ML030700604

From kanterella
Jump to navigation Jump to search
Final As-Administered Walkthrough Jpms for the Quad-Cities Initial Examination - December 2002
ML030700604
Person / Time
Site: Quad Cities  Constellation icon.png
Issue date: 11/30/2002
From: Moreland K
Exelon Generation Co
To:
Office of Nuclear Reactor Regulation
References
50-254/02-301, 50-265/02-301
Download: ML030700604 (95)


Text

Page 1 Nuclear Generation Group Job Performance Measure Bypass the Reactor Building Ventilation Isolation JPM Number: B.1.a.

Revision Number: 2 Date: 11/2002 NOTE: Original Signed - Disk Copy No Signatures Developed By:

Instructor Date Validated By:

SME or Instructor Date Review By:

Operations Representative Date

B.1.a.

Job Performance Measure (JPM)

Page 2 SIMULATOR SETUP INSTRUCTIONS

1. Reset the simulator to IC 94 (rst 94 from zip disk).
2. IC

Description:

Shutdown reactor following a scram.

NOTE:

It is okay to use a similar IC to the IC listed above, provided the IC actually used is verified to be compatible with this and other JPMs that are scheduled to be run concurrently.

3. Manual Actuation:
  • Ensure that the QGA packet for QCOP 1600-17 is complete, including safety glasses, and in the drawer next to the ANSO desk.
4. Malfunctions:
  • Insert a group II Isolation using malfunction RP07A & RP07B (imf rp07a)&(imf rp07b)
5. Remotes: NONE
6. Overrides: NONE
7. When the above steps are completed for this and other JPMs to be run concurrently, then validate the concurrently run JPMs using the JPM Validation Checklist.
8. This completes the setup for this JPM.

B.1.a.

Job Performance Measure (JPM)

Page 3 Revision Record (Summary)

Revision 0, This JPM is developed IAW guidelines established in NUREG 1021 Rev 8 ES-301 and Appendix C. This JPM meets the criteria of Category B.1 "Control Room Systems," for RO/SRO candidates.

Revision 1 The JPM was revised to incorporate validation time and comments.

Revision 2 The JPM was revised to incorporate NRC validation comments.

Information For Evaluators Use:

UNSAT requires written comments on respective step.

  • Denotes CRITICAL steps.

Number any comments in the Comment Number column on the following pages. Then annotate that comment in the Comments section at the bottom of the page. The comment section should be used to document the reason that a step is marked as unsatisfactory and to document unsatisfactory performance relating to management expectations.

Some operations that are performed from outside of the control room may require multiple steps. These items may be listed as individual steps in this JPM. It is acceptable for the candidate to direct the local operator to perform groups of procedure steps instead of calling for each individual item to be performed.

The timeclock starts when the candidate acknowledges the initiating cue.

B.1.a.

Job Performance Measure (JPM)

Page 4 INITIAL CONDITIONS A small leak inside the U-1 Drywell has caused the pressure to increase to 3.5 psig.

All automatic functions occurred as expected.

The MSIV room temperature has increased to 164°F and the Unit Supervisor wants to restart the Reactor building ventilation per QGA 300.

This JPM is NOT time critical.

INITIATING CUE Bypass the Reactor building ventilation isolation on U-1 IAW QCOP 1600-17 Provide examinee with:

QGA support packet for QCOP 1600-17 when directed by cue.

Fill in the JPM Start Time when the student acknowledges the Initiating Cue.

B.1.a.

Job Performance Measure (JPM)

Page 5 JPM Start Time:

PERFORMANCE OBJECTIVE STANDARDS SAT UNSAT N/A EVALUATOR: If this JPM is being simulated in the control room, DO NOT ALLOW THE CANDIDATE TO OPEN THE JUMPER PACKET!

EVALUATOR: Disregard the above statement if the JPM is being performed in the simulator.

CUE: Provide candidate with QGA support packet for QCOP 1600-17.

  • F.1.a.

Install 901-15 panel jumpers.

Installs/verbalizes placing jumper between pts 49 & 50 on terminal board B.

[ ]

[ ]

[ ]

CUE: If jumper is not numbered, tell the candidate that the jumper number is # 22.

F.1.a.

Record jumper number.

Records jumper number &

checks QCOP 1600-17 step F.1.a.

[ ]

[ ]

[ ]

Evaluators Note: Verification steps may be performed when time permits and therefore are allowed to be performed out-of-sequence. If asked for verification, give a cue that the jumpers will be verified later.

F.1.a.(1)

Verification.

Installation is verified.

[ ]

[ ]

[ ]

  • F.1.b.

Install 901-15 panel jumpers.

Installs/verbalizes placing jumper between pts. 38 & 39 on terminal board E.

[ ]

[ ]

[ ]

CUE: If jumper is not numbered, tell the candidate that the jumper number is # 23.

F.1.b.

Record jumper number.

Records jumper number &

checks QCOP 1600-17 step F.1.b.

[ ]

[ ]

[ ]

F.1.b.(1)

Verification Verifier verifies installation.

[ ]

[ ]

[ ]

EVALUATOR: The candidate should inform you that the task is complete.

  • CRITICAL STEP JPM Stop Time:

B.1.a.

Job Performance Measure (JPM)

Page 6 Operators Name:

Job

Title:

RO

SRO

JPM

Title:

Bypass the Reactor Building Ventilation Isolation JPM Number: B.1.a.

Revision Number: 2 Task Number and

Title:

SRN-1600-P25 Given a reactor plant in a QGA situation, perform/simulate installing and removing one of the following sets of jumpers in accordance with the indicated procedure.

K/A Number and Importance:

K/A:

288000 A2.01 Rating:

3.3/3.4 Suggested Testing Environment: Simulator Actual Testing Environment:

Simulator

Plant

Control Room Testing Method: Simulate Faulted: Yes I No Perform Alternate Path: Yes I No Time Critical: Yes I No Estimated Time to Complete: _6_minutes Actual Time Used: minutes

References:

QCOP 1600-17 Rev. 3

B.1.a.

Job Performance Measure (JPM)

Page 7 EVALUATION

SUMMARY

Were all the Critical Elements performed satisfactorily?

Yes

No The operators performance was evaluated against the standards contained in this JPM, and has been determined to be:

Satisfactory Unsatisfactory Comments:

Evaluators Name:

(Print)

Evaluators Signature:

Date:

Page 8 INITIAL CONDITIONS (Student Copy)

A small leak inside the U-1 Drywell has caused the pressure to increase to 3.5 psig.

All automatic functions occurred as expected.

The MSIV room temperature has increased to 164°F and the Unit Supervisor wants to restart the Reactor building ventilation per QGA 300.

This JPM is NOT time critical.

INITIATING CUE Bypass the Reactor building ventilation isolation on U-1 IAW QCOP 1600-17

Page 9 Nuclear Generation Group Job Performance Measure RCIC Manual Initiation (Hardcard) with a Turbine Trip JPM Number: B.1.b.

Revision Number: _2_

Date: 11/2002 NOTE: Original Signed - Disk Copy No Signatures Developed By:

Instructor Date Validated By:

SME or Instructor Date Review By:

Operations Representative Date

B.1.b.

Job Performance Measure (JPM)

Page 10 SIMULATOR SETUP INSTRUCTIONS

9. Reset the simulator to IC 94 (rst 94).
10. IC

Description:

Reactor stable after scram.

11. Manual Actuation:

Ensure that the RCIC system is in its normal standby lineup.

12. Malfunctions:

Simulate failure of the RCIC exhaust check valve to open by closing the exhaust line manual isolation valve using remote function (mrf rc04r close)

When prompted by the evaluator, reopen the valve using (mrf rc04r open) and give the report that the check valve appeared to be stuck closed but you have cycled it manually and it now is free to move. No damage and everything is satisfactory in the RCIC room.

When prompted by the evaluator, give report as NLO dispatched to RCIC room to verify the rupture diaphragm intact, report diaphragm is intact and all looks normal and satisfactory.

13. Remotes: NONE
14. Overrides: NONE
15. When the above steps are completed for this and other JPMs to be run concurrently, then validate the concurrently run JPMs using the JPM Validation Checklist.
16. This completes the setup for this JPM.

B.1.b.

Job Performance Measure (JPM)

Page 11 Revision Record (Summary)

Revision 0, This JPM is developed IAW guidelines established in NUREG 1021 Rev 8 ES-301 and Appendix C. This JPM meets the criteria of Category B.1 "Control Room Systems," for RO/SRO candidates.

Revision 1 The JPM was revised to incorporate validation time and comments.

Revision 2 The JPM was revised to incorporate NRC validation comments.

Information For Evaluators Use:

UNSAT requires written comments on respective step.

  • Denotes CRITICAL steps.

Number any comments in the Comment Number column on the following pages. Then annotate that comment in the Comments section at the bottom of the page. The comment section should be used to document the reason that a step is marked as unsatisfactory and to document unsatisfactory performance relating to management expectations.

Some operations that are performed from outside of the control room may require multiple steps. These items may be listed as individual steps in this JPM. It is acceptable for the candidate to direct the local operator to perform groups of procedure steps instead of calling for each individual item to be performed.

The timeclock starts when the candidate acknowledges the initiating cue.

B.1.b.

Job Performance Measure (JPM)

Page 12 INITIAL CONDITIONS

  • A loss of feedwater has resulted in a reactor scram and entry into QGA 100.
  • The Unit Supervisor has decided that RCIC should be used to restore reactor water level.
  • Hardcard use has been authorized by the Unit Supervisor.
  • RCIC is in its normal standby lineup.
  • This JPM is not time critical INITIATING CUE Manually initiate Unit 1 RCIC using the hardcard and inject into the reactor vessel.

Fill in the JPM Start Time when the student acknowledges the Initiating Cue.

B.1.b.

Job Performance Measure (JPM)

Page 13 JPM Start Time:

PERFORMANCE OBJECTIVE STANDARDS SAT UNSAT N/A Obtain hardcard for RCIC MANUAL STARTUP from the 901-4 panel.

