Appendix D Scenario Outline Form ES-D-1 3

4 5

Facility:

I P2 Scenario No.:

4 Op Test No.:

1 Examiners:

Candidates:

CRS RO MOT-CFWOOI B MAL-SG N 004A PLP-RHR022 RLY-PPL487 RLY-PPL488 PO Initial Conditions: 50% power MOL 21 Charging Pump 00s 21 CCW Pump 00s Small SG Tube Leak Turbine 21 rupture disc is leaking. Reduce Power to 250 MWe at 200 MWe per hour and remove Main Turbine and Generator from service 5 GPD Tu mover:

Critical Tasks:

Manually actuate at least one train of SIS-actuated safeguards before any of the following:

Transition to any E-1 series, E-2 series, or E-3 series procedure or transition to any FRP Completion of step 5.a of ES-0.1 Trip all RCPs prior to completion of E-0 step 12 Isolate the LOCA outside of containment before transition out of ECA-1.2 I

Event Malf. No..r I

7-=--

CRF002AV Event Description Reduce load Rod P-6 Dropped Rod during rod motion C (CRS) 1 21 Condensate Pump Failure M (ALL)

Steam Line Rupture Downstream of MSIVs. RCS Leak Outside of vc.

Failure of automatic actuation of Safety Injection. Manual initiation required.

tivity, (I)nstrument, (C)omponent, (M)ajor

Scenario Event Description IP2 Simulator Scenario 4 The team will assume the shift and continue with a load reduction in progress in accordance with POP-3.1, beginning at step 4.14.

When rod motion occurs, Control Rod P-6 will ratchet into the core due to a moving gripper failure, requiring the load reduction to be stopped and the condition evaluated IAW AOP-ROD-1.

When the plant is stable, a bearing failure on 21 Condensate Pump will occur. The team will start the standby Condensate Pump IAW AOP-FW-1, Loss of Feedwater.

When SG Levels are stable, a Steam Line Rupture downstream of the MSlVs will occur, requiring a reactor trip. Subsequently, Automatic SI actuation will fail to occur when demanded, requiring manual actuation. Simultaneous with reactor trip, a rupture will occur on the RHR discharge header outside of containment.

EOP flow path: E ECA-1.2 - E-I

Indian Point Unit 2 2003 NRC Initial License Examination Simulator Scenario Setup Scenario 4 Reset simulator to IC-226 (PW nano1007)

Place diskette in A drive Click the button to run batch file New#l.bat and verify that the following malfunctions are active or Pendina:

21 Charging Pump 00s:

21 CCW Pump 00s:

IRF LOA-EPSO10 (-1 0) OUT Place pump control switch in TPO and apply danger tag IRF LOA-EPS013 (-1 0) OUT Place pump control switch in TPO and apply danger tag Auto SI Master Relays Stuck Contacts IMF RLY-PPL487 (-1 0) 2 IMF RLY-PPL488 (-1 0) 2 MAL-CRF002AV P6 Dropped Rod IMF MAL-CRF002AV (-1 0) 1 BRG I Failure Condensate Pump 21 MTR IMF MOT-CFW001B (2 0) 0.000 600 0.000 Event trigger #2 S/G 21 HDR LEAK DNSTRM CHK VLV MAL-SGN004A Event trigger #3 RHR PUMP DISCHARGE HDR Leak IMF FLX-RHR008 (30 0) 0.000 0 0.000 IRF PLP-RHR033 (30 0) 100.000 0 IRF PLP-RHR022 (30 0) 100.000 0 Event trigger #30 on reactor trip Materials needed for scenario:

0 Graph Book 0

Tags for tagged equipment 0

Reactivity Summary Sheet POP-3.1 marked up to step 4.14 Note: None

Indian Point Unit 2 2003 NRC Initial License Examination Simulator Scenario Turnover Information Scenario 4 The plant is at 50% power, steady state conditions exist.

Middle of Life, Cb is 1029 ppm.

EFPD = 340 Control Bank D = 195 steps Tavg = 553.5 O F RCS Pressure = 2235 psig Pressurizer Level = 42%

A small Steam Generator Tube Leak exists on 23 SG, less than 5 gallons per day.

Risk Assessment = GREEN Daily Risk Factor = 0.94 The followinq equipment is out of service:

0 21 Charging Pump. Return expected in approximately 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

21 Component Cooling Water Pump. Return to service in approximately 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />.

Team instructions:

0 0

The Main Turbine 21 Rupture Disc is leaking approximately 12 SCFM.

In accordance with POP-3.1, continue to shut down at a rate of 200 MWe per hour and remove the Main Turbine and Generator from service.

Appendix D Operator Action Form ES-D-2 Scenario#

4 Event#

1 Reduce Load CRS RO RO RO BOP RO RO Note: Proceed to event 2 when rod motion causes the droppedlmisaligned rod malfunction to occur.

Refers to POP 3.1 Note: CRS may review previously performed steps in the POP to verify that they have been completed.

BORATE per SOP 3.2, Reactor Coolant System Boron Concentration Control, as necessary to maintain control banks above insertion limits required by GRAPH RPCB, Cycle 14 Core Operating Limits Report.

Note: Actions for boration are on pages 7 of this scenario guide necessary, PLACE rod control in MANUAL to maintain rods above the Insertion Limit.

MAINTAIN delta flux within the target band.

MONITOR condenser sextants for sodium increase.

JERIFY TAvF AND Pressurizer Level are maintained on Drogram per Graph RCS-2, Pressurizer Level V.S. TAVE.

