Bryce L. Shriver PPL Susquehanna, LLC " tI I / t Senior Vice President and 769 Salem Boulevard Chief Nuclear Officer Berwick, PA 18603 Tel. 570.542.3120 Fax 570.542.1504 blshriver@pplweb.com JUN 0 5 2002 I .P 4* TM U.S. Nuclear Regulatory Commission Attn: Document Control Desk Mail Station OP 1-17 Washington, DC 20555 SUSQUEHANNA STEAM ELECTRIC STATION REVISIONS TO ERDS DATA POINT LIBRARY REFERENCE FILE DUE TO THE INSTALLATION OF LEFM PLA-5489 Docket No.50-387 In accordance with 10 CFR 50 Appendix E Section VI.3, attached are revisions to the ERDS Data Point Library as a result of the installation of the Leading Edge Flow Meter (LEFM) in Susquehanna SES Unit 1.

If you have any questions, please contact Mr. C. T. Coddington at (610) 774-4019.

Sincerely, B. L. Shriver Attachment copy: NRC Region I Mr. S. L. Hansell, NRC Sr. Resident Inspector Mr. T. G. Colburn, NRC Sr. Project Manager Mr. E. M. Thomas, NRC Project Manager

S'28- SAFETY RELATED CSD ER-005 "OTIHER QUALITY FILE NO. N/A CRITICAL SOFTWARE (C) PAGE 1 of 84 NcN -QUALITYD

. TM COMPUTER SYSTEM DOCUMENT EMERGENCY RESPONSE DATA SYSTEM (ERDS)

DATA POINT LIBRARY (DPL)

PPL SUSQUEHANNA, LLC - UNITS 1 AND 2 CONTROLLED 4 05/23/02 Admin. Correction-DCN 98-0656 was H.A. Clatch N/A incorporated into Rev. 3; Addition of LEFM Pts. To Unit 1 3 06/01/01 Addition of LEFM Pts. To Unit 2 H.A. Clatch N/A W.A. DeLuca 2 05/13/98 Addition of Unit 1 PICSY H.A. Clatch N/A G.J. Krupko 1 11/14/95 Addition of Unit 2 PICSY M.L. Orloski N/A Henry P. Seager 0 11/30/92 Initial Issue J.L. Angstadt N/A D.D. Kelley REV. DATE DESCRIPTION PREPARED BY VERIFIED APPROVED FORM NSEI-AD-505-1, Rev. 2, Page 1 of 1 (Electronic Form)

CSD-ER-005 Revision 4 Page 2 of 84 Procedure Change Summary TITLE: EMERGENCY RESPONSE DATA SYSTEM (ERDS) DATA POINT LIBRARY (DPL)

1) Administrative Change - DCN 98-0656 had been incorporated into Revision 3 but not noted on the cover sheet.
2) Appendix C changes
a. Replaced points NFF52, NFF53 and NFF54 (pages 28, 29 and 30) in the data stream with points NFF77, NFF78 and NFF79 (old pages 78,79 and 80).
b. Made the REACTOR UNIT for points NFF78, NFF79 and NFF80 SQI/SQ2.
c. Deleted pages 78, 79 and 80 and re-numbered pages 78 thru 87 to pages 78 thru 84.

CSD-ER-005 Revision 4 Page 3 of 84 Emergency Response Data System (ERDS)

Data Point Library (DPL)

Table of Contents Page Section 1.0 Scope ................... .... ........................ 4 Section 2.0 General Information ................ ................. 4 Section 3.0 References .................... ..................... 5

. . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Appendix A Appendix B . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Appendix C .. . . . . . . . . . . . . . . . . . . . . . . . .. . 7

. . . . . . . . . . .. . . . I . . . . . . . . . . . . . 7 8 Appendix D

. . . . . . . . . . . . . . . . . . . . . . . . . . . . 82 Appendix E

CSD-ER-005 Revision 4 Page 4 of 84 1.0 SCOPE This CSD documents the Emergency Response System Data Point Library (DPL) submitted to the U.S. Nuclear Regulatory Commission to meet the DPL requirements of NUREG-1394 Rev.l, Emergency Response Data System (ERDS) Implementation.

2.0 General Information The Appendices of this CSD have been named to correspond to the Appendices of NUREG-1394, Rev. 1. Not all of the information required by NUREG 1394, Rev. 1 appendix is included in this document.

NOTICE Changes to Appendix C or E of this CSD may require that the NRC be notified of the change. Reference CSD-PIC-759 for additional guidance.

CSD-ER-005 Revision 4 Page 5 of 84 The following list identifies the NUREG Appendices, and where the information (if any) required by that Appendix is provided:

Appendix Description Response Emergency Response Data System PP&L response provided in ERDS Transmission/Reception Plan letter PLA-3704 dated December 20, 1991.

ERDS Communication Description and Survey Questionnaire PP&L response provided in letter PLA-3672 dated Data Point Library October 24, 1991.

Data Point Library Reference Included in this CSD.(')

File Definitions No response required.

Appendix duplicated in 2 Critical Safety Function this CSD for convenience. '

Parameters 3 Included in this CSD.( )

Engineering Units Coding Scheme"4 No response required.

Zero Reference Coding Scheme(s) Reference NUREG 1394, Rev. 1 for details.

Coding Scheme for Unit Name and No response required.

Unit ID Reference NUREG 1394, Rev. 1 for details.

Computer Point Selection 6 No response required.

Reference NUREG 1394, Rev. 1 for details.

No response required.

Reference NUREG 1394, Rev. 1 for details.

"l This Appendix provides detailed information for each point listed in Appendix E.

ý2) This Appendix provides a description of each field in the Data Point Library and the fields maximum character length.

(3) This Appendix provides a summary of all the computer points that are utilized for ERDS. Reference Appendix C of NUREG-1394 for additional guidance on Data Point Library entries.

'4) This Appendix provides the preferred engineering units abbreviations for use in the Engineering Units field of the Data Point Library entries.

(5) This Appendix provides the accepted abbreviations for the Zero Reference Point field of the entries in the Data Point Library that require this field.

(6) This Appendix provides guidance on the selection of computer points to satisfy the ERDS requirements.

3.0 REFERENCES

3.1 NUREG-1394, Rev. 1, Emergency Response Data System (ERDS)

Implementation 3.2 NSEP-QA-500, Process Computer Quality Assurance and Design Control Program

CSD-ER-005 Revision 4 Page 6 of 84 APPENDIX A & B Appendix A & B are not included in this CSD.

Reference Section 2.0 for more information on these appendices.

CSD-ER-005 Revision 4 Page 7 of 84 APPENDIX C DATA POINT LIBRARY

CSD-ER-005 Revision 4 Page 8 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQl/SQ2 Data Feeder: N/A NRC ERDS Parameter: NI POWER RNG Point ID: PWR Plant Spec Point Desc.: REACTOR POWER Generic/Cond Desc.: Nuclear Instruments, Power Range Analog/Digital: A Engr Units/Dig States:

Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: 125 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 6 How Processed: Averaged (ref. Unique System Desc.)

Sensor Locations: Each APRM has 21 to 22 LPRMs as inputs Alarm/Trip Set Points: Reference Unique System Desc.(J' NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low, High Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: A Supplier proprietary algorithm basically averages the highest number of on-scale APRMs whose values are in agreement.

"(I)-Various trip set points exist for the APRMs depending on the plant Condition (i.e. Condition 1-5).

Note: PWR is a composite SPDS parameter with the following points as inputs: NM551, NM552, NM553, NM554, NM555, NM556.

CSD-ER-005 Revision 4 Page 9 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQl/SQ2 Data Feeder: N/A NRC ERDS Parameter: NI INTER RNG Point ID: NN109 Plant Spec Point Desc.: IRM A FLUX (% OF SCALE)

Generic/Cond :esc.: Nuclear Instruments, Inter Rng A Analog/Digital: A Engr Units/Dig States:

Engr Units Conversion: N/A Minimum Instr Range: 0.0 Maximum Instr Range: 100.0 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locatirns: Reference Unique System Desc.

Alarm/Trip Set Points: Reference Unique System Desc. :

NI Detector t:wer Supply Cut-off Power Level: N/A NI Detector P=wer Supply Turn-on Power Level: N/A Instrument Failure Mode: Low, High Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: The electrical full-in limit, positions the detector 18" above the active fuel center line. The mechanical full-in limit is 21" above the active fuel center line. The location of the detector during normal reactor operation (full-out limit) is 24" below the bottom of the active fuel. The GE coordinate (radial position) of the detector in the core is 16-53.

, - When the plant is in Condition 2-5 there is an upscale neutron flux/RPS trip = 95.8%, an upscale neutron flux/Rod Block = 86.2%, and a downscale neutron flux/Rod Block = 4.2%. These blocks/trips are bypassed in Condition 1.

CSD-ER-005 Revision 4 Page 10 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ:/SQ2 Data Feeder: NiA NRC ERDS Parameter: N: INTER RNG Point ID: NN=12 Plant Spec Point Desc.: 7RYl D FLUX (% OF SCALE)

Generic/Cond Desc.: Nuclear Instruments, Inter Rng D Analog/Digital: A Engr Units/Dig States:

Engr Units Conversion: N/.A Minimum Instr Range: 0.0 Maximum Instr Range: 13 .0 Zero Point

Reference:

Reference Point Notes: NSA PROC or SENS: S Number of Sensors:

How Processed: N/ A Sensor Locations: Re.ference Unique System Desc.

Reference Unique System Desc. :

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode: Lcw, High Temperature Compensation For DP Transmitters:

N ,"A Level Reference Leg:

Unique System Desc.: electrical full-in limit, positions the detector 18" above the ac-ive fuel center line. The mechanical full-in limit is 21" above toe active fuel center line. The location of the detector during nor-mal reactor operation (full-out limit) is 24' below the bottom of the active fuel. The GE coordinate (radial position) of the detector in the core is 32-37.

- When the plant is in Condition 2-5 there is an upscale neutron flux/RPS trip = 95.8%, an upscale neutron flux/Rod Block = 86.2%, and a downscale neutron flux/Rod Block = 4.2%. These blocks/trips are b-._-assed in Condition 1.

CSD-ER-005 Revision 4 Page 11 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQI/SQ2 Data Feeder: N/A NRC ERDS Parameter: NI INTER RNG Point ID: NN115 Plant Spec Point Desc.: IFIM G FLUX (% OF SCALE)

Generic/Cond Desc.: Nuclear Instruments, Inter Rng G Analog/Digital: A Engr Units/Dig States:

Engr Units Conversion: N/A Minimum Instr Range: 0.0 Maximum Instr Range: 100.0 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: Reference Unique System Desc.

Alarm/Trip Set Points: Reference Unique System Desc.<)

NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low, High Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: The electrical full-in limit, positions the detector 18" above the active fuel center line. The mechanical full-in limit is 21" above the active fuel center line. The location of the detector during normal reactor operation (full-out limit) is 24" below the bottom of the active fuel. The GE coordinate (radial position) of the detector in the core is 48-13.

S- When the plant is in Condition 2-5 there is an upscale neutron flux/RPS trip = 95.8%, an upscale neutron flux/Rod Block = 86.2%, and a downscale neutron flux/Rod Block = 4.2%. These blocks/trips are bypassed in Condition 1.