Obtains hardcard for RCIC MANUAL STARTUP from the 901-4 panel.

[ ] [ ] [ ]

Hardcard step 1 Manually initiates RCIC using the manual initiation pushbutton.

Depresses and holds the RCIC MAN INITIATION pushbutton on the 901-4

[ ] [ ] [ ]

Verifies the system lines up to inject.

Using indications on the 901-4 panel verifies system valves are lining up for injection.

[ ] [ ] [ ]

Identifies turbine trip on high exhaust pressure.

Identifies turbine trip by alarm 901-4 D-15 and cause is due to high exhaust pressure by alarm 901-4 C-14.

[ ] [ ] [ ]

901-4 C-14 step B.1.

Verifies the automatic actions occurred.

Verifies that the MO 1-1301-60 MIN FLOW VLV and the MO 1-1301-61 STM TO TURB VLV are closed

[ ] [ ] [ ]

  • 901-4 C-14 step B.2.

Verifies steam exhaust check valve open by dispatching operator to RCIC room.

Verifies 1-1301-64 RCIC TURB EXH STOP CK VLV is open by dispatching NLO to RCIC room.

[ ] [ ] [ ]

901-4 C-14 step B.3.

Determines if high torus pressure exists.

Determines that a high torus pressure does not exist as indicated on 1-1602-1 TORUS PRESS.

[ ] [ ] [ ]

901-4 C-14 step B.4.

Determines if the exhaust diaphragm has ruptured.

Determines that the exhaust diaphragm has not ruptured by:

Absence of alarm 901-4 A-16 RCIC room temp normal on 901-21 RCIC room rads normal on 901-02 Dispatches NLO to RCIC room to verify that rupture diaphragm is intact.

[ ] [ ] [ ]

Evaluator Note: Prompt the Simulator operator to provide cue from previously dispatched (step 901-4 C-14 B.2.) operator sent to inspect the exhaust line stop-check valve, that he found it stuck, but manually cycled it and it is now free to move. No damage, everything is sat.

Also have Simulator Operator provide cue as the NLO sent to inspect the rupture diaphragm (step 901-4 C-14 B.4.) that everything appears normal in the RCIC room and that the rupture diaphragm is intact.

In the next step, if the candidate seeks input from US, provide cue that condition has been corrected and RCIC operation is required.

B.1.b.

Job Performance Measure (JPM)

Page 14 PERFORMANCE OBJECTIVE STANDARDS SAT UNSAT N/A 901-4 C-14 step B.5.

Determines cause of high exhaust pressure has been corrected and RCIC IS required for operation.

Starts turbine trip recovery IAW QCOA 1300-01.

Determines cause of high exhaust pressure has been corrected and RCIC IS required for operation. Starts turbine trip recovery IAW QCOA 1300-01.

[ ] [ ] [ ]

QCOA 1300-01 step D.1.

Verifies automatic actions occurred.

Previously done in step B.1.of 901-4C-14

[ ] [ ] [ ]

QCOA 1300-01 step D.2.

Determines if a trip or isolation occurred.

Previously determined by 901-4 C-14 and operator reports from the field.

[ ] [ ] [ ]

Evaluator Note: In the next step, the candidate may ask US if initiation signal should be reset to prevent system from autostarting following reset of the turbine trip.

Provide cue that it is NOT desired to clear the initiation signal and reiterate need for RCIC injection.

QCOA 1300-01 step D.4.

Determines that initiation signal has not cleared.

Determines that initiation signal is not cleared by alarm 901-4 D-16.

[ ] [ ] [ ]

  • QCOA 1300-01 step D.7.b.

Resets the turbine trip.

Verifies high exhaust pressure trip signal clear, by absence of alarm 901-4 C-14, and resets turbine trip by depressing TURB RESET pushbutton.

[ ] [ ] [ ]

QCOA 1300-01 step D.9.

Restarts RCIC for injection IAW QCOP 1300-02 Hard Card.

Determines turbine trip is reset by absence of any alarms, and that RCIC is required for operation. References Hard card to restart system.

[ ] [ ] [ ]

Hardcard step 1 Manually initiates RCIC using the manual initiation pushbutton.

Depresses and holds the RCIC MAN INITIATION pushbutton on the 901-4

[ ] [ ] [ ]

Verifies the system lines up to inject.

Using indications on the 901-4 panel verifies system valves reposition and system is injecting at ~400 gpm.

[ ] [ ] [ ]

EVALUATOR: The candidate should inform you that the task is complete.

JPM Stop Time:

B.1.b.

Job Performance Measure (JPM)

Page 15 Operators Name:

Job

Title:

RO

SRO

JPM

Title:

RCIC Manual Initiation (Hardcard) with a Turbine Trip JPM Number: B.1.b.

Revision Number: 2 Task Number and

Title:

SR-1300-P01, Given a reactor plant in an accident condition where RCIC fails to autostart and/or fails to start with the auto pushbutton, start RCIC for injection in accordance with QCOP-1300-02. (Important PRA Operator Action - starting RCIC terminates 13 of the top 200 Core Damage Sequences)

K/A Number and Importance:

K/A: 217000 A2.02 Rating: 3.8/3.7 Suggested Testing Environment: Simulator Actual Testing Environment:

Simulator

Plant

Control Room Testing Method: Simulate Faulted: Yes I No Perform Alternate Path: I Yes No Time Critical: Yes I No Estimated Time to Complete: _30_minutes Actual Time Used: minutes

References:

QCOP 1300-02, Rev. 22 QCOA 1300-01 Rev 11 QCAN 901-4 C-14 Rev 1 QCAN 901-4 D-15 Rev 4 QCAN 901-4 D-16 Rev 6 QCAN 901-4 E-16 Rev 0

B.1.b.

Job Performance Measure (JPM)

Page 16 EVALUATION

SUMMARY

Were all the Critical Elements performed satisfactorily?

Yes

No The operators performance was evaluated against the standards contained in this JPM, and has been determined to be:

Satisfactory Unsatisfactory Comments:

Evaluators Name:

(Print)

Evaluators Signature:

Date:

Page 17 INITIAL CONDITIONS (Student Copy)

  • A loss of feedwater has resulted in a reactor scram and entry into QGA 100.
  • The Unit Supervisor has decided that RCIC should be used to restore reactor water level.
  • Hardcard use has been authorized by the Unit Supervisor.
  • RCIC is in its normal standby lineup.
  • This JPM is not time critical INITIATING CUE Manually initiate Unit 1 RCIC using the hardcard and inject into the reactor vessel.

Page 18 Nuclear Generation Group Job Performance Measure Supply Bus 14-1 from Bus 24-1 using the Hardcard JPM Number: B.1.c.

Revision Number: _2_

Date: 11/2002 NOTE: Original Signed - Disk Copy No Signatures Developed By:

Instructor Date Validated By:

SME or Instructor Date Review By:

Operations Representative Date

B.1.c.

Job Performance Measure (JPM)

Page 19 Revision Record (Summary)

Revision 0, This JPM is developed IAW guidelines established in NUREG 1021 Rev 8 ES-301 and Appendix C. This JPM meets the criteria of Category B.1 "Control Room Systems," for RO/SRO candidates.

Revision 1 The JPM was revised to incorporate validation time and comments.

Revision 2 The JPM was revised to incorporate NRC validation comments.

Information For Evaluators Use:

UNSAT requires written comments on respective step.

  • Denotes CRITICAL steps.

Number any comments in the Comment Number column on the following pages. Then annotate that comment in the Comments section at the bottom of the page. The comment section should be used to document the reason that a step is marked as unsatisfactory and to document unsatisfactory performance relating to management expectations.

Some operations that are performed from outside of the control room may require multiple steps. These items may be listed as individual steps in this JPM. It is acceptable for the candidate to direct the local operator to perform groups of procedure steps instead of calling for each individual item to be performed.

The timeclock starts when the candidate acknowledges the initiating cue.

B.1.c.

Job Performance Measure (JPM)

Page 20 SIMULATOR SETUP INSTRUCTIONS

17. Reset the simulator to IC 94 (rst 94).
18. IC

Description:

NOTE:

It is okay to use a similar IC to the IC listed above, provided the IC actually used is verified to be compatible with this and other JPMs that are scheduled to be run concurrently.

19. Manual Actuation:
  • Place the 1C RHR pump in PTL on 901-3 panel.
  • Place the 1D RHR pump in PTL on 901-3 panel.
  • Place the U-1 EDG control switch in STOP on the 901-8 panel.
20. Malfunctions:
  • Prevent the U-1 EDG from starting (imf dg03a)
  • Trip the bus 14 to 14-1 tie breaker 152-1427 (imf ed04m)
  • Acknowledge alarms associated with the bus 14 to bus 14-1 breaker trip as part of setup.
21. Remotes: When asked by the candidate for U-2 to close bus 24-1 to 14-1 crosstie breaker on U-2, use remote function (mrf ed34r close) to close in the breaker and report to candidate that the bus 24-1 to 14-1 crosstie breaker on U-2 is closed in.
22. Overrides: NONE
23. When the above steps are completed for this and other JPMs to be run concurrently, then validate the concurrently run JPMs using the JPM Validation Checklist.
24. This completes the setup for this JPM.

B.1.c.

Job Performance Measure (JPM)

Page 21 INITIAL CONDITIONS

  • Unit 1 has experienced a transient resulting in a LOCA and drywell pressure of 5 psig.
  • The bus 14 to bus 14-1 tie breaker has tripped.
  • Bus 14-1 is de-energized.
  • Unit 2 is operating at 150 MWE in a split configuration (load is split between the UAT and the RAT).
  • The 1B Core Spray pump and the 1C and 1D RHR pumps are in PTL and have been verified.
  • The Unit Supervisor has authorized hardcards.
  • This JPM is not time critical INITIATING CUE Energize bus 14-1 from bus 24-1 using the hardcard.

Fill in the JPM Start Time when the student acknowledges the Initiating Cue.

