Revised Emergency Procedure EP-PS-245-2 Dose Assessment Supervisor for Susquehanna Units 1 & 2
ML021910440
Person / Time
Site: Susquehanna  Talen Energy icon.png
Issue date: 07/02/2002
From:
Susquehanna
To:
Document Control Desk, Office of Nuclear Security and Incident Response
References
EP-PS-245-2
Download: ML021910440 (48)


Text

Jul.

02, 2002 Page 1

of 1

MANUAL HARD COPY DISTRIBUTION DOCUMENT TRANSMITTAL 2002-3225 USER INFORMATION:

LAIELAUREL P

EMPL#:23244 CA#:

0386

'Adde.ss: NUCSA2 Phone#:

254-3658 TRANSMITTAL INFORMATION:

-TO*

LA1M'LAUREL B

07/02/2002 LOCATION:

DOCUMENT CONTROL DESK FROM:

NUCLEAR RECORDS DOCUMENT CONTROL CENTER

'NUCSA-2)

THE FOLLOWING CHANGES HAVE OCCURRED TO THE HARDCOPY OR ELECTRONIC MANUAL ASSIGNED TO YOU:

245 245 DOSE ASSESSMENT SUPERVISOR REMOVE MANUAL TABLE OF CONTENTS DATE:

05/23/2002 ADD MANUAL TABLE OF CONTENTS DATE:

07/01/2002 CATEGORY:

PROCEDURES TYPE:

EP ID:

EP-PS-245 REPLACE:

REV:3 REPLACE:

REV:3 UPDATES FOR HARD COPY MANUALS WILL BE DISTRIBUTED WITHIN 5

DAYS IN ACCORDANCE WITH DEPARTMENT PROCEDURES.

PLEASE MAKE ALL CHANGES AND ACKNOWLEDGE COMPLETE IN YOUR NIMS INBOX UPON RECEIPT OF HARD COPY.

FOR ELECTRONIC MANUAL USERS, ELECTRONICALLY REVIEW THE APPROPRIATE DOCUMENTS AND ACKNOWLEDGE COMPLETE IN YOUR NIMS INBOX.

TAB 2 EP-PS-245-2 EMERGENCY CLASSIFICATION CHECK 0 1.0 TIMING OF CLASSIFICATION o

1.1 UNUSUAL EVENT An UNUSUAL EVENT shall be declared within 15 minutes of having information necessary to make a declaration.

o 1.2 ALERT An ALERT shall be declared within 15 minutes of having information necessary to make a declaration.

O 1.3 SITE AREA EMERGENCY A SITE AREA EMERGENCY shall be declared within 15 minutes of having information necessary to make a declaration.

1.4 GENERAL EMERGENCY A GENERAL EMERGENCY shall be declared within 15 minutes of having information necessary to make a declaration.

EP-AD-000-200, Revision 16, Page 1 of 39

TAB 2 EP-PS-245-2 CLASSIFICATION OF EMERGENCY CONDITIONS USE OF EMERGENCY CLASSIFICATION MATRIX NOTE: CONFIRM THAT INDICATORS AND/OR ALARMS REFLECT ACTUAL CONDITIONS PRIOR TO TAKING ACTION BASED ON THE INDICATOR OR ALARM.

The matrix is worded in a manner that assumes parameter values indicated are the actual conditions present in the plant.

The matrix is designed to make it possible to precisely classify an abnormal occurrence into the proper emergency classification based on detailed Emergency Action Level (EAL) descriptions.

It is impossible to anticipate every abnormal occurrence.

Therefore, before classifying any abnormal occurrence based on the EALs in the matrix, one should verify that the general conditions prevalent in-plant and offsite meet the general class description of the emergency classification.

In addition, prior to classification, one should be aware of the ramifications in-plant and particularly offsite of that classification. Special consideration of offsite consequences should be made prior to declaring a GENERAL EMERGENCY.

EP-AD-000-200, Revision 16, Page 2 of 39

TAB 2 EP-PS-245-2 POLICY STATEMENT ON EMERGENCY DECLARATIONS Policy When an emergency action level (EAL) is exceeded but the plant quickly returns below the EAL, the emergency should be declared. If appropriate, the emergency can also be downgraded or terminated at essentially the same time and the Emergency Notification Form can say the emergency was declared and terminated (or downgraded) minutes later.

Example The main steam lines isolate on high radiation due to a large oil intrusion into the vessel. The isolation on high radiation is a trigger to declare an Alert. If it can quickly be determined that the cause was not damage to the fuel and we should not be in an Alert, then the Alert should be declared and terminated with the same notification report.

Basis Declaring the emergency will notify interested offsite personnel and will demonstrate that we recognize that we exceeded an EAL. Immediately terminating or downgrading will avoid activation of company and offsite facilities that are not required for this event.

EP-AD-000-200, Revision 16, Page 3 of 39

TAB 2 EP-PS-245-2 CLASS DESCRIPTIONS UNUSUAL EVENT ALERT SITE AREA EMERGENCY GENERAL EMERGENCY Events that are occurring or have occurred which indicate a potential degradation of the level of safety of the plant.

No releases of radioactive material requiring offsite response or monitoring are expected unless further degradation of safety systems occurs.

Events that are occurring or have occurred which involve an actual or potential substantial degradation of the level of safety of the plant. Any releases are expected to be limited to small fractions of the EPA Protective Action Guideline exposure levels.

Events that are occurring or have occurred which involve actual or imminent major failures of plant functions needed for protection of the public.

Any releases are not expected to exceed EPA Protective Action Guideline exposure levels except inside the emergency planning boundary.

Events that are occurring or have occurred which involve actual or imminent substantial core degradation or melting with potential for loss of containment integrity. Expectation is that releases will exceed EPA Protective Action Guideline exposure levels beyond the emergency planning boundary.

EP-AD-000-200, Revision 16, Page 4 of 39

TAB 2 EP-'PS-245-2 CATEGORY INDEX TO THE MATRIX FOR THE CLASSIFICATION OF EMERGENCY CONDITIONS TABLE OF CONTENTS CATEGORY 1

2 3

4 5

6 7

8 9

10 11 12 13 14 15 16 17 18 19 20 21 EVENT PAGE AIRCRAFT/TRAIN ACTIVITY.............................................................

6 CONTROL ROOM EVACUATION....................................................

7 FUEL CLADDING DEGRADATION..................................................

8 G EN E RA L......................................................................................

11 INJURED/CONTAMINATED PERSONNEL....................................

12 IN-PLANT HIGH RADIATION..........................................................

13 LOSS OF AC POWER......................................................................

14 LOSS OF CONTROL ROOM ALARMS AND ANNUNCIATORS....... 15 LOSS OF DC POWER.....................................................................

16 LOSS OF DECAY HEAT REMOVAL CAPABILITY......................... 17 LOSS OF REACTIVITY CONTROL..................................................

18 LOSS OF REACTOR VESSEL INVENTORY.................................. 20 NATURAL PHENOMENA...............................................................

