ML022390550

From kanterella
Jump to navigation Jump to search
Draft - Section C Operating
ML022390550
Person / Time
Site: Calvert Cliffs  Constellation icon.png
Issue date: 07/11/2002
From: Conte R
Division of Reactor Safety I
To: Cruse C
Constellation Nuclear
References
50-317/02301, 50-318/02301
Download: ML022390550 (69)


Text

SCENARIO #2 SETUP

j.

2 Dropped CEAs (35 and 37)

CEDS012_35 and _37 onF6 andF7

k.

12 SG Tube Rupture MS002_02 (1 tube) on F8

6.

Enter Panel Overrides

a.

IC13 - INSTR AIR COMPR(S) Annunciator (K-25) to ON.

b.

1C07 - VCT Outlet MOV Handswitch, CVC-501, in CLOSE on Event Trigger for MOV CVC-501 in close.

c.

1C09 - Annunciators (2) for 13 HPSI Pp tagout-OFF.

d.

1C13 - Annunciators (2) for 13 CCW Pp tagout - OFF.

7.

Enter Remote Functions / Administrative

a.

Danger tag 13 CCW Pump.

b.

Danger tag 13 JHPSI Pump.

c.

Place off-normal tags on the CCW Head Tank due to Makeup CV

d.

Remote Functions to rackout 13 HPSI Pp.

e.

Remote Functions to rackout 13 CCW Pp.

8.

Set simulator time to real time, then place simulator in CONTINUE.

9.Give crew briefing.

a.

Present plant conditions:

100% power - MOC/10,200 MWD/MTU. Unit 2 is in Mode 5. RCS Boron - 900 PPM.

b.

Power history:

100% for previous 68 days.

c.

Equipment out of service:

13 CCW Pump out of service due to a broken shaft.

Estimated return to service is tomorrow-noon.

13 HPSI Pump out of service due motor bearing failure during the STP 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> ago. Estimated return to service in 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. IAS 3.5.2.

SCENARIO #2 SETUP

d.

Abnormal conditions:

11 CCW Head Tank Makeup CV is isolated due to leakby.

Alarm K-25 (INSTR AIR COMPR(S) is hanging, air compressors check out ok, alarm card swapped out but still in alarm. I&C is working up a troubleshooting plan.

e.

Surveillances due:

STP-029 (CEA Movement Test) due by end of shift.

SM will discuss with CRS shortly after turnover.

f.

Instructions for shift:

Maintain 100% power.

10.

Allow crew 3-5 minutes to acclimate themselves with their positions.

11.

Instructions for the Booth Operator.

a.

Activate malfunctions F1-F5 when each is cued by the lead evaluator.

b.

Activate the next malfunction (F6) after about a 5% power move and with the Lead Examiner's concurrence, then about 30 seconds activate F7.

c.

When Vital Auxiliaries is complete activate F8.

SCENARIO #2 SETUP RESPONSES TO CREW REQUEST If a request and response is not listed, delay response until reviewed with the examiner. Responses to routine requests, which have no effect the scenario, do not require examiner clearance.

REQUEST

RESPONSE

1.

OWC/E&C investigate failure of the Hotwell Level Controller (4405).

2.

OWC coordinate investigation of failure of 11 CW Pump.

3.

TBO close CAR-101 and Inlet MOV-5225 and secure 1 IA amertap.

4.

OWC/E&C investigate failure of VCT Level Transmitter.

5.

OWC/GS-NPO contacted regarding PORV 402 leakage.

6.

TBO/Chemistry investigate Turbine Plant sample alarm and SG Sample Panel alarm

7.

TBO close CAR-104 and 12B Inlet MOV and secure 12B amertap.

8.

OSO ensure all demins ready to be placed in service.

9.

Chemistry contacted for additional info.

10.

Chemistry contacted to sample SGs.

11.

Directs TBO to align 12 ADV to 1C43 with zero percent output.

Acknowledge request.

Acknowledge request. After 5 minutes the electricians report the breaker is tripped on over current.

Acknowledge each request. Three minutes after each request report the action complete.

Acknowledge request.

Acknowledge report.

Acknowledge report. After 2 minutes report as Chemistry, there is a bad tube leak in 12B waterbox. 45 ppb Na and Conductivity of 18 micro seimens.

Acknowledge each request. Three minutes after each request report the action complete.

Acknowledge report. After three minutes report all demins ready to be placed in service.

Report secondary chemistry is in Action Level 2.

After about 15 minutes report quantitative samples show significant activity in 12 SG.

After three minutes operate as directed.

SCENARIO #2 SETUP SHIFT TURNOVER I.

Present Plant Conditions 100%

II.

Bumup:

10200 MWD/MTU (MOC)

III.

Power History 100% for previous 68 days.

IV.

Equipment out of Service:

13 CCW Pump out of service due to a broken shaft. Estimated return to service is tomorrow-noon.

13 HPSI Pump out of service due motor bearing failure during the STP 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> ago. Estimated return to service in 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. IAS 3.5.2.

V.

Abnormal Conditions:

11 CCW Head Tank Makeup CV is isolated due to leakby.

Alarm K-25 (INSTR AIR COMPR(S) is hanging, air compressors check out ok, alarm card swapped out but still in alarm. I&C is working up a troubleshooting plan.

VI.

Surveillances Due:

VII.

Instructions for Shift STP-029 (CEA Movement Test) due by end of shift. SM will discuss with CRS shortly after turnover.

Maintain 100% power.

VIII. U2 Status and Major Equipment OOS:

Mode 5 - no CW Pps and 23AFW Pp is OOS.

Simulation Facility Calvert Cliffs Scenario No.: 3 Op Test No.:

1 Simulation Facility Calvert Cliffs Scenario No.: 3 Op Test No.:

1 Examiners:

Operators:

SRO RO CRO Objectives:

To evaluate the applicant's ability to conduct a unit power reduction, to implement the ARMs, OIs, AOPs, as appropriate, for malfunctioning systems and/or controls including a failure of PRZR level control channel (llOX) which causes a broken shaft on 12 Charging Pp, a failed FRV Controller (1121) and a SGFP oil leak causing a rapid power reduction. A loss of 11 BA Pp occurs at the start of the downpower. The crew will be forced to trip the unit when the running SGFP trips. Two stuck CEAs require boration to meet reactivity but a loss of 11 4KV Bus will force the crew to EOP-8 for reactivity not being met. In EOP-8, boration will be restored via IPSI injection and 11 AFW Pp will trip resulting in a loss of feed. The crew can restore AFW by aligning 12 AFW Pp.

Initial Conditions:

The plant is at 67% Power, MOC (IC-17) 11 Chg Pp is OOS 12 SGFP Pp is OOS.

11 CCW Head Tank Makeup CV is isolated due to leakby.

INSTR AIR COMPR(S) alarm (K-25) hanging.

Turnover:

Present plant conditions: 67% power, MOC; Unit 2 is in MODE 5 - no CW Pps and 23 AFW Pp unavailable.

Power history: 67% power for previous 4 days.

Equipment out of service:

1) 11 Chg Pp packing replacement. Expected to be returned to service in 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />. All Chg. Pumps have been repacked, currently running in the packing on 13.
2) 12 SGFP Pp to repair steam leak on LP poppets. It is disassembled, expected to be returned to service tomorrow
3) 11 CCW Head Tank Makeup CV is isolated due to leakby.
4) Alarm K-25 INSTR AIR COMPR(S) is hanging. No problems with the compressors, I & C is investigating, alarm card has been swapped out.

Surveillances due: 1B DG STP-0-8 due today. SM will bring STP to CR when ready.

Instructions for shift:

1) Maintain current power level. Perform 1B DG STP-0-8 when directed by SM.

'-islJ.).'ioc I

WzuW.aoc 1

Event l Malf.

l Event Event No.

l No.

Type*

Description Preload FW004_02 12 SGFP OOS.

CEDS010_28 2 stuck CEAs.

CEDSO1O_42 Remote Func 11 CHG Pp OOS. (bkr rackout)

PNL OVR INSTR AIR COMPR(S) alarm hanging.

(K-25)

RCS026_01 I

RO About 3 minutes after the crew has taken the watch, PRZR level contr. (1 loX)

(low) fails low. The RO should acknowledge the alarm, inform the CRS and refer to the ARM. Level control should be shifted to channel Y and the OWC notified.

T.S. 3.3.10 should be entered.