B.1.c.

Job Performance Measure (JPM)

Page 22 JPM Start Time:

PERFORMANCE OBJECTIVE STANDARDS SAT UNSAT N/A Obtain hardcard for BUS 14-1 TO BUS 24-1 TIE OPERATION (BUS 14-1 DEAD) from the 901-74 panel.

Obtains hardcard for BUS 14-1 TO BUS 24-1 TIE OPERATION (BUS 14-1 DEAD) from the 901-74 panel.

[ ] [ ] [ ]

Hardcard step 1 Places control switches in pull to lock to isolate bus 14.

Places the following control switches in PTL.

  • Bus 14-1 & Bus 61 Tie breaker
  • U1 Diesel Gen toBus 14-1 ACB
  • Busses 14 and 14-1 Tie Breaker

[ ] [ ] [ ]

  • Hardcard step 2 Directs the Unit 2 NSO or ANSO to operate the synchronization switch and close bus 24-1 & 14-1 tie breaker.

Directs the Unit 2 RO to perform the following two steps on the 902-8 panel:

1. Place SYNCH switch to ON for BUS 24-1 & 14-1 tie ACB.
2. Close BUS 24-1 & 14-1 tie ACB

[ ] [ ] [ ]

Evaluators Note: If candidate asks the evaluator to perform this task, direct them to use the phone to contact the U-2 RO (simulator operator) for performance of these two tasks.

Simulator Operator Note: When asked by the candidate for U-2 to close bus 24-1 to 14-1 crosstie breaker on U-2, use remote function (mrf ed34r close) to close in the breaker and report to candidate that the bus 24-1 to 14-1 crosstie breaker on U-2 is closed in.

  • Hardcard step 3.a.

Places the synchronization switch ON for the crosstie.

Places the synchronization switch on the 901-8 panel to ON for BUS 24-1

& 14-1 tie ACB.

[ ] [ ] [ ]

  • Hardcard step 3.b.

Close bus 14-1 & 24-1 tie breaker.

Closes and holds (for approximately 10 seconds) the BUS 24-1 & 14-1 tie ACB on the 901-8 panel. Verifies BUS 24-1 & 14-1 tie ACB closed indication light and bus 14-1 live light lit.

[ ] [ ] [ ]

EVALUATOR: The candidate should inform you that the task is complete.

JPM Stop Time:

B.1.c.

Job Performance Measure (JPM)

Page 23 Operators Name:

Job

Title:

RO

SRO

JPM

Title:

Supply Bus 14-1 from Bus 24-1 using the Hardcard JPM Number: B.1.c.

Revision Number: 2 Task Number and

Title:

SR-6500-P04. Given a loss of normal power to an emergency bus (13-1/14-1) with a failure of the associated emergency diesel to start, supply power to the emergency bus using the crosstie from unit 2 and restore 480 VAC busses in accordance with QOA 6500-03, QCOP 6500-08, QOA 6700-04 and QOA 6700-01. (SOER 83-6 r4)

K/A Number and Importance:

K/A: 262001 A4.01 Rating: 3.4/3.7 Suggested Testing Environment: Simulator Actual Testing Environment:

Simulator

Plant

Control Room Testing Method: Simulate Faulted: Yes I No Perform Alternate Path: Yes I No Time Critical: Yes I No Estimated Time to Complete: _7 _minutes Actual Time Used: minutes

References:

QCOP 6500-08, Rev. 13

B.1.c.

Job Performance Measure (JPM)

Page 24 EVALUATION

SUMMARY

Were all the Critical Elements performed satisfactorily?

Yes

No The operators performance was evaluated against the standards contained in this JPM, and has been determined to be:

Satisfactory Unsatisfactory Comments:

Evaluators Name:

(Print)

Evaluators Signature:

Date:

Page 25 INITIAL CONDITIONS (Student Copy)

  • Unit 1 has experienced a transient resulting in a LOCA and drywell pressure of 5 psig.
  • The bus 14 to bus 14-1 tie breaker has tripped.
  • Bus 14-1 is de-energized.
  • Unit 2 is operating at 150 MWE in a split configuration (load is split between the UAT and the RAT).
  • The Unit Supervisor has authorized hardcards.
  • This JPM is not time critical INITIATING CUE Energize bus 14-1 from bus 24-1 using the hardcard.

Page 26 Nuclear Generation Group Job Performance Measure Perform a Manual Scram Functional Test with Rod Drifts JPM Number: B.1.d.

Revision Number: 2 Date: 11/2002 NOTE: Original Signed - Disk Copy No Signatures Developed By:

Instructor Date Validated By:

SME or Instructor Date Review By:

Operations Representative Date

B.1.d.

Job Performance Measure (JPM)

Page 27 Revision Record (Summary)

Revision 0, This JPM is developed IAW guidelines established in NUREG 1021 Rev 8 ES-301 and Appendix C. This JPM meets the criteria of Category B.1 "Control Room Systems," for RO/SRO candidates.

Revision 1 The JPM was revised to incorporate validation time and comments.

Revision 2 The JPM was revised to incorporate NRC validation comments.

Information For Evaluators Use:

UNSAT requires written comments on respective step.

  • Denotes CRITICAL steps.

Number any comments in the Comment Number column on the following pages. Then annotate that comment in the Comments section at the bottom of the page. The comment section should be used to document the reason that a step is marked as unsatisfactory and to document unsatisfactory performance relating to management expectations.

Some operations that are performed from outside of the control room may require multiple steps. These items may be listed as individual steps in this JPM. It is acceptable for the candidate to direct the local operator to perform groups of procedure steps instead of calling for each individual item to be performed.

The timeclock starts when the candidate acknowledges the initiating cue.

B.1.d.

Job Performance Measure (JPM)

Page 28 SIMULATOR SETUP INSTRUCTIONS

25. Reset the simulator to IC _21_ (rst 21).

NOTE:

This JPM will result in a manual scram being inserted by the candidate. If this will effect other JPMS, it should be used alone or with administrative JPMS that do not require the use of the simulator or process computer.

26. Provide a copy of QCOS 0500-02 with section D.1. filled out for Unit 1 as a Normal Surveillance, signed and dated by the Unit Supervisor, and section D.2.

initialed as EO/ANSO.

27. Manual Actuation:

NONE Malfunctions:

Assign B RPS tripped to trigger 2 trg 2 E2 Assign rod 1815 to drift in when RPS B is tripped imf rd03r1815(2)

Assign rod 2227 to drift in when RPS B is tripped imf rd03r2227(2)

Assign rod 1839 to drift in when RPS B is tripped imf rd03r1839(2)

Assign rod 0627 to drift in when RPS B is tripped imf rd03r0627(2)

Remotes:

NONE Overrides:

NONE

28. When the above steps are completed for this and other JPMs to be run concurrently, then validate the concurrently run JPMs using the JPM Validation Checklist.
29. This completes the setup for this JPM.

B.1.d.

Job Performance Measure (JPM)

Page 29 INITIAL CONDITIONS

  • The Unit Supervisor has ordered that a manual scram functional test be performed this shift on Unit 1.
  • This JPM is not time critical.

INITIATING CUE Perform a U-1 Manual Scram Functional Test IAW QCOS 0500-02.

Provide a copy of QCOS 0500-02 with section D.1. filled out for Unit 1 as a Normal Surveillance, signed and dated by the Unit Supervisor, and section D.2. initialed as EO/ANSO.

Fill in the JPM Start Time when the student acknowledges the Initiating Cue.

B.1.d.

Job Performance Measure (JPM)

Page 30 JPM Start Time:

PERFORMANCE OBJECTIVE STANDARDS SAT UNSAT N/A

  • H.1.a.

Depress the Channel A manual scram pushbutton.

Depress lefthand pushbutton.

[ ]

[ ]

H.1.b.

Verify red light in Channel A manual scram pushbutton is lit.

Red light lit.

[ ]

[ ]

[ ]

H.1.c.

Verify Channel A scram solenoid group lights out.

Four RPS A scram solenoid lights not lit.

[ ]

[ ]

[ ]

H.1.d.

Verify Channel A Manual Scram alarm.

Annunciator 901-5 A-10 lit.

[ ]

[ ]

[ ]

  • H.1.e.

Reset half scram and verify all 4 lights lit for Channel A and B.

Positions RPS scram reset switch first to position 2 and 3 then to position 1 and 4.

- Verifies all 4 lights lit for Channel A and B.

[ ]

[ ]

H.1.f.

Reset Channel A Manual Trip alarm.

Depresses reset pushbutton AND verifies Annunciator 901-5 A-10 not lit.

[ ]

[ ]

  • H.2.a.

Depress the Channel B manual scram pushbutton.

Depresses righthand pushbutton.

[ ]

[ ]

H.2.b.

Verify red light in Channel B manual scram pushbutton is lit.

Red light lit.

[ ]

[ ]

[ ]

H.2.c.

Verify Channel B scram solenoid GP lights out.

Four RPS B scram solenoid lights not lit.

[ ]

[ ]

[ ]

H.2.d.

Verify Channel B Manual Scram alarm.

Annunciator 9015 A-15 lit.

[ ]

[ ]

[ ]

  • F.5.

Recognizes rod drifts requiring a reactor scram per section F.5.

Recognizes that 4 rods are drifting into the core, and inserts a manual reactor scram.

[ ]

[ ]

Cue: Inform candidate that JPM is over when reactor is scrammed.

JPM Stop Time:

B.1.d.

Job Performance Measure (JPM)

Page 31 Operators Name:

Job

Title:

RO

SRO

JPM

Title:

Perform a Manual Scram Functional Test with Rod Drifts JPM Number: B.1.d.

Revision Number: 2 Task Number and

Title:

SR-0500-P01 - Given an operating reactor plant, perform the manual scram functional test in accordance with QCOS 500-2.