CSD-ER-005 Revision 4 Page 12 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQl/SQ2 Data Feeder: N/A NRC ERDS Parameter: NI INTER RNG Point ID: NNl16 Plant Spec Point Desc.: [RM H FLUX (% OF SCALE)

Generic/Cond Desc.: Nuclear Instruments, Inter Rng H Analog/Digital: A Engr Units/Dig States:

Engr Units Conversion: N/A Minimum Instr Range: 0.0 Maximum Instr Range: 000.0 Zero Point

Reference:

Ž7/A Reference Poinz Notes: :7/A PROC or SENS:

Number of Sensors:

How Processed: Ž7/A Sensor Locations: Reference Unique System Desc.

Alarm/Trip Set Points: Reference Unique System Desc.Y NI Detector Power Supply Cut-off Power Level: ,/A NI Detector Power Supply Turn-on Power Level: ';/A Instrument Failure Mode: Low, High Temperature Compensation For DP Transmitters: Ž7/A Level Reference Leg: ',/A Unique System Desc.: :he electrical full-in limit, positions the detector 18" above the active fuel center line. The mechanical full-in limit is 21' above the active fuel center line. The location of the detector during normal reactor operation (full-out limit) is 24" below the bottom of the active fuel. The GE coordinate (radial position) of the detector in the core is 16-13.

- When the plant is in Condition 2-5 there is an upscale neutron flux/RPS trip = 95.8%, an upscale neutron flux/Rod Block = 86.2%, and a downscale neutron flux/Rod Block = 4.2%. These blocks/trips are bypassed in Condition 1.

CSD-ER-005 Revision 4 Page 13 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQI/SQ2 Data Feeder: N/A NRC ERDS Parameter: Not Listed Point ID: NN*.X01 Plant Spec Point Desc.: .AMA RANGE SWITCH POSN Generic/Cond Desc.: IR)M A Range Switch Position Analog/Digital: A Engr Units/Dig States: N/A Engr Units Conversion: N/A Minimum Instr Range:

10 Maximum Instr Range:

10A Zero Point

Reference:

N/A Reference Point Notes:

PROC or SENS: P Number of Sensors:

How Processed: Reference Unique System Desc.

Sensor Locations: Panel lC651G-11D IRM range switch A Alarm/Trip Set Points: N A NI Detector Power Supply Cut-off Power Level: NA NI Detector Power Supply Turn-on Power Level:

NiA Instrument Failure Mode:

Temperature Compensation N/A For DP Transmitters:

Level Reference Leg:

Unique System Desc.: The analog value for switch position is calculated from the IRM switch position digital inputs.

- Panel 1C651 is for SQl, Panel 2C651 is for SQ2

CSD-ER-005 Revision 4 Page 14 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQl/SQ2 Data Feeder: N/A NRC ERDS Parameter: Not Listed Point ID: NNX04 Plant Spec Point Desc.: IRhM D RANGE SWITCH POSN Generic/Cond Desc.: IAM D Range Switch Position Analog/Digital: A Engr Units/Dig States: N/A Engr Units Conversion: N/A Minimum Instr Range: 1 Maximum Instr Range:

Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 10 How Processed: Reference Unique System Desc.

Sensor Locations: Panel 1C651( l-IID IRM range switch D Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-otf Power Level: NIA NI Detector Power Supply Turn-on Power Level: N,/A Instrument Failure Mode: N/A Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: The analog value for switch position is calculated from the IRM switch position digital inputs.

S- Panel IC651 is for SQl, Panel 2C651 is for SQ2

CSD-ER-005 Revision 4 Page 15 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQi/SQ2 Data Feeder: N/A NRC ERDS Parameter: Not Listed Point ID: NNX 07 Plant Spec Point Desc.: I7FM G RANGE SWITCH POSN Generic/Cond Desc.: IRM G Range Switch Position Analog/Digital: A Engr Units/Dig States: N/A Engr Units Conversion: N/A Minimum Instr Range: 1 Maximum Instr Range: 10 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS:

Number of Sensors:

How Processed: Reference Unique System Desc.

Sensor Locations: Panel IC651E1)-IID IRM range switch G Alarm/Trip Set Points:

NI Detector Power Supply.

Cut-off Power Level: N A NI Detector Power Supply, Turn-on Power Level:

Instrument Failure Mode: N/A Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: The analog value for switch position is calculated from the IRM switch position digital inputs.

Panel 1C651 is for SQl, Panel 2C651 is for SQ2

CSD-ER-005 Revision 4 Page 16 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQl/SQ2 Data Feeder: N/A NRC ERDS Parameter: Not Listed Point ID: NNX 08 Plant Spec Point Desc.: INM H RANGE SWITCH POSN Generic/Cond Desc.: IR-M H Range Switch Position Analog/Digital: A Engr Units/Dig States: N/A Engr Units Conversion: N/A Minimum Instr Range: 1 Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS: P 10 Number of Sensors:

How Processed: Reference Unique System Desc.

Panel

/C651A1'-IID IRM range switch H Sensor Locations:

N/A Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode: N/A Temperature Compensation For DP Transmitters: NIA Level Reference Leg: N/A The analog value for switch position is calculated from the IRM switch Unique System Desc.:

position digital inputs.

ePanel 1C51 is for SQC, Panel 2C651 is for SQ2

CSD-ER-005 Revision 4 Page 17 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 051/13/98 Reactor Unit: SQI/SQ2 Data Feeder: N/A NRC ERDS Parameter: Not Listed Point ID: NNZ54 Plant Spec Point Desc.: IRM DET NOT FULL IN POS Generic/Cond Desc.: IRM Det(s) not full in Position Analog/Digital: D Engr Units/Dig States: NO/YES Engr Units Conversion: N/A Minimum Instr Range: N/A Maximum Instr Range: N/A Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: s Number of Sensors:

How Processed: N/A Sensor Locations: Full in limit switch on IRIM drive unit Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level:

NiA NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode: Value = Yes (i.e. Not In)

Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: This parameter is a logical 'or' of the Plant's eight (8) IRM detectors such that if an;.- detector is not in the full in position this parameter will be true (YES).

CSD-ER-005 Revision 4 Page 18 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQI/SQ2 Data Feeder: N/A NRC ERDS Parameter: Not Listed Point ID: NNZ 59 Plant Spec Point Desc.: 1RM BYPASS Generic/Cond Desc.: IRM Bypass Analog/Digital: D Engr Units/Dig States: NO/YES Engr Units Conversion: N/A Minimum Instr Range: N/A Maximum Instr Range: N/A Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: Panel 1C651(Gl -ID IRM bypass switch Alarm/Trio Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Value = No (i.e. not Bypassed)

Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: This parameter is a logical 'or' of the Plant's eight (8) IRM detectors bypass status such that if n detector is bypassed this be true (YES).

parameter will Panel 1C651 is for SQl, Panel 2C651 is for SQ2

CSD-ER-005 Revision 4 Page 19 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQI/SQ2 Data Feeder: N/A NRC ERDS Parameter: NI SOURC RNG Point ID: NNI_001Z Plant Spec Point Desc.: SPR A LOG RATE Generic/Cond Desc.: Nuclear Instruments, Sourc Rng A Analog/Digital: A Engr Units/Dig States: CPS Engr Units Conversion: N/A Minimum Instr Range: .1 Maximum Instr Range: 1E6 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: Reference Unique System Desc.

Alarm/Trip Set Points: Reference Unique System Desc. (1 NI Detector Power Supply Cut-off Power Level:

N/A NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode: Low, High Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: The electrical full-in limit, positions the detector 18" above the active fuel center line. The mechanical full-in limit is 21" above the active fuel center line. The location of the detector during normal reactor operation (full-out limit) is 24" below the bottom of the active fuel. The GE coordinate (radial position) of the detector in the core is 16-45.

1 when the plant is in Condition 2 - 5, there is an upscale alarm/rod block = 1 x 105 CPS, an upscale/non-coincident trio = 2 x l05 CPS, and a downscale/rod block = 4.1 CPS. These blocks/trips are bypassed when the plant is Condition 1. The upscale/non-coincident trip is defeated when the RPS shorting links are installed.

CSD-ER-005 Revision 4 Page 20 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05 /13/98 Reactor Unit: SQ*/SQ2 Data Feeder: NiA NRC ERDS Parameter: N: SOURC RNG Point ID: NIT1002Z Plant Spec Point Desc.: SFM B LOG RATE Generic/Cond Desc.: Nuclear Instruments, Sourc Rng B Analog/Digital: A Engr Units/Dig States: CPS Engr Units Conversion: N/A Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

NIA Reference Point Notes: N.'A2 PROC or SENS: S Number of Sensors: 1 How Processed: N/i Sensor Locations: Reference Unique System Desc.

Alarm/Trio Set Points: Reference Unique System Desc.1)

NI Detector Power Supply Cut-off Power Level: N!A NI Detector Power Supply Turn-on Power Level: N,'A Instrument Failure Mode: Lc., High Temperature Compensation For DP Transmitters: N/1 Level Reference Leg: N/A Unique System Desc.: The electrical full-in limit, positions the detector 18" above the active fuel center line. The mechanical full-in limit is 21' above the active fuel center line. The location of the detector during nc--al reactor operation (full-out limit) is 24" below the bottom of the active fuel. The GE coordinate (radial position) of the detector in :he core is 40-45.

When the plant is in Condition 2 - 5, there is an upscale alarm/rod blcck = 1 x 105 CPS, an upscale/non-coincident trip = 2 X 105 CPS, and a do-, scale/rod block = 4.1 CPS. These blocks/trips are bypassed when the pla*t is Condition 1. The upscale/non-coincident trip is defeated when the RPS shorting links are installed.

CSD-ER-005 Revision 4 Page 21 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQl/SQ2 Data Feeder: N/A NRC ERDS Parameter: NI SOURC RNG Point ID: NNI003Z Plant Spec Point Desc.: SRIM C LOG RATE Generic/Cond Desc.: Nuclear Instruments, Sourc Rng C Analog/Digital: A Engr Units/Dig States: CPS Engr Units Conversion: N/A Minimum Instr Range: .1 Maximum Instr Range: lE6 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors:  !

How Processed: N/A Sensor Locations: Reference Unique System Desc.

Alarm/Trip Set Points: Reference Unique System Desc.(1i NI Detector Pcwer Supply Cut-off Power Level: N/A NI Detector Po.,er Supply Turn-on Power Level: N'/A Instrument Failure Mode: Low, High Temperature Compensation For DP Transmizters: N/A Level Reference Leg: N/A Unique System Desc.: The electrical full-in limit, positions the detector 18" above the active fuel center line. The mechanical full-in limit is 21" above the active fuel center line. The location of the detector during normal reactor operation (full-out limit) is 24" below the bottom of the active fuel. The GE coordinate (radial position) of the detector in the core is 40-21.

- When the plant is in Condition 2 - 5, there is an upscale alarm/rod block = 1 x 105 CPS, an upscale/non-coincident trip = 2 X 105 CPS, and a downscale/rod block = 4.1 CPS. These blocks/trips are bypassed when the plant is Condition 1. The upscale/non-coincident trip is defeated when the RPS shorting links are installed.