MAINTAIN steam generator levels between 40 and 50 percent qarrow Ranae.

Appendix D Operator Action Form ES-D-2 RO 11 Op Test No.:

1 Scenario#

4 Event#

1 NULL manual setpoint on feedwater regulating valve control to facilitate rapid transfer from AUTOMATIC to MANUAL control.

Event

Description:

Reduce Load I

NOTE WHEN erratic governor operation is observed, governor oil pressure may be raised above the controlling load limit to avoid adverse Main Turbine operation.

RO INITIATE load decrease using either of the following as directed by CRS:

o Governor control o Load Limit control

_ _ _ _ _ _ ~ _ _ _ _

Appendix D Operator Axon Form ES-D-2 Op Test No.:

1 Scenario#

4 Event#

1 I

Event

Description:

Reduce Load Refers to SOP-3.2 for boration RO DETERMINE RCS Boron concentration from reactor coolant sample analysis.

RO o

analysis following concentration adjustment is NOT yet available, ESTIMATE Boron concentration based on latest readings.

t I

I NOTE Determinations should be based upon rod position, RCS Boron concentration, Xenon level variations. incremental Boron and rod worth, and operating experience.

RO RO DETERMINE magnitude of increase in Boron concentration necessary to accomplish desired reactivity change using one or more of the following references:

o GRAPH CVCS-3A, Boration Nomograph for Hot RCS o GRAPH CVCS-3B, Boration Nomograph for Cold RCS o GRAPH CVCS-6, Boration - Dilution Tables o GRAPH RV-2, Total Power Defect (PCM) as a Function of Power and Boron Concentration at MOL o GRAPH RV-3, Differential Boron Worth (Hot Zero Power) at MOL o GRAPH RV-4, Total Temperature Defect (PCM) as a Function of Temperature and Boron Concentration at MOL o GRAPH RV-9, IP2 Cycle 15 Reactivity Equivalents o POP 1.2, Reactor Startup o WCR 1, Reactivity Summary IF the change in RCS Boron concentration is anticipated to be greater than or equal to 25 ppm, OPERATE Pressurizer heaters to open spray valve.

Appendix D Operator Action Form ES-D-2 Event

Description:

Reduce Load RO ESTIMATE total volume of boron required for boration from boration graphs or references listed in step 4.5.2.

PLACE the RCS Makeup Control switch to STOP.

RO RO SET Boric Acid Integrator to amount determined in step 4.5.3.

RO FCV-1 IOA, Boric Acid Flow Control, may be left in AUTO or placed in MANUAL as directed by CRS.

PLACE the RCS Makeup Mode Selector switch to BORATE.

RO VERIFY boric acid transfer pumps are in AUTO.

RO RO PLACE the RCS Makeup Control switch to START.

NOTE 3ATPs shifting to fast speed is verified by both counter operation and by the respective ast speed lights illuminating.

I Ro VERIFY BATPs shift to fast speed.

IF in manual, ADJUST FCV-1 I OA, Boric Acid Flow Control, to obtain desired boric acid flow rate (may be greater than meter range).

~

Appendix D Operator Action Form ES-D-2 Op Test No.:

1 Scenario#

4 Event#

1 Page 9

of 25 Event

Description:

Reduce Load Time 11 Position 11 Applicants Actions or Behavior RO RO RO RO RO IF desired to maximize Boron flow, CLOSE the appropriate BATP recirculation valve.

o HCV-104 Inlet Inlet o HCV-105 CVCS/Boric Acid Tank 22 BA CVCS/Boric Acid Tank 21 BA MONITOR Nuclear Instrumentation, Rod position, and RCS temperature closely during any reactivity changes.

WHEN boration operation has been completed, PERFORM the following:

o PLACE the RCS Makeup Control switch to STOP.

o PLACE the Makeup Mode Selector switch to MANUAL.

o ADJUST FCV-11 OA, Boric Acid Flow Control, dial setting to the new RCS Boron concentration per applicable CVCS Graph:

o GRAPH CVCS-IA, Blended Makeup - (0-500) with 120 Gpm PW o GRAPH CVCS-1 B, Blended Makeup - (0-2000) with 120 Gpm PW o GRAPH CVCS-IC, Blended Makeup with Various PW Flows VERIFY FCV-11 OA control switch in AUTO.

PLACE the RCS Makeup Control switch to START.

Appendix D Operator Action Form ES-D-2

~

10 of 25 1 p Test No.:

1 Scenario#

4 Event#

1 Page Event

Description:

Reduce Load Time 11 Position 11 Applicant's Actions or Behavior I

RO RO

~

RO RO CRS RO VERIFY approximately 30 gallons of blended makeup flows through blender.

PLACE RCS Makeup Control switch to STOP.

SELECT AUTO on RCS Makeup Mode Selector switch.

PLACE the RCS Makeup Control switch to START.

IF Reactor is shutdown, REQUEST a sample for RCS Boron concentration within 30 minutes of completing the boration.

LOG amount of boric acid added to system for boration in CCR Log Book.

When rod motion occurs, proceed to event 2

Page 11 of 25 -

Op Test No.:

1 Scenario#

4 Event#

2 Event

Description:

Misaligned/Dropped Control Rod P-6 Time 11 Position 11 Applicant's Actions or Behavior CRS Booth Instructor: When rod motion occurs, Control Rod P-6 should ratchet into the core.

Implements AOP-ROD-1 Rod Control and Indication Systems Malfunctions Note: The more Control Bank D inserts the more deviation rod P-6 will exDerience.