K/A Number and Importance:

K/A: 212000 A4.01 RATING: 4.6/4.6 Suggested Testing Environment: Simulator Actual Testing Environment:

Simulator

Plant

Control Room Testing Method: Simulate Faulted: Yes I No Perform Alternate Path: I Yes No Time Critical: Yes I No Estimated Time to Complete: _9 _minutes Actual Time Used: minutes

References:

QCOS 0500-02, Rev. 12

B.1.d.

Job Performance Measure (JPM)

Page 32 EVALUATION

SUMMARY

Were all the Critical Elements performed satisfactorily?

Yes

No The operators performance was evaluated against the standards contained in this JPM, and has been determined to be:

Satisfactory Unsatisfactory Comments:

Evaluators Name:

(Print)

Evaluators Signature:

Date:

Page 33 INITIAL CONDITIONS (Student Copy)

  • The Unit Supervisor has ordered that a manual scram functional test be performed this shift on Unit 1.
  • This JPM is not time critical.

INITIATING CUE Perform a U-1 Manual Scram Functional Test IAW QCOS 0500-02.

Page 34 Nuclear Generation Group Job Performance Measure Perform The Core Spray Pump Operability Test For Core Spray Pump B With Failure Of Minimum Flow Valve JPM Number: B.1.e.

Revision Number: 2 Date: 11/2002 NOTE: Original Signed - Disk Copy No Signatures Developed By:

Instructor Date Validated By:

SME or Instructor Date Review By:

Operations Representative Date

B.1.e.

Job Performance Measure (JPM)

Page 35 Revision Record (Summary)

Revision 0, This JPM is developed IAW guidelines established in NUREG 1021 Rev 8 ES-301 and Appendix C. This JPM meets the criteria of Category B.1 "Control Room Systems," for RO/SRO candidates.

Revision 1 The JPM was revised to incorporate validation time and comments.

Revision 2 The JPM was revised to incorporate NRC validation comments.

Information For Evaluators Use:

Provide a copy of QCOS 1400-04 Core Spray Pump Operability Test with section D.1 and D.2. filled out for Unit 1 for a Partial for Core Spray Subsystem B signed and dated by the Unit Supervisor.

Steps H.1.a. marked N/A.

H.1.b.(1),(2),(4)&(5) initialed of as EO/ANSO.

H.1.b.(3) recorded as 5 seconds, and H.1.b.(3)(a) initialed as ANSO.

H.2. marked N/A.

H.4.a. marked N/A.

UNSAT requires written comments on respective step.

  • Denotes CRITICAL steps.

Number any comments in the Comment Number column on the following pages. Then annotate that comment in the Comments section at the bottom of the page. The comment section should be used to document the reason that a step is marked as unsatisfactory and to document unsatisfactory performance relating to management expectations.

Some operations that are performed from outside of the control room may require multiple steps. These items may be listed as individual steps in this JPM. It is acceptable for the candidate to direct the local operator to perform groups of procedure steps instead of calling for each individual item to be performed.

The timeclock starts when the candidate acknowledges the initiating cue.

B.1.e.

Job Performance Measure (JPM)

Page 36 SIMULATOR SETUP INSTRUCTIONS

30. Reset the simulator to IC 21 (rst 21).

NOTE:

It is okay to use a similar IC to the IC listed above, provided the IC actually used is verified to be compatible with this and other JPMs that are scheduled to be run concurrently.

31. Provide a copy of QCOS 1400-04 Core Spray Pump Operability Test with section D.1 and D.2. filled out for Unit 1 for a Partial for Core Spray Subsystem B signed and dated by the Unit Supervisor.

Steps H.1.a. marked N/A.

H.1.b.(1),(2),(4)&(5) initialed of as EO/ANSO.

H.1.b.(3) recorded as 5 seconds, and H.1.b.(3)(a) initialed as ANSO.

H.2. marked N/A.

H.4.a. marked N/A.

32. Manual Actuation:

NONE Malfunctions:

Fail the Core Spray Minimum Flow Valve to Auto Close using (imf cs06b)

Override 1-1402-38B handswitch to neutral using (ior dihs1140238b norm)

Remotes:

NONE Overrides:

NONE

33. When the above steps are completed for this and other JPMs to be run concurrently, then validate the concurrently run JPMs using the JPM Validation Checklist.
34. This completes the setup for this JPM.

B.1.e.

Job Performance Measure (JPM)

Page 37 INITIAL CONDITIONS

  • The Core Spray System is in its normal standby lineup IAW QCOP 1400-01.
  • The Core Spray Pump Operability Test is required to be performed this shift.
  • All personnel are cleared out of the 1B Core Spray room as controlled by the EO.
  • This JPM is not time critical.

INITIATING CUE Perform the Core Spray Pump Operability Test for the 1B Core Spray Pump IAW QCOS 1400-04.

Fill in the JPM Start Time when the student acknowledges the Initiating Cue.

B.1.e.

Job Performance Measure (JPM)

Page 38 JPM Start Time:

PERFORMANCE OBJECTIVE STANDARDS SAT UNSAT N/A H.3.a.

Verify torus level < -2 narrow range, then alternate suction pressure limit > 1 psig is met.

Checks torus level. Verifies at > -2 (alternate suction pressure limit not applicable).

[ ]

[ ]

  • H.3.b.(1).

Start 1B Core Spray pump.

Positions pump CS to start.

Red light lit.

[ ]

[ ]

CUE: If NLO is asked to report on pump operating status, report that the 1B Core Spray pump is operating satisfactorily.

H.3.b.(2).

Verify MO 1-1402-38B opens.

Verifies MO 38B open light lit.

[ ]

[ ]

  • H.3.b.(3).

Open MO 1-1402-4B.

Positions 4B CS to fully open valve open light lit.

[ ]

[ ]

  • H.3.b.(4).

Verify MO 1-1402-38B closes.

Determines that the 38B did not close.

[ ]

[ ]

H.3.b.(4).

Attempts to close the 1-1402-38B.

Positions the CS for the 38B to close.

Identifies that the valve still didnt close.

[ ]

[ ]

[ ]

H.3.b.(4).

Report the Min. Flow valve did not close.

Informs US that 1-1402-38B did not close.

[ ]

[ ]

CUE: Acknowledge report as US.

When candidate identifies need to shutdown the pump IAW step F.6, give cue as US to shutdown the pump IAW the procedure.

If candidate informs US that QCAP 0230-19 needs to be initiated, acknowledge that you as US will perform the procedure.

  • H.3.c.(1).

Close MO 1-1402-4B.

Positions CS to close. Close light lit.

[ ]

[ ]

  • H.3.c.(3).

Stop 1B Core Spray pump.

Positions pump CS to stop Green light lit.

[ ]

[ ]

EVALUATOR:

When the pump is OFF, inform the candidate that the JPM is complete.

JPM Stop Time:

  • Emergent Critical Step

B.1.e.

Job Performance Measure (JPM)

Page 39 Operators Name:

Job

Title:

RO

SRO

JPM

Title:

Perform the Core Spray Pump Operability Test For Core Spray Pump B With Failure Of Minimum Flow Valve JPM Number: B.1.e.

Revision Number: 2 Task Number and

Title:

SR-1400-P05 - Given a reactor plant with a core spray loop in a standby lineup, perform the Core Spray Pump Flow Rate Test and return the core spray loop to standby in accordance with QCOS 1400-01.

K/A Number and Importance:

K/A: 209001 A4.04 RATING: 2.9/2.9 Suggested Testing Environment:Simulator Actual Testing Environment:

Simulator

Plant

Control Room Testing Method:

Simulate Faulted: Yes I No Perform Alternate Path: I Yes No Time Critical: Yes I No Estimated Time to Complete:_15_minutes Actual Time Used: minutes

References:

QCOS 1400-04, Rev. 10

B.1.e.

Job Performance Measure (JPM)

Page 40 EVALUATION

SUMMARY

Were all the Critical Elements performed satisfactorily?

Yes

No The operators performance was evaluated against the standards contained in this JPM, and has been determined to be:

Satisfactory Unsatisfactory Comments:

Evaluators Name:

(Print)

Evaluators Signature:

Date:

Page 41 INITIAL CONDITIONS (Student Copy)

  • The Core Spray System is in its normal standby lineup IAW QCOP 1400-01.
  • The Core Spray Pump Operability Test is required to be performed this shift.
  • All personnel are cleared out of the 1B Core Spray room as controlled by the EO.
  • This JPM is not time critical.

INITIATING CUE Perform the Core Spray Pump Operability Test for the 1B Core Spray Pump IAW QCOS 1400-04.

Page 42 Nuclear Generation Group Job Performance Measure Venting Of the Primary Containment due to High Hydrogen with a Failure of a Vent Valve to Open JPM Number: _B.1.f._

Revision Number: _2_

Date: _11/2002_

NOTE: Original Signed - Disk Copy No Signatures Developed By:

Instructor Date Validated By:

SME or Instructor Date Review By:

Operations Representative Date

B.1.f.

Job Performance Measure (JPM)

Page 43 Revision Record (Summary)

Revision 0,This JPM is developed IAW guidelines established in NUREG 1021 Rev 8 ES-301 and Appendix C. This JPM meets the criteria of Category B.1 "Control Room Systems," for RO/SRO candidates.

Revision 1 The JPM was revised to incorporate validation time and comments.

Revision 2 The JPM was revised to incorporate NRC validation comments.

Information For Evaluators Use:

UNSAT requires written comments on respective step.

  • Denotes CRITICAL steps.

Number any comments in the Comment Number column on the following pages. Then annotate that comment in the Comments section at the bottom of the page. The comment section should be used to document the reason that a step is marked as unsatisfactory and to document unsatisfactory performance relating to management expectations.

Some operations that are performed from outside of the control room may require multiple steps. These items may be listed as individual steps in this JPM. It is acceptable for the candidate to direct the local operator to perform groups of procedure steps instead of calling for each individual item to be performed.

The timeclock starts when the candidate acknowledges the initiating cue.

B.1.f.