22 ONSITE FIRE/EXPLOSION......................................

24 RADIOLOGICAL EFFLUENT...........................................................

26 SECURITY EVENT...........................................................................

30 SPENT FUEL RELATED INCIDENT...............................................

32 STEAM LINE BREAK......................................................................

34 TOXIC/FLAMMABLE GASES..........................................................

37 TECHNICAL SPECIFICATION SAFETY LIMIT...............................

38 DRY FUEL STORAGE.....................................................................

39 EP-AD-000-200, Revision 16, Page 5 of 39

TAB 2 EP-PS-245-2 I - AIRCRAFTITRAIN ACTIVITY UNUSUAL EVENT EAL# 1.1 Aircraft crash or train derailment onsite as indicated by:

Visual observation or notification received by control room operator.

ALERT EAL# 1.2 Aircraft or missile strikes a station structure as indicated by:

Direct observation or notification received by control room operator.

SITE AREA EMERGENCY EAL# 1.3 Severe damage to safe shutdown equipment from aircraft crash or missile impact when not in cold shutdown, determined by:

(A and B and C)

A. Direct observation or notification received by control room operator.

and B. Shift Supervisor evaluation.

and C. Reactor Coolant temperature greater than 200OF as indicated on Panel 1 C651 (2C651).

GENERAL EMERGENCY EAL# 1.4 None.

EP-AD-000-200, Revision 16, Page 6 of 39

TAB 2 EP-PS-245-2 2 - CONTROL ROOM EVACUATION UNUSUAL EVENT EAL# 2.1 None.

ALERT EAL# 2.2 Control Room evacuation as indicated by:

(A and B)

A. Initiation of control room evacuation procedures.

and B. Establishment of control of shutdown systems from local stations.

SITE AREA EMERGENCY EAL# 2.3 Delayed Control Room Evacuation as indicated by:

(A and B)

A. Initiation of control room evacuation procedures.

and B. Shutdown systems control at local stations not established within 15 minutes.

GENERAL EMERGENCY EAL# 2.4 None.

EP-AD-000-200, Revision 16, Page 7 of 39

TAB 2 EP-PS-245-2 3-FUEL CLADDING DEGRADATION UNUSUAL EVENT EAL# 3.1 Core degradation as indicated by:

(A or B)

A. Valid Off-gas Pre-treatment Monitor high radiation alarm annunciation on Panel 1C651 (2C651) or indication on Panel 1C600 (2C600).

or B. Reactor coolant activity, determined by sample analysis greater than or equal to 2 j.Ci/cc of 1-131 equivalent.

ALERT EAL# 3.2 Severe fuel cladding degradation as indicated by:

(A or B or C or D)

A. Valid Off-gas Pre-treatment monitor High-High radiation alarm annunciation on Panel 1C651 (2C651) or indication on Panel 1C600 (2C600).

or B. Valid Reactor coolant activity greater than 300 pCi/cc of equivalent 1-131, as determined by sample analysis.

or C. Valid Main Steam Line High radiation trip annunciation or indication on Panel 1C651 (2C651).

or D. Valid containment post accident monitor indication on Panel 1C601 (2C601) greater than 200 R/hr. (An 8R/hr correction factor must be added manually to the indication to offset a downscale error if primary containment temperature exceeds 225 degrees Fahrenheit.

Reference EC-079-0521.)

(CONTINUED ON NEXT PAGE)

EP-AD-000-200, Revision 16, Page 8 of 39

TAB 2 EP-PS-245-2 3 - FUEL CLADDING DEGRADATION (continued)

SITE AREA EMERGENCY EAL# 3.3 Severely degraded core as indicated by:

(A or B)

A. Reactor coolant activity greater than 1,000 RCi/cc of equivalent 1-131 as determined by sample analysis.

or B. Valid containment post accident monitor indication on Panel 1C601 (2C601) greater than 400 R/hr. (An 8 R/hr correction factor must be added manually to the indication to offset a downscale error if primary containment temperature exceeds 225 degrees Fahrenheit.

Reference EC-079-0521.)

(CONTINUED ON NEXT PAGE)

EP-AD-000-200, Revision 16, Page 9 of 39

TAB 2 EP-PS-245-2 3 - FUEL CLADDING DEGRADATION (continued)

GENERAL EMERGENCY EAL# 3.4.a Fuel cladding degradation. Loss of 2 out of 3 fission product barriers (fuel cladding and reactor coolant pressure boundary) with potential loss of the third barrier (primary containment) as indicated by:

(A or B)

A. (1 and 2)

1. Valid containment post accident monitor indication on Panel 1C601 (2C601) greater than 400 R/hr. (An 8 R/hr correction factor must be added manually to the indication to offset a downscale error if primary containment temperature exceeds 225 degrees Fahrenheit. Reference EC-079-0521.)

and

2. (a or b or c)
a. Containment pressure greater than 40.4 PSIG, indicated on Panel 1C601 (2C601).

or

b. A visual inspection of the containment indicates a potential for loss of containment (e.g. anchorage or penetration failure, a crack in containment concrete at tendon).

or

c. Other indications of potential or actual loss of primary containment.

or B. (1 and 2)

1. Reactor coolant activity greater than 1,000 ýtCi/cc of equivalent 1-131 as determined by-sample analysis.

and

2. Actual or potential failure of reactor coolant isolation valves to isolate a coolant leak outside containment as determined by valve position indication on Panel 1C601 (2C601) or visual inspection.

OR EAL# 3.4.b Core melt as indicated by:

(A and B)

A. Valid containment post accident monitor indication on Panel 1C601 (2C601) greater than 2000 R/hr. (An 8 R/hr correction factor must be added manually to the indication to offset a downscale error if primary containment temperature exceeds 225 degrees Fahrenheit. Reference EC-079-0521.)

and B. Containment high pressure indication or annunciation on Panel 1C601 (2C601).

EP-AD-000-200, Revision 16, Page 10 of 39

TAB 2 EP-PS-245-2 4-GENERAL UNUSUAL EVENT EAL# 4.1 Plant conditions exist that warrant increased awareness on the part of plant operating staff or state and/or local offsite authorities as indicated by:

Events that are occurring or have occurred which indicate a potential degradation of the level of safety of the plant. No releases of radioactive material requiring offsite response or monitoring are expected unless further degradation of safety systems occurs.

ALERT EAL# 4.2 Other plant conditions exist that warrant precautionary activation of PP&L, State, County, and local emergency centers as indicated by:

Events that are occurring or have occurred which involve an actual or potential substantial degradation of the level of safety of the plant. Any releases are expected to be limited to small fractions of the EPA Protective Action Guideline exposure levels.

SITE AREA EMERGENCY EAL# 4.3 Other plant conditions exist that warrant activation of emergency centers and monitoring teams or a precautionary notification to the public near the site as indicated by:

Events that are occurring or have occurred which involve actual or imminent major failures of plant functions needed for protection of the public. Any releases are not expected to exceed EPA Protective Action Guideline exposure levels except inside the emergency planning boundary.

GENERAL EMERGENCY EAL# 4.4 Other plant conditions exist, from whatever, source, that make release of large amounts, of radioactivity in a short time period available as indicated by:

Events that are occurring or have occurred which involve actual or imminent substantial core degradation or melting with potential for loss of containment integrity. Expectation is that releases will exceed EPA Protective Action Guideline exposure levels beyond the emergency planning boundary.