RO Indications received:

Alarm SF 2-7 Control Rod or Power Distribution Trouble Alarm FC 2-4 NIS Power Range Channel Deviation 3%

Control Rod P-6 IRPI indicates lower than the rest of Control Bank D PlCS alarms for Rod to Bank deviation and Rod to Rod deviation Determines continuous unwarranted rod motion is NOT occurring.

RO Determines that indication of a dropped or misaligned rod or IRPl failure exists.

Diagnoses malfunction as a misaligned control rod RO

Appendix D Operator Action Form ES-D-2 c

I OpTest 1

Scenario#

4 Event#

2 Event

Description:

Misaligned/Dropped Control Rod P-6 RO CRS CRS RO Places rod control in MANUAL Refers to the following Technical Specifications 0 3.1 0.3, Quadrant Power Tilt Limits 0

3.10.5, Rod Misalignment Limitations 0

3.10.7, Inoperable Rod Limitations Notify I&C to investigate for cause of misaligned rod Determines actual position of misaligned rod Booth Operator: Call as I&C and inform that time compression is being utilised.

I&C has determined that the cause of the failure was a blown fuse and the fuse has been replaced.

Initiates a CR to document malfunction Determines that affected rod is below remainder of rods in its group.

Appendix D Operator Action Form ES-D-2 Op Test No.:

1 Scenario#

4 Event#

2 Page 13 of 25 Event

Description:

MisalignedlDropped Control Rod P-6 1

Time 1

Position

[

Applicants Actions or Behavior 11 Obtains the following from Reactor Engineer:

Booth Operator: Respond as RE that reactor should stay at or below current power level for rod withdrawal, and no rate limitation on withdrawal.

When ready to realign the rod, or at Lead Evaluators discretion, proceed to Event 3

Amendix D ODerator Action Form ES-D-2 CRS 1

1 Direct performance of immediate actions of AOP-FW-I Loss of Feedwater Op Test No.:

1 Scenario#

4 Event#

3 Event

Description:

21 Condensate Pump Trips RO Booth Instructor: When directed by lead evaluator, insert the following command:

TRG!2, Actuates event trigger 2:

Checks if any MBFP is operating (yes)

Announces immediate actions complete 1 BRG 1 Failure Condensate Pump 21 MTR IMFMOT-CFW001B (2 0) 100 600 0.000 Indications available:

Increasing amps on panel SC meter for 21 Condensate Pump Amps 21 MBFP speed slowly increases Alarm SE 3-2 Bearing Monitor after about 3 minutes 21 Condensate Pump trips after about 4.5 minutes After pump trip:

S/G levels decrease Multiple S/G level alarms 21 MBFP Low Suction Pressure Cutback actuates Diagnoses 21 Condensate Pump malfunction BOP NOTE: The CRS may direct the BOP operator to manually trip 21 Condensate pump due to indications of failure.

Reviews Immediate actions using the procedure CRS Determine that a Condensate Pump has tripped ALL I

Amendix D ODerator Action Form ES-D-2 c

Page 15 of 25 -

Op Test No.:

1 Scenario#

4 Event#

3 Event

Description:

21 Condensate Pump Trips Time 11 Position

1)

Applicant's Actions or Behavior I

BOP I

Ro RO Evaluator Note: Conti Determine that 22 Condensate pump is not running Start 22 Condensate Pump Check if load reduction is necessary to maintain FF>SF and MBFP suction pressure >310 (expected result is no load reduction necessary)

Check Tave maintained on program Check if MBFP suction pressure cutback is actuating ue with Event 4 when SG levels are increasing with FF>SF, or at the discretion of the lead evaluator

Amendix D ODerator Action Form ES-D-2 1

Op Test No.:

1 Scenario#

4 Event#

4,5 Page 16 of 25 Event

Description:

Steam Line Rupture, Auto SI Actuation Failure, LOCA Outside Containment CRS I Booth Instructor: When directed, insert the followina command:

Direct reactor trip and entry to E-0, Reactor Trip or Safety Injection TRG!3, Actuates Event Trigger 3 S/G 21 HDR LEAK DNSTRM CHK VLV IMF MAL-SGN004A (3 0) 25 180 0.000 I Actuates when reactor trip breakers open:

RHR PUMP DISCHARGE HDR Leak '

IMF FLX-RHR008 (30 0) 100 0.00 0 IRF PLP-RHR033 (30 0) 100.000 0 IRF PLP-RHR022 (30 0) 100.000 0 Indications available:

Reactor Power Increases Turbine Load Decreases S/G levels increase ALARM SA 3-2, PZR Low Pressure 2185 ALARM SA 3-3, PZR Low Level Auto Reactor Trip SI First Out Alarm Determine reactor trip required.

TEAM Verify reactor trip RO Verify Turbine Trip RO Verify Power to 480 V Buses BOP

Appendix D Operator Action Form ES-D-2 Op Test No.:

Scenario#

4 Event#

4, 5 Event

Description:

Steam Line Rupture, Auto SI Actuation Failure, LOCA Outside Containment Critical Task:

Manually actuate at least one train of SIS-actuated safeguards before any of the following:

0 Transition to any E-I series, E-2 series, or E-3 series procedure or transition to any FRP o

Completion of step 5.a of ES-0.1

)Critical I F

RO CRS/BOP RO RO RO Check if SI is actuated (no)

Determines that SI is required but not actuated.