CSD-ER-005 Revision 4 Page 22 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQl/SQ2 Data Feeder: N/A NRC ERDS Parameter: NI SOURC RNG Point ID: NNl 004Z Plant Spec Point Desc.: SRM D LOG RATE Generic/Cond Desc.: Nuclear Instruments, Sourc Rng D Analog/Digital: A Engr Units/Dig States: CPS Engr Units Conversion: N/A Minimum Instr Range: .1 Maximum Instr Range: lE6 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: Reference Unique System Desc.

Alarm/Trip Set Points: Reference Unique System Desc.A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low, High Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: The electrical full-in limit, positions the detector 18" above the active fuel center line. The mechanical full-in limit is 21" above the active fuel center line. The location of the detector during normal reactor operation (full-out limit) is 24" below the bottom of the active fuel. The GE coordinate (radial position) of the detector in the core is 16-21.

-I When the plant is in Condition 2 - 5, there is an upscale alarm/rod block = 1 x 10 CPS, an upscale/non -coincident trip = 2 X 105 CPS, and a downscale/rod block = 4.1 CPS. These blocks/trips are bypassed when the plant is Condition 1. The upscale/non-coincident trip is defeated when the RPS shorting links are installed.

CSD-ER-005 Revision 4 Page 23 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: Cz ,113/98 Reactor Unit: SQI/SQ2 Data Feeder: N;A NRC ERDS Parameter: Nc: Listed Point ID: N=:Y 001Z Plant Spec Point Desc.: SFM POSITION A Generic/Cond Desc.: SF-M Position A Analog/Digital: D Engr Units/Dig States: NCT ININ Engr Units Conversion:

Minimum Instr Range: N/A N A Maximum Instr Range:

N 2 Zero Point

Reference:

Reference Point Notes: N4 2 PROC or SENS: S Number of Sensors:

How Processed:

Sensor Locations: Sc-- drive motor limit switch Alarm/Trip Set Points: N A NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

N A Instrument Failure Mode: N A Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc.:

CSD-ER-005 Revision 4 Page 24 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQI/SQ2 Data Feeder: N/A NRC ERDS Parameter: Not Listed Point ID: NPY002Z Plant Spec Point Desc.: SEM POSITION B Generic/Cond Desc.: SEM Position B Analog/Digital: D Engr Units/Dig States: NOT IN,IN Engr Units Conversion: N/A Minimum Instr Range: N/A Maximum Instr Range: N/A Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors:

How Processed: N/A Sensor Locations: SRM drive motor limit switch Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: Ni A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Value = 'Not In' Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unicue System Desc.:

CSD-ER-005 Revision 4 Page 25 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05 13/98 Reactor Unit: SQc/SQ2 Data Feeder: N, A NRC ERDS Parameter: Nc: Listed Point ID: NY0 03 Z Plant Spec Point Desc.: SRY POSITION C Generic/Cond Desc.: SPY Position C Analog/Digital: D Engr Units/Dig States: NOT IN,IN Engr Units Conversion: N/A Minimum Instr Range: N /A Maximum Instr Range: N/A Zero Point

Reference:

NI Reference Point Notes: N, A PROC or SENS: S Number of Sensors:

How Processed: NA.

Sensor Locations: drive motor limit switch Alarm/Trip Set Points:

tI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply N A Turn-on Power Level:

Instrument Failure Mode: Value = 'Not In' Temperature Compensation For DP Transmitters: N/-A Level Reference Leg: NA Unique System Desc.:

CSD-ER-005 Revision 4 Page 26 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: Not Listed Point ID: NPY004Z Plant Spec Point Desc.: SRM POSITION D Generic/Cond Desc.: SRM Position D Analog/Digital: D Engr Units/Dig States: NOT IN,IN Engr Units Conversion: N/A Minimum Instr Range: N/A Maximum Instr Range: N/A Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors:

How Processed: N/A Sensor Locations: SRM drive motor limit switch Alarm/Trip Se: Points: N/A NI Detector Pcwer Supply Cut-off Power Level: N/A NI Detector Pgwer Supply Turn-on Power Level: N/A Instrument Failure Mode: Value = 'Not In' Temperature Ccmpensation For DP Transmitters: IN/A Level Reference Leg: N/A Unique System Desc.:

CSD-ER-005 Revision 4 Page 27 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05 '13/98 Reactor Unit: SQ:/SQ2 Data Feeder:

NRC ERDS Parameter: RE-AC VES LEV Point ID: RVL Plant Spec Point Desc.: REACTOR WATER LEVEL Generic/Cond Desc.: Reactor Vessel Water Level Analog/Digital: A Engr Units/Dig States: IN_`HES Engr Units Conversion: Ni A Minimum Instr Range: -3:0 Maximum Instr Range: 503 Zero Point

Reference:

B: SKRT Reference Point Notes: B-S.XRT = near bottom of dryer skirt()

PROC or SENS: P Number of Sensors: Reference Unique System Desc.

How Processed: Reference Unique System Desc.

Sensor Locations: Reactor Bldg Elevation 749' Alarm/Trip Set Points: Reference Unique System Desc. :21 NI Detector Power Supply Cut-off Power Level: N ,.

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode: Loc, High Temperature Compensation For DP Transmitters: N Level Reference Leg: Wet Unique System Desc.: S---ýS has 13 Rx water level inputs in 6 different range groups, narrow, wide, extended, upset, shutdown & fuel zone. A Supplier proprietary a1=orithm will arrive at a value for RWL by either averaging only valid signals in the most appropriate range group or by selection of a single leael signal.

-Zero point reference is 527.5" above vessel zero (bottom drain 0.0").

TAF is at 366.31".

- Various initiations or trips will occur at Level 1 (-149"), Level 2

(-3B"), Level 3 (+12.5") and Level 8 (+54")

Nc-e: RWL is a composite SPDS parameter with the following points as in.its: NFL001Z, NFL002Z, NFL003Z, NFL004Z, NFL005Z, NFL007Z, NBL001Z, NHB302Z, NBL003Z, NBL004Z, NBL005Z, NBL006Z, and NBL007Z.

CSD-ER-005 Revision 4 Page 28 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/23/02 Reactor Unit: SQI/SQ2 Data Feeder: N A NRC ERDS Parameter: MlAIN FD FLOW Point ID: NFF7 7 Plant Spec Point Desc.: R'K FLOW A Generic/Cond Desc.: Feedwater Flow A into React Syst Analog/Digital: A Engr Units/Dig States: M-SS/H Engr Units Conversion: N/A Minimum Instr Range: 0.0 Maximum Instr Range: 8. 000 Zero Point

Reference:

N 'A Reference Point Notes: N'A PROC or SENS: S Number of Sensors:

How Processed: N/A Sensor Locations: Reference Unique System Desc.

Alarm/Trip Set Points: N*A NI Detector Power Supply Cut-off Power Level: N A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low - downscale Temperature Compensation For DP Transmitters: N/A Level Reference Leg: NI/.A Unique System Desc.: Flaw is measured on discharge line of Pump A prior to common feedwater header.

CSD-ER-005 Revision 4 Page 29 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/23/02 Reactor Unit: SQl/SQ2 Data Feeder: N/A NRC ERDS Parameter: MA:N FD FLOW Point ID: NFF78 Plant Spec Point Desc.: :r FLOW B Generic/Cond Desc.: Feedwater Flow B into React Syst Analog/Digital: A Engr Units/Dig States: MLBS/H Engr Units Conversion: N/A Minimum Instr Range: 0.0 Maximum Instr Range: 8.000 Zero Point

Reference:

N/A Reference Poin= Notes:

PROC or SENS: S Number of Sensors:

How Processed:

Sensor Locations: Reference Unique System Desc.

Alarm/Trip Set Points:

NI Detector Pcwer Supply Cut-off Power Level: ./A NI Detector Pcwer Supply Turn-on Power Level:

Instrument Failure Mode: Low - downscale Temperature Compensation For DP Transmitters:

Level Reference Leg: N/A Unique System Desc.: Flow is measured on discharge line of Pump B prior to common feedwater header.

CSD-ER-005 Revision 4 Page 30 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: Cz*/23/o2 Reactor Unit: Sýl/SQ2 Data Feeder: N A NRC ERDS Parameter: MAtIN FD FLOW Point ID: NFF79 Plant Spec Point Desc.: -X FLOW C Generic/Cond Desc.: Feedwater Flow C into React Syst Analog/Digital:

Engr Units/Dig States: M-BS/H Engr Units Conversion: N"A Minimum Instr Range: 0.0 Maximum Instr Range: 8 . 000 Zero Point

Reference:

N A Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed:

Sensor Locations: Reference Unique System Desc.

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

instrument Failure Mode: Lc, - downscale Temperature Compensation For DP Transmitters: N.A Level Reference Leg:

Unique System Desc.: Frrw is measured on discharge line of Pump C prior to common feedwater header.

CSD-ER-005 Revision 4 Page 31 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05 /13/98 Reactor Unit: SQI/SQ2 Data Feeder: N,'A NRC ERDS Parameter: RCIC FLOW Point ID: -- 01 Plant Spec Point Desc.: RC:C FLOW Generic/Cond Desc.: Reactor Core Isolat Cooling Flow Analog/Digital: A Engr Units/Dig States: GPM Engr Units Conversion: N/A Minimum Instr Range: 0.3 Maximum Instr Range: 700.0 Zero Point

Reference:

NiA Reference Point Notes:

PROC or SENS: S Number of Sensors: 1 How Processed: N A Sensor Locations: Between RCIC pump and pump discharge valve('>

Alarm/Trip Set Points: At.--m, Low Flow at 60 GPM NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode: Higzh, Low Temperature Compensation For DP Transmitters: N,,A Level Reference Leg: N!A Unique System Desc.: - Reactor Building Elevation 645'

CSD-ER-005 Revision 4 Page 32 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05 /13/98 Reactor Unit: SI/SQ2 Data Feeder: N. A NRC ERDS Parameter: R;S PRESSURE Point ID: P-_: P R Plant Spec Point Desc.: REACTOR PRESSURE Generic/Cond Desc.: Reactor Coolant System Pressure Analog/Digital: A Engr Units/Dig States: PSIG Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range:

Zero Point

Reference:

Reference Point Notes:

PROC or SENS:

Number of Sensors: Reference Unique System Desc.

How Processed: Reference Unique System Desc.

Sensor Locations: Reactor Bldg Elevation 749' Alarm/Trip Set Points: A-arm @ 1020 PSIG, Trip @ 1037 PSIG NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode: Lcw, High Temperature Compensation For DP Transmitters:

Level Reference Leg:

Unique System Desc. A Supplier proprietary algorithm arrives at a value for RXPR by either selecting a single signal or by averaging signals depending on the results of validation and verification of the five sensed pressure sianal inputs.

Nc:e: RXPR is a composite SPDS parameter with the following points as incuts: NFP001Z, NFP002Z, NFP003Z, NFP005Z, and NFP006Z.

CSD-ER-005 Revision 4 Page 33 of 84 SUSQUEHANNA STEAOM ELECTRIC STATION UN:TS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: HPCI FLOW Point ID: NGF01 Plant Spec Point Desc.: HPCI PP DSCH LINE FLOW Generic/Cond Desc.: High Pressure Coolant Injec Flow Analog/Digital: A Engr Units/Dig States: GPM Engr Units Conversion: N/A Minimum Instr Range: 0.0 Maximum Instr Range: 6000 Zero Point

Reference:

N,/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors:  !