EP-AD-000-200, Revision 16, Page 11 of 39

TAB 2 EP-PS-245-2 5.- INJURED/CONTAMINATED PERSONNEL UNUSUAL EVENT EAL# 5.1 Transportation of externally contaminated injured individual from site to offsite medical facility as deemed appropriate by Shift Supervisor.

ALERT EAL# 5.2 None.

SITE AREA EMERGENCY EAL# 5.3 None.

GENERAL EMERGENCY EAL# 5.4 None.

EP-AD-000-200, Revision 16, Page 12 of 39

TAB 2 EP-PS-245-2 6 - IN-PLANT HIGH RADIATION UNUSUAL EVENT EAL# 6.1 Unanticipated or unplanned concentrations of airborne activity exist in normally accessible areas, which are not due to planned maintenance activities, as indicated by:

Concentrations exceed 500 times the DAC values of 10CFR20 Appendix B, Table I values for a single isotope, or for multiple isotopes where CA CB CC CN

Ž500 DACA DAC2 DACc DACN ALERT EAL# 6.2 Unexpected in-plant high radiation levels or airborne contamination which indicates a severe degradation in the control of radioactive material as indicated by:

Area Radiation Monitor reading 1000 times normal annunciation on Panel 1C601 (2C601) or indication on Panel 1C600 (2C600).

SITE AREA EMERGENCY EAL# 6.3 None.

GENERAL EMERGENCY EAL# 6.4 None.

EP-AD-000-200, Revision 16, Page 13 of 39

TAB 2 EP-PS-245-2 7 - LOSS OF AC POWER UNUSUAL EVENT EAL# 7.1 Loss of offsite power or loss of all onsite AC power supplies as indicated by:

(A or B)

A. Loss of power to Startup Transformer 10 and 20 annunciation or indication on Panel 0C653.

or B. Failure of all diesel generators to start or synchronize to the emergency buses by indication or annunciation on Panel 0C653.

ALERT EAL# 7.2 Loss of all offsite power and all onsite AC power supplies as indicated by:

(A and B)

A. Loss of power to Startup Transformer 10 and 20 annunciation or indication on Panel 0C653.

and B. Failure of all diesel generators to start or synchronize to the emergency buses by annunciation or indication on Panel 0C653.

SITE AREA EMERGENCY EAL# 7.3 Loss of all offsite power and loss of all onsite AC power supplies for greater than 15 minutes as indicated by:

(A and B and C)

A. Loss of offsite power.

and B. Failure of all diesel generators to startup or synchronize to the emergency buses by indication or annunciation on 0C653.

and C. The above conditions exist for greater than 15 minutes.

GENERAL EMERGENCY EAL# 7.4 None.

EP-AD-000-200, Revision 16, Page 14 of 39

TAB 2 EP-PS-245-2 8 - LOSS OF CONTROL ROOM ALARMS AND ANNUNCIATORS UNUSUAL EVENT EAL# 8.1 None.

ALERT EAL# 8.2 Loss of all control room annunciators as indicated by:

In the opinion of the Shift Supervisor, all Control Room annunciators and the Plant Process Computer are lost, or insufficient annunciators are available to safely operate the unit(s) without supplemental observation of plant systems.

SITE AREA EMERGENCY EAL# 8.3 All annunciators lost and plant transient initiated while annunciators are lost as indicated by:

(A and B)

A. In the opinion of the Shift Supervisor, all Control Room annunciators and the Plant Process Computer are lost, or insufficient annunciators are available to safely operate the unit(s) without supplemental observation of plant systems.

and B. (1 or2 or3 or4)

1. Low-Low reactor water level indication on Panel lC651-(2C651) followed by ECCS initiation on Panel 1C601 (2C601).

or

2. Reactor coolant temperature change greater than 100OF per hour indication on recorder TR-1 R006 on Panel 1 C007 (2C007) (Reactor Building elevation 683').

or

3. High reactor pressure indication on Panel 1C651 (2C651) and followed by scram indication on Panel 1C651 (2C651).

or

4. Any indication that transient has occurred or is in progress.

GENERAL EMERGENCY EAL# 8.4 None.

EP-AD-000-200, Revision 16, Page 15 of 39

TAB 2 EP-PS-245-2 9 - LOSS OF DC POWER UNUSUAL EVENT EAL# 9.1 None.

ALERT EAL# 9.2 Loss of onsite vital DC power as indicated by:

(A and B)

A. Less than 210 volts on the 250 VDC main distribution Panel buses, 1D652 (2D652) and 1D662 (2D662) as indicated by trouble alarms on Panel 1C651 (2C651).

and B. Less than 105 volts on the 125 VDC main distribution buses 1D612 (2D612), 1D622 (2D622), 1D632 (2D632), and 1D642 (2D642) as indicated by trouble alarms on Panel 1C651 (2C651).

NOTE: Buses are not tripped on undervoltage condition.

SITE AREA EMERGENCY EAL# 9.3 Loss of all vital onsite DC power sustained for greater than 15 minutes as indicated by:

(A and B-and C)

A. Less than 210 volts on the 250 VDC main distribution Panel buses, 1D652 (2D652) and 1 D662 (2D662) as indicated by trouble alarms on Panel 1C651 (2C651).

and B. Less than 105 volts on the 125 VDC main distribution buses 1D612 (2D612), 1D622 (2D622), 1D632 (2D632), and 1D642 (2D642) as indicated by trouble alarms on Panel 1C651 (2C651).

and C. The above condition exists for greater than 15 minutes.

NOTE: Buses are not tripped on undervoltage condition.

GENERAL EMERGENCY EAL# 9.4 None.

EP-AD-000-200, Revision 16, Page 16 of 39

TAB 2 EP-PS-245-2 10 - LOSS OF DECAY HEAT REMOVAL CAPABILITY UNUSUAL EVENT EAL# 10.1 None.

ALERT EAL# 10.2 Inability to remove decay heat while in plant condition 4, inability to maintain the plant in cold shutdown as indicated by:

Inability to maintain reactor coolant temperature less than 200OF with the reactor mode switch in shutdown; exception is when testing per Special Test Exception TS 3.10.1 which allows maximum temperature of 212 0F.

SITE AREA EMERGENCY EAL# 10.3 Inability to remove decay heat while the plant is shutdown as indicated by:

(A and B and C)

A. Reactor Mode switch in shutdown.

and B. Reactor Coolant System temperature greater than 200OF and rising.

and C. Suppression Pool temperature greater than 120OF and rising.

GENERAL EMERGENCY EAL# 10.4 Inability to remove decay heat while the plant is shutdown with possible release of large amounts of radioactivity as indicated by:

(A and B and C)

A. Reactor mode switch in shutdown.

and B. Reactor coolant system temperature greater than 200OF and rising.

and C. Suppression pool temperature greater than 290°F indicated on the computer output (MAT 12,13,14,15 or 16).

EP-AD-000-200, Revision 16, Page 17 of 39

TAB 2 EP-PS-245-2 11 - LOSS OF REACTIVITY CONTROL UNUSUAL EVENT EAL# 11.1 Inadvertent Criticality as indicated by:

Unexpected increasing neutron flux indication on Panel 1C651 (2C651).