PERFORMS Manual SI actuation by depressing both manual SI actuation pushbuttons on panel SB-2 CRS directs BOP to perform E-0 Attachment 1 Verify AFW Pumps Running (yes)

Verify total AFW flow greater than 400 gpm (yes)

Verify SI System Flow Places one RHR pump to pullout Call as Nuclear Watch NPO and report a large leak of apparently RCS steamlLiquid in the piping penetration area. The leak appears to be on RHR discharge piping and you cannot get close due to steam temperature and radiation levels.

Check RCP Seal Cooling Starts 22 Service Water Pump

~~

~

~

Appendix D

~

Operator Action

~

Form ES-D-2 Op Test No.:

1 Scenario#

4 Event#

4,5 Page -

18 of 25 11 Event

Description:

Steam Line Rupture, Auto SI Actuation Failure, LOCA Outside Containment Time I Position 11 Applicants Actions or Behavior Check RCS Temperatures RO Check PRZR PORVs and Spray valves closed I

I Critical Task 1 Trip all RCPs prior to completion of E-0 step 12 Critical Task TEAM RO RO RO RO CRS/BOP CRS Check if RCPs should be stopped Check SI pumps -At Least One Running Checks subcooling less than 23°F.

PERFORMS - Stops all RCPs Check if any SG is faulted (no)

Check if SG tubes are Intact (yes)

Check if RCS is intact (yes)

NOTE: All containment parameters are normal Check if SI should be terminated (no)

Check icAttachmen7 is complete.

Initiate monitoring of CSF Status trees

Appendix D Operator Action Form ES-D-2 1

1 Page Of "_I 1

Scenario#

4 Event#

4,5 I OP Test No.: -

Event

Description:

Steam Line Rupture, Auto SI Actuation Failure, LOCA Outside Containment RO RO RO RO TEAM CRS RO CRS/RO BOP BOP Reset SI Check if RHR Pumps should be stopped (yes)

Check SG Levels Check PAB Radiation - Normal (NO)

Diagnose cause of abnormal PAB Radiation levels due to a Loss of RCS inventory outside of contaiment Transition to ECA-1.2, LOCA Outside Containment Verify Proper valve alignment (all in correct position)

Verify SI has been reset Reset Containment isolation Phase A and Phase B Establish Instrument Air to Containment

Appendix D Operator Action Form ES-D-2 Page 2 of 25 -

Op Test No.:

1 Scenario#

4 Event#

4,5 Event

Description:

Steam Line Rupture, Auto SI Actuation Failure, LOCA Outside Containment Time 1

Position 11 Applicant's Actions or Behavior I

I I

I Critical Task:

Isolate the LOCA outside containment before transition out of ECA-1.2 Critical Task TEAM RO CRS Try to identify and Isolate Break Sequentially close and open the following valves (or sets of valves) and monitor for an RCS pressure increase 0

RHR Pump cold leg injection valves MOV-746 and MOV-747.

Determines that the Leak is isolated when MOV-746 and MOV-747 are closed.

Check if break is isolated (yes)

Determines RCS sressure is increasina Transitions to E-I, Loss of Reactor or Secondary Coolant Terminate scenario when transition is announced to E-1

Appendix D Operator Action Form ES-D-2 Event

Description:

, Automatic Action Verification fi Time Position Op Test No.:

1 Scenario#

4 Event#

Page 21 of 25 Note -

This attachment must be terminated upon CRS transition to ECA-0.0, Loss of All AC Power.

BOP Verify proper Charging system operation:

a. Start at least one charging pump in manual at maximum speed
b. Align charging pump suction to the RWST 0

Open charging pump suction valve from RWST Close charging pump suction valve from VCT 0 LCV-112C Place RCS Makeup Control switch to STOP o LCV-112B 0

0 o

Notify CRS of any automatic actions that failed to occur during performance of this attachment 3

Equipment found misaligned due to operator action should NOT be repositioned.

I BOP Check 345 KV MO Disc Switch F7 Open (no)

Checks generator output breakers - OPEN

Appendix D Operator Action Form ES-D-2 Scenario#

4 Event#

Page 22 of 25, Automatic Action Verification Op Test No.:

1 Event

Description:

Time 1

Position 11 Applicants Actions or Behavior BOP BOP BOP BOP Check status of 480 volt busses:

1. All 480V busses - ENERGIZED BY OFF-SITE POWER
2. Dispatch NPO to reset:

0 All lighting 0

MCC24A 0 MCC27A 0 MCC29A

1. Stop all Condensate Pumps Verify FW Isolation:

o Main Boiler Feed Pumps - TRIPPED o Main Boiler Feed Pump Discharge Valves o FW Regulating valves - CLOSED o

FW Stop Valves - CLOSED o SG Blowdown Isolation Valves - CLOSED

- CLOSED Check if Main Steam Lines should be isolated:

a. Check for either:

High Steam Line flow with EITHER Tave less than 541 deg F OR Steam line pressure less than 525 psig.

OR 0

Containment pressure - EVER GREATER THAN 24 psig

b. Verify MSlVs - CLOSED Verify proper Service Water System operation:

I. Three Service Water Pumps - Running on Essential Header

2. Service Water valves from Diesel Generator - OPEN

Appendix D Operator Action Form ES-D-2 Op Test No.:

~

BOP BOP BOP BOP Verify SI system pumps running:

a. Three SI pumps - RUNNING
b. 22 SI pump discharge isolation MOV-851A
c. Two RHR pumps - RUNNING AND MOV-851 B - OPEN Verify proper emergency SI System valve alignment:
a.
b.

C.