How Processed: N/A Sensor Locations: ?ump discharge line - Rx Bldg Elev. 645' Alarm/Trip Set Points: Alarm, Low Flow at 300 G;:.

NI Detector Power Supply Cut-off Power Level:

N 'A NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode: "Nigh, Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.:

CSD-ER-005 Revision 4 Page 34 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 03/13/98 Reactor Unit: SQI/SQ2 Data Feeder: N/A NRC ERDS Parameter: LPCI FLOW Point ID: NEI 301 Plant Spec Point Desc.: RFR SYS A FLOW Generic/Cond Desc.: Low Press Coolant Inject A Flow Analog/Digital: A Engr Units/Dig States: GPM Engr Units Conversion: N/A Minimum Instr Range: 0.0 Maximum Instr Range: 30000 Zero Point

Reference:

N/A Reference Point Notes: Ni A PROC or SENS: S Number of Sensors:

How Processed: N/A Sensor Locations: Reference Unique System Description Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode: Eigh, Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: Flow sensed by a flow element in the RHR distribution piping downstream of the RHR heat exchanger.

CSD-ER-005 Revision 4 Page 35 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQl/SQ2 Data Feeder: N/A NRC ERDS Parameter: LPCI FLOW Point ID: -"F 02 Plant Spec Point Desc.: R.R SYS B FLOW Generic/Cond Desc.: Low Press Coolant Inject B Flow Analog/Digital: A Engr Units/Dig States: GPM Engr Units Conversion: N/A Minimum Instr Range: 0.0 Maximum Instr Range: 30000 Zero Point

Reference:

N /A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed:

Sensor Locations: Reference Unique System Desc.

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode: High, Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc. Flow sensed by a flow element in the RHR distribution piping downstream of the RHR heat exchanger.

CSD-ER-005 Revision 4 Page 36 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQt/SQ2 Data Feeder: N/A NRC ERDS Parameter: CR SPRAY FL Point ID: LPCS Plant Spec Point Desc.: TO7AL CORE SPRAY FLOW Generic/Cond Desc.: Core Spray Cooling System Flow Analog/Digital: A Engr Units/Dig States: GPM Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: 10.000 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 2 How Processed: Sum (Reference Unique System Desc.)

Sensor Locations: Reference Unique System Descriptionl Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: Ni/A NI Detector Pcwer Supply Turn-on Power Level: N/A Instrument Failure Mode: High, Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: A Supplier proprietary algorithm calculates LPCS as the sum of the CS Loop A and Loop B flows. The algorithm utilizes the position of the CS Test Isolation Valve as well as drywell pressure, reactor vessel pressure, and reactor water level in the selection and validation of each loop's flow.

The algorithm selects a value for flow for each loop from either the measured loop flow or the calculated loop flow (based on loop pressure and pump-head performance curve) depending on the algorithm logic table.

ý' -Downstream of Pump A & C (Loop A) Discharge connection and Pump B & D Loop B) Discharge connection.

Note: LPCS is a composite SPDS parameter with the following points as inputs: NSF001Z, NSF002Z, NSP001Z, and NSP002Z.

CSD-ER-005 Revision 4 Page 37 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N A NRC ERDS Parameter: DW FD SMP LV Point ID: RLL004Z Plant Spec Point Desc.: A DRWL SUMP LEVEL Generic/Cond Desc.: Drvwell Floor Drain Sump Level A Analog/Digital: A Engr Units/Dig States:

Each 1W ý 1 Gallon(l)

Engr Units Conversion:

1%

Minimum Instr Range:

Maximum Instr Range:

Zero Point

Reference:

BTESUMP = Bottom of Sump 2

Reference Point Notes: Reference Unique System Desc.) :

PROC or SENS: S Number of Sensors: 1 How Processed: N, A Sensor Locations: Lr-.-.jell1 Floor Drain Elev. 704' Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level: N;A instrument Failure Mode:

Temperature Compensation For DP Transmitters: N,A Level Reference Leg: N /A Unique System Desc.: - Instrumentation output is level switch driven, each step is approximately 15 gals.

Input referenced to bottom of sump. Actual instrument zero is .25" below input reference point.

Uzon containment isolation output of sump is also isolated.

CSD-ER-005 Revision 4 Page 38 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQl/SQ2 Data Feeder: N/A NRC ERDS Parameter: LW FD SMP LV Point ID: RLL005Z Plant Spec Point Desc. B DRWL SUMP LEVEL Generic/Cond Desc.: Drywell Floor Drain Sump Level B Analog/Digital: A Engr Units/Dig States:

Engr Units Conversion: Each 1% , 1.2 Gallon for SQl(")

Each 1% ý 1 Gallon for SQ2 Minimum Instr Range: 37.5 Maximum Instr Range: 100 Zero Point

Reference:

BSUMP = Bottom of Sump Reference Point Notes: Reference Unique System Desc.(2)

PROC or SENS: S Number of Sensors:

How Processed: N/A Sensor Locations: Dr)-well Floor Drain Elev. 704' Alarm/Trip Set Points: N /A NI Detector Power Supply Cut-off Power Level: NiA NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: - Instrumentation output is level switch driven, each step is approximately 16 gals for Unit 1 (SQl) and 15 gals for Unit 2 (SQ2).

Input referenced to bottom of sump. Actual instrument zero is .25" below input reference point.

Upon containment isolation output of sump is also isolated.

CSD-ER-005 Revision 4 Page 39 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQl/SQ2 Data Feeder: N/A NRC ERDS Parameter: EFF GAS RAD Point ID: EGRNRX1 Plant Spec Point Desc.: RAD OF RELEASED NBLGAS-RX 1 VENT Generic/Cond Desc.: Rad of Released NBLGAS-Rx 1 Vent Analog/Digital: A Engr Units/Dig States: uCI/Min Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: N/A Zero Point

Reference:

N'/A Reference Point Notes: N/A PROC or SENS:

Number of Sensors:

How Processed: Average Sensor Locations: Reference Unique System Desc.ý"

Alarm/Trip Set Points: N/A NI Detector Power Supply Cu:-off Power Level:

NI Detector Power Supply Turn-on Power Level: NiA Instrument Failure Mode: Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: NIA Unique System Desc.: The Eberline Control Terminal provides 1 min averages for the Noble Gas release component. EGRNRX1 is created by averaging the properly selected Noble Gas range (low, mid or high) 1 min average releases for a 15 min period. EGRNRX1 is updated each quarter hour (i.e. it is not a sliding 15 min average). Therefore, the same value of EGRNRX1 will be transmitted each minute for a given fifteen minute period until the next update is available.

" - Isokinetic sample drawn @ Rx Bldg vent near Rx Bldg roof.

CSD-ER-005 Revision 4 Page 40 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQI/SQ2 Data Feeder: N/A NRC ERDS Parameter: EFF GAS RAD Point ID: EGRPRXl Plant Spec Point Desc.: RAD OF RELEASED PART -RX 1 VENT Generic/Cond Desc.: Rad of Released PART -Rx 1 Vent Analog/Digital: A Engr Units/Dig States: uCI/Min Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: N/A Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 1 How Processed: Average Sensor Locations: Reference Unique System Desc.('

Alarm/Trip Set Points: N,/A NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level: NiA Instrument Failure Mode: Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg:

Unique System Desc.: The Eberline Control Terminal provides 1 min averages for the Beta Particulate release component. EGRPRX1 is created by averaging the

! min average releases for a 15 min period. EGRPRX1 is updated each Quarter hour (i.e. it is not a sliding 15 min average). Therefore, the same value of EGRPRX1 will be transmitted each minute for a given fifteen minute period until the next update is available.

- - Isokinetic sample drawn @ Rx Bldg vent near Rx Bldg roof.

CSD-ER-005 Revision 4 Page 41 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQl/SQ2 Data Feeder: N/A NRC ERDS Parameter: EFF GAS RAD Point ID: EGRIRXl Plant Spec Point Desc.: RAD OF RELEASED 1131 -RX 1 VENT Generic/Cond Desc.: Rad of Released 1131 -Rx 1 Vent Analog/Digital: A Engr Units/Dig States: uCI/Min Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: N/A Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors:

How Processed: Average 1

Sensor Locations: Reference Unique System Desc.( 1 Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: The Eberline Control Terminal provides 1 min averages for the 1131 release component. EGRIP.X1 is created by averaging the 1 min average releases for a 15 min period. EGRIRX1 is updated each quarter hour (i.e. it is not a sliding 15 min average). Therefore, the same value of EGRIRXI will be transmitted each minute for a given fifteen minute period until the next update is available.

- Isokinetic sample drawn @ Rx Bldg vent near Rx Bldg roof.

CSD-ER-005 Revision 4 Page 42 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: C 5/13/98 Reactor Unit: SQI/SQ2 Data Feeder: N/A NRC ERDS Parameter: EFF GAS RAD Point ID: EGRNTBl Plant Spec Point Desc.: R_-LDOF RELEASED NBLGAS-TB 1 VENT Generic/Cond :esc.: Rad of Released NBLGAS-TB 1 Vent Analog/Digital: A Engr Units/Dir States: uCI/Min Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: N,/A Zero Point

Reference:

>,7A Reference Poin: Notes: N, A PROC or SENS: p Number of Sensors: 1 How Processed: Ave rage Sensor Locatizns: Reference Unique System Desc.ý '

Alarm/Trip Se: Points: NA NI Detector P::er Supply Cut-off Power Level:

N, NI Detector Poer Supply Turn-on Power Level:

Instrument Failure Mode: Low Temperature Compensation For DP Transmitzers: N/A Level Reference Leg: N!'.A Unique System Zesc.: The Eberline Control Te-rinal provides 1 min averages for the Noble Gas re-ease component. EGRN-BE is created by averaging the properly selected Noble Gas range (low, mid or high) 1 min average releases for a 15 min period. EGRNTB1 is updated each quarter hour (i.e. it is not a sliding 15 min average) . Therefore, the same value of EGRNTB1 will be transmitted each minute for a given fifteen minute period until the next update is available.

S- Isokinetic sample draA-n 9 Turbine Bldg vent near Rx Bldg roof.

CSD-ER-005 Revision 4 Page 43 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 0z/13/98 Reactor Unit: SzQ!/SQ2 Data Feeder: N 'A NRC ERDS Parameter: EFF GAS RAD Point ID: EZRPTB1 Plant Spec Point Desc.: PAD OF RELEASED PART -TB 1 VENT Generic/Cond Desc.: Pad of Released PART -TB 1 Vent Analog/Digital: A.

Engr Units/Dig States: uCi /Min Engr Units Conversion: N iA Minimum Instr Range: 0 Maximum Instr Range:

Zero Point

Reference:

N A Reference Point Notes: N A PROC or SENS:

Number of Sensors:

How Processed: Average Sensor Locations: Reference Unique System Desc.U1)

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level: NA NI Detector cwer Supply Turn-on Power Level:

Instrument Failure Mode:

Temperature Ccmpensation For DP Transmitters:

Level Reference Leg:

Unique Systen Desc.: -he Eberline Control Terminal provides 1 min averages for the Beta PZarziculate release component. EGRPTB1 is created by averaging the

! =in average releases for a 15 min period. EGRPTBI is updated each a:arter hour (i.e. it is not a sliding 15 min average). Therefore,

-e same value of EGRPTB1 will be transmitted each minute for a given 0--teen minute period until the next update is available.