ALERT EAL# 11.2 Failure of the Reactor Protection System or the Alternate Rod Insertion System to initiate and complete a scram that brings the reactor subcritical as indicated by:

(A or B) and (C and D and E)

A. Trip of at least one sub-channel in each trip system (RPS A and RPS B) as indicated by annunciators and trip status lights on Panel 1C651 (2C651).

or B. Trip of both trip systems (ARI A and ARI B) as indicated by annunciators on Panel 1C601 (2C601).

and C. Failure of control rods to insert, confirmed by the full core display 1C651 (2C651) or process computer indications.

and D. Failure to bring the reactor subcritical confirmed by neutron count monitoring indication on Panel 1C651 (2C651).

and E. Reactor power >5% as indicated on Panel 1C651 (2C651).

indication on Panel rate on the neutron (CONTINUED ON NEXT PAGE)

EP-AD-000-200, Revision 16, Page 18 of 39

TAB 2 EP-PS-245-2 11 - LOSS OF REACTIVITY CONTROL (continued)

SITE AREA EMERGENCY EAL# 11.3 Loss of functions needed to bring the reactor subcritical and loss of ability to bring the reactor to cold shutdown as indicated by:

(A and B and C and D)

A. Inability to insert sufficient control rods to bring the reactor subcritical as indicated by count rate on the neutron monitoring instrumentation on Panel 1C651 (2C651).

and B. (1 or2)

Failure of both loops of standby liquid control to inject into the vessel indicated by:

1. Low pump discharge pressure indication on Panel 1C601 (2C601).

or

2. Low flow indication on Panel 1C601 (2C601).

and C. Reactor coolant temperature greater than 2000 F, indicated on Panel 1C651 (2C651).

and D. Reactor power >5% indicated on Panel 1C651 (2C651).

GENERAL EMERGENCY EAL# 11.4 Loss of functions needed to bring the reactor subcritical and transient in progress that makes release of large amounts of radioactivity in a short period possible as indicated by:

(A or B) and (C and D)

A. Trip of at least one sub-channel in each trip system (RPS A and RPS B), indicated by annunciation or trip status lights on Panel 1C651 (2C651).

or B. Trip of both systems (ARI A and ARI B) as indicated by annunciators on Panel 1C601 (2C601).

and C. Loss of SLC system capability to inject, indicated by instrumentation on Panel 1C601 (2C601).

and D. Reactor power greater than 25% of rated, indicated on Panel 1C651 (2C651).

EP-AD-000-200, Revision 16, Page 19 of 39

TAB 2 EP-PS-245-2 12 - LOSS OF REACTOR VESSEL INVENTORY UNUSUAL EVENT EAL# 12.1 Valid initiation of an Emergency Core Cooling System (ECCS) System as indicated by:

(A or B)

A. Initiation of an ECCS System and low, low, low reactor water level (-129) annunciation or indication on Panel 1C651 (2C651).

or B. Initiation of an ECCS System and High Drywell Pressure annunciation or indication on Panel 1C601 (2C601).

ALERT EAL# 12.2 Reactor coolant system leak rate greater than 50 gpm as indicated by:

(A or B)

A. Drywell floor drain sump A or B Hi-Hi alarm on Panel 1C601 (2C601) and 2 or more drywell floor drain pumps continuously running as indicated on Panel 1C601 (2C601).

or B. Other estimates of Reactor coolant system leakage indicating greater than 50 gpm.

SITE AREA EMERGENCY EAL# 12.3 Known loss of coolant accident greater than make-up capacity as indicated by:

Water level below (and failure to return to) top of active fuel for greater than three minutes as indicated on fuel zone level indicator on Panel 1C601 (2C601).

(CONTINUED ON NEXT PAGE)

EP-AD-000-200, Revision 16, Page 20 of 39

TAB 2 EP-PS-245-2 12 - LOSS OF REACTOR VESSEL INVENTORY (continued)

GENERAL EMERGENCY EAL# 12.4.a Loss of coolant accident with possibility of imminent release of large amounts of radioactivity as indicated by:

Water level below (and failure to return to) top of active fuel for greater than 20 minutes as indicated on fuel zone level indicator on Panel 1C601 (2C601).

OR EAL# 12.4.b Loss of Reactor Vessel inventory. Loss of 2 out of 3 fission product barriers (fuel cladding & reactor coolant pressure boundary) with potential loss of the third barrier (primary containment), as indicated by:

(A or B)

A. (1 and 2 and 3)

1. High drywell pressure annunciation or indication on Panel 1C601 (2C601).

and

2. (aorborc)
a. Containment pressure exceeds 40.4 PSIG as indicated on Panel 1C601 (2C601).

or

b. A visual inspection of the containment indicates a potential or actual loss of containment (e.g. anchorage or penetration failure).

or

c. Containment isolation valve(s) fail to close as indicated by valve position

- indication on Panel 1C601 (2C601).

and

3. Reactor Vessel level drops below (and fails to return to) top of active fuel for greater than three minutes as indicated on fuel zone level indicator on Panel 1C601 (2C601).

or B. (1 and 2)

1. Failure of reactor pressure vessel isolation valves to isolate coolant break outside containment as indicated by valve position indication on Panel 1C601 (2C601) or visual inspection.

and

2. Reactor vessel level drops below (and fails to return to) top of active fuel for greater than three minutes as indicated on fuel zone level indicator on Panel 1C601 (2C601).

EP-AD-000-200, Revision 16, Page 21 of 39

TAB 2 EP-PS-245-2 13 - NATURAL PHENOMENA UNUSUAL EVENT EAL# 13.1 Natural phenomenon occurrence as indicated by:

(A or B or C)

A. Tornado impact on site.

or B. Hurricane impact on site.

or C. Earthquake detected by seismic instrumentation systems on Panel 0C696.

ALERT EAL# 13.2 Natural Phenomenon Occurrence as indicated by:

(A or B or C)

A. Tornado with reported wind velocities greater than 200 mph impacting on site.*

or B. Reported hurricane or sustained winds greater than 70 mph.*

or C. Earthquake at greater than operating basis earthquake (OBE) levels as indicated on Panel 0C696.

  • Telephone numbers for the National Weather Bureau are located in the Emergency Telephone Directory.

(CONTINUED ON NEXT PAGE)

EP-AD-000-200, Revision 16, Page 22 of 39

TAB 2 EP-PS-245-2 13-NATURAL PHENOMENA (continued)

SITE AREA EMERGENCY EAL# 13.3 Severe natural phenomenon occurrence, with plant not in cold shutdown, as indicated by:

(A and B)

A. Reactor Coolant Temperature greater than 200OF as indicated on Panel 1C651 (2C651).

and B. (1 or 2 or 3)

1. Reported hurricane or sustained winds greater than 80 mph.*

or

2. Earthquake with greater than Safe Shutdown Earthquake (SSE) levels as indicated on Panel 0C696.

or

3. Tornado with reported wind velocities greater than 220 mph impacting on site.*

GENERAL EMERGENCY EAL# 13.4 None.

Telephone numbers for the National Weather Bureau are located in the Emergency Telephone Directory.