Job Performance Measure (JPM)

Page 44 SIMULATOR SETUP INSTRUCTIONS

35. Reset the simulator to IC 95 (rst 95 ). This IC is a shutdown reactor, stable following a scram and is setup specifically for this JPM. If it is not available follow the directions below.
36. IC

Description:

The Reactor is scrammed, Group II isolation in effect, DW pressure 8.6 psig, Torus pressure 6.9 psig.

NOTE:

It is okay to use a similar IC to the IC listed above, provided the IC actually used is verified to be compatible with this and other JPMs that are scheduled to be run concurrently.

37. Manual Actuations:

Depress both scram buttons to scram the Reactor then perform QCGP 2-3 actions.

Prevent HPCI injection by tripping HPCI with the trip latch.

Ensure reactor building vents have isolated and B SBGT train is operating.

Ensure AO-1601-61, 62, 63, 60, 23, 24 are closed.

Start the 7th DW cooler.

38. Malfunctions:

Cause a Group II Isolation to seal in using malfunction RP07.

(imf rp07a) & (imf rp07b)

Insert Main Steam line leak after the flow restrictors (imf ms05a 0.1)

Override the 1-1601-61 valve closed (ior dihs1160161 close)

39. Remotes: NONE
40. Overrides:

Override the Hydrogen recorder to 2.5 (ior aoh212406a 25)

B.1.f.

Job Performance Measure (JPM)

Page 45

41. When the above steps are completed for this and other JPMs to be run concurrently, then validate the concurrently run JPMs using the JPM Validation Checklist.
42. This completes the setup for this JPM.

B.1.f.

Job Performance Measure (JPM)

Page 46 INITIAL CONDITIONS A transient has occurred resulting in hydrogen generation.

The US has entered the Hydrogen control procedure, QGA 200-5.

Chemistry has sampled the containment atmosphere and determined that the offsite release rate will stay below the LCO when venting has commenced.

Chemistry has recommended using SBGTS as a vent path.

There are as many fans as possible operating.

SBGT is operating.

The Essential Service bus and both RPS busses are energized.

Station Director has given permission to vent (NOT OK to exceed release rates).

This JPM is not time critical.

INITIATING CUE Line-up and begin venting the Torus through SBGT in accordance with QCOP 1600-13 to reduce hydrogen concentration in the containment.

Fill in the JPM Start Time when the student acknowledges the Initiating Cue.

B.1.f.

Job Performance Measure (JPM)

Page 47 JPM Start Time:

PERFORMANCE OBJECTIVE STANDARDS SAT UNSAT N/A Obtain the procedure to be used.

Procedure QCOP 1600-13 obtained.

[ ] [ ]

F.2.

Verify closed the following Primary Containment valves:

Verify closed the following Primary Containment valves:

a. Torus 2 Vent vlv.

AO 1-1601-61, closed light lit.

[ ] [ ] [ ]

b. DW 2 Vent vlv.

AO 1-1601-62, closed light lit.

[ ] [ ] [ ]

c. Vent to SBGTS.

AO 1-1601-63, closed light lit.

[ ] [ ] [ ]

d. Torus 18 Vent vlv.

AO 1-1601-60, closed light lit.

[ ] [ ] [ ]

e. DW 18 Vent vlv.

AO 1-1601-23, closed light lit.

[ ] [ ] [ ]

f. Vent to RX Bldg. Exh Sys.

AO 1-1601-24, closed light lit.

[ ] [ ] [ ]

F.3.a.

Verify "B" SBGTS train is running.

"B" train of SBGTS verified running.

[ ] [ ] [ ]

F.3.b.

Announce evacuation of SBGT area and that plant radiological conditions may change as containment is vented.

Announcement made over plant page.

[ ] [ ] [ ]

F.3.c.

Verify MASTER VENT MODE switch in NORM.

Verifies switch in NORM.

[ ] [ ] [ ]

F.3.d.(1)

Place the VENT ISOL SIG BYP key switch to TORUS position and verifies alarm actuates.

Switch is momentarily placed in TORUS position, AND alarm 901-3 A-15 verified on.

[ ] [ ] [ ]

F.3.d.(2)

Open Vent to SBGTS.

Positions AO 1-1601-63 CS to open open light lit.

[ ] [ ] [ ]

F.3.d.(3)

Attempts to open the Torus 2" Vent valve and recognizes valve fails to open.

Positions AO 1-1601-61 CS to open identifies valve did not change position, open light not lit.

[ ] [ ]

Notifies US of valve failure to open.

Notifies US that 1-1601-61 valve failed to open.

[ ] [ ] [ ]

B.1.f.

Job Performance Measure (JPM)

Page 48 PERFORMANCE OBJECTIVE STANDARDS SAT UNSAT N/A CUE: Acknowledge 1-1601-61 valve failed to open. If candidate stops at this point or requests direction from the US, ask them for their recommendation. If candidate does not offer a recommendation, tell them to continue on with procedure.

Note to evaluator: The next step in the procedure F.3.e. allows the candidate to vent the drywell if torus venting is not able to control hydrogen concentration as long as drywell pressure is less than 25psig.

  • F.3.e.(1)

Place the VENT ISOL SIG BYP key switch to DRYWELL position and verifies alarm actuates.

Switch is momentarily placed in DRYWELL position, AND alarm 901-3 A-15 verified on.

[ ] [ ]

F.3.e.(2)

Verifies Torus 2" Vent valve closed.

Verifies AO 1-1601-61 closed closed light lit.

[ ] [ ]

  • F.3.e.(3)

Open Vent to SBGTS.

Verifies AO 1-1601-63 open open light lit.

[ ] [ ]

  • F.3.e.(4)

Opens the Drywell 2" Vent valve.

Positions AO 1-1601-62 CS to open open light lit.

[ ] [ ]

Evaluator Note: Due to simulator set-up for this JPM, drywell pressure and hydrogen concentration will not show a reducing trend so you must cue candidate that these parameters are decreasing.

Cue: Inform candidate that drywell pressure and hydrogen concentration is dropping.

F.3.e.(6)

Monitor Release Rate.

Monitors, 1/2-1704-19, CHIMNEY GAS ACTIVITY recorder on Panel 912-4 AND 1/2-1740-202, MN CHIMNEY GAS ACTIVITY recorder 912-1.

[ ] [ ] [ ]

F.3.e.(6)(a)

Verify release rate limit is NOT being exceeded.

Contacts Chemistry or verifies absence of alarms 912-1 E-9 and F-9 on 912-1 to ensure limit is NOT being exceeded.

[ ] [ ]

F.3.e.(7)

Logs data in log book.

Log the following information in the Unit Log Book:

(a) Time of venting start & stop.

(b) Drywell and Torus pressure at time of vent start & stop.

[ ] [ ]

EVALUATOR: The candidate should inform you that the task is completed.

JPM Stop Time:

B.1.f.

Job Performance Measure (JPM)

Page 49 Operators Name:

Job

Title:

RO

SRO

JPM

Title:

Venting Of the Primary Containment due to High Hydrogen with a Failure of a Vent Valve to Open JPM Number: B.1.f.

Revision Number: 2 Task Number and

Title:

SR-0001-P038, Post Accident Venting Of The Primary Containment K/A Number and Importance:

K/A: 500000 EA1.03 Rating: 3.4/3.2 Suggested Testing Environment: Simulator Actual Testing Environment:

Simulator

Plant

Control Room Testing Method: Simulate Faulted: Yes I No Perform Alternate Path: I Yes No Time Critical: Yes I No Estimated Time to Complete: 20 minutes Actual Time Used: minutes

References:

QCOP 1600-13, Rev. 15

B.1.f.

Job Performance Measure (JPM)

Page 50 EVALUATION

SUMMARY

Were all the Critical Elements performed satisfactorily?

Yes

No The operators performance was evaluated against the standards contained in this JPM, and has been determined to be:

Satisfactory Unsatisfactory Comments:

Evaluators Name:

(Print)

Evaluators Signature:

Date:

Page 51 INITIAL CONDITIONS (Student Copy)

A transient has occurred resulting in hydrogen generation.

The US has entered the Hydrogen control procedure, QGA 200-5.

Chemistry has sampled the containment atmosphere and determined that the offsite release rate will stay below the LCO when venting has commenced.

Chemistry has recommended using SBGTS as a vent path.

There are as many fans as possible operating.

SBGT is operating.

The Essential Service bus and both RPS busses are energized.

Station Director has given permission to vent (NOT OK to exceed release rates).

This JPM is not time critical.

INITIATING CUE Line-up and begin venting the Torus through SBGT in accordance with QCOP 1600-13 to reduce hydrogen concentration in the containment.

Page 52 Nuclear Generation Group Job Performance Measure Pressurize The Main Steam Lines JPM Number: B.1.g.

Revision Number: _2_

Date: 11/2002 NOTE: Original Signed - Disk Copy No Signatures Developed By:

Instructor Date Validated By:

SME or Instructor Date Review By:

Operations Representative Date

B.1.g.

Job Performance Measure (JPM)

Page 53 Revision Record (Summary)

Revision 0, This JPM is developed IAW guidelines established in NUREG 1021 Rev 8 ES-301 and Appendix C. This JPM meets the criteria of Category B.1 "Control Room Systems," for RO/SRO candidates.

Revision 1 The JPM was revised to incorporate validation time and comments.

Revision 2 The JPM was revised to incorporate NRC validation comments.

Information For Evaluators Use:

UNSAT requires written comments on respective step.

  • Denotes CRITICAL steps.

Number any comments in the Comment Number column on the following pages. Then annotate that comment in the Comments section at the bottom of the page. The comment section should be used to document the reason that a step is marked as unsatisfactory and to document unsatisfactory performance relating to management expectations.

Some operations that are performed from outside of the control room may require multiple steps. These items may be listed as individual steps in this JPM. It is acceptable for the candidate to direct the local operator to perform groups of procedure steps instead of calling for each individual item to be performed.

The timeclock starts when the candidate acknowledges the initiating cue.

B.1.g.