2 CVCS003_02 C

RO 12 Chg. Pp shaft breaks on start following 1 lOX failure, however, the pump stops again when channel Y is selected. It is unlikely the crew will notice the failure here, but probably later during the downpower or boration to meet reactivity control in EOP-0. When discovered the crew is expected to attempt to ensure boration via another means and to contact the OWC for assistance.

3 FW018_02 I

CRO Next, 12 SG FRV Controller (1121) fails. The CRO should acknowledge the (LO) alarm and inform the CRS. The CRS should direct the CRO to maintain SG level and implement AOP-3 G. The CRS should direct the CRO to place the controller switch in the Main Fail position. The CRS should direct the OWC to contact the System Engineer for assistance.

4 PNL OVR C

CRO The CRO acknowledges the SGFP Conditioner Level Low Alarm, informs the (Conditioner R

RO CRS and dispatches the TBO. Following the TBO report, a rapid downpower level low C

RO will be initiated to take 11 SGFP off. (The crew may notice the charging pump alarm)

N CRO malfunction at this time.) The OWC should be contacted for assistance and CVCS014_01 notifications. As the power reduction to take 11 SGFP off is begun, 11 BAPp FW004_01 trips off when started. The RO will either use 12 BA Pp or gravity feed from the BASTs. At =50% power, 11 SGFP trips. The CRS should order the unit tripped due to loss of feed. EOP-0 is implemented, the RO notes 2 stuck CEAs and commences boration.

5 4KVOO1_01 M

ALL After the RO reports on Pressure and Inventory, a loss of 11 4KV Bus occurs (may refer to AOP-71). The CRS orders a reassessment of safety functions. The RO should determine reactivity is no longer being met due to no charging and direct the TBO to align 13 Chg. Pp to 14 bus. With the TBO being unsuccessful the CRS will enter EOP-8 for failure to meet reactivity.

6 AFW001_01 M

ALL EOP-8 is entered and the selected Success Paths begun. Boration is restored via EPSI injection. While working to establish boration, 11 AFW Pp trips the CRS or CRO should direct the TBO to investigate and align 12 AFW Pp. After AFW has been restored and boration, established, the scenario can be terminated.

  • (N)ormal, (R)eactivity (l)nstrument, (C)omponent, Major Transient

-c o L

U/zv3.Uoc 2

SCENARIO 3 OVERVIEW The candidates will take the shift at =67% power.

About 3 minutes after the crew has taken the watch, PRZR level contr. (11OX) fails low. The RO should acknowledge the alarm, inform the CRS and refer to the ARM. Level control should be shifted to channel Y and the OWC notified. T.S. 3.3.10 should be entered.

12 Chg. Pp shaft breaks on start following 11X failure, however, the pump stops again when channel Y is selected. It is unlikely the crew will notice the failure here, but probably later in the scenario during the downpower or boration to meet reactivity control in EOP-0. When discovered the crew is expected to attempt to ensure boration via another means and to contact the OWC for assistance.

Next, 12 SG FRV Controller (1121) fails. The CRO should acknowledge the alarm and inform the CRS. The CRS should direct the CRO to maintain SG level and implement AOP-3G. The CRS should direct the CRO to place the controller switch in the Main Fail position. The CRO will control level via the PDI. The CRS should direct the OWC to contact the System Engineer for assistance.

The CRO acknowledges the SGFP Status Panel alarm and determines the alarm to be a SGFP Conditioner Level Low Alarm, informs the CRS and dispatches the TBO. Following the TBO report of a bad oil leak on 11 SGFP pump, a rapid downpower will be initiated to take 11 SGFP off. (The crew may notice the charging pump malfunction at this time.) The OWC should be contacted for assistance and notifications. As the power reduction to take 11 SGFP off is begun, 11 BA Pp trips off when started for the initial boration. The RO will either use 12 BA Pp or gravity feed from the BASTs to borate. At =50% power, 11 SGFP trips. The CRS should order the unit tripped due to loss of feed. EOP-0 is implemented, the RO notes 2 stuck CEAs and commences boration.

After the RO reports the status of RCS Pressure and Inventory, a loss of 11 4KV Bus occurs (may refer to AOP-7I).

The CRS should order a reassessment of safety functions. The RO should determine reactivity is no longer being met due to no charging flow and direct the TBO to align 13 Chg. Pp to 14 bus. The TBO's attempts to realign the 13 Charging Pump will initially be unsuccessful. The CRS will enter EOP-8 for failure to meet Reactivity Control.

EOP-8 is entered and the selected Success Paths begun. Boration is restored via HPSI injection. While working to establish boration, 11 AFW Pp trips the CRS or CRO should direct the TBO to investigate and align 12 AFW Pp.

After AFW has been restored and boration established, the scenario can be terminated.

0203.doc 3

0203.doc 3

Scenario No: l 3 l Event No. I 1 Page 4 of 1I1 Event

Description:

PZR level Control channel 1 lOX fails Low.

Time Position Applicant's Actions or Behavior CUE Annunciator E PZR CH. XLVL alarms.

E PZR HTR CUTOUT All Charging pumps start.

RO Acknowledges alarm, identifies and reports LT-1 IOX has failed low.

Refers to the ARM SRO Acknowledges report and directs RO to:

Shift PZR level control to channel Y Shift PZR heater cutout to channel Y Resets Proportional Heaters RO Perform actions as directed by SRO SRO Refers to T.S. 3.3.10l SRO Contacts OWC/I&C to investigate failure of 1-LT-11OX.

Scenario No:

3 Event No. l2 Page 5 of 11 Event

Description:

12 Chg. Pp Shaft Failure Time Position Applicant's Actions or Behavior CUE:

Low amps on 12 Chg. Pp Low charging flow for running pump combination (Note it is unlikely this failure will be noticed here, it is expected that it will be picked up either on the rapid downpower or the fast boration for 2 stuck CEAs)

RO Identifies and reports 12 Chg. Pp appears to be degraded SRO Acknowledges report and directs RO to:

Ensure charging flow via 13 Chg. Pp Align 13 Chg. Pp to 14 Bus, (if necessary)

RO Perform actions as directed by SRO Directs TBO to shift 13 Chg. Pp to 14 Bus (in EOP-0)

Dispatches ABO to investigate 12 Chg. Pp SRO Contacts OWC/I&C to investigate failure of 12 Chg. Pp and assist in getting 13 Chg. Pp aligned to 14 Bus

Scenario No:

3 Event No.

3 Page 6 of 11 Event

Description:

1 Failure of FRV Controller (1121)

Time Position 1 Applicant's Actions or Behavior CUE:

SG level deviation alarm (computer alarm)

Big "F' on face of FRV Controller 1121 CRO Acknowledges alarm, checks SG levels, notes FRV control has shifted to the PDI Informs SRO SRO Acknowledges report Implements AOP-3G Directs CRO to:

  • Placethe 1121FRVControllerinMAINFAIL Adjust the PDI CONTR to maintain zero inches SG level Determines BYP OVERRIDE is not available CRO Performs actions as directed by the CRS.

SRO Directs OWC to investigate FIC-1121 and to contact the system engineer.

Scenario No:

3 EventNo.

4 Page 7 of 11 Event

Description:

Oil Leak on 11 SGFP (Rapid Downpower)

Time Position Applicant's Actions or Behavior CUE:

SGFP Conditioner Level Low Alarm on SGFP Status Panel CRO Acknowledges Alarm, informs SRO and Dispatches TBO to 11 SGFP to investigate Refers to ARM SRO Acknowledges report from CRO When TBO reports control oil leak on 11 SGFP, directs the crew to commence a rapid downpower to take the unit offnine per OP-3:

Directs RO to initiate equalizing boron and commence downpower Directs CRO reduce turbine load to maintain Tc on program Directs the CRO to maintain SG level due to failed FRV Controller May direct TBO to fill 11 SGFP oil reservoir RO Initiates PZR spray flow to equalize RCS Boron:

Energizes all PZR backup heater banks Adjusts PZR Pressure Controller setpoint to maintain 2250 psia Commences boration from the BASTs followed by shifting suction to the RWT:

Opens BA direct makeup valve Verifies two charging pumps running (may notice 12 Chg. Pp failure here (Event 2))

Notes 11 BA Pp trips on start, informs SRO and uses 12 BA Pp Runs 12 BA Pp for 30 seconds (BAST gravity feed may be used instead)