EP-AD-000-200, Revision 16, Page 23 of 39

TAB 2 EP-PS-245-2 14 - ONSITE FIREIEXPLOSION UNUSUAL EVENT EAL# 14.1 Significant fire within the plant as indicated by:

(A and B)

A. Activation of fire brigade by Shift Supervisor.

and B. Duration of fire longer than 15 minutes after time of notification.

OR Explosion inside security protected area, with no significant damage to station facilities, as indicated by:

Visual observation or notification received by control room operator and Shift Supervisor evaluation.

ALERT EAL# 14.2 On-site Fire/Explosion as indicated by:

(A or B)

A. Fire lasting more than 15 minutes and fire is in the vicinity of equipment required for safe shutdown of the plant and the fire is damaging or is threatening to damage the equipment due to heat, smoke, flame, or other hazard.

or B. (1 and 2)

Explosion damage to facility affecting plant operation as determined by:

1. Direct observation or notification received by control room operator.

and

2. Shift Supervisor observation.

(CONTINUED ON NEXT PAGE)

EP-AD-000-200, Revision 16, Page 24 of 39

TAB 2 EP-PS-245-2 14-ONSITE FIRE/EXPLOSION (continued)

SITE AREA EMERGENCY EAL# 14.3 Damage to safe shutdown equipment due to fire or explosion has occurred when plant is not in cold shutdown, and damage is causing or threatens malfunction of equipment required for safe shutdown of the plant as determined by:

(A and B and C)

A. Direct observation or notification received by control room operator.

and B. Shift Supervisor evaluation.

and C. Reactor Coolant Temperature greater than 200°F as indicated on Panel 1C651 (2C651).

GENERAL EMERGENCY EAL# 14.4 None.

EP-AD-000-200, Revision 16, Page 25 of 39

TAB 2 EP-PS-245-2 15-RADIOLOGICAL EFFLUENT UNUSUAL EVENT EAL# 15.1.a Radiological gaseous effluents exceed 2 times the Technical Requirement Limits for 60 minutes or longer as indicated by:

(A or B)

A. Valid Building Vent Stack Monitoring System (SPING) indications on Panel 0C630 or 0C677.

1. Noble gases >1.70E+6 gCi/min., or
2. 1-131 >2.08E+2 gCi/min., or
3. Particulate >1.54E+3 pCi/min., or or B. Confirmed sample analyses for gaseous releases indicating total site release rates exceed:
1. Noble gases >1000 mrem/year whole body, or
2. Noble gases >6000 mrem/year skin, or
3. 1-131, 1-133, H-3, and particulates with half-lives >8 days >3000 mrem/year to any organ (inhalation pathways only).

OR EAL# 15.1.b Radiological liquid effluents exceed Technical Requirement Limits for instantaneous release as indicated by:

Report of radiological liquid effluent exceeding Technical Requirement Limits. This includes effluent sources such as Service Water or RHR Service Water Loops A or B.

(CONTINUED ON NEXT PAGE)

EP-AD-000-200, Revision 16, Page 26 of 39

TAB 2 EP-PS-245-2 15-RADIOLOGICAL EFFLUENT (continued)

ALERT EAL# 15.2.a Radiological gaseous effluents exceed 200 times the Technical Requirement Limits for 15 minutes or longer as indicated by:

(A or B)

A. Valid Building Vent Stack Monitoring System (SPING) indications on Panel 0C630 or 0C677.

1. Noble gases >1.70E+8 J4Ci/min., or
2. 1-131 >2.08E+4 g.Ci/min., or
3. Particulate >1.54E+5 pCi/min.

or B. Confirmed sample analyses for gaseous releases indicating total site release rates exceed:

1. Noble gases >1.OE+5 mrem/year whole body, or
2. Noble gases >6.OE+5 mrem/year skin, or
3. 1-131, 1-133, H-3, and particulates with half-lives >8 days >3.OE+5 mrem/year to any organ (inhalation pathways only).

OR EAL# 15.2.b Radiological liquid effluents exceed 10 times Technical Requirement Limits for instantaneous release as indicated by:

Report of radiological liquid effluent release exceeding 10 times Technical Requirement Limits. This includes effluent sources such as Service Water or RHR Service Water Loops Aor B.

(CONTINUED ON NEXT PAGE)

EP-AD-000-200, Revision 16, Page 27 of 39

TAB 2 EP-PS-245-2 15 - RADIOLOGICAL EFFLUENT (continued)

SITE AREA EMERGENCY EAL# 15.3 Radiological effluent corresponds to greater than 50 mrem W.B.(1) or 250 mrem thyroid(2) for a half-hour or 500 mrem W.B.(0) or 2500 mrem thyroid(2) for 2 minutes at the emergency plan boundary as indicated by:

OR Emergency plan boundary dose is projected to exceed 500 mrem W.B. (1) within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> as indicated by:

(A or B)

A. Dose projections based on:

(1 or2)

1. Building vent stack monitoring system indications on Panel 0C630 or 0C677.

or

2. Field monitoring data onsite or offsite.

or B. Dose projections based on:

(1 or2)

1. Building vent stack monitoring system indications on Panel 0C630 or 0C677.

or

2. Field monitoring data onsite or offsite (CONTINUED ON NEXT PAGE)

(1)

The sum of the Effective Dose Equivalent resulting from the exposure to external sources and the Committed Effective Dose Equivalent incurred from all significant inhalation pathways during the early phase.

(2)

Committed Dose Equivalent to the thyroid from radioiodine.

EP-AD-000-200, Revision 16, Page 28 of 39

TAB 2 EP-PS-245-2 15 - RADIOLOGICAL EFFLUENT (continued)

GENERAL EMERGENCY EAL# 15.4 Radiological effluent release corresponds to 1 rem whole body(1) or 5 rem(2) thyroid at the emergency plan boundary as indicated by:

OR Offsite doses are projected to exceed 1 rem whole body(1) or 5 rem thyroid(2) due to the event as indicated by:

(A or B)

A. Dose projections based on:

(1 or2 or3)

1. Building Vent Stack Monitoring System indication on Panel 0C630 or 0C677.

or

2. Field monitoring data onsite or offsite.

or

3. In-plant conditions.

or B. Dose projections based on:

(1 or2 or3)

1. Building Vent Stack Monitoring System indication on Panel 0C630 or 0C677.

or

2. Field monitoring data onsite or offsite.

or

3. In-plant conditions.

(1) The sum of the Effective Dose Equivalent resulting from the exposure to external sources and the Committed Effective Dose Equivalent incurred from all significant inhalation pathways during the early phase.

(2)

Committed Dose Equivalent to the thyroid from radioiodine.

EP-AD-000-200, Revision 16, Page 29 of 39

TAB 2 EP-PS-245-2 16 - SECURITY EVENT UNUSUAL EVENT EAL# 16.1 Security threat or attempted entry or attempted sabotage as indicated by:

(A or B or C)

A. A report from Security of a security threat, attempted entry, or attempted sabotage of the owner controlled area adjacent to the site.

or B. Any attempted act of sabotage which is deemed legitimate in the judgment of the SHIFT SUPERVISOR/EMERGENCY DIRECTOR, and affects plant operation.

or C. A site specific credible security threat notification.

