L-PI-09-021, 2008 Unit 2 180-Day Steam Generator Tube Inspection Report

From kanterella
Jump to navigation Jump to search

2008 Unit 2 180-Day Steam Generator Tube Inspection Report
ML091180466
Person / Time
Site: Prairie Island Xcel Energy icon.png
Issue date: 04/27/2009
From: Wadley M
Northern States Power Co, Xcel Energy
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
L-PI-09-021
Download: ML091180466 (116)


Text

@ XcelEnergy6 "A

Prairie lsland Nuclear Generating Plant Northern States Power Company, M~nnesota APR 2 7 2009 U S Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 Prairie lsland Nuclear Generating Plant Unit 2 Docket 50-306 License No. DPR-60 2008 Unit 2 180-Dav Steam Generator Tube Inspection Report In accordance with Prairie lsland Nuclear Generating Plant, Unit 2 Technical Specification 5.6.7 "Steam Generator Tube lnspection Report", Northern States Power Company, Minnesota submits the enclosed report of steam generator tube inspections performed during the 2008 refueling and maintenance outage on Unit 2.

Summarv of Commitments This letter contains no new commitments and no revisions to existing commitments.

Michael D. Wadley Site Vice President, Prairie lsland Nuclear Generating Plant Northern States Power Company - Minnesota Enclosure cc: Administrator, Region Ill, USNRC Project Manager, Prairie Island, USNRC Resident Inspector, Prairie Island, USNRC 1717 Wakonade Drive East Welch, Minnesota 55089-9642 Telephone: 651.388.1 121

ENCLOSURE 1 Prairie Island Nuclear Generating Plant - Unit 2 2008 Steam Generator Tube Inspection Report In accordance with Prairie Island Nuclear Generating Plant (PINGP), Unit 2 Technical Specification 5.6.7, Northern States Power Company, a Minnesota corporation (NSPM) submits this report of steam generator tube inspections performed during the 2008 refueling and maintenance outage on Unit 2 (2R25).

PINGP Unit 2 has two Westinghouse Model 51 Steam Generators (SGs) with approximately 51,500 square feet of heat transfer. Each SG has 3,388 mill annealed Alloy 600 u-tubes manufactured by Blairsville and Huntington which have an outside diameter of 0.875 inch and a nominal wall thickness of 0.050 inch. The tubes are configured in a square pitch of 1.281 inches with 46 rows and 94 columns. The tube u-bends vary in radius from 2.1875 inches for a row 1 tube to 59.844 inches for a row 46 tube. The tube straight length is 378.230 inches for all tubes in the bundle. Rows 1 and 2 were subject to in situ stress relieving using Westinghouse thermal treatment process during the May 2000 refueling outage. The tubes were roll expanded at each tube end for approximately 2.75 inches leaving an open tubesheet crevice.

The tubesheet is A-508 Class 2 material 21.0 inches thick with Weld Deposit Inconnel cladding 0.2 inches thick and a tube extension beyond the clad of 0.2 inches for an overall thickness of 21.4 inches. The tubes are supported by seven A-285 Grade C drilled tube support plates (TSPs) 0.750 inches thick and two anti-vibration bars (AVBs).

The original AVB design consisted of two square (0.387 x 0.387) Inconnel 600 bars with an alphatized chrome-plated surface, with a 44º bar nested in a 136º bar that intersected the tubes between one and four times. The replacement AVB design consisted of two hinged rectangular (0.750 x variable) stainless steel bars set at 25º and 60º from the centerline axis of the tube bundle that intersected the tubes between two and four times.

PINGP Unit 2 has a Technical Specification (T.S.5.5.8.c.2 (b)) approved repair method of hardroll expanding non-sleeved portions of tubes in the (hot leg) tubesheet in order to apply the F* and EF* criteria. Figure 1 provides an illustration of the original equipment manufacturers (OEM) tube-to-tubesheet configuration and each of the three possible reroll elevations (AR1, AR2 and ARE) utilized at PINGP.

Page 1 of 115

TOP OF TUBESHEET BOTTOM OF TUBESHEET Figure 1 Reroll Configuration Page 2 of 115

Italicized text represents technical specification excerpts. Each excerpt is followed by the appropriate information intended to address each specific requirement and also includes additional details based on benchmarking recent submittals and Staff requests for additional information of peer Licensees. A legend of codes and field names is included at the end of the report.