After 12 BA Pp is secured, shuts BA direct makeup valve Verifies open RWT outlet valve Verifies Shut VCT outlet Inserts CEAs, if necessary, and maintains ASI within the limits of the COLR Requests Peer checks for reactivity manipulations CRO Reduces turbine load to maintain Tc within 5F of program Monitors turbine parameters not to exceed 150 0 F/hr rate of change of 1St stage shell inner metal temperature (Point 6 on TR-4404) 750F lt stage shell metal temperature differential (Diff between Points 6 & 7 on TR-4404)

Unloading rate of 10% step change or 5°/0/min SRO Coordinates power reduction between RO and CRO SRO Contacts OWC for support for oil leak for 11 SGFP CRO Recognizes 11 SGFP has tripped, informs the SRO SRO Recognizes a total loss of feed has occurred:

Directs RO to trip the reactor and for RO and CRO to implement EOP-0, POST-TRIP IMMEDIATE ACTIONS

Scenario No: l 3 l Event No. l 5 Page 8 of 11 Event

Description:

11 SGFP Trip/Reactor Trip Time Position Applicant's Actions or Behavior CUE:

Manual Reactor Trip initiated RO Perform Post-Trip Immediate Actions:

Depresses ONE set of Manual RX TRIP buttons Checks reactor tripped Prompt drop in NI power Negative SURl Informs SRO Reactivity Safety Function is completel

.CR Checks reactor has tripped Ensures turbine has tripped:l Depresses Turbine TRIP buttonl Checks the Turbine MAIN STOP VALVES shutl Checks Turbine SPEED dropsl Verifies turbine generator output breakers open:l 11 GENBUS BKE, 0-CS-552-22l 11 GEN TIE BKR, 0-CS-552-23 Verifies 1 1 GEN and EXCITER FIELD BKRs 1-CS-41 and 1-CS-41E are openl Ensure both MSR 2nd STG STh SOURCE MOVs are shut:

l-MS-4025-MOV (l1MSR) 1-MS4026-MOV (12 MSR)

Informs SRO the Turbine is Tripped CR0 Checks 11 OR 14 4KV Vital Bus energized Checks 125 VDC and 120 VAC busses energized Verifies CCW flow to RCPs Informs SRO Vital Auxiliaries Safety Function is complete.

Scenario No: l 3 I Event No. l 5 Page 9 of 11 Event

Description:

11 SGFP Trip/Reactor Trip Time Position Applicant's Actions or Behavior RO Ensures PZR pressure stabilizes between 1850 psia and 2300 psia and is trending to 2250 psia Determines PZR level is stabilizing between 80 and 180 inches or trending to 160 inches Ensures RCS subcooling GREATER THAN 300F Informs SRO RCS Pressure and Inventory Safety Function can is complete CREW Notes loss of 11 4KV Bus SRO directs reverification of Safety Functions RO Notes boration is no longer in progress, informs the SRO Directs TBO to shift 13 Chg. Pp to 14 Bus Reports Reactivity cannot be met due to two stuck CEAs and no boration in progress CRO Reverifies and reports Turbine is Tripped CRO Reverifies Vital Auxiliaries Starts OCDG Verifies Switchgear Ventilation in service per OI-22H Establishes CCW flow to RCPs Reports Vital Auxiliaries are complete RO Reverifies RCS Pressure and Inventory and reports is complete (may report not met due to lowering PZR level with no Chg. Pps running)

CRO Verifies Turbine Bypass Valves or ADVs operating to maintain:

SG pressures between 850 and 920 psia Tcold between 5250 and 5350F Directs ABO to operate ADVs locally to maintain RCS temperature Checks at least one SG available for controlled heat removal SG level between -170 and +30 inches Initiates Aux Feedwater to maintain S/G level Tc >5250 F Checks at least one RCP operating in a loop with a SG available for heat removal Checks loop delta T is <100F Informs SRO Core and RCS Heat Removal Safety Function is complete

Scenario No:

3 EventNo. lo 5 Page 10 of 11 Event

Description:

11 SGFP Trip/Reactor Trip Time Position Applicant's Actions or Behavior SRO May refer to AOP-7I Directs OWC/TIBO to tie 1Y09 and MYlO with OlO supplying CREW Checks Containment pressure is <0.7 psig Checks Containment temperature is <1200F.

Checks containment radiation monitor alarms CLEAR with NO unexplained trends Checks RMS alarms CLEAR with NO unexplained trends:

1-RIC-5415 U-1 wide range noble gas 1-RI-1752 Condenser Offgas 1-RI-4014 Unit 1 SG Blowdown 1-RI-5415 Unit 1 Main Vent Gaseous Informs SRO CNNT Environment and Rad Levels External to CNINT are complete SRO Conducts EOP-0 mid-brief and directs operators to reverify Safety Function Crew Reverifies Safety Functions SRO Determines Recovery Procedure per Diagnostic Flowchart:

All Safety Functions met - NO Event Diagnosis - Reactivity NOT MET v

Directs transition to EOP-8

Scenario No:

3 Event No.

6 Page 11 of 11 Event

Description:

EOP-8, Functional Recovery Procedure/Loss of Feed Time Position Applicant's Actions or Behavior SRO Briefs crew prior to EOP-8 implementation l

Directs actions per EOP-8 RO Performs RCP Trip strategy (determines RCPs not required to be tripped at this time)

SRO Contacts Chemistry for SG samples and to place the Hydrogen analyzers in service SRO Directs operators to select success paths for all safety functions.

Verifies selected success paths [RC-3(or 1), VA-I, PIC4, HR-1, CE-1, RLEC-1]

Determines sequence of success path performance [PIC, RC, VA, HR, CE, RLEC] (all met except PIC-4)

Directs operators to implement success paths (PIC and RC) lRO Commences RC-3 Verifies power <104%

Verifies SUR is negative CRO Commences PIC-4

  • Coordinates with RO to Establish RCS Pressure and Inventory Control using SIS 11~'

sk Continues to monitor RCS temperature and reactor power Informs SRO boration has been established SRO With Reactivity Control established, directs RO to Commence next Success Path (VA-1) or RO to take over PIC from CRO and assign VA-1, HR-I to CRO

  • Informs SRO 1 AFW Pp has tripped and all feed has been lost Wa b te rM When boration is established and secondary heat sink restored, the scenario may be terminated

SCENARIO #3 SETUP OVERVIEW/OBJECTIVES To evaluate the applicant's ability to conduct a unit power reduction, to implement the ARMs, OIs, AOPs, as appropriate, for malfunctioning systems and/or controls including a failure of PRZR level control channel (11 OX) which causes a broken shaft on 12 Charging Pp, a failed FRV Controller (1121) and a SGFP oil leak causing a rapid power reduction. A loss of 11 BA Pp occurs at the start of the downpower. The crew will be forced to trip the unit when the running SGFP trips. Two stuck CEAs require boration to meet reactivity but a loss of 11 4KV Bus will force the crew to EOP-8 for reactivity not being met. In EOP-8, boration will be restored via BPSI injection and 11 AFW Pp will trip resulting in a loss of feed. The crew can restore AFW by aligning 12 AFW Pp.

INSTRUCTOR SCENARIO INFORMATION

1.

Reset to IC-17.

Draft Spin #0202

2.

Perform switch check.

Spin # Used

3.

Place simulator in CONTINUE, advance charts and clear alarm display.

4.

Place simulator in FREEZE.

5.

Enter Malfunctions

a.

12 SGFP Trip FW004_02 at time zero

b.

2 Stuck CEAs (Untrippable)

CEDSO10_28 and _42 at time zero

c.

PZR Level Controller (1 OX) Fails Low RCS026-01 (Low) onF1

d.

12 Chg. PP Shaft Breaks CVCS003_02 on F2

e.

12 SG FRV Controller Fails Low FWO18_02 (Low) on F3 f

I IBA Pp Trips CVCS014_01 onF4

g.

I1SGFPTrips FW004_01 onF5

h.

Loss of 11 4KV Bus 4KVOO1_01 F6

i.

Trip of 11 AFW Pp AFWOO1_01 onF7

SCENARIO #3 SETUP

6.

Enter Panel Overrides

a.

IC13 - INSTR AIR COMPR(S) Annunciator (K-25) to ON.

b.

lC09 - Annunciators (2) for 1 1 Chg. Pp tagout-OFF.

7.

Enter Remote Functions / Administrative

a.

Danger tag I 1 Chg. Pp

b.

Danger tag 12 SGFP Pp.

c.

Place off-normal tags on the CCW Head Tank due to Makeup CV

d.

Remote Functions to rackout 1 1 Chg. Pp.

8.