SI pump cold leg injection valves - OPEN o 856A o 856E o 856C o 856D RHR HX CCW outlet valves - OPEN o 822A o 822B RHR HX MOVS - OPEN o 746 0 747 Verify Containment Fan Coolers - IN SERVICE:

a. Five fan coolers - RUNNING
b. NORM OUT valves - OPEN
c. TCV-1104 and TCV-1105 - BOTH OPEN Verifv AFW flow to all SGs

Appendix D Operator Action Form ES-D-2 Op Test No.:

1 Scenario#

, 4 Event#

Page 24 of 25 Event

Description:

, Automatic Action Verification Attachmei 2 provides a I BOP Verify Containment Ventilation Isolation:

1. Containment Purge Valves - CLOSED 0

FCV-1170 0

FCV-1171 0

FCV-1172 0

FCV-1173 0

PCV-1190 0

PCV-1191 0

PCV-I192

2. Containment Pressure Relief Valves - CLOSED Note
of Phase A valves Verify Containment Isolation Phase A
1. Phase A -ACTUATED 0

0 0

IVSW valves - OPEN 0

1410 0

1413 Train A master relay CAI (above rack E)

Train B master relay CA2 (above rack F)

2. Phase A valves - CLOSED 0 SOV-3518 0

SOV-3519 0 WCP valves - OPEN:

0 PCV1238 0

PCV1239 0

PCV 1240 0

PCV1241

3. Place personnel and equipment hatch solenoid control switches to INCIDENT on SM panel
4. Dispatch NPO to periodically check 0

IVSWTank 0

Level - GREATER THAN 92%

0 Pressure - GREATER THAN 57 PSIG 0 WCP header pressures - GREATER THAN 52 PSlG

Appendix D Operator Action Form ES-D-2 Op Test No.:, Automatic Action Verification Evaluator note: The following step is intended for High Containment pressure condition. It will not be performed if conditions arent met Check if Containment Spray should be actuated:

BOP BOP BOP

1.
2.
3.
4.
5.
6.

Containment Pressure - EVER GREATER THAN 24 PSlG Verify spray pumps - RUNNING Verify spray pump discharge valves - OPEN 0 MOV-866A 0

MOV-8666 0

MOV-866C 0

MOV-866D Verify Containment Isolation Phase B valves -

CLOSED STOP all RCPs Verify IVSW Isolation Valves - OPEN 0 7864 0 7865 0 7866 0

7867 Verify CCR Air Conditioner Train A and B - RUNNING IN INCIDENT MODE 2 Notify CRS that Attachment 1 is complete

Appendix D Scenario Outline Form ES-D-1 Malf. No.

Event TY Pe*

R (RO)

N (BOP)

XMT-I (RO)

RCS028A MAL-C (ALL)

EPS007D FLX-CFWO50 M (ALL)

MAL-EPS001 MOC-C (BOP) swsoo9 Facility:

I P2 Scenario No.:

5 Op Test No.:

1 Examiners:

Candidates:

CRS RO PO Event Description Increase Load PT-455 PRZR Pressure Controlling Channel fails high Loss of 480V Bus 6A Feed water Header leak inside containment. Loss of all AC power ESW Pumps Fail to Auto Start Initial Conditions: 15% power MOL Turnover:

The plant tripped 76 hours8.796296e-4 days <br />0.0211 hours <br />1.256614e-4 weeks <br />2.8918e-5 months <br /> ago due to a switchyard fault. Repairs have been completed and plant startup is in progress IAW POP 1.3 at step 4.53.

Continue with the plant startup at a rate of 200 MW per hour.

Critical Tasks:

Establish at least 400 gpm AFW flow to the SGs before SG dry-out occurs V R level less than 14%)

Isolate RCP Seal Injection before starting a Charging Pump.

Event I L

  • (N)ormal, (R)eactivity, (I)nstrument, (C)omponent, (M)ajor

Scenario Event Description IP2 Simulator Scenario 5 U

The team will assume the shift and continue with a plant startup in progress in accordance with POP-1.3, beginning at step 4.53.

During the power increase, PRZR Pressure Controlling Transmitter PT-455 will fail high requiring manual control of PRZR Pressure IAW AOI-28.0 and AOI-28-5. The CRS will refer to Technical Specifications.

480V AC Bus 6A will fault requiring implementation of AOI-27.1.I

3. The team will perform immediate operator actions that include starting a Charging Pump, and starting a Service Water Pump on the essential header. Bus 6A will not be recovered due to failure.

A rupture of the feed water piping to 21 SG inside of containment will result in a reactor trip and safety injection actuation. Simultaneous to the reactor trip, a fault will occur on the Station Auxiliary Transformer resulting in a loss of offsite power. 21 EDG will start, but its output breaker will not close. 22 EDG will fail to start. 23 EDG will start but cannot be used to energize faulted bus 6A. The team will diagnose a loss of all AC power and transition to ECA-0.0.

During execution of ECA-0.0, Bus 5A will be energized from the 13.8KV power source. The scenario will be terminated when transition to ECA-0.2 is announced.