5.6.7 Steam Generator Tube Inspection Report

a. A report shall be submitted within 180 days after initial entry into MODE 4 following completion of an inspection performed in accordance with the Specification 5.5.8, Steam Generator (SG) Program.

Initial entry into MODE 4 occurred on October 27, 2008, dictating submittal of this report on or before Saturday, April 25, 2009. In accordance with 10 CFR 50.4, this report will be due on the next business day, Monday, April 27, 2009.

The report shall include:

1. The scope of inspections performed on each SG, Table 1 and the text that follows, provides the scope of inspections performed during 2R25.

Page 3 of 115

TABLE 1 SCOPE TECHNIQUE S/G 21 S/G 22 Full Length1 Bobbin 100% (3127) 100% (3122)

Rows 1 through 4 U-Bends MRPC 100% (350) 100% (352)

Rows 5 through 8 U-Bends MRPC 33% (114) 33% (123)

Hot Leg Tubesheets MRPC 100% (3127) 100% (3122)

Hot Leg Roll Plugs MRPC 25% (63) 25% (62)

Supplementald MRPC 100% (310) 100% (318)

Baseline new Re-Rolls Bobbin/MRPC 100% (190) 100% (144)

Post In Situ Pressure Test MRPC N/A N/A Plug Visual 100% (261) 100% (266)

Upper Internalse Visual 100% N/A Top of Tubesheetf Visual 100% N/A PLPg Visual General Notes:

The scope of inspections is provided as a percentage followed by the total number of tests parenthetically where practical.

For clarity, only three digit codes that require supplemental MRPC testing and utilized during 2R25 are included in d below.

DNT is called at > 2.0 Volt, and all the other codes in d below (DSI, INR, MBM, NQI, PLP and PSI) do not have a voltage calling criteria.

Specific Notes:

1 Except the bend portion of rows 1 through 4 u-bends.

d Supplemental MRPC testing (including the +Point coil) was based on bobbin results to inspect all TSP DNT 2.0V, Freespan DNT 5.0V, DSI, TSP INR 1.5V, MBM, NQI, PLP (Bound MRPC PLPs), PSI, Cold Leg Thinning 40% or < 40%

and 1.5V signals/indications to detect latent tube degradation, to refute/confirm, to characterize (axial, circumferential or volumetric) and/or obtain additional length and depth measurements.

e Inspection of upper internals included the Swirl Vane Moisture Separators, Feed Ring Hangers, Holes, and Plugs, Upper Transition Girth Weld, Thermal Sleeve, Magnetic Particle Examine of the Feedwater Nozzle, Ultrasonic inspections of Feed Ring Tee, and Feedwater to Reducer Welds Downcomer, and other upper bundle components per NRC Generic Letter 97-06.

f Tube lane and periphery of the tube bundle inspected using Camera Transporter System.

g Locating possible loose part (PLP) indications for investigation and possible removal based on eddy current results (not necessary).

Page 4 of 115

2. Active degradation found, Primary Side Inspections -Thinning, wear, outside diameter stress corrosion cracking (ODSCC) and primary water stress corrosion cracking (PWSCC) were found in both SGs during 2R25 and are captured within the corrective action process. These Mechanisms have been previously reported.

Secondary Side Inspections - None found

3. Nondestructive examination techniques utilized for each degradation mechanism, Table 2 and the text that follows, provides the Electric Power Research Institute (EPRI) Examination Technique Specification Sheet (ETSS) (techniques) utilized during 2R25 for existing and potential degradation and proactive sampling.