Set simulator time to real time, then place simulator in CONTINUE.

9.Give crew briefing.

a.

Present plant conditions:

67% power - MOCI10,200 MWD/ITU. Unit 2 is in Mode 5. RCS Boron - 980 PPM.

b.

Power history:

67% for previous 4 days.

c.

Equipment out of service:

1 1 Chg. Pp out of service for packing replacement.

Expected to be returned to service in 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />. All Chg. Pps have been repacked, currently running in packing in 13.

12 SGFP out of service to repair steam leak on LP poppets. It is disassembled, expected to be returned to service tomorrow.

d.

Abnormal conditions:

11 CCW Head Tank Makeup CV is isolated due to leakby.

Alarm K-25 (INSTR AIR COMPR(S) is hanging, air compressors check out ok, alarm card swapped out but still in alarm. I&C is working up a troubleshooting plan.

e.

Surveillances due:

lB DG STP-0-8 due today. SM will bring to CR when ready.

f.

Instructions for shift:

Maintain current power level. Perform 1B DG STP-0-8 when directed by SM.

10.

Allow crew 3-5 minutes to acclimate themselves with their positions.

SCENARIO #3 SETUP

11.

Instructions for the Booth Operator.

a.

Activate malfunction F1 when cued by the lead examiner then immediately activate F2.

b.

Activate the next malfunction (F3) when cued by the lead examiner.

c.

When cued by the lead examiner, insert SGFP Status Panel "Conditioner Level Low" alarm and immediately after Panel Override Annunciator C-69 ON (SGFP Status Panel).

d.

As the rapid downpower is commenced, when the RO starts 11 BA Pp, immediately activate F4.

e.

After power has been reduced at least 5%, and with the lead examiner's concurrence activate F5.

f After the unit is tripped, remove Panel override for annunciator C-69.

g.

After the RO reports RCS Pressure and Inventory status, activate F6.

h.

In EOP-8, while the RO is working to establish boration, activate F7.

SCENARIO #3 SETUP RESPONSES TO CREW REQUEST If a request and response is not listed, delay response until reviewed with the examiner. Responses to routine requests, which have no effect the scenario, do not require examiner clearance.

REQUEST

RESPONSE

1.

OWC/E&C investigate failure of the PRZR Level Controller, 1-LT-1 1OX.

2.

OWC/E&C investigate failure of the 12 SG FRV Controller, 1121.

3.

TBO investigate SGFP Conditioner Level Low alarm.

4.

ABO investigate trip of 11 BA Pp.

5.

ABO investigate 12 Chg. Pp low flow.

6.

TBO/OWC/Electricians shift 13 CHG. Pp to 14 Bus.

7.

TBO investigate trip of 11 AFW Pp and align 12 AFW Pp for service.

Acknowledge request.

Acknowledge request.

Acknowledge request. After Two minutes, report a large control oil leak on 11 SGFP and recommend the SGFP be removed from service as soon as possible.

Acknowledge request. After 3 minutes, report 11 BA Pp tripped on overcurrent.

Acknowledge report. After three minutes, report 12 Chg. Pp has a broken shaft.

Acknowledge report. After 2 minutes report as TBO unable to get it to shift, seems to be hung up.

As additional assistance is rendered continue to give report of unable to get it shifted to 14 Bus.

Acknowledge request. After three minutes, align 12 AFW Pp for operation.

SCENARIO #3 SETUP SHIFT TURNOVER I.

Present Plant Conditions 67%

II.

Burnup:

10200 MWD/MTU (MOC)

III.

Power History 67% for previous 4 days.

IV.

Equipment out of Service:

11 Chg. Pp out of service for packing replacement. Expected to be returned to service in 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />. All Chg. Pps have been repacked, currently running in packing in 13.

12 SGFP out of service to repair steam leak on LP poppets. It is disassembled, expected to be returned to service tomorrow.

V.

Abnormal Conditions:

11 CCW Head Tank Makeup CV is isolated due to leakby.

Alarm K-25 (INSTR AIR COMPR(S) is hanging, air compressors check out ok, alarm card swapped out but still in alarm. I&C is working up a troubleshooting plan.

VI.

Surveillances Due:

VII.

Instructions for Shift 1B DG STP-0-8 due today. SM will bring to CR when ready.

Maintain current power level. Perform 1B DG STP-0-8 when directed by SM.

VIII. U2 Status and Major Equipment OOS:

Mode 5 - no CW Pps and 23AFW Pp is OOS.

C;_

l_

v Simuwauou racuity ualvert uiqns Examiners:

Scenario No.: 4 (Spare)

Operators:

Op Test No.:

1 SRO RO CRO Objectives:

To evaluate the applicant's ability to conduct a unit power increase, to implement the ARMs, Ols, AOPs, as appropriate, for malfunctioning systems and/or controls including raising power, a failure of the SRW Controller for the Main Generator H12 Cooler, a failure of the letdown backpressure regulator and a dropped CEA. When the CEA drops, the crew will implement AOP-lB. As the dropped CEA is being recovered a loss of 14 4KV Bus occurs. The crew will shift charging suction back to the VCT, stabilize the unit and implement AOP-7I. Next, a loss of offsite power occurs and the Main Turbine does not Trip. The crew should determine a manual reactor trip is required, trip the unit and implement EOP-0. The LA DG does not start and the OC DG Tie Bus is faulted resulting in a Station Blackout. The crew will implement EOP-7. As actions for EOP-7 are being performed, 11 AFW Pp will trip. The crew will be able to restore AFW using 12 AFW Pump allowing them to remain in the optimal procedure.

Initial Conditions:

The plant is at 75% Power, MOC (IC-18) 13 CCW Pp is OOS 12ChargingPp isOOS INSTR AIR COMPR(S) alarm (K-25) hanging.

Turnover:

Present plant conditions: 75% power, MOC; Unit 2 is in MODE 5 - no CW Pps and 23 AFW Pp unavailable.

Power history: 100% power for previous 190 days. Then reduced to z68% 3 days ago for 12 SGFP repairs.

Equipment out of service:

1) 13 CCW Pp has a broken shaft, expected repair tomorrow-noon.
2) Alarm K-25 INSTR AIR COMPR(S) is hanging. No problems with the compressors, I & C is investigating, alarm card has been swapped out.
3) 12 Charging Pp is OOS due to severe packing leakage. The packing is being replaced. Expected to be ready for PMT in about 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.

Surveillances due: None.

Instructions for shift:

1) Unit 1 had been at z68% power the previous 3 days to repair a steam leak on 12 SGFP. Both SGFPs are operating in parallel. Continue raising power to 100% per OP-3.
2) Perform PMTon 12 Charging Pump when returned to service.

Z Ut4.doe-1

Event Malf.

Event Event No.

No.

Type*

Description Preload DGOC004 OC DG tie bus faulted.

DG002_02 1A DG start failure.

CCW002_03 13 CCW Pp OOS TGO02 Turbine fails to trip.

Remote Func 12 Chg Pp OOS PNL OVR INSTR AIR COMPR(S) alarm hanging.

(K-25) l N/A R

RO After the crew takes the watch, the CRS should brief the crew on the power N

CRO increase to 100% per OP-3. After the brief the RO and CRO should coordinate to raise power while maintaining plant parameters within acceptable limits and Tc on program.

2 TGO30_01 I

CRO After power has been raised at least 5%, the SRW controller for the Main (closed)

Generator H12 cooler fails the valve shut. When the high temperature alarm is received, the CRO should acknowledge the alarm, inform the CRS and refer to the ARM. The CRO should determine TIC-1608 has failed low causing the CV to go shut, take manual control and restore H2 temperature. The OWC should be contacted for assistance.

3 CVCS005 I

RO Next, Letdown backpressure transmitter PT-201 fails low. The RO acknowledges the alarm, informs the CRS and refers to the ARM. The CRS should direct the RO to take manual control and restore letdown flow. The OWC should be contacted for support.

4 CEDS012_34 C

RO After the PT-201 failure CEA 34 drops. The RO should acknowledge the alarms, inform the CRS and refer to the ARM. The CRS should implement AOP-1B and address T.S. 3.1.4. Theprimaiywillbe stabilized and realignment time determined. After notifying maintenance and correcting the cause, realignment will be commenced.

5 4KV001_04 C

CRO As the CEA is being withdrawn, 14 4KV Bus is lost. The crew should stop CEA withdrawl, diagnose the bus loss, shift Charging Pump suction back to the VCT and stabilize the unit. The CRS should implement AOP-7I. The CRO will perform APO-7I actions as directed by the CRS. The OWC should be contacted for support.