EOP flow path: E ECA-0.0 - ECA-0.2

Indian Point Unit 2 2003 NRC Initial License Examination Simulator Scenario Setup Scenario 5 Reset simulator to IC-227(PW nano1007)

Place diskette in A drive Click button to run batch file New#2. bat and verify that the following malfunctions are e-active or pending:

bat NeW2.bat PT-455 PZR PRESS CH.l fails hiqh XMT-RCS028A ( I 0) 2255 60 2235 Event trigger # I 480V Bus 6A Fault IMF MAL-EPS007D (2 0) TRUE Event Trigger #2 Feedwater Header Leak in VC IMF FLX-CFW050 (3 0) 25 900 0.000 Event Trigger #3 EDG 21 Output Breaker Failed As-Is IMF BKR-DSG001 (-1 0) 5 EDG 22 Air Start Failure IMF MAL-DSG003B (-1 0) TRUE LOA to transfer BA Pumps IRF LOA-CVCO93 (30 0) 0.000000 0 IRF LOA-CVCO84 (30 2) 100.000 5 Event trigger #30 W

Triqqer to Close Seal Water MOVs IMF MOV-CVC002 (29 0) 2 IMF MOV-CVCOO5 (29 5) 2 IMF MOV-CVCOO6 (29 IO) 2 IMF MOV-CVC007 (29 15) 2 IMF MOV-CVC008 (29 20) 2 IMF MOV-CCW004 (29 30) 2 Event trigger #29 Triqqer to open Bus 5A MCC breakers IRF LOA-EPS052 (28 0) TRIP IRF LOA-EPS049 (28 5) TRIP IRF LOA-EPS053 (28 I O ) TRIP IRF LOA-EPS755 (28 15) TRIP Event trigger #28 Materials needed for scenario:

0 0

GraphBook POP-I.3 marked up to step 4.53 Note: None

Appendix D Operator Action Form ES-D-2 Event

Description:

Increase Load II II 1 Op Test No.:

1 Scenario#

5 Event#

1 Page 5

of 18 I CRS RO RO RO RO RO BOP Refers to POP 3.1 Note: CRS may review previously performed steps in the POP to verify that they have been completed.

Withdraw Control Rods as necessary to MAINTAIN delta flux within the target band and Tave on program DILUTE per SOP-3.2, Reactor Coolant System Boron Concentration Control, as necessary to maintain delta-Flux within the target band and Tave on program.

Note: Actions for DILUTION are on pages 6 of this scenario guide VERIFY TAVF AND Pressurizer Level are maintained on program per Graph RCS-2, Pressurizer Level V.S. TAVE.

MAINTAmsteam generator levels between 40 and 50 percent Narrow Range.

NULL manual setpoint onfeedwater regulating valve control to facilitate rapid transfer from AUTOMATIC to MANUAL control.

INITIATE load increase using either of the following as directed by CRS:

o Governor control o Load Limit control

Appendix D Operator Action Form ES-D-2 Event

Description:

Increase Load RO Refers to SOP-3.2 for dilution DETERMINE RCS Boron concentration from reactor coolant sample analysis.

o E analysis following concentration adjustment is NOT yet available, ESTIMATE Boron concentration based on latest readings.

NOTE Determinations should be based upon rod Dosition. RCS Boron concentration, Xenon level varia ins, increml RO RO RO

?tal Boron'and rod worth, and operating experience.

DETERMINE magnitude of decrease in Boron concentration necessary to accomplish desired reactivity change using one or more of the following references:

o GRAPH CVCS-6, Boration - Dilution Tables o GRAPH RV-2, Total Power Defect (PCM) as a Function of Power and Boron Concentration at MOL o GRAPH RV-3, Differential Boron Worth (Hot Zero Power) at MOL o GRAPH RV-4, Total Temperature Defect (PCM) as a Function of Temperature and Boron Concentration at MOL o GRAPH RV-9, IP2 Cycle 15 Reactivity Equivalents o POP 1.2, Reactor Startup o WCR 1, Reactivity Summary IF the change in RCS Boron concentration is anticipated to be greater than or equal to 25 ppm, OPERATE Pressurizer heaters to open spray valve.

ESTIMATE total volume of PW required for dilution from graphs

Appendix D 0 perat or Act ion Form ES-D-2 RO Scenario #

5 Event#

1 Page 7

of SET Primary Water integrator to amount determined in step 4.5.3.

I I Event

Description:

Increase Load RO Position I

Applicants Actions or Behavior 1

MONITOR Nuclear Instrumentation, Rod position, and RCS temperature closely during any reactivity changes.

or references listed in step 4.5.2.

PLACE the RCS Makeup Control switch to STOP.

RO PLACE the RCS Makeup Mode Selector switch to DILUTE.

RO PLACE the RCS Makeup Control switch to START.

RO WHEN dilution operation has been completed, PERFORM the following:

0 0

0 0

RO 0

0 PLACE the RCS Makeup Control switch to STOP.

PLACE the Makeup Mode Selector switch to MANUAL.

ADJUST FCV-1 10A, Boric Acid Flow Control, dial setting to the new RCS Boron concentration per applicable CVCS Graph:

GRAPH CVCS-IA, Blended Makeup - (0-500) with 120 Gpm PW GRAPH CVCS-1 B, Blended Makeup - (0-2000) with 120 Gpm PW GRAPH CVCS-I C, Blended Makeup with Various PW Flows

Appendix D Operator Action Form ES-D-2 Scenario #

5 Event#

1 Page 8

of Event

Description:

Increase Load I

Ro I

Ro SELECT AUTO on RCS Makeup Mode Selector switch.

PLACE the RCS Makeup Control switch to START.

LOG amount of PW added to system for dilution in CCR Log Book.

When reactor power has been changed by approximately 70%, or at the discretion of the Iead evaluator, proceed to event 2.