Page 5 of 115

TABLE 2 MECHANISM ORIENTATION LOCATION TECHNIQUE AVB Wear1 Volumetric U-bend 96004.3 Rev. 11 Thinning1 Volumetric Non-dented TSP 96001.1 Rev. 11 ODSCC1 Axial Tubesheet Crevice 21409.1 Rev. 5 ODSCC1 Axial Top of Tubesheet 21409.1 Rev. 5 PWSCC1 Axial Roll Transition 20511.1 Rev. 8 PWSCC1 Axial Tube End 20511.1 Rev. 8 PWSCC1 Axial & Circ. U-bend 96511.2 Rev. 16 IGA/ODSCCd Axial Non-dented TSP 96007.1 Rev. 11 IGA/ODSCCd Axial Non-dented TSP 21409.1 Rev. 5 PLP Wear1 Volumetric Freespan 27091.2 Rev. 0 TLBD Wear1 Volumetric Freespan 96004.3 Rev. 11 Thinning1 Volumetric Top of Tubesheet 96001.1 Rev. 11 Roll Transition and ODSCCd Axial 21409.1 Rev. 5 Dented TSP Roll Transition and ODSCCd Circ. 21410.1 Rev. 6 Dented TSP PWSCC1 Circ Roll Transition 20510.1 Rev. 7 PWSCCd Axial Dented TSP 20511.1 Rev. 8 PWSCCd Circ Dented TSP 20510.1 Rev. 7 PWSCCe Axial & Circ. Roll Plug Transition 99-TR-FSW-010f Pittingd Volumetric Top of Tubesheet 96005.2 Rev. 9 ODSCCd Axial Freespan DNT <5V 24013.1 Rev. 2 1 Active is synonymous with the term existing degradation that is found in the EPRI Steam Generator Integrity Assessment Guidelines. Therefore the classical definition applies (i.e., one historical or current indication equates to active).

d Potential degradation based on internal and external operating experience on steam generators with similar designs, operating conditions and materials.

e Proactive Sampling is used to challenge engineering assumptions such as material susceptibility or when the Arrhenius equation predicts susceptibility in a future sequential period. These samples are considered informational sample plans that are not subject to the periodicity requirements of T.S.5.5.8.d.3.

f 99-TR-FSW-010 Rev. 00 Appendix H Qualification for Eddy Current Testing Steam Generator Mechanical Tube Plugs ABBCE, November 2, 1998.

Page 6 of 115

4. Location, orientation (if linear), and measured sizes (if available) of service induced indications, Tables 3 and 4 provide the location and measured size of each reported indication in each steam generator respectively for degradation found during 2R25 that was sized with the bobbin coil. All the tubes in these two tables were returned to service using the depth based criteria for tube repair.

Tables 5 and 6 provide the location, orientation and length (if available) of each reported indication in each steam generator respectively for degradation found during 2R25 that is located below the F* distance of a tube that has never been repaired by the rerolling process. These tubes are considered F*0 tubes and all the tubes in the two tables were returned to service using the F* Alternate Repair Criteria (ARC) without any additional rerolling during 2R25.

Tables 7 and 8 provide the location, orientation and length (if available) of each reported indication in each steam generator respectively for degradation found during 2R25 (or known to exist from previous inspections) that is located below the F* distance of a tube that was repaired by rerolling in a previous outage at the first reroll repair location (approximately 3.75 to 5.00 above the tube end). These tubes are considered F*1 tubes and all the tubes in the two tables were returned to service using the F* ARC without any additional rerolling during 2R25.

Tables 9 and 10 provide the location, orientation and length (if available) of each reported indication in each steam generator respectively for degradation found during 2R25 (or known to exist from previous inspections) that is located below the F* distance of a tube that was repaired by rerolling in a previous outage at the second reroll repair location (approximately 5.75 to 7.00 above the tube end).

These tubes are considered F*2 tubes and all the tubes in the two tables were returned to service using the F* ARC without any additional rerolling during 2R25.

Tables 11 and 12 provide the location, orientation and length (if available) of each reported indication in each steam generator respectively for degradation found during 2R25 (or known to exist from previous inspections) that is located below the EF* distance of a tube that was repaired by rerolling in a previous outage at the elevated reroll repair location (approximately 16.38 to 18.38 above the tube end).

These tubes are considered EF* tubes and all the tubes in the two tables were returned to service using the EF* ARC without any additional rerolling during 2R25.