- Isokinetic sample drawn @ Turbine Bldg vent near Rx Bldg roof.

CSD-ER-005 Revision 4 Page 44 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQl/SQ2 Data Feeder: N/A NRC ERDS Parameter: EFF GAS RAD Point ID: EGRITB1 Plant Spec Point Desc.: RAD OF RELEASED 1131 -TB 1 VENT Generic/Cond Desc.: Rad of Released 1131 -TB 1 Vent Analog/Digital: A Engr Units/Dig States: uCI/Min Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: N/A Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS:

Number of Sensors:

How Processed: Average Sensor Locations: Reference Unique System Desc.(i)

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low Temperature Compensation For DP Transmitters:

Ž7/A Level Reference Leg:

Unique System Desc.: :he Eberline Control Terminal provides 1 min averages for the 1131 release component. EGRITBI is created by averaging the 1 min average releases for a 15 min period. EGRITBI is updated each quarter hour (i.e. it is not a sliding 15 min average). Therefore, the same value of EGRITBI will be transmitted each minute for a given fifteen minute period until the next update is available.

- Isokinetic sample drawn @ Turbine Bldg vent near Rx Bldg roof.

CSD-ER-005 Revision 4 Page 45 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05-/13/98 Reactor Unit: SQI/SQ2 Data Feeder: N A NRC ERDS Parameter: EFF GAS RAD Point ID: EGRNSGTS Plant Spec Point Desc.: R-_D OF RELEASED NBLGAS-SGTS VENT Generic/Cond Desc.: Rad of Released NBLGAS-SGTS Vent Analog/Digital: A Engr Units/Dig States: uC!/Min Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: N,A Zero Point

Reference:

N;A Reference Point Notes: NA PROC or SENS:

Number of Sensors:

How Processed: A-,-erage Sensor Locations: Reference Unique System Desc.

Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level: N,A NI Detector Power Supply Turn-on Power Level: NA Instrument Failure Mode:

Temperature Compensation For DP Transmitters: N/ A Level Reference Leg: NA Unique System Desc.: The Eberline Control Terminal provides 1 min averages for the Noble Gas renease component. EGRNSGTS is created by averaging the properly selected Noble Gas range (low, mid or high) 1 min average releases for a 15 min period. EGRNSGTS is updated each quarter hour (i.e. it is not a sliding 15 min average). Therefore, the same value of EGRNSGTS will be traznsmitted each minute for a given fifteen minute period until the next undate is available.

- Isokinetic sample drawn 9 SGTS vent near Rx Bldg roof.

CSD-ER-005 Revision 4 Page 46 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: C5/13/98 Reactor Unit: SQI/SQ2 Data Feeder: N/A NRC ERDS Parameter: EFF GAS RAD Point ID: EGRPSGTS Plant Spec Point Desc.: RAD OF RELEASED PART -SGTS VENT Generic/Cond Desc.: Rad of Released PART -SGTS Vent Analog/Digital: A Engr Units/Dig States: uCI/Min Engr Units Conversion: NiA Minimum Instr Range: 0 Maximum Instr Range: "NiA Zero Point

Reference:

N 'A Reference Point Notes: NiA PROC or SENS:

Number of Sensors:

How Processed: Average Sensor Locations: Reference Unique System Desc.i Alarm/Trip Set Points:

N 'A NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode: Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: The Eberline Control Terminal provides 1 min averages for the Beta Particulate release comnonent. EGRPSGTS is created by averaging the 1 mn average releases for a 15 min period. EGRPSGTS is updated each csarter hour (i.e. it is not a sliding 15 min average). Therefore, the same value of EGRPSGTS will be transmitted each minute for a given fifteen minute period until the next update is available.

- - Isokinetic sample drawn @ SGTS vent near Rx Bldg roof.

CSD-ER-005 Revision 4 Page 47 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQL /SQ2 Data Feeder: N/A NRC ERDS Parameter: EFF GAS RAD Point ID: EC?.ISGTS Plant Spec Point Desc.: RAD OF RELEASED 1131 -SGTS VENT Generic/Cond Desc.: Rad of Released 1131 -SGTS Vent Analog/Digital: A Engr Units/Dig States: uC /Min Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: NIA Zero Point

Reference:

NiA N; A Reference Point Notes:

PROC or SENS: P Number of Sensors: 1 How Processed: Arage Sensor Locations: Reference Unique System Desc."

Alarm/Trip Set Points: NA NI Detector Power Supply Cut-off Power Level:

N.A NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode: Low Temperature Compensation For DP Transmitters:

N/A Level Reference Leg:

Unique System Desc.: The Eberline Control Terminal provides 1 min averages for the 1131 release ccr.ponent. EGRISGTS is created by averaging the 1 min average releases fcr a 15 min period. EGRISGTS is updated each quarter hour (i.e. it is nct a sliding 15 min average) . Therefore, the same value of EGRISGTS will be transmitted each minute for a given fifteen minute period until the next update is available.

"- Isokinetic sample drawn @ SGTS vent near Rx Bldg roof.

CSD-ER-005 Revision 4 Page 48 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: EFF GAS RAD Point ID: EGRNRX2 Plant Spec Point Desc.: RAD OF RELEASED NBLGAS-RX 2 VENT Generic/Cond Desc.: Rad of Released NBLGAS-Rx 2 Vent Analog/Digital: A Engr Units/Dig States: uCI/Min Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: N/A Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 1 How Processed: Average Sensor Locations: Reference Unique System Desc."

Alarm/Trip Se: Points: N/A NI Detector Pcwer Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: The Eberline Control Terminal provides 1 min averages for the Noble Gas release component. EGRNRX2 is created by averaging the properly selected Noble Gas range (low, mid or high) 1 min average releases for a fifteen min period. EGRNRX2 is updated each quarter hour (i.e. it is not a sliding 15 min average). Therefore, the same value of EGRNRX2 will be transmitted each minute for a given fifteen minute period until the next update is available.

- - Isokinetic sample drawn @ Rx Bldg vent near Rx Bldg roof.

CSD-ER-005 Revision 4 Page 49 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQI/SQ2 Data Feeder: N/A NRC ERDS Parameter: EFF GAS RAD Point ID: EGRPRX2 Plant Spec Point Desc.: RAD OF RELEASED PART -RX 2 VENT Generic/Cond Desc.: Rad of Released PART -Rx 2 Vent Analog/Digital: A Engr Units/Dig States: uCI/Min Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: N/A Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 1 How Processed: Average Sensor Locations: Reference Unique System Desc.ýI)

Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: 4/A Instrument Failure Mode: Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: The Eberline Control Terminal provides 1 min averages for the Beta Particulate release component. EGRPRX2 is created by averaging the 1 min average releases for a 15 min period. EGRPRX2 is updated each quarter hour (i.e. it is not a sliding 15 min average). Therefore, the same value of EGRPRX2 will be transmitted each minute for a given fifteen minute period until the next update is available.

1- Isokinetic sample drawn @ Rx Bldg vent near Rx Bldg roof.

CSD-ER-005 Revision 4 Page 50 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQl/SQ2 Data Feeder: N/A NRC ERDS Parameter: EFF GAS RAD Point ID: EGRIRX2 Plant Spec Point Desc.: RAD OF RELEASED 1131 -RX 2 VENT Generic/Cond Desc.: Rad of Released 1131 -Rx 2 Vent Analog/Digital: A Engr Units/Dig States: uCI/Min Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: N/A Zero Point

Reference:

N!A Reference Point Notes:

PROC or SENS:

Number of Sensors:

How Processed: Average Sensor Locations: Reference Unique System Desc.('

N.i Alarm/Trip Set Points:

NI Detector Power Supply Cut-off Power Level: N!'A NI Detector Pcwer Supply Turn-on Power Level:

Instrument Failure Mode: Low Temperature Compensation N/A For DP Transmitters:

Level Reference Leg: NiA Unique System Desc.: The Eberline Control Terminal provides 1 min averages for the 1131 release component. EGRIRX2 is created by averaging the 1 min average releases for a 15-min period. EGRIRX2 is updated each quarter hour (i.e.

iz is not a sliding 15 min average). Therefore, the same value of EGRIRX2 will be transmitted each minute for a given fifteen minute period until the next update is available.

- Isokinetic sample drawn @ Rx Bldg vent near Rx Bldg roof.

CSD-ER-005 Revision 4 Page 51 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQI/SQ2 Data Feeder: N/A NRC ERDS Parameter: EFF GAS RAD Point ID: EG.RNTB2 Plant Spec Point Desc.: R*n OF RELEASED NBLGAS-TB 2 VENT Generic/Cond Desc.: Rad of Released NBLGAS-TB 2 Vent Analog/Digital: A Engr Units/Dig States: uCI/Min Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: N/A Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 1 How Processed: Average Sensor Locations: Reference Unique System Desc.Y Alarm/Trip Set Points: N /A NI Detector Pzwer Supply Cut-off Power Level: Ni A NI Detector Pzwer Supply N ,'A Turn-on Power Level: N/.:

Instrument Failure Mode: Low Temperature Ccnpensation For DP Transmi:ters: N/A Level Reference Leg: N/A Unique System Lesc.: The Eberline Control Terminal provides 1 min averages for the Noble Gas release component. EGRNTB2 is created by averaging the properly selected Noble Gas range (low, mid or high) 1 min average releases for a 15 min period. EGRNTB2 is updated each quarter hour (i.e. it is not a sliding 15 min average). Therefore, the same value of EGRNTB2 will be transmitted each minute for a given fifteen minute period until the next update is available.

- Isokinetic sample drawn @ Turbine Bldg vent near Rx Bldg roof.

CSD-ER-005 Revision 4 Page 52 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQl/SQ2 Data Feeder: N/A NRC ERDS Parameter: EFF GAS RAD Point ID: EGRPTB2 Plant Spec Point Desc.: RAD OF RELEASED PART -TB 2 VENT Generic/Cond Desc.: Rad of Released PART -TB 2 Vent Analog/Digital: A Engr Units/Dig States: uCI/Min Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: N/A Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 1 How Processed: Average Sensor Locations: Reference Unique System Desc.)

Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply" Turn-on Power Level: N/A Instrument Failure Mode: Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: The Eberline Control Terminal provides 1 min averages for the Beta Particulate release component. EGRPTB2 is created by averaging the 1 min average releases for a 15 min period. EGRPTB2 is updated each quarter hour (i.e. it is not a sliding 15 min average). Therefore, the same value of EGRPTB2 will be transmitted each minute for a given fifteen minute period until the next update is available.

1 _ Isokinetic sample drawn @ Turbine Bldg vent near Rx Bldg roof.

CSD-ER-005 Revision 4 Page 53 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: EFF GAS RAD Point ID: EZRITB2 Plant Spec Point Desc.: RAD OF RELEASED 1131 -TB 2 VENT Generic/Cond Desc.: Rad of Released 1131 -TB 2 Vent Analog/Digital: A Engr Units/Dig States: uCI/Min Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: N/A Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors:

How Processed: Average 1

Sensor Locations: Reference Unique System Desc.( )

Alarm/Trip Set Points: N 'A NI Detector Power Supply Cut-off Power Level: N" A NI Detector Power Supply Turn-on Power Level:

Instrument Failure Mode: Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: The Eberline Control Terminal provides 1 min averages for the 1131 release component. EGRITB2 is created by averaging the 1 min average releases for a 15 min period. EGRITB2 is updated each quarter hour (i.e. it is not a sliding 15 min average). Therefore, the same value of EGRITB2 will be transmitted each minute for a given fifteen minute period until the next update is available.