Appendix D 0 pe ra tor Act ion Form ES-D-2 Op Test No.:

Scenario#

5 Event#

2 Booth Instructor: When directed by lead evaluator, click button to insert the following command:

TRG!1, Actuates event trigger 1 :

PT-455 PZR PRESS CH.l fails hiqh XMT-RCS028A (1 0) 2255 60 2235 Indications received:

Pressurizer Pressure Channel I indication increases to 2255 over 60 seconds Spray valves modulate open Actual Pressurizer Pressure decreases Alarm SA 3-2 PRZR Low Pressure 2185 PSlG RO CRS RO Diagnoses Pressurizer pressure control system malfunction Directs RO to perform immediate operator actions of AOI-28.0, tnstrument Failures (NOTE: bulleted steps may be performed in any order)

Performs Immediate Actions from memory.

Verifies the following controls:

0 Turbine Load - Stable 0

Rod Control - Stable 0 PRZR Pressure Control - NOT STABLE Determines S/G control is not affected Places PRZR Pressure master controller or individual spray valve controllers in manual and closes spray valves 0

PRZR Level Control - Stable 0

MBFP Speed - Normal 0

S/G Levels - Normal.

0 S/G Pressure Control - Normal Announces Immediate Actions Complete

Appendix D Operator Action Form ES-D-2 CRS Scenario #

5 Event#

2 PRZR PRESS CHI FAILS HIGH Event

Description:

v procedure.

I Directs review of immediate Operator Actions usina the BOP Performs Alarm Response Procedures for annunciators in alarm RO Diagnose PRZR Pressure Channel 1 instrument malfunction RO Manually controls Pressurizer Pressure at 2235 or within the band directed by the CRS Transition to AOI-28.5 Pressurizer Pressure Channel Fails High CRS BOP Determine that the failed channel is the controlling channel RO Places P/455A Pressurizer Pressure Defeat Switch in rack B6 to Defeat 1&4 Verifies Pressurizer Pressure control is in MANUAL RO RO CRS I

Return Pressurizer Pressure control to AUTO Determine that placing bistable trip switches to trip for affected channel will not cause a reactor trip.

Appendix D Operator Action Form ES-D-2 Event

Description:

PRZR PRESS CHI FAILS HIGH Trips bistable trip switches in Red A-4 rack 0

PC-455B Hi Press Trip (Alarm and proving lamp) 0 PC-455A Lo Press Trip (Alarm and proving lamp) 0 PC-455E SI (Alarm and proving lamp) 0 PC-45%

UnblockSI (No alarm, no light) 0 TC-411A Overtemp Trip (Alarm and proving lamp)

I I

Refers to Technical Specification Tables 3.5-2 and 3.5-3 CRS Proceed to event 3 when bistables have been tripped, or af the discretion of the lead evaluator.

Appendix D Operator Action Form ES-D-2 CRS Event

Description:

Loss of 480V Bus 6A Directs RO and BOP to perform immediate operator actions of AOI-27.1.13, Loss of a 480 V Bus Booth Instructor: When directed bv lead evaluator, insert the following command:

Ro TRG!2, Actuates event trigger 2:

Check Charging Pumps Determine that no Charging Pumps are running Starts 21 or 22 Charging pumps 480V Bus 6A Fault Bop IMFMAL-EPS007D (2 0) TRUE Checks Service Water Pumps Determines that ESW header pressure is low Starts 24 SW Pump Indications received :

21 and 22 EDGs start. 22 EDG Fails to start Multiple Alarms associated with deenergized 480V bus and breaker trips.

Deenergized equipment powered from bus 6A including the running charging pump Diagnoses 480V Bus 6A de-energized BOP Checks RCS temperature > 200°F Checks CRDM fans - At Least three running (expect 4 running) 1 BOP I Announces Immediate Actions Complete Directs review of immediate actions using the procedure I

CRS I

Appendix D Operator Action Form ES-D-2 Loss of 480V Bus 6A TEAM Time 1

Position I

Applicants Actions or Behavior Place control switches for bus 6A loads in pullout and OPEN bus 6A MCC Feeder breakers Booth instructor: Click button to swap inservice boric acid pumps, when Nuke Side NPO is dispatched.

BOP Diagnose 480 Volt Bus 6A De-energized BOP Dispatch NPO to perform visual inspection of switchgear for Bus 6A equipment Determine Bus 6A Lockout Status light is not lit BOP Booth Instructor: NPO should report that Bus 6A has apparently suffered a catastrophic failure. Report that the back of Bus 6A switchgear is deformed and paint is blistered and smell of acrid odor.

Determine that amber light for breaker 52/6A is lit BOP Dispatch NPO to shutdown 23 EDG BOP INITIATE Technical Specification Shutdown CRS Note: Proceed to event 4 when the team has determined that a shutdown is required, or at the lead evaluators discretion.

L.

RO Appendix D Operator Action Form ES-D-2 Diagnoses 21 SG Level decreasing rapidly and containment conditions degrading Page 14 of 18 1 Op Test No.:

1 Scenario#

5 Event#

4,5,6 CRS I

I Event

Description:

, Automatic Action Verification Direct performance of immediate actions of E-0, Reactor Trip or Safety Injection Time I

Position 1

Applicant's Actions or Behavior Bop Booth Instructor: When directed by lead evaluator, insert the following command:

TRG!3, Actuates event trigger 3:

Feedwater Header Leak in VC IMF FLX-CFWO50 (3 0) 25.000 900 0.000 Checks Status of 480V Busses Determines that no 480V Bus is energized Announces to team that transition to ECA-0.0 is required Indications available:

Containment Sump level alarms on panel SB-I Containment Humidity alarm on panel SM 21 SG Feed Flow decreases and 21 SG Level decreases Auto reactor trip if no manual trip actuated.