ALERT EAL# 16.2 Ongoing Security Compromise as indicated by:

(A or B)

A. A report from Security that a security compromise is at the site but no penetration of protected areas has occurred.

or B. Any act of sabotage which results in an actual or potential substantial degradation of the level of safety of the plant as judged by the SHIFT SUPERVISOR/EMERGENCY DIRECTOR.

SITE AREA EMERGENCY EAL# 16.3 An ongoing adversary event threatens imminent loss of physical control of plant as indicated by:

(A or B)

A. Report from Security that the security of the plant vital area is threatened by unauthorized (forcible) entry into the protected area.

or B. Any act of sabotage which results in actual or likely major failures of plant functions needed for protection of the public as judged by the SHIFT SUPERVISOR/EMERGENCY DIRECTOR.

(CONTINUED ON NEXT PAGE)

EP-AD-000-200, Revision 16, Page 30 of 39

TAB 2 EP-PS-245-2 16 - SECURITY EVENT (continued)

GENERAL EMERGENCY EAL# 16.4 Loss of physical control of facilities as indicated by:

(A or B)

A. Report from Security that a loss of physical control of plant vital areas has occurred.

or B. Any act of sabotage which results in imminent significant cladding failure or fuel melting with a potential for loss of containment integrity or the potential for release of significant amounts of radioactivity in a

short time as judged by the SHIFT SUPERVISOR/EMERGENCY DIRECTOR.

EP-AD-000-200, Revision 16, Page 31 of 39

TAB 2 EP-PS-245-2 17 - SPENT FUEL RELATED INCIDENT UNUSUAL EVENT EAL# 17.1 Unanticipated or unplanned concentrations of airborne activity exist in normally accessible areas, which is not due to planned maintenance activities, as indicated by:

Concentrations exceed 500 times the DAC values of 10CFR20 Appendix B, Table I values for a single isotope, or full multiple isotopes where CA CB Ccc CN

>500

+

+-

DACA DACB DACc DACN ALERT EAL# 17.2 Unexpected in-plant high radiation levels or airborne contamination which indicates a severe fuel handling accident as indicated by:

Refuel floor area radiation monitor reading 1000 times normal annunciation on Panel 1C601 (2C601) or indication on Panel 1C600 (2C600).

(CONTINUED ON NEXT PAGE)

EP-AD-000-200, Revision 16, Page 32 of 39

TAB 2 EP-PS-245-2 17 - SPENT FUEL RELATED INCIDENT (continued)

SITE AREA EMERGENCY EAL# 17.3.a Major damage to irradiated fuel with actual or clear potential for significant release of radioactive material to the environment as indicated by:

(A and B)

A. Dropping, bumping, or otherwise rough handling of a new OR irradiated fuel bundle with irradiated fuel in the pool.

and B. (1 or2)

1. Refueling floor area radiation monitor reading 1000 times normal annunciation on Panel 1C601 (2C601) or indication on Panel 1C600 (2C600).

or

2. Reactor Building vent stack monitoring system high radiation annunciation or indication on Panel 0C630 or 0C677.

OR EAL# 17.3.b Damage to irradiated fuel due to uncontrolled decrease in the fuel pool level to below the level of the fuel as indicated by:

(A and B)

A. (1 or2)

1. Uncovering of irradiated fuel confirmation by verification of significant leakage from spent fuel pool.

or

2. Visual observation of water level below irradiated fuel in the pool.

and B. (1 or2)

1. Refueling floor area radiation monitor annunciation on Panel 1C651 (2C651) or indication on Panel 1C600 (2C600).

or

2. Reactor Building vent stack monitoring system high radiation annunciation or indication on Panel 0C630 or 0C677.

GENERAL EMERGENCY EAL# 17.4 None.

EP-AD-000-200, Revision 16, Page 33 of 39

TAB 2 EP-PS-245-2 18 - STEAM LINE BREAK UNUSUAL EVENT EAL# 18.1 None.

ALERT EAL# 18.2 MSIV malfunction causing leakage as indicated by:

(A and B)

A. Valid MSIV closure signal or indication on Panel 1C601 (2C601).

and B. (1 or2)

1. Valid Main Steam Line flow indication on Panel 1 C652 (2C652).

or

2. Valid Main Steam Line radiation indication on Panel 1C600 (2C600).

(CONTINUED ON NEXT PAGE)

EP-AD-000-200, Revision 16, Page 34 of 39

TAB 2 EP-PS-245-2 18 - STEAM LINE BREAK (continued)

SITE AREA EMERGENCY EAL# 18.3 Steam line break occurs outside of containment without isolation as indicated by:

(A or B or C or D)

A. (1 and 2)

1. Failure of both MSIVs in the line with the leak to close as indicated by position indication on Panel 1C601 (2C601).

and

2. (a orb)
a. High MSL flow annunciation on Panel 1C601 (2C601) or indication on Panel 1C652 (2C652).

or

b. Other indication of main steam leakage outside containment.

or B. (1 and 2)

1. Failure of RCIC steam isolation valves HV-F008 and HV-F007 to close as indicated on Panel 1C601 (2C601).

and

2. (aorborcordoreorf)
a. RCIC steamline pipe routing area high temperature annunciation on Panel 1C601 (2C601), or indication on Panel 1C614 (2C614).

or

b. - RCIC equipment area high temperature annunciation on Panel 1C601 (2C601) or indication on Panel 1C614 (2C614).

or

c. RCIC steamline high flow annunciation on Panel 1C601 (2C601).

or

d. RCIC steamline tunnel ventilation high delta temperature annunciation on Panel 1C601 (2C601).

or

e. RCIC turbine exhaust diaphragm high pressure annunciation on Panel 1C601 (2C601).

or

f. Other indication of steam leakage from the RCIC system.

(CONTINUED ON NEXT PAGE)

EP-AD-000-200, Revision 16, Page 35 of 39

TAB 2 EP-PS-245-2 18 - STEAM LINE BREAK (continued)

SITE AREA EMERGENCY (continued) or

0. (1 and 2)
1. Failure of HPCI steam isolation valves HV-F002 and HV-F003 to close as indicated by position indicator on Panel 1C601 (2C601).

and

2. (a -orb orc ord ore orf)
a. HPCI steamline pipe routing area high temperature annunciation on Panel 1C601 (2C601), or indication on Panel 1C614 (2C614).

or

b. HPCI equipment area high temperature annunciation on Panel 1C601 (2C601) or indication on Panel 1C614 (2C614).

or

c. HPCI steamline high flow annunciation on Panel 1C601 (2C601).

or

d. HPCI steamline tunnel ventilation high delta temperature annunciation on Panel 1C601 (2C601).

or

e. HPCI turbine exhaust diaphragm high pressure annunciation on Panel 1C601 (2C601).

or

f. Other indication of steam leakage from the HPCI system.

or D. Any other un-isolatable steam line breaks.

GENERAL EMERGENCY EAL# 18.4 None.

EP-AD-000-200, Revision 16, Page 36 of 39

TAB 2 EP-PS-245-2 19 - TOXIC/FLAMMABLE GASES UNUSUAL EVENT EAL# 19.1 Nearby or onsite release of potentially harmful quantifies of toxic or flammable material as indicated by:

Visual observation or notification received by the control room operator.