" - Isokinetic sample drawn S Turbine Bldg vent near Rx Bldg roof.

CSD-ER-005 Revision 4 Page 54 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQl/SQ2 Data Feeder: N/A NRC ERDS Parameter: EEF GAS RAD Point ID: EGRNSITE Plant Spec Point Desc.: RAD OF RELEASED NBLGAS-SITE TOTL Generic/Cond Desc.: Rad of Released NBLGAS-Site Totl Analog/Digital: A Engr Units/Dig States: uCI/Min Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: N/A Zero Point

Reference:

N/A Reference Point Notes: Ni A PROC or SENS: P Number of Sensors: 5 How Processed: Reference Unique System Desc.

Sensor Locations: N/A Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level:

NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: N/A Temperature Compensation For DP Transmitters: N/A Level Reference Leg: NiA Unique System Desc.: A Site Total 1 min average for the Noble Gas release component is created by summing the Noble Gas 1 min averages of the Rx 1, TB 1, SGTS, Rx 2 and TB 2 vents. EGRNSITE is created by averaging the Site Total 1 min averages for a 15 min period. EGRNSITE is updated each quarter hour (i.e. it is not a sliding 15 min average). Therefore, the same value for EGRNSITE will be transmitted each minute for a given fifteen minute period until the next update is available.

CSD-ER-005 Revision 4 Page 55 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQl/SQ2 Data Feeder: N/A NRC ERDS Parameter: EFF GAS RAD Point ID: EGRPSITE Plant Spec Point Desc.: RAD OF RELEASED PART -SITE TOTL Generic/Cond Desc.: Rad of Released PART -Site Totl Analog/Digital: A Engr Units/Dig States: uCI/Min Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: N/A Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 5 How Processed: Reference Unique System Desc.

Sensor Locations: N/A Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: N/A Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: A Site Total 1 min average for the Beta Particulate release component is created by summing the Beta Particulate 1 min averages of the Rx 1, TB 1, SGTS, Rx 2 and TB 2 vents. EGRPSITE is created by averaging the Site Total 1 min averages for a 15 min period. EGRPSITE is updated each quarter hour (i.e. it is not a sliding 15 min average). Therefore, the same value for EGRPSITE will be transmitted each minute for a given fifteen minute period until the next update is available.

CSD-ER-005 Revision 4 Page 56 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQl/SQ2 Data Feeder: N/A NRC ERDS Parameter: EFF GAS RAD Point ID: EGRISITE Plant Spec Point Desc.: RAD OF RELEASED 1131 -SITE TOTL Generic/Cond Desc.: Rad of Released 1131 -Site Totl Analog/Digital: A Engr Units/Dig States: uCI/Min Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: N/A Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 5 How Processed: Reference Unique System Desc.

Sensor Locations: NiA Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: N/A Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: A Site Total 1 min average for the 1131 release component is created by summing the 113! 1 min averages of the Rx 1, TB 1, SGTS, Rx 2 and TB 2 vents. EGRISITE is created by averaging the Site Total 1 min averages for a 15-min period. EGRISITE is updated each quarter hour (i.e. it is not a sliding 15-min average). Therefore, the same value for EGRISITE will be transmitted each minute for a given fifteen minute period until the next update is available.

CSD-ER-005 Revision 4 Page 57 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQI/SQ2 Data Feeder: N/A NRC ERDS Parameter: EFF LIQ RAD Point ID: VZR001Z Plant Spec Point Desc.: LRW DSCH RAD MON Generic/Cond Desc.: Radioactivity of Released Liqlds Analog/Digital: A Engr Units/Dig States: CPM Engr Units Conversion: N/A Minimum Instr Range: 10 Maximum Instr Range: NE6 Zero Point

Reference:

N/A Reference Point Notes: NIA PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: Ref. Unique System Desc.(1>

Alarm/Trip Set Points: Varies - Ref. Unique System Desc.)2)

NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: NIA Instrument Failure Mode: Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: SSample drawn from LRW discharge pipe prior to release to environment.

The Liquid Radwaste Effluent Monitor is a microprocessor based NMC Licuid Radiation Monitor. A single gamma scintillation detector is exposed to the sample of the discharge stream. Discharge is governed bv Radiation Effluent release permit.

Detector alarm settings are determined for each release based upon tank activity & background values at the sample unit.

CSD-ER-005 Revision 4 Page 58 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: Not Listed Point ID: VDF001Z Plant Spec Point Desc.: LRW DISCHARGE FLOW Generic/Cond Desc.: LRW Discharge Flow Analog/Digital: A Engr Units/Dig States: GPM Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: 100 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A 1

Sensor Locaticns: Reference Unique System Desc.i )

Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A On Liquid Radwaste discharge line prior to environment. The liquid Unique System Desc.:

radwaste line discharges into the Cooling tower discharge pipe. The cooling tower discharge pipe goes to the Susquehanna River.

CSD-ER-005 Revision 4 Page 59 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQl/SQ2 Data Feeder: N/A NRC ERDS Parameter: DW RAD Point ID: PCA Plant Spec Point Desc.: PRIMARY CONTAINMENT ACTIVITY Generic/Cond Desc.: Radiation Level in the Drywell Analog/Digital: A Engr Units/Dig States: R/HR Engr Units Conversion: N/A Minimum Instr Range: 1 Maximum Instr Range: 1E8 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 2 How Processed: Average (ref. Unique System Desc.)

Sensor Locations: Dr-vwell on Bioshield Wall Alarm/Trip Set Points: Alarm 400 R/HR and 2000 R/HR NI Detector Power Supply Cut-off Power Level: NIA NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: A Supplier proprietary algorithm selects the point with the higher value if the difference between the two points exceeds a predefined delta.

Note: PCA is a composite SPDS parameter with the following points as inputs: MAR001Z and MAR002Z.

CSD-ER-005 Revision 4 Page 60 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQI/SQ2 Data Feeder: N/A NRC ERDS Parameter: MN STEAM RAD Point ID: NAR01 Plant Spec Point Desc.: MAIN STEAM LINE RAD A Generic/Cond Desc.: Radiation Lvl of Main Stm Line A Analog/Digital: A Engr Units/Dig States: MR/H Engr Units Conversion: N/A Minimum Instr Range: 1.000 Maximum Instr Range: 1.0E6 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A 11 Sensor Locations: Reference Unique System Desc.(

Alarm/Trip Set Points: 7 times Background at Full Power NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: Standard BWR Main Steam Line Radiation Monitoring design and configuration.

- - The detectors (A-D) are located in the steam tunnel as close as practical to the containment. The detectors are arranged such that each detector will view all steam lines with approximately the same response.

CSD-ER-005 Revision 4 Page 61 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ!/SQ2 Data Feeder: N/A NRC ERDS Parameter: MN STEAM RAD Point ID: NAR02 Plant Spec Point Desc.: MAIN STEAM LINE RAD B Generic/Cond Desc.: Radiation Lvl of Main Stm Line B Analog/Digital: A Engr Units/Dig States: MR/H Engr Units Conversion: N/A Minimum Instr Range: 1.000 Maximum Instr Range: 1.0E6 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 "How Processed: N/A Sensor Locations: Reference Unique System Desc.i' Alarm/Trip Set Points: 7 times Background at Full Power NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: Standard BWR Main Steam Line Radiation Monitoring design and configuration.

'i - The detectors (A-D) are located in the steam tunnel as close as practical to the containment. The detectors are arranged such that each detector will view all steam lines with approximately the same response.

CSD-ER-005 Revision 4 Page 62 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE N-Date: 05/13/98 Reactor Unit: SQl/SQ2 Data Feeder: N/A NRC ERDS Parameter: M-N STEAM RAD Point ID: NAR0 3 Plant Spec Point Desc.: MAIN STEAM LINE RAD C Generic/Cond Desc.: Radiation Lvl of Main Stm Line C Analog/Digital: A Engr Units/Dig States: MR/H Engr Units Conversion: N/A Minimum Instr Range: 1.000 Maximum Instr Range: 1.0E6 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: Reference Unique System Desc.t Alarm/Trip Set Points: 7 times Background at Full Power NI Detector Power Supply Cut-off Power Level: NA NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: Standard BWR Main Steam Line Radiation Monitoring design and cocnfiguration.

1" - The detectors (A-D) are located in the steam tunnel as close as practical to the containment. The detectors are arranged such that each detector will view all steam lines with approximately the same response.

CSD-ER-005 Revision 4 Page 63 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ!/SQ2 Data Feeder: N/A NRC ERDS Parameter: W% STEAM RAD Point ID: A-0 4 Plant Spec Point Desc.: MAIN STEAM LINE RAD D Generic/Cond Desc.: Radiation Lvl of Main Stm Line D Analog/Digital: A Engr Units/Dig States: f'R/H Engr Units Conversion: N/A Minimum Instr Range: 1.000 Maximum Instr Range: 1. 0E6 Zero Point

Reference:

N.'A Reference Point Notes: N, A PROC or SENS: S Number of Sensors:  !

How Processed: N, A Sensor Locations: 1 Reference Unique System Desc. )

Alarm/Trip Set Points: 7 times Background at Full Power NI Detector Power Supply Cut-off Power Level: N, A NI Detector Power Supply Turn-on Power Level: N; A Instrument Failure Mode: Lcw Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N,'A Unique System Desc.: Standard BWR Main Steam Line Radiation Monitoring design and ccnfiguration.

- The detectors (A-D) are located in the steam tunnel as close as practical to the containment. The detectors are arranged such that each detector will view all steam lines with approximately the same response.

CSD-ER-005 Revision 4 Page 64 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: o5/13/98 Reactor Unit: SQl/SQ2 Data Feeder: N/A NRC ERDS Parameter: DW PRESS Point ID: DWPR Plant Spec Point Desc.: DRYWELL PRESSURE Generic/Cond Desc.: Drywell Pressure Analog/Digital: A Engr Units/Dig States: PSIG Engr Units Conversion: N/A Minimum Instr Range: -15.0 Maximum Instr Range: 250.0 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 5 How Processed: Reference Unique System Desc.

Sensor Locations: Reactor Bldg. Elevation 719' Alarm/Trip Se: Points: Trip @ 1.72 PSIG NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: High, Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: A Supplier proprietary algorithm selects the value for DWPR by using up to five inputs, one Narrow Range (NR) signal (-3.0 to +3.0 PSIG), two Intermediate Range (IR) signals (-15.0 to +65.0 PSIG), and two Wide Range (WR) signals (0 to -250.0 PSIG) . If the NR signal is onscale then it is selcted for DWPR. If the NR signal is invalid and the IR signal(s) are onscale then they are utilized for DWPR. If both NR and IR signals are invalid then the WR signals will be utilized for DWPR.

Note: DWPR is a composite SPDS parameter with the following points as inputs: MAP001Z, MAP003Z, MAP004Z, MAP005Z, and MAP006Z.