Auto SI on High Containment Pressure and Steam Line Delta-P Following Trip Loss of Offsite Power occurs Loss of All 480 V busses NOTE: The CRS may direct the RO to manually trip the reactor due to rapidly deteriorating plant transient.

I I

Verifies Reactor Tripped RO Verifies Turbine Tripped RO

Appendix D Operator Action Form ES-D-2 CRS Page 15 of 18 4 I OpTest No.:

1 Scenario #

5 Event#

4,5,6 Directs team to perform immediate actions of ECA-0.0, Loss of All AC Power Event

Description:

, Automatic Action Verification I

Applicant's Actions or Behavior Time I

Position 1

RO CRS Critical tal Verify Turbine Trip Announce immediate actions complete Verify immediate actions using the procedure RO Verify Reactor Trip RO Check if RCS is isolated 0 Checks PORVS closed 0

0 Checks letdown isolation valves closed Checks excess letdown isolation valve closed Establish at least 400 gpm AFW flow to the SGs before SG dry-out occurs (WR level less than 14%)

Critical Task TEAM Verify AFW Flow - Greater than 400 GPM 0

Manually open PCV-1139 Steam Supply regulator Valve to start 22 AFW Pump 0

Manually align 22 AFWP FCVs as necessary 0 Adjust HCV-1118 Steam Supply Speed Control valve

L.

Appendix D Operator Action Form ES-D-2 Op Test No.:

Scenario#

5 Event#

4,5,6 Page 16 of Event

Description:

, Automatic Action Verification t-BOP BOP/CRS +

Try to restore power to any 480V bus 0

Check EDGs running (22 not running, 21 EDG running) 0 Attempt to close 21 EDG output breaker (will not close) 0 Dispatch NPO to emergency start 22 EDG 0

Locally trip running EDGs (Note, they will probably be auto tripped before this step is performed due to lack of SW cooling) 0 Attempt to manually energize 480V bus using any available power supply per A01-27.1.I and AOI-27.1.I 3

Determine that 480 Bus cannot be readily energized from CCR Booth Instructor: NPO dispatched to start 22 EDG reports that both air start motors appear to be mechanically bound. 22 EDG will not start. NPO will contact work control for assistance.

Booth Instructor: When asked, DO reports that 13.8 KV power is available from 13W92 Evaluator Note: When power is restored to any 480V bus, then recovery actions ihould continue starting with step 24 of ECA-0.0 RO CRS Place Equipment in Pullout:

0 CSPumps 0

SI Pumps 0

FCUs 0

Motor Driven AFW Pumps 0 Turning Gear Oil Pump 0

Bearing Oil Pump 0 Turbine Auxiliary Oil Pump 0

CCWPumps 0

RHRPumps Dispatch personnel to Locally Restore AC Power

u-Event

Description:

, Automatic Action Verification Appendix D Operator Action Form ES-D-2 Time I

Position I Applicants Actions or Behavior I

of 18 1 Page 17 Op Test No.:

1 Scenario#

5 Event#

4, 5, 6 CRS Check 13.8KV feeder 13W92 ENERGIZED (yes)

BOP BOP CRS/BOP Place 52/SS5 and 52/EG1 in Pullout Energize Bus 5A from 13.8KV via 52/GT25 Direct NPO to remove control power fuses for 52/5A and manually close breaker 52/5A Attempt to restore power to busses per the following while continuing with step 8:

0 AOI-27.0 Diagnosis and Response to Electrical Failure 0

SOP-27.1.3 Operation of 13.8KV System 0 A01-27.1.1 Loss of Normal Station Power 0 AOI-27.1.13 LOSS Of 480V BUS Critical Task Isolate RCP Seal Injection before starting a Charging Pump.

Critical Task TEAM Booth Operator: Wher Dispatch personnel to locally close valves to isolate RCP Seals and Place valve Switches to CLOSED position 0

0 0

MOV-222 RCP seal return isolatin valve outside containment MOV-250A-D, RCP seal injection isolation valves outside containment MOV-789, RCP thermal barrier CCW return isolation valve outside containment NPO directed to Isolate RCP seals, click the button:

When NPO directed to oDen MCC breakers on Bus 5A. click this button:

~~

~~

~~

~~

~

Appendix D Operator Action Form ES-D-2 CRS Op Test No.:

1 Scenario#

5 Event#

4,546 Page 18 of Select Recovery Procedure Determine transition to ECA-0.2 (expected)

Event

Description:

, Automatic Action Verification Time 1

Position Applicant's Actions or Behavior Booth Instructor: When NPO dispatched, click to execute Remove control power fuses breaker 52/5A

"*I Mechanically locally close breaker 52/5A Evaluator BOP BOP CRS RO BOP BOP Press 86l5A reset pushbutton and verify white light is on Close 52/SS5.

Inform team that Bus 5A is energized Determine that ECA-0.0 Step 24 should be performed per step 6 CAUTION.

Manually control SG atmospheric Steam Dumps to stabilize SG Pressures Verify Service Water system operation Verify the following equipment is loaded onto bus 5A 0

MCC26A 0

MCC29A 0

21 Battery Charger 0 21 Static Inverter on alternate power ote: Team will be unable to close breaker for MCC 29A due to blackout relay not reset.

Booth Operator: If NPO dispatched to reset MCC29A, inform the CCR that VICC29A breaker will not close.

I I

rerminate scenario when transition from ECA-0.0 is announced.