ALERT EAL# 19.2 Entry of toxic or flammable gases into the facility, with subsequent habitability problem as indicated by:

Visual observation, direct measurement, or notification received by the control room operator.

SITE AREA EMERGENCY EAL# 19.3 Toxic or flammable gases enter vital areas, restricting access and restricted access constitutes a safety problem, as determined by:

(A and B)

A. Shift Supervisor's evaluation.

and B. Visual observation, direct measurement, or notification-received by control room operator.

GENERAL EMERGENCY None.

EP-AD-000-200, Revision 16, Page 37 of 39 EAL# 19.4

TAB 2 EP-PS-245-2 20 - TECHNICAL SPECIFICATION SAFETY LIMIT UNUSUAL EVENT EAL# 20.1 Abnormal occurrences which result in operator complying with any of the Technical Specification SAFETY LIMIT ACTION statements indicated by:

(A or B or C or D)

A. Exceeding THERMAL POWER, low pressure or low flow safety limit 2.1.1.1.

or B. Exceeding THERMAL POWER, high pressure and high flow safety limit 2.1.1.2.

or C. Exceeding REACTOR VESSEL WATER LEVEL safety limit 2.1.1.3.

or D. Exceeding REACTOR COOLANT SYSTEM PRESSURE safety limit 2.1.2.

ALERT EAL# 20.2 None.

SITE AREA EMERGENCY EAL# 20.3 None.

GENERAL EMERGENCY EAL# 20.4 None.

EP-AD-000-200, Revision 16, Page 38 of 39

TAB 2 EP-PS-245-2 21 - DRY FUEL STORAGE UNUSUAL EVENT EAL# 21.1.a.

Situations are occurring or have occurred during the transport of the irradiated spent fuel to the onsite storage facility, which jeopardize the integrity of the spent fuel or its container as indicated by:

(A or B)

A. Radiological readings exceed 2 R/hour at the external surface of any transfer cask or horizontal storage module.

or B. Radiological readings exceed 1 R/hour one foot away from the external surface of any transfer cask or horizontal storage module.

OR EAL# 21.1.b. Situations are occurring or have occurred at the irradiated spent fuel storage facility, which jeopardize the integrity of the dry cask storage system as indicated by:

(A A.

or B)

Radiological readings exceed 2 R/hour at the external surface of any transfer cask or horizontal storage module.

or B. Radiological readings exceed 1 R/hour one foot away from the external surface of any transfer cask or horizontal storage module.

ALERT EAL# 21.2 None.

SITE AREA EMERGENCY EAL# 21.3 None.

GENERAL EMERGENCY EAL# 21.4 None.

EP-AD-000-200, Revision 16, Page 39 of 39

TAB 4 EP-PS-245-4 METNENT DATA ACQUISITION OPTIONS The following are sources of meteorological and ventilation data at Susquehanna SES:

A. ACQUISITION OF METNENT DATA FROM THE PICSY TERMINAL

1. From the SSES LOGO display, select E-PLAN MENU or type EPM and

[ENTER].

2. All required meteorological and ventilation (MET/VENT) inputs for the MIDAS dose projections can be obtained by selecting the METNENT DATA display option on the E-PLAN menu.
a. Vent and Primary Met Tower Data is displayed on page 1 of this display.
b. Use the PAGE FORWARD command if the Back-up Tower data is required.
c. Should neither the Primary or Back-up Tower be available, obtain the Downriver Tower data as follows:
1)

Click on the E-PLAN MENU button at the top right hand corner of the METNENT DATA screen.

2)

On the E-Plan menu select and click on the MET DATA screen.

3)

Obtain the Downriver Tower wind speed (Point ID VMS05B), wind direction (Point ID VMX09B), and sigma theta (Point ID VMXlOB).

4)

Return to the E-Plan menu by clicking on the E-PLAN MENU button at the bottom right hand corner of the MET DATA screen.

d. Other options - see Step 6 below.
3. If the Primary Met Tower AT data is not available, determine the wind speed corrected stability class as follows:
a. Determine the initial (uncorrected) stability class using the measured value of sigma theta and the Supplemental Meteorological Information Table 1 (or page 2 of the PICSY screen).
b. Determine the wind speed corrected stability classification using the initial classification, the measured wind speed, and, as appropriate, either Table 2 or Table 3.

EP-AD-000-124, Revision 19, Page 1 of 8

TAB 4 EP-PS-245-4

4. The PICSY QUALITY CODES for the display colors are as follows:

YELLOW:

DATA ACCEPTABLE RED:

DATA EXCEEDS WARNING LIMIT MAGENTA:

DATA EXCEEDS ALARM SETPOINT WHITE:

DATA SUSPECT

5. If a hard copy printout of the information is required you may either:
a. Select the PRINT option using the pull down menu (screen copy takes approximately 3 minutes to complete); or
b. Initiate the MET/VENT DATA LOG option as follows:
1)

On the E-PLAN menu, select the FREE FORMAT LOG MENU.

2)

To activate the TSC log, press [Fl], [22], and [ENTER].

To activate the EOF log, press [Fl], [9], and [ENTER]..

NOTE: Be sure to read the log description because there are 2 logs for the TSC and 2 logs for the EOF.

3)

The log will start printing at the next quarter hour.

4)

To deactivate the TSC log, press [F3], [22], and [E.NTER].

To deactivate the EOF log, press [F3], [9], and [ENTER].

6. If historical MET/VENT information is required, refer to the following instructions:
a. At command line, type: GD ^METVENT1 and [ENTER].
b. Group point display for that display file will come up. Press the [F3] key for history. (See bottom of screen for F key menu.) A dialog box will appear.
c. The work file name to be used is ARCHIVE.D, which is the default for that field.
d. Enter the desired retrieval time. (Enter 15 for the delta time to receive a fifteen-minute period. Click on OK.)
e. Group point display will return with 1 or 2 point values.

EP-AD-000-124, Revision 19, Page 2 of 8

TAB 4 EP-PS-245-4

f. Press the [F4] key if you want to step slowly through the data. Press the [F5]

key if you want to step quickly through the data. (See bottom of screen for F key menu for more options.)

g. The group point display will return to real time when history is complete. A message at the top of the screen will alert you that it is returning to real time.
6. To exit the menu, select the [ESC] key.

B. Site-specific meteorological information can be obtained by contacting either ABS Consulting or the National Weather Service (NWS).

1. ABS Consulting ABS Consulting is the primary meteorological contractor for the Susquehanna Steam Electric Station (SSES). ABS Consulting has the ability to interrogate the primary and backup meteorological towers on a real-time basis and provide short and long-term weather forecasts for the site and surrounding area.

ABS Consulting provides this emergency service to PPL ONLY during normal working hours. The SSES Project Managers name, phone number and mailing address are as follows:

ABS Consulting Mark Abrams (301) 907-9100 (301) 907-0050 (Fax)

ABS Consulting Suite 620 East 7315 Wisconsin Avenue Bethesda, MD 20814

2. NATIONAL WEATHER SERVICE The National Weather Service's (NWS) primary meteorological support responsibility for a radiological emergency at SSES resides with the NWS office at Binghamton, New York. In the event the Binghamton office is unable to provide this support, the designated backup is the NWS office in State College, Pennsylvania.