CSD-ER-005 Revision 4 Page 65 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQl/SQ2 Data Feeder: N/A NRC ERDS Parameter: DW TEMP Point ID:

Plant Spec Point Desc.: DRYWELL TEMPERATURE Generic/Cond Desc.: Drywell Temperature Analog/Digital: A Engr Units/Dig States: DEGF Engr Units Conversion: N/A Minimum Instr Range: 40 Maximum Instr Range: 440 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 8 How Processed: A-.-erage (Reference Unique System Desc.)

Sensor Locations: Reference Unique System Desc.

Alarm/Trip Set Points: Alarm 135'F NI Detector Power Supply Cut-off Power Level: N, A NI Detector Power Supply Turn-on Power Level: N, A Instrument Failure Mode: Hig=h, Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: A Supplier proprietary algorithm uses the Technical Specification met-hod for calculating dry-dell average air temperature which selects the higher valid signal from a minimum of 3 of the following drywell areas: top, middle, bottom and pedestal. DWT is then calculated as the average of the 3 or 4 valid signals selected. If there is less than 3 t-alid signals then the algorithm cannot calculate an average value.

Sensor Locations (elevation, azimuth) : (79718", 2950) , (797' 8",1100),

(752' 2",2700), (752' 20,900), (737',300o), (7371,1500), (7111,2700),

(720 ,850)

Note: DWT is a composite SPDS parameter with the following points as inputs: MAT001Z, MAT002Z, MAT003Z, MAT004Z, MAT005Z, MAT006Z, MAT007Z, and MAT008Z.

CSD-ER-005 Revision 4 Page 66 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ!/SQ2 Data Feeder: N/A NRC ERDS Parameter: SP TEMP Point ID: SPT Plant Spec Point Desc.: SUPPRESSION POOL TEMPERATURE Generic/Cond Desc.: Suppression Pool Temperature Analog/Digital: A Engr Units/Dig States: DEGF Engr Units Conversion: N/A Minimum Instr Range: 30 Maximum Instr Range: 230 Zero Point

Reference:

N 'A Reference Point Notes: N:'A PROC or SENS: P Number of Sensors: 2 How Processed: Average Sensor Locations: Reference Unique System Desc.

Alarm/Trip Set Points: Alarm at 90'F, 105'F, 11 0 'F & 120'F NI Detector Power Supply Cut-off Power Level: N A NI Detector Power Supply Turn-on Power Level: N'A Instrument Failure Mode: Lcw, High Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: A Supplier proprietary algorithm calculates SPT as the average of the two inputs if they are valid and agree, otherwise the higher of the two signals is selected. Each of the inputs to the algorithm is provided by a Suppression Pool Temperature Monitoring System (SPOTMOS). The SPDTMOS unit uses up to 8 temperature inputs to calculate the average temperature. The RTD inputs to SPOTMOS that are used to calculate the average temperature are located at appoximately the 21 foot level in the suppression pool.

Note: SPT is a composite SPDS parameter with the following points as inputs: MAT012Z and MAT013Z.

CSD-ER-005 Revision 4 Page 67 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQl/SQ2 Data Feeder: N/A NRC ERDS Parameter: SP LEVEL Point ID: SPWL Plant Spec Point Desc.: SUPPRESSION POOL WATER LEVEL Generic/Cond Desc.: Suppression Pool Water Level Analog/Digital: A Engr Units/Dig States: FEET Engr Units Conversion: N/A Minimum Instr Range: 4.5 Maximum Instr Range: 49 Zero Point

Reference:

TNKBOT Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 4 How Processed: Reference Unique System Desc.

Sensor Locations: Rx Bldg Elev. 645' Alarm/Trip Set Points: High Ž> 23.75 ft, Low < 22.25 ft NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low, High Temperature Compensation For DP Transmitters: N/A Level Reference Leg: Wet Unique System Desc.: A Supplier proprietary algorithm uses 2 Narrow Range (NR), 18-26.5 ft, and 2 Wide Range (WR), 4.5-49 ft, signals to arrive at a value for SPWL.

The NR signals are given preference over the WR signals. In cases in which NR signals do not agree and are not confirmed by WR signals, a signal (or average of signals) with greater deviation from Normal Water Level (NWL), measured at 23 ft, is used because it is a critical safety concern. A WR signal (or average of WR signals) may be chosen over a NR signal if it is verified as having a greater deviated value from the NWL than the NR signal.

Note: SPWL is a composite SPDS parameter with the following points as inputs: MAL001Z, MAL002Z, MAL003Z, and MAL004Z.

CSD-ER-005 Revision 4 Page 68 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQI/SQ2 Data Feeder: N/A NRC ERDS Parameter: H2 CONC Point ID: HYDGN Plant Spec Point Desc.: CONTNMNT. HYDROGEN CONCENTRATION Generic/Cond Desc.: Drywell Hydrogen Concentration Analog/Digital: A Engr Units/Dig States:

Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: 30 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 2 How Processed: Average (ref. Unique System Desc.)

1 Sensor Locations: Reference Unique System Desc.i )

Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low, High Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: Each of the inputs has dual range capability and will have a range of 0-10% or 0-30%. A Supplier proprietary algorithm will calculate HYDGN as the average of the two inputs if they are both on the same range and agree. Any other combination of valid points (e.g. points disagree, are on different ranges, only one on-scale) will cause the algorithm to select only one of the two inputs for the value of HYDGN.

'i-_ Sample drawn from drywell or suppression chamber and measured at Panel 1C226A & B for SQl and 2C226A & B for SQ2, Reactor Building Elev. 719'.

Note: HYDGN is a composite SPDS parameter with the following points as inputs: MAC003Z and MAC004Z.

CSD-ER-005 Revision 4 Page 69 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQl/SQ2 Data Feeder: N/A NRC ERDS Parameter: 02 CONC Point ID: OXYGN Plant Spec Point Desc.: CONTNMNT. OXYGEN CONCENTRATION Generic/Cond Desc.: Drywell Oxygen Concentration Analog/Digital: A Engr Units/Dig States:

Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: 25 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 2 How Processed: Average (ref. Unique System Desc.)

Sensor Locations: Reference Unique System Desc.(1e Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N, A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low, High Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: Each of the inputs has dual range capability and will have a range of 0-10% or 0-25%. A Supplier proprietary algorithm will calculate OXYGN as the average of the two inputs if they are both on the same range and agree. Any other combination of valid points (e.g. points disagree, are on different ranges, only one on-scale) will cause the algorithm to select only one of the two inputs for the value of OXYGN.

- Sample drawn from drwaell or suppression chamber and measured at Panel IC226A & B for SQl and 2C226A & B for SQ2, Reactor Building Elev. 719'.

Note: OXYGN is a composite SPDS parameter with the following points as inputs: MAC001Z and MAC002Z.

CSD-ER-005 Revision 4 Page 70 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQl/SQ2 Data Feeder: N/A NRC ERDS Parameter: CST LEVEL Point ID: CSL01 Plant Spec Point Desc.: COND STORAGE TANK 1 LVL Generic/Cond Desc.: Condensate Storage Tank 1 Level Analog/Digital: A Engr Units/Dig States:

Engr Units Conversion: Each 1% ý 3,000 Gallons Minimum Instr Range: 0.0 Maximum Instr Range: 100.0 Zero Point

Reference:

TNKBOT Reference Point Notes: Zero is 13.5 inches above tank bottom PROC or SENS: S Number of Sensors:

How Processed: N/A Sensor Locations: 7.5 inches below zero reference Alarm/Trip Set Points: Low level at 0% (ref. Unique System Desc.)

NI Detector Pcwer Supply Cut-off Power Level: NIA NI Detector Pcwer Supply Turn-on Power Level: NA Instrument Failure Mode: Low or High (on LI, LR and Computer point)

Temperature Ccmpensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: Zero is 10,000 gallons above HPCI suction.

The RWST and both CSTs can be manually cross connected. The capacity of each CST is 300,000 gallons and the RWST capacity is 680,000 gallons.

CSD-ER-005 Revision 4 Page 71 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: CST LEVEL Point ID: CSL02 Plant Spec Point Desc.: COND STORAGE TANK 2 LVL Generic/Cond Desc.: Condensate Storage Tank 2 Level Analog/Digital: A Engr Units/Dig States:

Engr Units Conversion: Each 1% ý 3,000 gallons Minimum Instr Range: 0.0 Maximum Instr Range: 100.0 Zero Point

Reference:

TNKBOT Reference Point Notes: Zero is 13.5 inches above tank bottom PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: 7.5 inches below zero reference Alarm/Trip Set Points: Low level at 0% (ref. Unique System Desc.)

NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low or High (on LI, LR and Computer point)

Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: Zero is 10,000 gallons above HPCI suction.

The RWST and both CSTs can be manually cross connected. The capacity of each CST is 300,000 gallons and the RWST capacity is 680,000 gallons.

CSD-ER-005 Revision 4 Page 72 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQl/SQ2 Data Feeder: N/A NRC ERDS Parameter: WIND SPEED Point ID: METULS Plant Spec Point Desc.: WIND SPEED-60M Generic/Cond Desc.: Wind Speed at Reactor Site -60M Analog/Digital: A Engr Units/Dig States: MPH Engr Units Conversion: N/A Minimum Instr Range: 1.0 Maximum Instr Range: 50.0 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 1 How Processed: 15 min average (ref. Unique System Desc)

Sensor Locations: Met Tower is ý 1,200 ft. ESE of Rx Bldg Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: 15 min average is a sliding 15 min average.

CSD-ER-005 Revision 4 Page 73 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQ1/SQ2 Data Feeder: N/A NRC ERDS Parameter: WIND SPEED Point ID: METLLS Plant Spec Point Desc.: WIND SPEED-10M Generic/Cond Desc.: Wind Speed at Reactor Site -10M Analog/Digital: A Engr Units/Dig States: MPH Engr Units Conversion: N/A Minimum Instr Range: 1-0 Maximum Instr Range: 50.0 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 1 How Processed: 15 min average (ref. Unique System Desc)

Sensor Locations: Me: Tower is ý 1,200 ft. ESE of Rx Bldg Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: 15 min average is a sliding 15 min average.

CSD-ER-005 Revision 4 Page 74 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQI/SQ2 Data Feeder: N/A NRC ERDS Parameter: WIND DIR Point ID: METULD Plant Spec Point Desc.: WIND DIR - 60 M Generic/Cond Desc.: Wind Dir at the React Site -60M Analog/Digital: A Engr Units/Dig States: DEGFR Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: 360 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 1 1

15 min vector average" )

How Processed:

Sensor Locations: Met Tower is , 1,200 ft. ESE of Rx Bldg Alarm/Trip Set Points: NIA NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: ý_ - 15 min average is a sliding 15 min average.

CSD-ER-005 Revision 4 Page 75 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQl/SQ2 Data Feeder: N/A NRC ERDS Parameter: WIND DIR Point ID: METLLD Plant Spec Point Desc.: WIND DIR - 10 M Generic/Cond Desc.: Wind Dir at the React Site -10M Analog/Digital: A Engr Units/Dig States: DEGFR Engr Units Conversion: N/A Minimum Instr Range: 0 Maximum Instr Range: 360 Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: P Number of Sensors: 1 How Processed: 15 min vector average Sensor Locations: Met Tower is ý 1,200 ft. ESE of Rx Bldg Alarm/Trip Set Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: Low Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: - - 15 min average is a sliding 15 min average.