Tables 13 and 14 provide the location, orientation and length of each reported indication in each steam generator respectively for degradation found during 2R25 that is located within (and in some cases also below) the F* distance of a tube that has never been repaired by rerolling in a previous outage. These tubes were successfully repaired during 2R25 at the first reroll repair location (approximately 3.75 to 5.00 above the tube end). These tubes are considered new F*1 tubes and all the tubes in the two tables were returned to service using the F* ARC with a new reroll installed during 2R25.

Page 7 of 115

Tables 15 and 16 provide the location, orientation and length (if available) of each reported indication in each steam generator respectively for degradation found during 2R25 (or known to exist from previous inspections) that is located within (and in some cases also below) the F* distance of a tube that was either successfully repaired by rerolling in a previous outage or failed the acceptance criteria during the current outage at the first reroll repair location. These tubes were successfully repaired during 2R25 at the second reroll repair location (approximately 5.75 to 7.00 above the tube end). These tubes are considered F*2 tubes and all the tubes in the two tables were returned to service using the F* ARC with a new reroll installed during 2R25.

Tables 17 and 18 provide the location, orientation and length (if available) of each reported indication in each steam generator respectively for degradation found during 2R25 (or known to exist from previous inspections) that is located within (and in some cases also below) the F* distance of a tube that was successfully repaired by rerolling in a previous outage at the second reroll repair location. These tubes were successfully repaired during 2R25 at the elevated reroll repair location (approximately 16.38 to 18.38 above the tube end). These tubes are considered EF* tubes and all the tubes in the two tables were returned to service using the EF*

ARC with a new reroll installed during 2R25.

Tables 19 and 20 provide the location, orientation (if linear) and measured sizes (if available) of indications in each steam generator respectively for tubes exceeding the plugging or repair criteria during 2R25. These tubes were all removed from service by plugging during 2R25.

A legend of fields and codes with brief explanations is provided at the end of this enclosure for clarification purposes.

Page 8 of 115

TABLE 3 Steam Generator 21 - Less than the Technical Specification Repair Limit TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM 1 1 16 4 0.71 31 01C 0.05 2 2 16 5 1.17 17 02C 0.05 3 3 18 5 1.00 13 01C -0.14 4 4 14 6 0.91 27 01C 0.00 5 5 19 6 1.25 25 NV1 0.00 6 6 21 7 0.76 1 01C 0.05 7 7 23 7 0.37 36 01C -0.16 7 8 23 7 0.37 23 01C -0.16 8 9 21 9 1.17 25 NV1 1.48 9 10 27 10 1.76 31 07H 25.58 10 11 25 11 0.98 16 02C 0.24 11 12 29 13 0.97 10 01C -0.26 12 13 31 17 0.42 2 01C -0.34 13 14 33 17 0.90 17 02C -0.05 14 15 34 17 0.61 1 02C -0.03 15 16 31 18 0.58 35 01C -0.34 16 17 34 18 0.95 8 01C -0.24 17 18 36 18 1.14 1 02C -0.24 18 19 36 21 1.09 27 02C 0.13 19 20 41 26 0.86 28 01C -0.26 19 21 41 26 1.42 28 01C 0.21 20 22 23 27 1.25 27 NV4 4.41 21 23 39 27 0.58 17 NV3 -0.03 22 24 41 27 1.59 30 01C -0.21 22 25 41 27 1.88 1 01C 0.13 23 26 18 28 1.45 27 NV2 0.77 23 27 18 28 1.06 22 NV2 12.15 24 28 34 28 0.80 18 NV3 -0.19 25 29 25 30 1.24 27 NV2 0.79 25 30 25 30 2.15 37 NV2 19.67 25 31 25 30 1.06 24 NV4 2.31 26 32 39 30 1.23 24 NV4 2.69 27 33 25 32 1.18 25 NV2 0.29 27 34 25 32 1.33 27 NV2 19.23 28 35 41 32 0.91 19 NV1 -0.03 28 36 41 32 1.10 22 NV2 -0.05 28 37 41 32 0.85 26 NV3 0.08 29 38 17 33 0.91 22 NV2 12.09 30 39 24 33 0.99 23 NV3 2.02 31 40 25 33 0.89 21 07H 27.96 31 41 25 33 2.14 37 NV2 1.62 31 42 25 33 1.91 35 NV2 20.42 31 43 25 33 0.92 22 NV4 0.89 32 44 39 34 0.98 23 NV2 35.51 32 45 39 34 1.54 31 NV4 2.68 33 46 44 34 0.96 29 05C -0.08 Page 9 of 115