Job Performance Measure (JPM)

Page 54 SIMULATOR SETUP INSTRUCTIONS

43. Reset the simulator to IC 94 (rst 94). This IC is a shutdown reactor, stable following a scram and is base IC setup specifically for this JPM.
44. IC

Description:

NOTE:

It is okay to use a similar IC to the IC listed above, provided the IC actually used is verified to be compatible with this and other JPMs that are scheduled to be run concurrently.

45. Manual Actuation:

Simulator operator must control reactor pressure manually with relief valves to control pressure 800-1000 psig while candidate is reopening the MSIVS.

46. Malfunctions:

Allow Gp I isolation to cause scram by performing the following:

Insert, then remove, malfunction RP05 A & B.

(imf rp05a) & (imf rp05b)

(dmf rp05a) & (dmf rp05b)

47. Remotes: NONE
48. Overrides: NONE
49. When the above steps are completed for this and other JPMs to be run concurrently, then validate the concurrently run JPMs using the JPM Validation Checklist.
50. This completes the setup for this JPM.

B.1.g.

Job Performance Measure (JPM)

Page 55 INITIAL CONDITIONS

  • A Group I Isolation occurred approximately 30 minutes ago on Unit 1 due to low-low reactor water level.
  • Reactor water level has been restored and is now being controlled by Feed/Condensate.
  • Another RO will control pressure between 800 and 1000 psig with relief valves.
  • The Main Steam Lines have been drained and the Steam line drain valves are shut.
  • RPV level has been maintained less than 100 during the time the MSIVs have been closed.
  • This JPM is not time critical INITIATING CUE Pressurize the Unit 1 Main Steam lines and re-open the MSIV's. Notify Unit Supervisor when all MSIVs are open.

Fill in the JPM Start Time when the student acknowledges the Initiating Cue.

B.1.g.

Job Performance Measure (JPM)

Page 56 JPM Start Time:

PERFORMANCE OBJECTIVE STANDARDS SAT UNSAT N/A Obtain procedure to be used.

Procedure QCOP 250-1 obtained.

[ ] [ ] [ ]

  • F.1.

Place MN STM ISOL RESET to INBD.

Places MN STM ISOL RESET to INBD.

[ ] [ ]

  • F.2.

Place MN STM ISOL RESET to OUTBD.

Places MN STM ISOL RESET to OUTBD.

[ ] [ ]

  • F.3.

Adjust 1 A/B PRESS SETPOINT 200 psig above Reactor Pressure, OR as high as possible.

Adjusts 200 psig above reactor pressure or as high as possible.

[ ] [ ] [ ]

  • F.4.

Open Outboard MSIVs:

a. AO 1-203-2A, 2A OUTBD MSIV
b. AO 1-203-2B, 2B OUTBD MSIV
c. AO 1-203-2C, 2C OUTBD MSIV
d. AO 1-203-2D 2D OUTBD MSIV Opens outboard MSIVs by taking each C/S to OPEN on 901-3 AO 1-203-2A red light lit indicating OPEN AO 1-203-2B red light lit indicating OPEN AO 1-203-2C red light lit indicating OPEN AO 1-203-2D red light lit indicating OPEN

[ ] [ ]

F.5.

Open Steamline drain valves:

a. MO 1-220-90A STM LINE DRN VLV
b. MO 1-220-90B STM LINE DRN VLV
c. MO 1-220-90C STM LINE DRN VLV
d. MO 1-220-90D STM LINE DRN VLV Opens steamline drain valves by taking each C/S to OPEN on 901-3 MO 1-220-90A red light lit indicating OPEN MO 1-220-90B red light lit indicating OPEN MO 1-220-90C red light lit indicating OPEN MO 1-220-90D red light lit indicating OPEN

[ ] [ ] [ ]

  • F.6.

Equalize pressure across MSIVs:

a. Open MO 1-220-1, STM DRN ISOL VLV
b. Open MO 1-220-2, STM DRN ISOL VLV
c. Slowly throttle Open MO 1-220-3, OUTSIDE DRN VLV Opens steam drain valve by taking each C/S to OPEN on 901-3.

MO 1-220-1 red light lit indicating OPEN MO 1-220-2 red light lit indicating OPEN MO 1-220-3 indicates Mid-position OR OPEN

[ ] [ ]

  • Emergent Critical Step

B.1.g.

Job Performance Measure (JPM)

Page 57 PERFORMANCE OBJECTIVE STANDARDS SAT UNSAT N/A F.7.

Monitor the following indications AND verify that differential pressure across the MSIVs are decreasing

a. Reactor Pressure
b. PI 1-3040-10, TURB THROT PRESS (at panel 901-7)

Differential Pressure is decreasing using reactor pressure instrumentation and turbine throttle pressure on PI 1-3040-10 on 901-7.

[ ] [ ] [ ]

EVALUATORS NOTE: The next step is conditional and need not be performed to satisfactorily complete this task. Step will be performed only if D/P does not decrease to < 200 psid.

F.8.

IF diff. press. across MSIVs does NOT dec. to <200 psid, THEN, at panel 901-7, close valves

a. MO 1-3004A, B, C and D, CONT VLVS ABOVE SEAT DRN
b. MO 1-3005, CONT VLVS BELOW SEAT DRN May close above and below seat drains on 901-7 if D/P is not decreasing MO 1-3004A, B, C and D green light lit indicating CLOSED MO 1-3005 green light lit indicating CLOSED on 901-7.

[ ] [ ] [ ]

EVALUATOR: Unit Supervisors permission is NOT a critical part of step F.9.

Candidate may elect to open 2 valves simultaneously to avoid a high flow isolation signal from occurring.

  • F.9.

WHEN diff. press. across the MSIVs is

<200 psid OR has stopped decreasing and Unit Supervisor has given permission to proceed, THEN open inboard MSIVs:

a. AO 1-203-1A, 1A INBD MSIV
b. AO 1-203-1B, 1B INBD MSIV
c. AO 1-203-1C, 1C INBD MSIV
d. AO 1-203-1D 1D INBD MSIV Opens inboard MSIVs by taking each C/S to OPEN on 901-3 OPENS AO 1-203-1A red light lit indicating OPEN OPENS AO 1-203-1B red light lit indicating OPEN OPENS AO 1-203-1C red light lit indicating OPEN OPENS AO 1-203-1D red light lit indicating OPEN

[ ] [ ]

EVALUATOR: The candidate should inform you that the task is complete.

JPM Stop Time:

B.1.g.

Job Performance Measure (JPM)

Page 58 Operators Name:

Job

Title:

RO

SRO

JPM

Title:

Pressurize the Main Steam Lines JPM Number: B.1.g.

Revision Number: 2 Task Number and

Title:

SR-0250-P01, Given a reactor plant at power when an inadvertent Group 1 isolation occurs, determine the cause, reset the Group 1, and re-open the MSIVs in accordance with QCOP 0250-01.

K/A Number and Importance:

K/A: 239001 A4.01 Rating: 4.2/4.0 Suggested Testing Environment: Simulator Actual Testing Environment:

Simulator

Plant

Control Room Testing Method: Simulate Faulted: Yes I No Perform Alternate Path: Yes I No Time Critical: Yes I No Estimated Time to Complete: _25_minutes Actual Time Used: minutes

References:

QCOP 250-01, Rev. 5

B.1.g.

Job Performance Measure (JPM)

Page 59 EVALUATION

SUMMARY

Were all the Critical Elements performed satisfactorily?

Yes

No The operators performance was evaluated against the standards contained in this JPM, and has been determined to be:

Satisfactory Unsatisfactory Comments:

Evaluators Name:

(Print)

Evaluators Signature:

Date:

B.2.a.

Page 60 INITIAL CONDITIONS (Student Copy)

  • A Group I Isolation occurred approximately 30 minutes ago on Unit 1 due to low-low reactor water level.
  • Reactor water level has been restored and is now being controlled by Feed/Condensate.
  • Another RO will control pressure between 800 and 1000 psig with relief valves.
  • The Main Steam Lines have been drained and the Steam line drain valves are shut.
  • RPV level has been maintained less than 100 during the time the MSIVs have been closed.
  • This JPM is not time critical INITIATING CUE Pressurize the Unit 1 Main Steam lines and re-open the MSIV's. Notify Unit Supervisor when all MSIVs are open.

B.2.a.

Page 61 Nuclear Generation Group Job Performance Measure Aligning Fire Protection Water to SSMP Room Cooler JPM Number: B.2.a.

Revision Number: 02 Date: 11/2002 NOTE: Original Signed - Disk Copy No Signatures Developed By:

Instructor Date Validated By:

SME or Instructor Date Review By:

Operations Representative Date

B.2.a.

Job Performance Measure (JPM)

B.2.a.

Page 62 Revision Record (Summary)

Revision 0, The reason for this JPM is to demonstrate the ability to terminate one of the twenty most probable Core Damage Sequences.

This JPM is developed IAW guidelines established in NUREG 1021 Rev 8 ES-301 and Appendix C. This JPM meets the criteria of Category B.2 "Facility Walk-Through," for RO/SRO candidates.

Revision 1 The JPM was revised to incorporate validation time and comments.

Revision 2 The JPM was revised to incorporate NRC validation comments.

Information For Evaluators Use:

All components are located in the Safe Shutdown Makeup Pump Room on the south wall.

UNSAT requires written comments on respective step.

  • Denotes CRITICAL steps.

Number any comments in the Comment Number column on the following pages. Then annotate that comment in the Comments section at the bottom of the page. The comment section should be used to document the reason that a step is marked as unsatisfactory and to document unsatisfactory performance relating to management expectations.

Some operations that are performed from outside of the control room may require multiple steps. These items may be listed as individual steps in this JPM. It is acceptable for the candidate to direct the local operator to perform groups of procedure steps instead of calling for each individual item to be performed.

The timeclock starts when the candidate acknowledges the initiating cue.

B.2.a.

Job Performance Measure (JPM)

B.2.a.

Page 63 INITIAL CONDITIONS There is a severe fire in RB 1S. SSMP is the injection source for U-1. Service Water is no longer available to the SSMP Room Cooler.

