used ³ 0.000E+00 ³ --- ³ RAD_SHAPE (12)

³ ³ ³ ³ ³ R017 ³ Fractions of annular areas within AREA: ³ ³ ³ ³ R017 ³ Ring 1 ³ not used ³ 1.000E+00 ³ --- ³ FRACA( 1)

R017 ³ Ring 2 ³ not used ³ 2.732E-01 ³ --- ³ FRACA( 2)

R017 ³ Ring 3 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 3)

R017 ³ Ring 4 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 4)

R017 ³ Ring 5 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 5)

R017 ³ Ring 6 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 6)

R017 ³ Ring 7 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 7)

R017 ³ Ring 8 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 8)

R017 ³ Ring 9 ³ not used ³ 0.000E+00 ³ --- ³ FRACA( 9)

R017 ³ Ring 10 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(10)

R017 ³ Ring 11 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(11)

R017 ³ Ring 12 ³ not used ³ 0.000E+00 ³ --- ³ FRACA(12)

³ ³ ³ ³ ³ 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 08:59 Page 5 Summary : Yankee Rowe Sensitivity Analysis=soil File: Tc-99_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ R018 ³ Fruits, vegetables and grain consumption (kg/yr) ³ 1.120E+02 ³ 1.600E+02 ³ --- ³ DIET(1)

R018 ³ Leafy vegetable consumption (kg/yr) ³ 2.140E+01 ³ 1.400E+01 ³ --- ³ DIET(2)

R018 ³ Milk consumption (L/yr) ³ 2.330E+02 ³ 9.200E+01 ³ --- ³ DIET(3)

R018 ³ Meat and poultry consumption (kg/yr) ³ 6.510E+01 ³ 6.300E+01 ³ --- ³ DIET(4)

R018 ³ Fish consumption (kg/yr) ³ 2.060E+01 ³ 5.400E+00 ³ --- ³ DIET(5)

R018 ³ Other seafood consumption (kg/yr) ³ 9.000E-01 ³ 9.000E-01 ³ --- ³ DIET(6)

R018 ³ Soil ingestion rate (g/yr) ³ 1.826E+01 ³ 3.650E+01 ³ --- ³ SOIL R018 ³ Drinking water intake (L/yr) ³ 4.785E+02 ³ 5.100E+02 ³ --- ³ DWI R018 ³ Contamination fraction of drinking water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FDW R018 ³ Contamination fraction of household water ³ not used ³ 1.000E+00 ³ --- ³ FHHW R018 ³ Contamination fraction of livestock water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FLW R018 ³ Contamination fraction of irrigation water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FIRW R018 ³ Contamination fraction of aquatic food ³ 1.000E+00 ³ 5.000E-01 ³ --- ³ FR9 R018 ³ Contamination fraction of plant food ³ 1.000E+00 ³-1 ³ --- ³ FPLANT R018 ³ Contamination fraction of meat ³ 1.000E+00 ³-1 ³ --- ³ FMEAT R018 ³ Contamination fraction of milk ³ 1.000E+00 ³-1 ³ --- ³ FMILK

³ ³ ³ ³ ³ R019 ³ Livestock fodder intake for meat (kg/day) ³ 2.710E+01 ³ 6.800E+01 ³ --- ³ LFI5 R019 ³ Livestock fodder intake for milk (kg/day) ³ 6.320E+01 ³ 5.500E+01 ³ --- ³ LFI6 R019 ³ Livestock water intake for meat (L/day) ³ 5.060E+01 ³ 5.000E+01 ³ --- ³ LWI5 R019 ³ Livestock water intake for milk (L/day) ³ 6.000E+01 ³ 1.600E+02 ³ --- ³ LWI6 R019 ³ Livestock soil intake (kg/day) ³ 5.000E-01 ³ 5.000E-01 ³ --- ³ LSI R019 ³ Mass loading for foliar deposition (g/m**3) ³ 4.000E-04 ³ 1.000E-04 ³ --- ³ MLFD R019 ³ Depth of soil mixing layer (m) ³ 2.300E-01 ³ 1.500E-01 ³ --- ³ DM R019 ³ Depth of roots (m) ³ 1.170E+00 ³ 9.000E-01 ³ --- ³ DROOT R019 ³ Drinking water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWDW R019 ³ Household water fraction from ground water ³ not used ³ 1.000E+00 ³ --- ³ FGWHH R019 ³ Livestock water fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWLW R019 ³ Irrigation fraction from ground water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ FGWIR