TABLE 3 Steam Generator 21 - Less than the Technical Specification Repair Limit TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM 34 47 23 37 1.14 26 NV2 0.62 34 48 23 37 1.65 32 NV2 17.18 35 49 17 38 0.70 15 NV2 0.32 36 50 45 42 2.24 24 02C -0.08 37 51 11 43 0.41 9 NV1 -0.06 38 52 36 43 0.91 20 07H 33.68 38 53 36 43 1.05 23 NV2 2.58 38 54 36 43 1.32 30 NV2 32.75 39 55 46 43 0.86 6 01C -0.24 40 56 43 44 1.70 27 01C -0.29 41 57 44 44 2.14 11 01C -0.19 42 58 28 45 1.91 34 07H 29.93 42 59 28 45 1.70 32 NV2 0.10 42 60 28 45 1.39 28 NV2 22.13 42 61 28 45 0.95 22 NV2 24.41 42 62 28 45 1.25 26 NV4 2.41 43 63 36 45 1.25 26 NV2 1.26 44 64 44 45 0.54 14 01C -0.08 45 65 45 45 0.32 23 01C 0.00 46 66 44 46 3.69 28 01C -0.13 47 67 46 46 1.30 1 01C 0.21 48 68 36 47 2.50 39 07H 33.83 48 69 36 47 1.78 32 NV2 2.08 48 70 36 47 1.36 26 NV2 32.24 49 71 39 47 1.62 33 NV2 35.12 49 72 39 47 1.76 35 NV4 3.12 50 73 35 48 2.13 36 07H 33.22 50 74 35 48 1.04 22 NV2 2.11 50 75 35 48 0.87 23 NV2 30.91 51 76 45 48 0.94 18 01C 0.13 52 77 29 50 0.84 22 07H 30.43 52 78 29 50 2.44 41 NV2 1.08 52 79 29 50 3.12 45 NV2 23.84 53 80 45 50 0.56 24 01C -0.08 54 81 11 51 0.22 5 NV4 0.00 55 82 29 52 0.99 24 NV2 1.00 56 83 41 53 1.64 13 01C -0.19 57 84 42 53 0.54 13 NV1 0.00 57 85 42 53 0.67 16 NV2 -0.03 58 86 43 54 0.26 22 01C -0.03 59 87 46 54 0.71 4 01C -0.08 60 88 22 55 0.78 24 NV2 18.00 61 89 34 56 0.82 19 NV3 -0.08 62 90 43 57 1.25 2 01C 0.16 63 91 41 58 1.44 17 01C -0.16 64 92 45 58 1.68 27 01C 0.00 65 93 8 59 0.53 30 04H 1.57 Page 10 of 115