CSD-ER-005 Revision 4 Page 76 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQi/SQ2 Data Feeder: N.'A NRC ERDS Parameter: S--AB CLASS Point ID: M-TSTAB Plant Spec Point Desc;: A-:R STABILITY AT THE REACT SITE Generic/Cond Desc.: Air Stability at the React Site Analog/Digital: A Engr Units/Dig States: STABI Engr Units Conversion: N/A Minimum Instr Range: N,'A Maximum Instr Range: N,*A Zero Point

Reference:

N.A Reference Point Notes: N, A PROC or SENS: P Number of Sensors: 1 How Processed: Reference Unique System Desc.

Sensor Locations: Reference Unique System Desc.

Alarm/Trip Set Points: N A NI Detector Power Supply Cut-off Power Level: N.A NI Detector Power Supply Turn-on Power Level: N, A Instrument Failure Mode: Reference Unique System Desc.

Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: The parameter is derived from the Delta Temperature between the 10 meter and 60 meter levels. If the Delta Temperature signal is invalid then the parameter is derived from the Sigma Theta of wind direction.

A value of 1 through 7 which corresponds to a stability class of A through F, or 9 (invalid) will be transmitted for METSTAB.

CSD-ER-005 Revision 4 Page 77 of 84 SUSQUEHANNA STEAM ELECTRIC STATION UNITS 1 & 2 ERDS DATA POINT LIBRARY REFERENCE FILE Date: 05/13/98 Reactor Unit: SQI/SQ2 Data Feeder: N/A NRC ERDS Parameter: Not Listed Point ID: EXERCISE Plant Spec Point Desc.: EXERCISE DATA Generic/Cond Desc.: Exercise Data Analog/Digital: D Engr Units/Dig States: NO/YES Engr Units Conversion: N/A Minimum Instr Range: N/A Maximum Instr Range: N/A Zero Point

Reference:

N/A Reference Point Notes: N/A PROC or SENS: S Number of Sensors: 1 How Processed: N/A Sensor Locations: RDAS variable (i.e. pseudo point)

Alarm/Trip Sec Points: N/A NI Detector Power Supply Cut-off Power Level: N/A NI Detector Power Supply Turn-on Power Level: N/A Instrument Failure Mode: N/A Temperature Compensation For DP Transmitters: N/A Level Reference Leg: N/A Unique System Desc.: This parameter is a constant whose value is equal to 0 when actual plant data is being transmitted and 1 when exercise/drill data is being transmitted.

CSD-ER-005 Revision 4 Page 78 of 84 APPENDIX D DATA POINT LIBRARY REFERENCE FILE DEFINITIONS

CSD-ER-005 Revision 4 Page 79 of 84 APPENDIX D DATA POINT LIBRARY REFERENCE FILE DEFINITIONS Date: The date that this form is filled out or modified. (Eight characters)

Reactor Unit: The nuclear power plant name and abbreviation from the enclosed list of sites. (Three characters)

Data Feeder: If there is more than one data feeder for your system, enter the acronym for the data feeder from which the point comes.

If there is only one data feeder, enter "N/A' in this field (Ten characters)

NRC ERDS Parameter: One of the parameters from the enclosed BWR or PWR parameter list. A single value should be transmitted for each parameter for each loop. If not on the list, insert "Not Listed" or "NL". (Twelve characters)

Point ID: Alphanumeric point description used to label the point during transmission.

(Twelve characters)

Plant-Specific Point

Description:

Licensee computer point description for the transmitted point. (Forty characters)

Generic Or Condensed

Description:

Parameter description from the enclosed list of points for a BWR or PWR. If not on the list, condense the plant-specific point description. (Thirty-two characters)

Analog/Digital: "A" if the signal is analog or numerical or "D if the signal is off/on. (One character)

Engineering Units Or Digital Engineering units used by the licensee for States display on licensee output devices. Use the engineering units abbreviations from the enclosed list when possible. When specifying pressure, use "PSIA" or "PSIG" rather than "PSI". For digital signals, give the "OFF" and "ON" state descriptors.

(Twelve characters)

Engineering Units Conversion: Notes about any special features of the A/D conversion and scaling. (Forty characters)

Minimum Instrument Range: Engineering units value below which data cannot go (bottom-of-scale value). (Ten characters)

CSD-ER-005 Revision 4 Page 80 of 84 Maximum Instrument Range: Engineering units value above which data cannot go (top-of-scale value). (Ten characters)

Zero Reference Point: Zero-point of engineering units scale used primarily for levels or heights. Use the zero reference point abbreviations from the enclosed list when possible. (Six characters)

Reference Point Notes: Notes about the reference point or other important and special features of the parameter. (Forty characters)

PROC or SENS: Is the point formed by processing more than one signal, or is the source a single sensor

("P" or "S")? (One character)

Number of Sensors: The number of signals processed in a full calculation assuming no bypassed or inoperative sensors. (Three characters)

How Processed: The processing algorithm (sum, average, weighted average, highest, lowest, or a short description). (Forty characters)

Sensor Locations: Description of the location(s) of the instrument(s) used. (Forty characters)

Alarm or Trip Setpoints: The most important setpoints for the parameter. State whether the limit is high or low. (Forty characters)

NI Detector Power Supply Cut-Off The power level at which the power supply Power Level: for the NI detector switches off. (Fifteen characters)

NI Detector Power Supply Turn-On The power level at which the power supply Power Level: for the NI detector switches on. (Fifteen characters)

Instrument Failure Mode: The mode in which this instrument fails.

Possible answers are HIGH, MEDIUM, OR LOW.

If available, provide the numeric value at which the instrument fails. (Thirty characters)

Temperature Compensation For DP This question pertains to differential Transmitters: pressure transmitters. Possible answers are "YES" or "NO" ("Y" or "N") . If the answer is "NO", please attach a copy of the correction curve. (One character)

CSD-ER-005 Revision 4 Page 81 of 84 Level Reference Leg: The type of level measurement (dry or wet) used on the level reference leg. (Three characters)

Unique System

Description:

Additional important information which will assist the NRC Operations Center personnel in understanding how the plant team interprets the data. (600 characters)

PICSY Plant Integrated Computer System - Unit 2

CSD-ER-005 Revision 4 Page 82 of 84 APPENDIX E CRITICAL SAFETY FUNCTION PARAMETERS

CSD ER-005 Revision 4 Page 83 of 84 CRITICAL SAFETY FUNCTION PARAMETERS - ERDS PARAMETER DESCRIPTION UNITS NI POWER RNG Nuclear Instruments, Power Range NI INTER RNG Nuclear Instruments, Inter Rng A NI INTER RNG Nuclear Instruments, Inter Rng D NI INTER RNG Nuclear Instruments, Inter Rng G NI INTER RNG Nuclear Instruments, Inter Rng H Not Listed IRM A Range Switch Position Not Listed IRM D Range Switch Position Not Listed IRM G Range Switch Position Not Listed IRM H Range Switch Position Not Listed IRM Det(s) not Full in Position NO/YES Not Listed IRM Bypass NO/YES NI SOURC RNG Nuclear Instruments, Sourc Rng A OPS NI SOURC RNG Nuclear Instruments, Sourc Rng B CPS NI SOURC RNG Nuclear Instruments, Sourc Rng C CPS NI SOURC RNG Nuclear Instruments, Sourc Rng D CPS Not Listed SRM Position A NOT IN/IN Not Listed SRM Position B NOT IN/IN Not Listed SRM Position C NOT IN/IN Not Listed SRM Position D NOT IN/IN CORE COOLING REAC VES LEV Reactor Vessel Water Level MAIN FD FLOW Feedwater Flow A into React Syst MLBS/H MAIN FD FLOW Feedwater Flow B into React Syst MLBS/H MAIN FD FLOW Feedwater Flow C into React Syst MLBS/H RCIC FLOW Reactor Core Isolat Cooling Flow GPM RCS INTEGRITY RCS PRESSURE Reactor Coolant System Pressure PSIG HPCI FLOW High Pressure Coolant Injec Flow GPM LPCI FLOW Low Press Coolant Inject A Flow GPM LPCI FLOW Low Press Coolant Inject B Flow GPM CR SPRAY FL Core Spray Cooling System Flow GPM DW FD SMP LV Drywell Floor Drain Sump Level A DW FD SMP LV Drywell Floor Drain Sump Level B

CSD ER-005 Revision 4 Page 84 of 84 RADIOACTIVITY CONTROL EFF GAS RAD Rad of Released NBLGAS-Rx 1 Vent uCI/MIN EFF GAS RAD Rad of Released PART -Rx 1 Vent uCI/MIN EFF GAS RAD Rad of Released 1131 -Rx 1 Vent uCI/MIN EFF GAS RAD Rad of Released NBLGAS-TB 1 Vent uCI/MIN EFF GAS RAD Rad of Released PART -TB 1 Vent uCIIMIN EFF GAS RAD Rad of Released 1131 -TB 1 Vent uCI/MIN EFF GAS RAD Rad of Released NBLGAS-SGTS Vent uCI/MIN EFF GAS RAD Rad of Released PART -SGTS Vent uCI/MIx EFF GAS RAD Rad of Released 1131 -SGTS Vent uCI/MIN EFF GAS RAD Rad of Released NBLGAS-Rx 2 Vent uCI/MIN EFF GAS RAD Rad of Released PART -Rx 2 Vent uCI/MIN EFF GAS RAD Rad of Released 1131 -Rx 2 Vent uCI/MIN EFF GAS RAD Rad of Released NBLGAS-TB 2 Vent uCI/MIN EFF GAS RAD Rad of Released PART -TB 2 Vent UCI/MIN EFF GAS RAD Rad of Released 1131 -TB 2 Vent uCI/MIN EFF GAS RAD Rad of Released NBLGAS-Site Totl uCI/MIN EFF GAS RAD Rad of Released PART -Site Totl uCI/MIN EFF GAS RAD Rad of Released 1131 -Site Totl uCI/MIN EFF LIQ RAD Radioactivity of Released Liq'ds CPM Not Listed LRW Discharge Flow GPM CND A/E RAD Condenser Air Ejector Radioactivity DW RAD Radiation Level in the Drywall R/HR MN STEAM RAG Radiation Lvl of Main Stm Line A MR/H MN STEAM RAD Radiation Lvl of Main Stm Line B MR/H MN STEAM RAD Radiation Lvl of Main Stm Line C MR/H MN STEAM RAD Radiation Lvl of Main Stm Line D MR/H CONTAINMENT CONDITIONS DW PRESS Drywall Pressure PSIG DW TEMN Drywall Temperature DEGF SP TEMP Suppression Pool Temperature DEGF SP LEVEL Suppression Pool Water Level FEET H2 CONC Drywall Hydrogen Concentration 9%

02 CONC Drywell Oxygen Concentration MISCELLANEOUS PARAMETERS CST LEVEL Condensate Storage Tank 1 Level CST LEVEL Condensate Storage Tank 2 Level WIND SPEED Wind Speed at Reactor Site -60M MPH WIND SPEED Wind Speed at Reactor Site -10M MPH WIND DIR Wind Dir at the React Site -60M DEGFR WIND DIR Wind Dir at the React Site -10M DEGFR STAB CLASS Air Stability at the React Site STABA EXERCISE DATA Exercise Data KO/YES