6 SWYD002 M

ALL About 5 minutes after the bus loss, a loss of offsite power occurs. IA DG does not start and 14 4KV bus is locked out. The OC Diesel will not energize the OC Tie Bus due to a fault. The Main Turbine will not trip automatically. The crew should recognize a reactor trip is required and trip the unit manually. The crew will implement EOP-0 and diagnose a station blackout exists.

7 AFWO01_01 C

ALL In EOP-7, 11 AFW Pp will trip but they can restore AFW using 12 AFW Pump.

1A DG will become available and the 11 4KV Bus energized. After the bus is energized the scenario can be terminated.

  • (N)ormal, (R)eactivity (L)nstrument, (C)omponent, M)ajor Transient VLI.oc 7--

SCENARIO 4 OVERVIEW The candidates will take the shift at -75% power with instructions to raise power to 100% per OP-3.

After the crew takes the watch, the CRS should brief the crew on the power increase to 100% per OP-3. After the brief the RO and CRO should coordinate to raise power while maintaining plant parameters within acceptable limits and Tc on program.

After power has been raised at least 5%, the SRW controller for the Main Generator H2 cooler fails the SRW valve closed. When the generator H2 high temperature alarm is received, the CRO should acknowledge the alarm, inform the CRS and refer to the ARM. The CRO should determine TIC-1608 has failed low causing the CV to go shut, take manual control and restore H2 temperature. The OWC should be contacted for assistance.

Next, Letdown backpressure transmitter PT-20 1 fails low. The RO acknowledges the alarm, informs the CRS and refers to the ARM. The CRS should direct the RO to take manual control and restore letdown flow. The OWC should be contacted for support.

After the PT-201 failure CEA 34 drops. The RO should acknowledge the alarms, inform the CRS and refer to the ARM. The CRS directs the CRO to reduce turbine load as necessary to maintain Tc on program, implement AOP-lB and address T.S. 3.1.4. The primary will be stabilized and realignment time determined. After notifying maintenance and correcting the cause, realignment will be commenced.

As the CEA is being withdrawn 14 4KV Bus is lost. The crew should stop CEA withdrawl, diagnose the bus loss, shift Charging Pump suction back to the VCT and stabilize the unit. The CRS should implement AOP-7I. The CRO will perform AOP-7I actions as directed by the CRS. The OWC should be contacted for support.

About 5 minutes after the bus loss, a loss of offsite power occurs. 1A DG does not start and 14 4KV Bus is locked out. The OC Diesel will not energize the OC Tie Bus due to a fault. The Main Turbine will not trip automatically.

The crew should recognize a reactor trip is required and trip the unit manually. The crew will implement EOP-0 and diagnose a station blackout exists.

In EOP-7 11 AFW Pp will trip but they can restore AFW using 12 AFW Pump. 1A DG will become available and the 11 4KV Bus energized. After the bus is energized the scenario can be terminated.

0204.doc 3

Scenario No:

4 Event No. I1 Page 4 of 12 Event

Description:

Power increase to 100%

Time Position Applicant's Actions or Behavior CUE Turnover directs the crew to raise power to 100%

SRO Performs brief of power escalation per OP-3 Notifies the System Operator power is being raised to 100%

Directs crew to begin a power escalation per OP-3 Verifies boration flow paths for going >80% power RO Withdraws CEAs Commences dilution Monitors reactor power, RCS temperatures during power increase Requests Peer checks for reactivity manipulations CRO Raises turbine load to maintain Tc within 20F of program Monitors feedstation to verify SfG levels are being maintained approximately 0 inches SRO Coordinates power escalation between RO and CRO l

Scenario No:

4 Event No. l 2 Page L of 12 Event

Description:

SRW Controller to Main Generator H2 Cooler Fails shut l Time [ Position Applicant's Actions or Behavior CUE:

Annunciator alarms 1 C02 - B21 - GEN MON STATUS PANEL CRO Acknowledges alarm, identifies and reports alarm is due to high generator H2 temperature l

Refers to the ARM Determines 1-TIC-1608 has failed SRO Acknowledges report and directs CRO to:

Shift 1-TIC-1608 to manual Restore H2 temperature Dispatches TBO to check out the TCV locally CRO Perform actions as directed by SRO SRO Contacts OWC/I&C to investigate failure of 1-TIC-1608

Scenario No:

4 Event No. l 3 Page.6 of 12 Event

Description:

Letdown Backpressure Transmitter, PT-201, Fails Low Time lPosition [

Applicant's Actions or Behavior CUE Annunciator F L/D PRESS F RAD MON FLOW LO RO Acknowledges alarm, notes lowering letdown flow, informs CRS Refers to the ARM Determines backpressure regulator, PT-201 has failed low (may think letdown relief has lifted and with SRO concurrence isolate letdown instead)

SRO Acknowledges report and:

Directs RO to take manual control of PT-20 1 Reestablish letdown flow Check for indication of L/D RV lift RO Takes PT-201 to manual Reestablishes letdown flow Verifies LID reliefs have reseated, if lifted SRO Directs OWC to investigate the failure of PT-201

Scenario No:

4 Event No. l 4 Page 7 of 12 Event

Description:

Dropped CEA Time Position Applicant's Actions or Behavior CUE:

Annunciator alarms lC05 - D-3 1 SECONDARY CEA POSITION DEVIATION +1-4" D-32 CEA MOTION INHIBIT Dropping Rx power, RCS temp. and press.

RO Acknowledges alarms, identifies CEA #34 has dropped and informs SRO Refers to the ARM SRO Acknowledges report Directs CRO to reduce turbine load to restore Tc to program Implements AOP-lB CRO Coordinates with RO and reduces turbine load to restore Tc to program SRO Determines CEA realignment time Contacts OWC to obtain support Directs RO to attempt CEA realignment (FrT is 1.56, realignment time =42 minutes)

Directs RO and CRO to NOT allow reactor power to rise above the power the unit was stabilized at while the CEA is being aligned RO Attempts CEA realignment using 5.25 inch pull and 15 second wait method Monitors reactor power, SUR, temp. etc.

Borates to maintain power at less than stabilized value SRO Refers to T.S. 3.1.4

Scenario No: l 4 Event No.

5 Page 8 of 12 Event

Description:

Loss of 14 4KV Bus Time Position Applicant's Actions or Behavior CUE:

Annunciator alarm - Numerous Loss of CEA position indication Loss of various control board indications 1-CVC-504-MOV RWT CHG PP SUCT valve open light lit 1-CVC-50 1-MOV VCT OUT valve closed light lit CREW Determines a loss of power has occurred and a reactor trip is not required Directs the RO to monitor the primary Diagnoses the power loss to be loss of 14 4KV Bus and that the bus is locked out due to a fault SRO Directs the RO to place all Charging Pps in Pull-To-Lock and shift Charging Pp suction back to the VCT Directs the CRO to reduce turbine load as necessary to maintain Tc on program Directs CRO to monitor Main Generator temperatures Implements AOP-71, LOSS OF 4KV. 480 VOLT OR 208/120 VOLT INSTRUMENT BUS POWER Reviews preliminary section and transitions to Section XXIII, 14 4KV Bus Directs RO to maintain PZR level within 15 inches of program not to exceed 225 inches Directs CRO to have plant operator tie lYlO to IY09 RO/CRO Perform actions directed by the SRO SRO Directs 13 Chg. Pp, 13 SRW Pp and 13 SW Pp be aligned to 11 4KV Bus (13 Chg. Pp is normally aligned to 11 bus)

Directs monitoring of CNMNT temperatures Directs lB DG be shutdown and starting air isolated SRO When power supplies have been realigned, directs starting of 13 SW and SRW Pps to restore SW and SRW flow to 11 headers Directs restoration of various plant loads Directs 1B DG be shutdown by locally tripping the fuel racks RO/CRO Perform actions directed by the SRO SRO After lYLO is reenergized:

Directs RO to restore charging and letdown per OI-2A, Chemical and Volume Control System Directs RO to return VCT Outlet and RWT Outlet valves to auto RO/CRO Perform actions directed by SRO SRO Reviews T.S. for loss of Bus (3.8.1 and 3.8.9). Note - this is not required prior to proceeding to the next event SRO Contact OWC or electricians to investigate Loss of 14 4KV Bus

Scenario No:

4 Event No. l 6 Page 9 of 12 Event

Description:

Loss of Offsite Power/EOP-0 Time Position Applicant's Actions or Behavior CUE:

Various annunciators associated with loss of offsite power/reactor trip.