TABLE 3 Steam Generator 21 - Less than the Technical Specification Repair Limit TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM 66 94 9 59 0.55 31 04H 1.55 67 95 43 59 2.07 24 01C 0.03 68 96 36 60 1.33 27 NV2 2.35 69 97 42 60 0.83 2 01C 0.03 70 98 43 60 1.11 1 01C 0.08 71 99 19 61 0.81 20 NV2 14.57 72 100 21 61 1.19 26 NV2 1.21 72 101 21 61 1.04 24 NV2 16.73 72 102 21 61 0.54 14 NV4 -0.11 73 103 23 61 1.47 30 NV2 1.56 73 104 23 61 1.03 24 NV2 18.91 73 105 23 61 1.04 24 NV4 0.30 74 106 39 61 0.65 8 01C -0.24 75 107 42 62 2.32 29 01C -0.11 76 108 36 63 3.36 45 NV2 2.76 77 109 39 63 1.00 1 01C 0.24 78 110 17 64 0.89 20 NV4 2.52 79 111 21 64 1.10 22 NV2 17.02 80 112 42 64 0.71 2 02C -0.32 81 113 43 64 1.34 16 01C -0.14 82 114 40 66 2.13 22 02C -0.11 83 115 21 67 0.58 14 NV2 0.38 84 116 26 69 1.61 29 07H 28.58 84 117 26 69 1.12 24 NV2 2.74 84 118 26 69 1.51 30 NV2 23.12 85 119 39 69 0.62 10 01C -0.24 86 120 40 70 0.70 17 02C -0.08 87 121 18 71 1.08 22 NV2 12.97 87 122 18 71 0.83 18 NV3 -0.03 88 123 39 71 1.99 28 01C -0.24 89 124 40 71 0.74 7 01C -0.27 90 125 26 72 1.28 28 NV2 1.30 90 126 26 72 2.04 36 NV2 21.94 91 127 36 72 1.62 15 01C -0.16 92 128 39 72 1.16 24 01C -0.11 93 129 38 73 0.54 17 01C -0.11 94 130 37 75 1.86 11 01C -0.05 95 131 34 76 1.38 18 02C 0.11 96 132 35 77 1.33 7 02C -0.05 97 133 32 78 2.61 30 02C -0.05 97 134 32 78 2.08 31 01C -0.24 98 135 23 85 0.41 13 01C 0.00 99 136 23 86 3.04 34 01C 0.08 100 137 25 86 1.72 17 01C 0.00 101 138 23 88 0.72 7 01C -0.08 102 139 12 90 1.75 19 01C -0.08 103 140 15 90 1.16 5 01C 0.05 Page 11 of 115

TABLE 3 Steam Generator 21 - Less than the Technical Specification Repair Limit TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM 104 141 18 90 0.64 1 02C 0.00 105 142 4 91 2.11 33 01C -0.19 106 143 7 91 2.54 25 01C -0.11 107 144 14 91 1.31 1 01C 0.00 108 145 16 91 1.53 37 01C 0.00 109 146 3 92 1.41 11 01C 0.14 110 147 8 92 2.02 36 01C -0.08 111 148 9 92 1.20 11 01C 0.00 112 149 10 92 1.24 5 01C 0.05 113 150 14 92 1.48 28 NV1 2.53 113 151 14 92 0.60 9 01C 0.08 114 152 2 93 0.58 4 02C 0.06 114 153 2 93 2.02 20 01C -0.11 115 154 3 93 0.56 3 01C -0.03 116 155 5 93 2.24 36 01C -0.05 117 156 6 93 0.73 23 02C -0.05 117 157 6 93 1.29 38 01C -0.16 118 158 5 94 1.17 28 01C 0.00 119 159 7 94 0.80 20 01C 0.05 Page 12 of 115

TABLE 4 Steam Generator 22 - Less than the Technical Specification Repair Limit TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM 1 1 12 3 2.87 39 02C 0.08 2 2 16 4 1.53 10 01C 0.11 3 3 17 5 1.39 16 01C 0.13 4 4 16 6 0.81 1 01C -0.11 5 5 17 6 0.74 18 01C -0.05 6 6 19 6 0.90 9 02C 0.10 7 7 20 6 1.07 23 01C 0.00 8 8 21 7 0.89 20 02C 0.03 8 9 21 7 0.86 21 01C -0.05 9 10 17 8 0.43 4 02C -0.03 10 11 25 9 1.85 36 01C 0.00 11 12 20 10 0.96 16 01C -0.05 12 13 24 10 1.44 22 01C -0.11 13 14 26 10 0.65 1 02C 0.21 14 15 28 11 1.00 1 02C 0.16 15 16 29 13 1.77 35 02C -0.03 15 17 29 13 0.84 21 01C -0.03 16 18 31 13 1.55 31 01C -0.16 17 19 29 15 0.37 11 01C -0.16 18 20 30 15 2.11 19 01C -0.10 19 21 34 16 2.65 32 02C 0.00 19 22 34 16 0.56 5 01C 0.21 20 23 34 17 0.51 30 02C -0.10 20 24 34 17 2.05 20 01C -0.08 21 25 30 19 0.75 1 01C -0.10 22 26 31 19 1.21 17 01C -0.18 23 27 32 20 0.51 12 01C -0.16 24 28 30 21 0.77 11 01C 0.21 25 29 36 22 0.80 28 02C 0.05 26 30 37 23 0.53 1 01C 0.03 27 31 37 24 1.54 28 01C -0.13 28 32 38 25 0.83 13 02C -0.16 28 33 38 25 0.85 11 01C 0.21 29 34 41 26 0.74 7 01C -0.08 30 35 39 29 0.62 20 02C -0.11 31 36 41 29 0.27 7 NV1 -0.21 31 37 41 29 0.59 15 NV3 0.11 32 38 42 29 0.76 38 01C 0.26 33 39 19 31 0.33 9 NV1 0.00 33 40 19 31 0.79 20 NV2 2.50 33 41 19 31 0.21 6 NV3 0.00 34 42 19 34 0.56 15 NV1 -0.03 35 43 43 34 0.42 32 03C -0.08 36 44 43 35 2.36 30 02C -0.16 37 45 38 36 0.85 21 NV2 2.45 38 46 44 36 1.29 20 02C -0.19 Page 13 of 115