EP-AD-000-124, Revision 19, Page 3 of 8

TAB 4 EP-PS-245-4 The role of the local NWS office is to provide weather information and forecasts in support of emergency response activities at SSES. The NWS can be consulted over the telephone if data interpretations, assessment, or forecasting assistance are needed.

This information will include the following:

"* Forecasts at current time and 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> of:

a.. 10-meter and 60-meter wind speed and wind direction,

b. Precipitation rate in inches per 15 minutes, and,
c. Boundary layer atmospheric stability described as STABLE, UNSTABLE, or NEUTRAL.

Estimates of current 10-meter and 60-meter wind speed and wind direction in the event of complete loss of onsite and offsite meteorological instrumentation.

General weather forecast from current time to 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> with special emphasis on significant weather occurrences such as major changes in wind speed, wind direction or synoptic weather patterns.

"* Periodic weather updates at time intervals dictated by the on-going weather and emergency situation.

NOTE: The NWS should ONLY be contacted when meteorological support from ABS Consulting is not available (i.e., weekends, holidays, and during the overnight hours).

Whenever contacting the NWS, be sure to provide the following information:

Name, Title, Facility, and Location Reason for the call

  • Status of the Emergency Return telephone number EP-AD-000-124, Revision 19, Page 4 of 8

TAB 4 EP-PS-245-4 The following telephone numbers are UNLISTED and should only be used for EMERGENCY situations.

PRIMARY CONTACT NWS EMERGENCY METEOROLOGICAL SUPPORT OFFICE National Weather Service Office Binghamton Regional Airport 32 Dawes Drive Johnson City, NY 13795 (607) 798-6625 (607) 729-7629 (607) 798-6624 (Fax)

BACKUP CONTACT NWS EMERGENCY METEOROLOGICAL SUPPORT OFFICE National Weather Service Office 227 W. Beaver Avenue, Suite 402 State College, PA 16801 (814) 237-1152 (814) 237-1153 (814) 234-9703 (Fax)

EP-AD-000-124, Revision 19, Page 5 of 8

TAB 4 EP-PS-245-4 PLANT COMPUTER METEOROLOGICAL DATA POINT IDENTIFIERS METEOROLOGICAL AVERAGING PARAMETER POINT ID*

UNITS PERIOD PRIMARY TOWER - east of the plant, 300' high red/white tower.

1 Om Wind Direction vma03 degrees 15 minutes 10m Wind Speed vma06 mph 15 minutes Delta T "A" vma0l

°C/50m 15 minutes Delta T "B" vma02

°C/50m 15 minutes 60m Wind Direction vma04 degrees 15 minutes 60m Wind Speed vma07 mph 15 minutes 10m Sigma Theta vmal0 degrees 15 minutes 60m Sigma Theta vmx24 degrees 15 minutes Precipitation Rate vmaO9 in/hr 15 minutes Ambient Temperature vmt08b OF 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> BACKUP TOWER - across from the SSES Learning Center.

lOm Wind Direction vma05 degrees 15 minutes 10m Wind Speed vma08 mph 15 minutes 10m Sigma Theta vma12 degrees 15 minutes DOWNRIVER TOWER - on Route 93 just east of Nescopeck.

1 Om Wind Direction vmx09b degrees 2 minutes**

10m Wind Speed vms05b mph 2 minutes**

10m Sigma Theta vmxl Ob degrees 2 minutes**

  • Letters are given here in lower case to differentiate the letter o from the number 0.

EP-AD-000-124, Revision 19, Page 6 of 8

TAB 4 EP-PS-245-4 SUPPLEMENTARY METEOROLOGICAL INFORMATION TABLES TABLE 1 ATMOSPHERIC STABILITY CLASSIFICATION Stability Class' Delta (Alternate)

Plume Width Temperature Sigma Theta

@ 10 miles

% of Hrs at Code Title (oC/50m)

(degrees)

(miles)

SSES A

Very Unstable

5-.95

>22.5 5.7 6

B Unstable

-.94 to -.85 17.5 to 22.4 4.3 3

C Slightly Unstable

-.84 to -.75 12.5 to 17.4 3.3 4

D Neutral

-.74 to -.25 7.5 to 12.4 2.3 35 E

Slightly Stable

-.24 to.75 3.8 to 7.4 1.6 32 F

Stable

.76 to 2.0 2.1 to 3.7 1.1 12 G

Very Stable

>2.0

<2.1

.75 8

TABLE 2 DAYTIME (08:00 to 18:00)

Initial Stability Class/

FINAL Wind Speed (MPH)

VALUE A

Wind Speed < 7 A

7 < Wind Speed < 9 B

9:< Wind Speed < 13 C

Wind Speed > 13 D

-B 9 < Wind Speed B

9:< Wind Speed < 13 C

Wind Speed > 13 D

C 13 < Wind Speed C

Wind Speed > 13 D

D, E, F, G Any wind speed.

D Example: If wind speed is 9 mph and sigma theta is 18 degrees @ 10 a.m., the initial stability class from Table 1 is "B" and the wind speed corrected stability class from Table 2 is

".C*"

TABLE 3 NIGHTTIME (18:00 to 08:00)

Initial Stability Class/

FINAL Wind Speed (MPH)

VALUE A

6 < Wind Speed F

6_< Wind Speed < 8 E

Wind Speed 2> 8 D

B 5 < Wind Speed F

5 <Wind Speed < 7 E

Wind Speed >_ 7 D

C 5 < Wind Speed E

Wind Speed > 5 D

D Any wind speed.

D E

11 < Wind Speed E

Wind Speed > 11 D

F,G 7 < Wind Speed F

7< Wind Speed < 11 E

Wind Speed > 11 D

EP-AD-000-124, Revision 19, Page 7 of 8

TAB 4 EP-PS-245-4 TABLE 4 Wind From Affected Affected EPB*

On-Site Team Site Boundary

% of Hrs Sector Degrees Sector Sector Distance (mi)

Distance (mi)

Distance (mi)

Affected SSES 348-11 N

S 0.34 0.25 0.38 6

12-33 NNE SSW 0.34 0.37 0.39 9

34-56 NE SW 0.34 0.33 0.61 12 57-78 ENE WSW 0.34 0.39 1.22 11 79-101 E

W 0.34 0.37 1.03 6

102 - 123 ESE WNW 0.34 0.41 0.61 4

124-146 SE NW 0.34 0.35 0.66 4

147-168 SSE NNW 0.34 0.29 0.59 4

169-191 S

N 0.34 0.29 0.59 5

192-213 SSW NNE 0.34 0.39 0.78 7

214-236 SW NE 0.34 0.42 0.58 11 237 - 258 WSW ENE 0.34 0.52 0.49 7

259-281 W

E 0.34 0.45 0.48 4

282-303 WNW ESE 0.34 0.18 0.50 3

304 - 326 NW SE 0.34 0.20 0.43 3

326 - 348 NNW SSE 0.34 0.20 0.41 5

4.

r r

CI L1 I L

J I~

EP-AD-000-124, Revision 19, Page 8 of 8 WIND SECTORS AND DISTANCES U-- aisiances estabiisned at Exclusion Axrea Boundary distance OT "IdUU 1!.