SRO Directs Unit 1 Reactor Trip and directs operators to implement EOP-0.

RO Perform Post-Trip Immediate Actions:

Depresses ONE set of Manual RX TRIP buttons Checks reactor tripped Prompt drop in NI power Negative SUR Checks ALL CEAs fully inserted (not able to verify due to loss of power effects)

Verifies demin water makeup to RCS is secured 11 & 12 RCMU pumps secured VCT M/U valve 1-CVC-512-CV is shut If RCS MIU is in DIRECT LINEUP, RWT CHG PP SUCT valve 1-CVC-504-MOV is shut (1-CVC-501-MOV must be opened first)

Informs SRO Reactivity Safety Function is complete. (may report not met due to inability to assess due to loss of power)

CRO Checks reactor has tripped Ensures Turbine has tripped:

Notes the Main Turbine has failed to trip, Depresses Turbine TRIP button and informs the SRO Checks the Turbine MAIN STOP VALVES shut (may not be able to assess due to power loss).

Checks Turbine SPEED drops. (may not be able to assess due to power loss)

Verifies turbine generator output breakers open:

11 GENBUSBKR, O-CS-552-22 11 GEN TIE BKRO, -CS-552-23 Verifies 11 GEN and EXCITER FIELD BKRs 1-CS-41 and l-CS41E are open Ensures both MSR 2nd STG STM SOURCE MOVs are shut:

1-MS-4025-MOV (1lMSR) 1-MS-4026-MOV (12 MSR)

Informs SRO the Turbine is Tripped (may report unable to assess).

Scenario No:

4 EventNo.

6 Page 10 of 12 Event

Description:

Loss of Offsite Power/EOP-0 l

Time Position Applicant's Actions or Behavior CRO Notes 11 and 14 4KV Vital Buses deenergized Starts the 0C DG Verifies lA DG running, l

Notes IA DG is not running, l

Attempts to start the 1A DG l

Since 1A DG did not start, dispatches OSO to 1A DG l

Dispatches TBO to close OC DG 11 4KV Bus disconnect, 189-1106 Checks 125 VDC and 120 VAC busses energized l

Determines IY09 and LYLO are deenergized Informs SRO Vital Auxiliaries cannot be met due to no vital 4KV Buses and no 120 Volt instrument buses and the 1A DG did not start RO Ensures PZR pressure stabilizes between 1850 psia and 23.00 psia and is trending to 2250 psia Determines PZR level is not stabilizing between 80 and 180 inches or trending to 160 inches Ensures RCS subcooling GREATER THAN 301F Informs SRO RCS Pressure and Inventory Safety Function can NOT be met due to low PZR pressure and PZR level CRO Verifies Turbine Bypass Valves or ADVs operating to maintain: (only ADVs are available locally)

SG pressures between 850 and 920 psia Tcold between 5250 and 5350F Directs ABO to locally open ADVs several turns Checks at least one SG available for controlled heat removal l

SG level between -170 and +30 inches Initiates Aux Feedwater to maintain S/G level Informs SRO Core and RCS Heat Removal Safety Function cannot be met due to no RCPs SRO Directs PWSIPPO/OSO investigate start failure of LA DG and to attempt to return to service

Scenario No:

4 Event No.

6 Page 11 of 12 Event

Description:

Loss of Offsite Power/EOP-0 l

Time Position Applicant's Actions or Behavior CREW Checks Contaimnent pressure less than 0.7 psig Checks Containment temperature less than 1200F Checks containment radiation monitor alarms CLEAR with NO unexplained trends Checks RMS alarms CLEAR with NO unexplained trends:

1-RIC-5415 U-1 wide range noble gas 1-RI-1752 Condenser Offgas 1-RI-4014 Unit 1 SGBlowdown 1-RI-5415 Unit 1 Main Vent Gaseous Informs SRO CNNT environment cannot be met and Rad Levels External to CNNT can not be met due loss of power (unable to assess) -

SRO Conducts EOP-0 mid-brief and directs operators to reverify Safety Functions CRO When the TBO has reported closing disconnect 189-1106:

CRO attempts to close 07 4KV Bus Tie Bkr, 152-0701 Notes 152-0701 immediately trips open Informs SRO SRO Determines Recovery Procedure per Diagnostic Flowchart:

All Safety Functions met - NO Single Event Diagnosis - YES-EOP-7 Directs transition to EOP-7

Scenario No: l 4 Event No.

7 Page 12 of 12 Event

Description:

EOP-7, Station Blackout/Loss of AFW Pump Time Position Applicant's Actions or Behavior SRO Briefs crew prior to EOP-7 implementation Directs actions per EOP-7 SRO Contacts System Operator to determine status of offsite power Contacts OWC for support in DG restoration CRO Protects the condenser from overpressure and minimizes S/G inventory loss Shuts both MSIVs l

Isolates S/G B/D RO Minimizes RCS inventory loss l

Isolates letdown (already isolated) l Maintains RCP bleedoffflowpath l

Shuts RCS sample valve Verifies RX and PZR vent valves are shut

~RO Secures Main Feed System CRO Aligns electrical system for power restoration Alignsl3KVand4KVbreakers Places 4KV Bus LOCI Sequencer keyswitches to ON Shuts CC CNMNT supply valve RO Verifies turbine and SGFP emergency oil pumps running CREW Notes failure of 11 AFW Pp Informs SRO SRO Directs TBO to align 12 AFW May implement EOP-8 although this is not expected or required RO Monitors SG levels After 12 AFW Pp is aligned, verifies AFW flow to both SGs Restores CCW flow RO Verifies Natural Circulation Maintains RCS subcooling When AFW has been established and Power restored to 11 4KV Bus the scenario can be terminated.

SCENARIO #4 SETUP OVERVIEW/OBJECTIVES To evaluate the applicant's ability to conduct a unit power increase, to implement the ARMs, O1s, AOPs, as appropriate, for malfunctioning systems and/or controls including raising power, a failure of the SRW Controller for the Main Generator H2 Cooler, a failure of the letdown backpressure regulator and a dropped CEA. When the CEA drops, the crew will implement AOP-1B. As the dropped CEA is being recovered a loss of 14 4KV Bus occurs. The crew will shift charging suction back to the VCT, stabilize the unit and implement AOP-7I.

Next, a loss of offsite power occurs and the Main Turbine does not Trip. The crew should determine a manual reactor trip is required, trip the unit and implement EOP-0. The IA DG does not start and the OC DG Tie Bus is faulted resulting in a Station Blackout. The crew will implement EOP-7. As actions for EOP-7 are being performed, 11 AFW Pp will trip. The crew will be able to restore AFW using 12 AFW Pump allowing them to remain in the optimal procedure.

INSTRUCTOR SCENARIO INFORMATION

1.

Reset to IC-18.

Draft Spin #0202

2.

Perform switch check.

Spin # Used

3.

Place simulator in CONTINUE, advance charts and clear alarm display.

4.

Place simulator in FREEZE.

5.

Enter Malfunctions

a.

13 CCW Pp Trip CCW002_03 at time zero

b.

OC DG Tie Bus Fault DGOC004 at time zero

c.

IA DG Start Failure DG002_02 at time zero

d.

Main Turbine Fails to Trip Automatically TGO02 at time zero

e.

Main Generator Hydrogen cooler SRW Control Valve Fails Shut TGO30_01 (closed) onF1

f.

Letdown Backpressure Regulator Fails Low (PT-201)

CVCS005 on F2

g.

CEA 34 Drops CEDSO12_34 on F3

h.

Loss of 14 4KV Bus 4KV001 04 onF4

SCENARIO #4 SETUP Loss of Offsite SWYD002 on F5

j.

Trip of 11 AFW Pp AFWOO1_01 onF6

6.

Enter Panel Overrides

a.

1C13 - INSTR AIR COMPR(S) Annunciator (K-25) to ON.

b.

lC07 - Annunciators (2) for 12 Chg. Pp tagout-OFF.

c.

IC13 - Annunciators (2) for 13 CCW Pp tagout-OFF.

7.

Enter Remote Functions / Administrative

a.

Danger tag 12 Chg. Pp

b.

Danger tag 13 CCW Pp.

c.

Remote Functions to rackout 13 CCW Pp.

d.

Remote Functions to rackout 12 Chg. Pp.

8.

Set simulator time to real time, then place simulator in CONTINUE.