TABLE 4 Steam Generator 22 - Less than the Technical Specification Repair Limit TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM 39 47 42 38 0.55 14 NV1 -0.11 39 48 42 38 0.57 15 NV2 -0.17 39 49 42 38 1.31 13 02C -0.22 40 50 38 39 0.43 11 NV1 0.00 40 51 38 39 0.50 12 NV2 0.00 41 52 43 39 0.56 4 02C -0.24 42 53 44 39 1.61 29 02C -0.14 43 54 44 40 3.31 27 02C 0.03 44 55 33 41 0.38 10 NV1 -0.25 45 56 40 41 0.64 15 NV1 -0.06 45 57 40 41 0.98 21 NV2 -0.14 45 58 40 41 1.05 22 NV3 -0.11 46 59 44 42 1.52 18 02C -0.11 47 60 46 42 1.97 2 02C -0.22 48 61 37 43 1.59 30 NV2 33.12 48 62 37 43 1.44 28 NV4 3.56 49 63 45 44 1.21 16 02C 0.08 50 64 39 45 0.71 14 NV1 -0.03 51 65 32 46 0.79 20 NV2 0.77 51 66 32 46 0.86 21 NV2 26.92 51 67 32 46 0.89 21 NV4 1.13 52 68 38 46 1.01 23 07H 35.85 52 69 38 46 0.89 23 NV4 3.15 53 70 38 47 1.05 22 NV2 1.87 54 71 38 48 1.21 26 NV2 2.18 55 72 41 48 0.55 15 NV2 0.00 56 73 44 48 1.05 16 01C -0.06 57 74 45 48 1.43 22 02C -0.14 57 75 45 48 1.02 9 01C 0.22 58 76 25 49 0.55 14 NV4 -0.05 59 77 26 49 0.62 15 NV4 0.37 60 78 32 49 0.92 18 NV4 0.03 61 79 11 50 0.45 12 NV1 -0.11 62 80 33 50 0.99 23 NV2 28.56 63 81 38 50 0.45 12 NV1 -0.31 63 82 38 50 0.99 23 NV2 -0.30 63 83 38 50 0.83 20 NV3 -0.11 63 84 38 50 2.23 38 NV4 -0.22 64 85 45 50 2.70 33 01C 0.11 65 86 37 51 0.88 20 NV2 2.08 65 87 37 51 0.81 20 NV2 33.26 66 88 33 52 0.82 21 07H 35.00 67 89 45 52 1.19 17 01C 0.14 68 90 40 53 1.06 11 01C 0.16 69 91 44 53 2.06 9 01C 0.14 70 92 46 53 1.64 19 02C -0.14 71 93 36 54 1.15 26 NV4 3.37 Page 14 of 115