You have been issued a flashlight, radio, and the AR tool box which includes; a V-key, an R-Key, VHR-key, a Fire Lock key, an S-Key, a straight blade screwdriver, a wire cutters, a crescent wrench.

This JPM is not time critical.

INITIATING CUE Align Fire Protection Water to SSMP Room Cooler in accordance with QCARP 0010-01 Attachment D.

Provide examinee with:

Copy of QCARP 0010-01 Attachment D.

Fill in the JPM Start Time when the student acknowledges the Initiating Cue.

B.2.a.

Job Performance Measure (JPM)

B.2.a.

Page 64 JPM Start Time:

PERFORMANCE OBJECTIVE STANDARDS SAT UNSAT N/A

Turns 1/2-2901-25 valve hand wheel clockwise until valve no longer moves.

[ ]

[ ]

[ ]

CUE: Indicate to the candidate that the valve will not longer turn after the proper technique is demonstrated.

Selects S Key and unlocks 1/2-2901-9 turns valve hand wheel counterclockwise until valve no longer moves.

[ ]

[ ]

[ ]

CUE: Indicate to the candidate that the lock is unlocked and that the valve will no longer turn after the proper technique is demonstrated.

  • Attachment D, step 3 Close 1/2-2999-9, SERVICE WATER TO SSMP ROOM COOLER BYPASS VALVE.

Turns 1/2-2999-9 valve hand wheel clockwise until valve no longer moves.

[ ]

[ ]

[ ]

CUE: Indicate to the candidate that the valve will not longer turn after the proper technique is demonstrated.

Attachment D, step 4 Verify SSMP Room Cooler Operation.

Checks to see if cooler is cooling room.

[ ]

[ ]

[ ]

CUE: After proper checks are made for Cooler operation (Proper checks should include that the candidate listens or feels for cool air flow discharging from the cooler, or verifying that the room is getting cooler), indicate to the candidate that the room is becoming cooler.

Attachment D, step 5 Notify U1 US that steps are complete.

Proper communication techniques.

[ ]

[ ]

[ ]

CUE: When informed, acknowledge as Unit One Unit Supervisor that you understand that the SSMP Room Cooler is lined up to the fire header.

Evaluator Note: Candidate should state that the JPM is complete.

  • CRITICAL STEP JPM Stop Time:

B.2.a.

Job Performance Measure (JPM)

B.2.a.

Page 65 Operators Name:

Job

Title:

RO

SRO

JPM

Title:

Align Fire Protection Water to SSMP Room Cooler JPM Number: B.2.a.

Revision Number: 2 Task Number and

Title:

SN 2900-P08 Given Unit 1 in an QCARP condition, transfer SSMP HVAC cooling water supply to the fire header and verify SSMP room cooler operation in accordance with QCARP 0010-01 Attachment D. (Important PSA task/transferring cooling water supply has Risk Achievement Worth (RAW) ranging from 1.25 alone to 655 in combination with other actions.

Accomplishing this task terminates 1 of the 20 most probable core damage sequences)

K/A Number and Importance:

K/A: 295018 AA1.01 RATING: 3.3/3.4 Suggested Testing Environment: Plant Actual Testing Environment:

Simulator

Plant

Control Room Testing Method: Simulate Faulted: Yes I No Perform Alternate Path: Yes I No Time Critical: Yes I No Estimated Time to Complete: _10_minutes Actual Time Used: minutes

References:

QCARP 0010-01 Attachment D, Rev. 1

B.2.a.

Job Performance Measure (JPM)

B.2.a.

Page 66 EVALUATION

SUMMARY

Were all the Critical Elements performed satisfactorily?

Yes

No The operators performance was evaluated against the standards contained in this JPM, and has been determined to be:

Satisfactory Unsatisfactory Comments:

Evaluators Name:

(Print)

Evaluators Signature:

Date:

Page 67 INITIAL CONDITIONS (Student Copy)

There is a severe fire in RB 1S. SSMP is the injection source for U-1. Service Water is no longer available to the SSMP Room Cooler.

You have been issued a flashlight, radio, and the AR tool box which includes; a V-key, an R-Key, VHR-key, a Fire Lock key, an S-Key, a straight blade screwdriver, a wire cutters, a crescent wrench.

This JPM is not time critical.

INITIATING CUE Align Fire Protection Water to SSMP Room Cooler in accordance with QCARP 0010-01 Attachment D.

Page 68 Nuclear Generation Group Job Performance Measure Depressurize the Scram Air Header JPM Number: B.2.b.

Revision Number: 2 Date: 11/2002 NOTE: Original Signed - Disk Copy No Signatures Developed By:

Instructor Date Validated By:

SME or Instructor Date Review By:

Operations Representative Date

B.2.b.

Job Performance Measure (JPM)

Page 69 Revision Record (Summary)

Revision 0 This JPM is developed IAW guidelines established in NUREG 1021 Rev 8 ES-301 and Appendix C. This JPM meets the criteria of Category B.2 "Facility Walk-Through," for RO/SRO candidates.

Revision 1 The JPM was revised to incorporate validation time and comments.

Revision 1 The JPM was revised to incorporate NRC validation comments.

Information For Evaluators Use:

All components are located in the U-2 reactor building 595 elevation near the southeast corner of the north CRD bank.

UNSAT requires written comments on respective step.

  • Denotes CRITICAL steps.

Number any comments in the Comment Number column on the following pages. Then annotate that comment in the Comments section at the bottom of the page. The comment section should be used to document the reason that a step is marked as unsatisfactory and to document unsatisfactory performance relating to management expectations.

Some operations that are performed from outside of the control room may require multiple steps. These items may be listed as individual steps in this JPM. It is acceptable for the candidate to direct the local operator to perform groups of procedure steps instead of calling for each individual item to be performed.

The timeclock starts when the candidate acknowledges the initiating cue.

B.2.b.

Job Performance Measure (JPM)

Page 70 INITIAL CONDITIONS An ATWS has occurred on Unit 2 with reactor power currently at 35%.

The Control Room is in QGA 101 and attempting to insert Control Rods.

The Unit Supervisor has directed performance of QCOP 0300-28 This JPM is not time critical INITIATING CUE Vent the U-2 scram air header to insert control rods in accordance with QCOP 0300-28 step F.3.

Provide candidate a copy of QCOP 0300-28.

Fill in the JPM Start Time when the student acknowledges the Initiating Cue.

B.2.b.

Job Performance Measure (JPM)

Page 71 JPM Start Time:

PERFORMANCE OBJECTIVE STANDARDS SAT UNSAT N/A

  • F.3.a.(1)

Close OR verify closed both 2-301-147A AND B, INST AIR TO SCRAM VLV PILOT AIR HDR A/B (FILT)

INLET VLV.

Rotates 2-301-147A AND 147B handwheels clockwise until they do not turn any further.

[ ]

[ ]

[ ]

Cue:

You have rotated the handwheels clockwise and they will not turn any further.

  • F.3.a.(2)

Manually open RV 2-0399-24 SCRAM AIR RELIEF VALVE RV, by lifting the relief valve handle.

Lifts handle on RV 2-0399-24.

[ ]

[ ]

[ ]

Cue:

You heard air blowing for several seconds, the flow then slowed and finally stopped. The Control Room reports that all the control rods have fully inserted. Restore the scram air header.

F.3.b.(1)

Close RV 2-0399-24 SCRAM AIR RELIEF VALVE RV.

Releases handle on RV 2-0399-24.

[ ]

[ ]

[ ]

Cue:

You have released the handle on the Relief Valve and it has returned to its original position.

F.3.b.(2)

Open either the 2-301-147A OR B, INST AIR TO SCRAM VLV PILOT AIR HDR A/B (FILT) INLET.

Rotates 2-301-147A OR 147B handwheel counterclockwise until it does not turn any further.

[ ]

[ ]

[ ]

Cue:

You have rotated the handwheel counterclockwise and it will not turn any further. If asked, scram air header pressure indication is 70 psig and rising.

EVALUATOR:

The candidate should inform you that the task is complete.

JPM Stop Time:

B.2.b.

Job Performance Measure (JPM)

Page 72 Operators Name:

Job

Title:

RO

SRO

JPM

Title:

Depressurize the scram air header JPM Number: B.2.b.

Revision Number: 2 Task Number and

Title:

SRN-0300-TP019 - Given a reactor plant in an ATWS condition (QGA),

locally isolate and depressurize the scram air header in accordance with QCOP 300-28.

K/A Number and Importance:

K/A: 295037 EA1.03 Rating: 4.1/4.1 Suggested Testing Environment: Plant Actual Testing Environment:

Simulator

Plant

Control Room Testing Method: Simulate Faulted: Yes I No Perform Alternate Path: Yes I No Time Critical: Yes I No Estimated Time to Complete: 10 minutes Actual Time Used: minutes

References:

QCOP 0300-28 Rev. 19

B.2.b.

Job Performance Measure (JPM)

Page 73 EVALUATION

SUMMARY

Were all the Critical Elements performed satisfactorily?

Yes

No The operators performance was evaluated against the standards contained in this JPM, and has been determined to be:

Satisfactory Unsatisfactory Comments:

Evaluators Name:

(Print)

Evaluators Signature:

Date:

B.2.c.

Page 74 of 1 INITIAL CONDITIONS (Student Copy)

An ATWS has occurred on Unit 2 with reactor power currently at 35%.

The Control Room is in QGA 101 and attempting to insert Control Rods.

The Unit Supervisor has directed performance of QCOP 0300-28 This JPM is not time critical INITIATING CUE Vent the U-2 scram air header to insert control rods in accordance with QCOP 0300-28 step F.3.

B.2.c.

Page 75 of 1 Nuclear Generation Group Job Performance Measure Perform the Aux Electric Room actions to Alignstart RHR in the Shutdown Cooling Mode in accordance with QCOP 1000-29.

JPM Number: B.2.c.