9.Give crew briefing.

a.

Present plant conditions:

75% power - MOC/10-.200 fWrD/NMTT T~n;t I jR

b.

Power history:

c.

Equipment out of service:

d.

Abnormal conditions:

e.

Surveillances due:

f.

Instructions for shift:

in Mode 5. RCS Boron - 954 PPM.

68% for previous 3 days due to 12 SGFP repairs, Raising power to 100% @ 30% per hour.

12 Chg. Pp out of service for packing replacement.

Expected to be ready for PMT in about 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.

13 CCW Pump out of service due to a broken shaft.

Estimated return to service is todorrow-noon.

Alarm K-25 (INSTR AIR COMPR(S) is hanging, air compressors check out ok, alarm card swapped out but still in alarm. I&C is working up a troubleshooting plan.

None.

Continue to raise power to 100% per OP-3.

Perform PMT on 12 Charging Pump when returned to service.

10.

11.

SCENARIO #4 SETUP Allow crew 3-5 minutes to acclimate themselves with their positions.

Instructions for the Booth Operator.

a.

After power has been raised at least 5%, and with the lead examiner's concurrence activate Fl.

b.

Activate the malfunctions F2-F4 when cued by the lead examiner.

c.

About 5 minutes after F4, with lead examiner's concurrence, activate F5.

d.

Several minutes after the crew enters EOP-7 activate F6.

SCENARIO #4 SETUP RESPONSES TO CREW REQUEST If a request and response is not listed, delay response until reviewed with the examiner. Responses to routine requests, which have no effect the scenario, do not require examiner clearance.

REQUEST

RESPONSE

1.

OWCJE&C investigate failure Main Generator H2 SRW Controller, TIC-1608.

2.

OWC/E&C investigate failure Letdown backpressure regulator, PT-201.

3.

Electricians investigate dropped CEA.

4.

OWC/Fuels Group informed of dropped CEA and request latest FrT and FxyT.

5.

OWC/electricians contacted for support for loss of 14 4KV Bus.

6.

OWC/PPO tie IY09 and lYlO, IY09 supplying.

7.

System Operator contacted regarding power availability.

8.

OSO/PWS investigate start failure of IA DG.

9.

OWC/electricians investigate failure of OC Tie Bus Bkr 152-0701 failure to close.

10.

OSO/PWS unisolate 1A DG lube oil pressure switch and start the 1A DG.

11.

Take local control of the ADVs.

Acknowledge request.

Acknowledge request.

Acknowledge request. After eight minutes, report a blown holding coil fiuse. Fuse can be replaced in two minutes if requested.

Acknowledge report. Report latest FrT is 1.56 and FxyT is 1.62 and are 3 days old.

Acknowledge request. After ten minutes, report 14 4KV Bus lost due to ground fault and will require further investigation Acknowledge request. After 3 minutes tie lY10 to IY09 and report.

Acknowledge request. Report a major disturbance on the grid, no estimate of time for power restoration.

Acknowledge request. When the crew enters EOP-7, report 1A DG shut down on low lube oil pressure. No oil leaks present, think pressure switch may be faulty. Several minutes later report the pressure switch is isolated.

Acknowledge request. After 5 minutes report the breaker is tripped on overcurrent.

After two minutes unisolate the pressure switch and report the engine is running normally.

Operate the ADVs as directed by the Control Room.

12.

Locally shut MEW isolation FW-128 and 131.

After eight minutes report they are shut.

SCENARIO #4 SETUP

13.

Align N2 to AFW control valves and control Report as complete 2-3 minutes after task is FW discharge pressure locally.

requested.

14.

Cross tie MCC-104 to MCC-1 14.

After 3 minutes tie the MCCs.

15.

Shut 1-CC-284 (CCW supply to Containment After 3 minutes shut the valve.

manual isolation).

16.

TBO investigate trip of 11 AFWPp and align Acknowledge request. After three minutes, align 12 AFW Pp for service.

12 AFW Pp for operation.

SCENARIO #4 SETUP SHIFT TURNOVER I.

Present Plant Conditions 75%

II.

Burnup:

10200 MWD/MTU (M4OC)

III.

Power History 68% for previous 3 days due to 12 SGFP repairs, Raising power to 100% @ 30% per hour.

IV.

Equipment out of Service:

12 Chg. Pp out of service for packing replacement. Expected to be ready for PMT in about 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.

13 CCW Pump out of service due to a broken shaft. Estimated return to service is tomorrow-noon.

V.

Abnormal Conditions:

VI.

Surveillances Due:

VII.

Instructions for Shift Alarm K-25 (INSTR AIR COMPR(S) is hanging, air compressors check out ok, alarm card swapped out but still in alarm. I&C is working up a troubleshooting plan.

1B DG STP-0-8 due today. SM will bring to CR when ready.

Continue power increase per OP-3.

Perform PMT on 12 Charging Pump when returned to service.

VII. -U2 Status and Major Equipment OOS:

Mode 5 - no CW Pps and 23AFW Pp is OOS.

~uuuauui raux~y~aivrt

..AUS

~

cnan

-No. 1 (-ae p~s~.

011~Uauon U1LracUUly S-alveru W-s Scenario.No.: I (Spare)

Op Test No.:

1 Examiners:

Operators:

SRO RO CRO To evaluate the applicant's ability to conduct a unit power increase, to implement the ARMs, Ols, AOPs, as Objectives:

appropriate, for malfunctioning systems and/or controls including failure of 11 CCW Pp, the PZR pressure control channel and selector switch, an RCP seal and the ADV controller. After the ADV controller fails the remaining seals fail on the affected RCP resulting in an RCS leak. After EOP-0 is entered, the RCS leak causes a SIAS actuation. SIAS 'A' fails to actuate requiring 11 or 12 HPSI Pump to be started manually to establish HPSI flow. As EOP-0 progresses, a steam leak begins in CNMNT from 12 SG requiring EOP-8 be implemented. The ADV Controller will not operate from the Control Room, the crew will have to operate the ADVs locally.

Initial Conditions:

The plant is at 100% Power, EOC 12 Main CPU is failed for 12 SG DFWCS 11 CCW Head Tank Makeup CV is isolated due to leakby.

13 HPSI Pp is OOS.

13 CCW Pp is OOS INSTR AIR COMPR(S) alarm (K-25) hanging.

Turnover:

Present plant conditions: 100% power, MOC; Unit 2 is in MODE 5 - no CW Pps and 23 AFW Pp unavailable.

Power history: 100% power for previous 68 days.

Equipment out of service:

1) 12 Main CPU is failed for 12 SG DFWCS. System engineer is investigating.
2) 13 HPSI Pp motor bearing failure during STP. It is disassembled, expected to be returned to service in 2 days. T.S. 3.5.2 Action Statement entered 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> ago.
3) 11 CCW Head Tank Makeup CV is isolated due to leakby.
4) 13 CCW Pp has a broken shaft, expected repair tomorrow-noon.
5)

Alann K-25 INSTR AIR COMPR(S) is hanging. No problems with the compressors, I & C is investigating, alarm card has been swapped out.

Surveillances due: STP-0-29 (CEA Movement Test) due by end of shift. SM will discuss with CRS shortly after turnover.

Instructions for shift:

1) Maintain 100% power.

0201.dococ

Event l Malf.

Event I

Event No.

l No.

Type*

Description Preload FWOO1_03 12 Main CPU on 12 SG DFWCS OOS.

ESFA002_01 SIAS 'A' fails to actuate automatically and manually.

ESFA001_01 SI 002 03 13 LHPSI Pp OOS.

CCW002_03 13 CCWPp OOS.

PNL OVD Pressurizer Press Controller Selector Switch in channel X.

PNL OVR INSTR AIR COMPR(S) alarm hanging.

1 CCW0201 C

CRO About 3 minutes after the crew takes the watch, 11 CCW Pp trips. The CRO will acknowledge the alarms, inform the CRS and refer to the ARM. The crew will check for common mode failure and the CRS will direct the CRO to start 12 CCW Pp. The CRS should refer to AOP-7C and T.S. 3.7.5. The CRS contacts the OWC for assistance.

2 RCS023 01 I

RO PRZR Press Channel 10OX fails high. The RO should acknowledge the alarms, (high) inform the CRS and refer to the ARM. The RO should note the lowering RCS pressure and the open spray valves. Pressure control should be shifted to channel Y and the spray valves verified shut. The RO should note the spray valves did not shut. The CRS should direct the spray controller be taken to manual and the spray valves closed. The CRS should contact the OWC for assistance.