³ ³ ³ ³ ³ R19B ³ Wet weight crop yield for Non-Leafy (kg/m**2) ³ 1.750E+00 ³ 7.000E-01 ³ --- ³ YV(1)

R19B ³ Wet weight crop yield for Leafy (kg/m**2) ³ 2.889E+00 ³ 1.500E+00 ³ --- ³ YV(2)

R19B ³ Wet weight crop yield for Fodder (kg/m**2) ³ 1.887E+00 ³ 1.100E+00 ³ --- ³ YV(3)

R19B ³ Growing Season for Non-Leafy (years) ³ 2.460E-01 ³ 1.700E-01 ³ --- ³ TE(1)

R19B ³ Growing Season for Leafy (years) ³ 1.230E-01 ³ 2.500E-01 ³ --- ³ TE(2)

R19B ³ Growing Season for Fodder (years) ³ 8.200E-02 ³ 8.000E-02 ³ --- ³ TE(3)

R19B ³ Translocation Factor for Non-Leafy ³ 1.000E-01 ³ 1.000E-01 ³ --- ³ TIV(1)

R19B ³ Translocation Factor for Leafy ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(2)

R19B ³ Translocation Factor for Fodder ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ TIV(3)

R19B ³ Dry Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(1)

R19B ³ Dry Foliar Interception Fraction for Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(2)

R19B ³ Dry Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RDRY(3)

R19B ³ Wet Foliar Interception Fraction for Non-Leafy ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(1)

R19B ³ Wet Foliar Interception Fraction for Leafy ³ 5.800E-01 ³ 2.500E-01 ³ --- ³ RWET(2)

R19B ³ Wet Foliar Interception Fraction for Fodder ³ 3.500E-01 ³ 2.500E-01 ³ --- ³ RWET(3)

R19B ³ Weathering Removal Constant for Vegetation ³ 3.300E+01 ³ 2.000E+01 ³ --- ³ WLAM

³ ³ ³ ³ ³ C14 ³ C-12 concentration in water (g/cm**3) ³ not used ³ 2.000E-05 ³ --- ³ C12WTR C14 ³ C-12 concentration in contaminated soil (g/g) ³ not used ³ 3.000E-02 ³ --- ³ C12CZ C14 ³ Fraction of vegetation carbon from soil ³ not used ³ 2.000E-02 ³ --- ³ CSOIL C14 ³ Fraction of vegetation carbon from air ³ not used ³ 9.800E-01 ³ --- ³ CAIR 1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 08:59 Page 6 Summary : Yankee Rowe Sensitivity Analysis=soil File: Tc-99_DCGL.RAD Site-Specific Parameter Summary (continued) 0 ³ ³ User ³ ³ Used by RESRAD ³ Parameter Menu ³ Parameter ³ Input ³ Default ³ (If different from user input) ³ Name

ÅÅÅÅÅ C14 ³ C-14 evasion layer thickness in soil (m) ³ not used ³ 3.000E-01 ³ --- ³ DMC C14 ³ C-14 evasion flux rate from soil (1/sec) ³ not used ³ 7.000E-07 ³ --- ³ EVSN C14 ³ C-12 evasion flux rate from soil (1/sec) ³ not used ³ 1.000E-10 ³ --- ³ REVSN C14 ³ Fraction of grain in beef cattle feed ³ not used ³ 8.000E-01 ³ --- ³ AVFG4 C14 ³ Fraction of grain in milk cow feed ³ not used ³ 2.000E-01 ³ --- ³ AVFG5 C14 ³ DCF correction factor for gaseous forms of C14 ³ not used ³ 8.894E+01 ³ --- ³ CO2F