Revision Number: 02 Date: 1108/2002 NOTE: Original Signed - Disk Copy No Signatures Developed By:

Instructor Date Validated By:

SME or Instructor Date Review By:

Operations Representative Date Approved By:

Training Department Date

B.2.c.

Job Performance Measure (JPM)

B.2.c.

Page 76 of 1 Revision Record (Summary) 1.Revision 0, The reason for this JPM is to demonstrate the ability to terminate one of the twenty most probable Core Damage Sequences.

This JPM is developed IAW guidelines established in NUREG 1021 Rev 8 ES-301 and Appendix C. This JPM meets the criteria of Category B.2. "Facility Walk Through," for RO/SRO candidates.

Revision 1 The JPM was revised to incorporate validation time and comments.

Revision 2 The JPM was revised to incorporate NRC validation comments.

Information For Evaluators Use:

All components are located in the Aux. Equipment Room. A key will need to be checked out at the Work Execution Center to access the cabinets in the Aux. Electric room UNSAT requires written comments on respective step.

Denotes CRITICAL steps.

Number any comments in the Comment Number column on the following pages. Then annotate that comment in the Comments section at the bottom of the page. The comment section should be used to document the reason that a step is marked as unsatisfactory and to document unsatisfactory performance relating to management expectations.

Some operations that are performed from outside of the control room may require multiple steps. These items may be listed as individual steps in this JPM. It is acceptable for the candidate to direct the local operator to perform groups of procedure steps instead of calling for each individual item to be performed.

The timeclock starts when the candidate acknowledges the initiating cue.

B.2.c.

Job Performance Measure (JPM)

B.2.c.

Page 77 of 8 INITIAL CONDITIONS Unit 2 is entering a refueling outage.

- The Control Room has been evacuated due to toxic gas in the ventilation system.

The Unit Supervisor has directed that the A Loop of Shutdown Cooling is to be placed in service from outside the Control Room.

The Condensate Transfer system is available.

- Operators have been briefed and are standing by outside the MSIV room at phone extension 2431 with Radiation Protection support and all necessary equipment to perform step F.7.

- The reactor is shut down with reactor pressure at 37 psig.

The plant is NOT using the QCARPs.

- The Shutdown Cooling suction header has been filled and vented.

- The RHR Service Water system is operating with discharge pressure of 275 psig.

- You have an Aux Electric Room key, and a jumper wire.

- This JPM is not time critical

-Unit 1(2) is entering a refueling outage.

- The Control Room has been evacuated due to toxic gas in the ventilation system.

-The Unit Supervisor has determined that A Loop Shutdown Cooling is being placed in service from outside the Control Room.

-The Condensate Transfer system is available.

- Operators have been briefed and are standing by in the plant with Radiation Protection support and all necessary equipment.

- The reactor is shut down with reactor pressure at 37 psig.

-The plant is NOT using the QARPs.

- The Shutdown Cooling suction header has been filled and vented.

- The RHR Service Water system is operating with discharge pressure of 275 psig.

- You have obtained an Aux Electric Room key, a jumper wire, and a small fuse pullers.

- This JPM is not time critical Initiating Cue: Perform the Aux Electric Room actions to align U-2ALoop RHR system in the Shutdown Cooling Mode in accordance with QCOP 1000-29 performing steps F.7.j.through F.7.l.

Initiating Cue: Perform the Aux Electric Room actions to start U1(2)

A Loop RHR system in the Shutdown Cooling Mode in accordance with QCOP 1000-29 starting at step F.7.j.

Provide examinee with:

1. Copy of QCOP 1000-29 signed off through step F.7.i.
2. Unit 2 Auxiliary Electric Room Key Fill in the JPM Start Time when the student acknowledges the Initiating Cue.

B.2.c.

Job Performance Measure (JPM)

B.2.c.

Page 78 of 8 Information For Evaluators Use:

UNSAT requires written comments on respective step.

  • Denotes CRITICAL steps.

Number any comments in the Comment Number column on the following pages. Then annotate that comment in the Comments section at the bottom of the page. The comment section should be used to document the reason that a step is marked as unsatisfactory and to document unsatisfactory performance relating to management expectations.

Some operations that are performed from outside of the control room may require multiple steps. These items may be listed as individual steps in this JPM. It is acceptable for the candidate to direct the local operator to perform groups of procedure steps instead of calling for each individual item to be performed.

The timeclock starts when the candidate acknowledges the initiating cue.

B.2.c.

Job Performance Measure (JPM)

B.2.c.

Page 79 of 8 JPM Start Time:

PERFORMANCE OBJECTIVE STANDARDS SAT UNSAT N/A Evaluator Note: Provide candidate with marked up copy of procedure and a U-2 Aux. Electric room key.

  • F.7.j.

Attachment B step 1.a.

Resets Group 2 isolation inboard logic per Attachment B.

Slides the ON/OFF switch for relay 595-115, located in the 901(2)-902-40 to the ON position.

[ ]

[ ]

[ ]

CUE: Indicate to the candidate that the ON/OFF switch for relay 595-115 is indicating ON.

  • F.7.j.

Attachment B, step 1.b.

Resets Group 2 isolation outboard logic per Attachment B.

Slides the ON/OFF switch for relay 595-116, located in the 901(2)-902-41 to the ON position.

[ ]

[ ]

[ ]

CUE: Indicate to the candidate that the ON/OFF switch for relay 595-116 is indicating ON.

Evaluators note: Portable radio use is NOT allowed in the Auxiliary Electric room, candidate should indicate that they would either use the phone or step out of the room to use the radio.

  • F.7.k.

Notifies operator to open the MO 2-1001-47 valve.

Using phone, notifies the operator standing by near the MO 2-1001-47 valve to open the valve

[ ] [ ] [ ]

CUE: Acknowledge notification of step completion and then Rreport asthat the an NLO that the has opened the MO 1(2)-1001-47 valve has been opened per step F.7.k. of QCOP 1000-29.

NOTE to Evaluator: Once started closed by momentary installation of the jumper, the valve contactors seal in until the valve is full open (30 to 40 seconds).

  • F.7.l.

Open the MO 1(2)-1001-50 SDC INBD ISOL LVL.

Momentarily places a jumper across terminals AA-12 and AA-13 in the 901(2)-902-40 panel.

[ ]

[ ]

[ ]

F.7.l.

Makes notification of step completion.

Notifies Unit Supervisor or other shift personnel that step F.7.l. is complete.

[ ]

[ ]

[ ]

CUE: Acknowledge notification of step completion and inform them that the JPM is complete. If questioned regarding valve position, state that an operator verified the MO 1(2)-1001-50 valve open via indication at the valve breaker.

  • CRITICAL STEP

B.2.c.

Job Performance Measure (JPM)

B.2.c.

Page 80 of 8 JPM Stop Time:

B.2.c.

Job Performance Measure (JPM)

B.2.c.

Page 81 of 8 Operators Name:

Job

Title:

NLO RO

SRO STA SRO Cert JPM

Title:

Perform the Aux Electric Room actions to start RHR in the Shutdown Cooling Mode in accordance with QCOP 1000-29.

JPM Number: B.2.c.

Revision Number: 200 Task Number and Title SRN-1000-P34 Given a shutdown reactor plant with the control room evacuated, perform the aux.

electric room actions to start RHR shutdown cooling operation in accordance with QCOP 1000-29 K/A Number and Importance:

K/A: APE 295021 AA1.02 RATING: 3.5/3.5 Suggested Testing Environment: Plant Actual Testing Environment:

Simulator I

Plant

Control Room Testing Method: I Simulate Faulted:

Yes II No Perform Alternate Path: Yes II No Time Critical: Yes I No Estimated Time to Complete: 24_10_minutesActual Time Used: minutes

References:

QCOP 1000-29, Rev. 11

B.2.c.

Job Performance Measure (JPM)

B.2.c.

Page 82 of 8 EVALUATION

SUMMARY

Were all the Critical Elements performed satisfactorily?

Yes

No The operators performance was evaluated against the standards contained in this JPM, and has been determined to be:

Satisfactory Unsatisfactory Comments:

Evaluators Name:

(Print)

Evaluators Signature:

Date:

B.1.a.

Job Performance Measure (JPM)

Page 83 Final Page INITIAL CONDITIONS (Student Copy)

Unit 2 is entering a refueling outage.

- The Control Room has been evacuated due to toxic gas in the ventilation system.

The Unit Supervisor has directed that the A Loop of Shutdown Cooling is to be placed in service from outside the Control Room.

The Condensate Transfer system is available.

- Operators have been briefed and are standing by outside the MSIV room at phone extension 2431 with Radiation Protection support and all necessary equipment to perform step F.7.

- The reactor is shut down with reactor pressure at 37 psig.

The plant is NOT using the QCARPs.

- The Shutdown Cooling suction header has been filled and vented.

- The RHR Service Water system is operating with discharge pressure of 275 psig.

- You have an Aux Electric Room key, and a jumper wire.

- This JPM is not time critical Initiating Cue: Perform the Aux Electric Room actions to align U-2ALoop RHR system in the Shutdown Cooling Mode in accordance with QCOP 1000-29 performing steps F.7.j.through F.7.l.

-Unit 1(2) is entering a refueling outage.

- The Control Room has been evacuated due to toxic gas in the ventilation system.

-The Unit Supervisor has determined that A Loop Shutdown Cooling is being placed in service from outside the Control Room.

-The Condensate Transfer system is available.

- Operators have been briefed and are standing by in the plant with Radiation Protection support and all necessary equipment.

- The reactor is shut down with reactor pressure at 37 psig.

-The plant is NOT using the QARPs.

- The Shutdown Cooling suction header has been filled and vented.

- The RHR Service Water system is operating with discharge pressure of 275 psig.

- You have obtained an Aux Electric Room key, a jumper wire, and a small fuse pullers.

- This JPM is not time critical Initiating Cue: Perform the Aux Electric Room actions to start U1(2)

A Loop RHR system in the Shutdown Cooling Mode in accordance with QCOP 1000-29 starting at step F.7.j.