3 RCS011 01 C

RO Next, the lower seal (first stage) fails on lIA RCP. The RO should note the (0-100% over alarm, inform the CRS and refer to the ARM. The crew should determine the 3 min) lower seal on 11A RCP has failed. The OWC and system engineer should be contacted.

4 MS015 I

CRO Two minutes after the notifications have been made the ADV controller fails (high) high causing the ADVs to open. The CRO will inform the CRS. The CRS should direct the CRO to take manual control of the ADVs and shut them. The RO should maintain reactor power less than 100%. The CRS should refer to AOP-7K. The CRS should contact the OWC for assistance.

5 RCS012_01 R

RO After the CRS has referenced AOP-7K, the l 1A RCP middle seal fails. The (0-100% over N

CRO crew should implement ARM guidance and begin an expeditious shutdown.

2 min)

The CRS should refer to OP-3 for guidance on for the shutdown.

6 RCS013 01 M

All After power has been reduced at least 5%, the 11A upper seal begins to fail (over 2 min) followed shortly thereafter by the failure of the vapor seal. With all the seals RCS003 (50 failed RCS leakage begins via the seals. The CRS will trip the unit based on gpm over 5 high RCP seal temperature and EOP-0 implemented. When SIAS actuates, min) train A fails to automatically and manually initiate. To establish HPSI flow 11 RCS014_01 or 12 BPSI must be started manually.

(over 4 min) 7 MS010_02 M

All After the first pass through the safety functions is complete, a steam break in (0-25% over CNMNT begins. When the crew attempts to operate the ADVs, they will not 3 min) operate from the Control Room. To establish heat removal via 11 SG, the ADV will have to be operated locally. The CRS should recognize two events are Panel taking place and implement EOP-8. After the Success Paths have been selected Override and 12 SG isolated, the scenario can be terminated.

ADVs closed IN zLi kjJUaniIL, ijajia "i

n-

-0)UMial, tkryodulvliy k1)nsibU1LU1Lt kJOIV1UjlV1K,1LL, klVI~aJul llialalsiXt 0201.dococ

SCENARIO 1 OVERVIEW The candidates will take the shift at 100% power with instructions to maintain power.

After the crew has taken the shift, 11 CCW Pp trips. The CRO will acknowledge the alarms, inform the CRS and refer to the ARM. The crew will check for common mode failure and the CRS will direct the CRO to start 12 CCW Pp. The CRS should refer to AOP-7C and T.S. 3.7.5. The CRS contacts the OWC for assistance.

Several minutes later, PRZR Press Channel 10OX fails high. The RO should acknowledge the alarms, inform the CRS and refer to the ARM. The RO should note the lowering RCS pressure and the open spray valves. Pressure control should be shifted to channel Y and the spray valves verified shut. The RO should note the spray valves did not shut. The CRS should direct the spray controller be taken to manual and the spray valves closed. Once the spray valves are closed, the RO should stabilize RCS pressure. The CRS should contact the OWC for assistance.

About 3 minutes after the crew has regained RCS pressure control, the lower seal (first stage) fails on 1 LA RCP.

The RO should note the alarm, inform the CRS and refer to the ARM. The crew should determine the lower seal on 1 A RCP has failed and monitor RCP parameters. The OWC and system engineer should be contacted.

Two minutes after the notifications have been made the ADV controller fails high causing the ADVs to open. The CRO diagnoses the open ADVs and inform the CRS. The CRS should direct the CRO to take manual control of the ADVs and shut them. The RO should maintain reactor power less than 100%. The CRS should refer to AOP-7K. The CRS contacts the OWC for assistance.

After the CRS has referenced AOP-7K, the 1 LA RCP middle seal fails. The crew should implement ARM guidance and begin an expeditious shutdown in accordance with OP-3. The CRS should refer to OP-3 and direct the unit shutdown at a rate less than 30%/o/hour. The appropriate notifications should be made.

After power has been reduced at least 5%/o, the 1 A RCP upper seal begins to fail followed shortly thereafter by the failure of the vapor seal. With all the seals failed RCS leakage begins via the seals. The CRS will trip the unit based on high RCP Controlled Bleed Off temperature and EOP-0 implemented. When SIAS actuates, train 'A' fails to initiate automatically and manually. To establish HPSI flow 11 or 12 HPSI must be started manually.

After the first pass through the safety functions is complete, a steam break in CNNT begins. When the crew attempts to operate the ADVs, they will not operate from the Control Room. To establish heat removal via 11 SG, the ADV will have to be operated locally. The CRS should recognize two events are taking place and implement EOP-8. After the Success Paths have been selected and 12 SG isolated, the scenario can be terminated.

0201.dococ

Scenario No:

1 Event No.

1 Page 4. of 13 Event

Description:

11 CCW Pp Trips.

Time Position Applicant's Actions or Behavior CUE After the crew takes the watch, the following alarms occur:

Annunciator Alarm - 1C13 - K CC PP DISCH PRESS LO RCP Status Panel Alarms CCW pressure indicates zero CRO Acknowledges alarms, notes 11 CCW Pp has tripped, informs the SRO Refers to the ARM SRO Acknowledges report and directs CRO to check for common mode failure (head tank level, motor overload alarm)

Directs CRO to start 12 CCW Pp Implements AOP-7C, LOSS OF COMPONENT COOLING WATER RO Monitors RCP temperatures CRO Performs actions as directed by the SRO Verifies 12 CCW Pp is running normally with normal system parameters SRO Refers to T.S. 3.7.5. and exits AOP-7C Contacts OWC for assistance

Scenario No:

1 Event No.

2 Page 5 of 13 Event

Description:

PZR Press. Control Channel lOOX Fails High Time I Position ]

Applicant's Actions or Behavior CUE:

Annunciator alarm 1C06 - E-29 PZR CH 100 PRESS Both PZR Spray valves come full open Lowering RCS pressure RO Acknowledges alarm, identifies and reports PT-IOOX has failed high Refers to the ARM Notes both PZR spray valves are open SRO Acknowledges report and directs RO to:

Shift PZR pressure control to channel Y Verify the PZR spray valves go closed Restore RCS pressure to normal RO Perform actions as directed by SRO Notes the spray valves failed to go closed, RCS pressure is continuing to lower and informs the SRO Informs SRO in T.S. action for DNB if RCS pressure goes less than 2200 psia SRO Directs RO to take 1-HIC-100 to manual and close the spray valves RO Takes HIC 100 to manual and demand to minimum Verifies Spray Valves go closed and RCS pressure restoring to normal Informs SRO SRO Contacts OWC/I&C to investigate failure of 1-PT-IOOX and failure of spray valves to close

Scenario No:

1 Event No.

3 Page 6 of 13 Event

Description:

1st Stage (Lower) Seal Fails on IlA RCP.

Time Position Applicant's Actions or Behavior CUE:

Annunciator E IlA RCP SEAL - TEMP II - PRESS RO Acknowledges alarm, checks RCP parameters, reports suspected seal failure on 11A RCP Refers to the ARM SRO Identifies/acknowledges report of 1 IA RCP seal failure Determines along with RO I1LA RCP the lower seal has failed Directs RO to monitor parameters Contacts System Engineer Notes if a second seal fails on 1 1A RCP the unit will have to be shutdown RO Monitors RCP parameters (bleedoff flow, pressures, temperatures)

SRO Contacts OWC/GS and System Engineer regarding IlA RCP seal failure

Scenario No:

1 Event No.

4 Page L of 13 Event

Description:

Atmospheric Dump Valves Fail Open.

Time Position Applicant's Actions or Behavior CUE:

Audible steam dump to atmosphere occurring Open indication of both ADVs Changing RCS parameters, temperature and pressure lowering CRO Identify and report both ADVs have gone full open, recommends taking to manual and closing SRO Identifies/acknowledges report of open ADVs Directs CRO to take ADV controller to manual and shut ADVs Implements AOP-7K, OVER COOLING EVENT IN MODE ONE OR TWO Determines a reactor trip is not required Monitors reactor power:

Directs RO to insert CEAs or borates (if necessary)

Directs CRO to reduce/adjust turbine load as necessary to restore/maintain Tc on program (if necessary)

RO Monitors reactor power and borates or inserts CEAs if necessary to maintain power CRO Takes ADV controller to manual and verifies both ADVs go closed Adjusts turbine load as necessary to maintain Tc on program SRO Contacts OWC to investigate failure of ADV Controller