³ ³ ³ ³ ³ STOR ³ Storage times of contaminated foodstuffs (days): ³ ³ ³ ³ STOR ³ Fruits, non-leafy vegetables, and grain ³ 1.400E+01 ³ 1.400E+01 ³ --- ³ STOR_T(1)

STOR ³ Leafy vegetables ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(2)

STOR ³ Milk ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(3)

STOR ³ Meat and poultry ³ 2.000E+01 ³ 2.000E+01 ³ --- ³ STOR_T(4)

STOR ³ Fish ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(5)

STOR ³ Crustacea and mollusks ³ 7.000E+00 ³ 7.000E+00 ³ --- ³ STOR_T(6)

STOR ³ Well water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(7)

STOR ³ Surface water ³ 1.000E+00 ³ 1.000E+00 ³ --- ³ STOR_T(8)

STOR ³ Livestock fodder ³ 4.500E+01 ³ 4.500E+01 ³ --- ³ STOR_T(9)

³ ³ ³ ³ ³ R021 ³ Thickness of building foundation (m) ³ not used ³ 1.500E-01 ³ --- ³ FLOOR1 R021 ³ Bulk density of building foundation (g/cm**3) ³ not used ³ 2.400E+00 ³ --- ³ DENSFL R021 ³ Total porosity of the cover material ³ not used ³ 4.000E-01 ³ --- ³ TPCV R021 ³ Total porosity of the building foundation ³ not used ³ 1.000E-01 ³ --- ³ TPFL R021 ³ Volumetric water content of the cover material ³ not used ³ 5.000E-02 ³ --- ³ PH2OCV R021 ³ Volumetric water content of the foundation ³ not used ³ 3.000E-02 ³ --- ³ PH2OFL R021 ³ Diffusion coefficient for radon gas (m/sec): ³ ³ ³ ³ R021 ³ in cover material ³ not used ³ 2.000E-06 ³ --- ³ DIFCV R021 ³ in foundation material ³ not used ³ 3.000E-07 ³ --- ³ DIFFL R021 ³ in contaminated zone soil ³ not used ³ 2.000E-06 ³ --- ³ DIFCZ R021 ³ Radon vertical dimension of mixing (m) ³ not used ³ 2.000E+00 ³ --- ³ HMIX R021 ³ Average building air exchange rate (1/hr) ³ not used ³ 5.000E-01 ³ --- ³ REXG R021 ³ Height of the building (room) (m) ³ not used ³ 2.500E+00 ³ --- ³ HRM R021 ³ Building interior area factor ³ not used ³ 0.000E+00 ³ --- ³ FAI R021 ³ Building depth below ground surface (m) ³ not used ³-1.000E+00 ³ --- ³ DMFL R021 ³ Emanating power of Rn-222 gas ³ not used ³ 2.500E-01 ³ --- ³ EMANA(1)

R021 ³ Emanating power of Rn-220 gas ³ not used ³ 1.500E-01 ³ --- ³ EMANA(2)

³ ³ ³ ³ ³ TITL ³ Number of graphical time points ³ 32 ³ --- ³ --- ³ NPTS TITL ³ Maximum number of integration points for dose ³ 17 ³ --- ³ --- ³ LYMAX TITL ³ Maximum number of integration points for risk ³ 1 ³ --- ³ --- ³ KYMAX

1RESRAD, Version 6.21 T<< Limit = 0.5 year 11/28/2003 08:59 Page 7 Summary : Yankee Rowe Sensitivity Analysis=soil File: Tc-99_DCGL.RAD Summary of Pathway Selections Pathway ³ User Selection

Å 1 -- external gamma ³ active 2 -- inhalation (w/o radon)³ active 3 -- plant ingestion ³ active 4 -- meat ingestion ³ active 5 -- milk ingestion ³ active 6 -- aquatic foods ³ active 7 -- drinking water ³ active 8 -- soil ingestion ³ active 9 -- radon ³ suppressed Find peak pathway doses ³ active