TABLE 4 Steam Generator 22 - Less than the Technical Specification Repair Limit TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM 72 94 39 54 0.97 24 07H 35.23 73 95 39 55 0.94 21 NV2 3.97 74 96 36 56 1.17 26 NV2 33.01 75 97 38 56 0.37 11 NV1 0.11 75 98 38 56 0.77 20 NV2 35.61 76 99 42 56 0.42 4 02C -0.03 77 100 17 57 0.86 21 NV1 3.43 78 101 43 57 2.04 35 NV3 0.00 78 102 43 57 0.62 13 NV4 -0.05 79 103 45 57 1.09 2 01C -0.05 80 104 35 58 1.01 24 07H 32.96 81 105 43 58 0.66 17 NV2 -0.08 81 106 43 58 1.31 13 01C -0.08 82 107 40 59 0.88 20 07H 35.08 83 108 41 60 1.70 13 02C -0.16 84 109 43 60 1.02 6 02C 0.00 85 110 41 61 1.46 27 02C -0.08 86 111 44 61 0.82 22 02C -0.17 87 112 44 62 0.77 1 02C -0.13 88 113 41 63 0.59 6 01C 0.00 89 114 43 63 1.64 1 02C -0.26 90 115 32 64 1.42 29 NV2 2.96 90 116 32 64 1.53 30 NV2 28.28 91 117 38 64 1.56 31 NV2 34.35 92 118 39 64 1.50 22 02C -0.21 93 119 42 64 3.08 27 02C -0.21 94 120 19 65 1.01 23 NV2 1.32 95 121 42 65 0.90 12 02C -0.08 96 122 43 65 3.03 22 02C -0.21 97 123 32 66 0.09 2 NV4 -0.16 98 124 40 66 1.34 1 02C 0.13 99 125 41 66 4.50 34 02C -0.11 100 126 32 67 1.26 23 NV1 -0.29 100 127 32 67 2.01 32 NV2 0.00 100 128 32 67 1.15 22 NV2 28.23 100 129 32 67 2.20 34 NV3 0.00 100 130 32 67 1.22 23 NV4 0.00 101 131 32 68 0.78 20 NV2 28.66 102 132 19 69 0.80 21 NV4 3.52 103 133 36 69 0.56 12 NV1 -0.03 103 134 36 69 0.81 16 NV2 -0.11 103 135 36 69 2.67 38 NV3 0.05 103 136 36 69 1.16 22 NV4 0.03 104 137 40 69 2.67 27 02C -0.10 105 138 36 70 2.34 39 NV2 4.86 105 139 36 70 2.73 42 NV2 32.71 106 140 16 71 0.48 14 NV3 -0.32 Page 15 of 115

TABLE 4 Steam Generator 22 - Less than the Technical Specification Repair Limit TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM 107 141 38 71 2.19 27 01C -0.08 108 142 40 71 4.79 23 02C -0.18 109 143 36 72 0.45 13 02C -0.13 110 144 37 72 1.61 1 02C -0.18 111 145 36 73 1.00 22 NV2 32.48 111 146 36 73 0.92 1 02C -0.13 112 147 33 75 1.51 21 01C -0.03 113 148 35 75 1.43 26 01C -0.05 114 149 36 75 2.32 22 02C -0.16 115 150 33 76 1.17 27 02C -0.13 115 151 33 76 1.43 20 01C 0.00 116 152 30 79 1.37 18 02C 0.13 116 153 30 79 0.93 9 01C 0.08 117 154 29 81 0.45 13 NV2 0.13 118 155 30 81 2.32 27 01C -0.05 119 156 29 82 3.44 25 02C -0.24 119 157 29 82 0.42 38 01C -0.08 120 158 30 82 3.38 24 02C -0.13 121 159 30 83 1.04 1 02C -0.18 122 160 29 84 1.78 1 02C -0.24 123 161 22 85 1.05 1 01C -0.16 124 162 24 85 0.52 1 01C -0.13 125 163 28 85 0.81 21 01C -0.21 125 164 28 85 1.02 13 01C 0.08 126 165 26 86 1.53 19 02C -0.13 127 166 20 87 0.99 1 01C -0.13 128 167 14 88 1.20 7 02C -0.08 129 168 22 88 2.43 22 02C -0.13 130 169 16 89 1.46 14 02C -0.10 130 170 16 89 0.69 16 01C -0.24 131 171 17 89 1.97 26 01C 0.00 132 172 18 89 0.49 22 02C -0.03 133 173 19 89 1.83 18 01C 0.00 134 174 21 89 1.15 1 02C -0.13 135 175 6 90 0.40 9 01C 0.00 136 176 12 90 1.00 18 01C -0.05 137 177 16 90 1.67 35 01C 0.03 138 178 17 90 0.94 1 01C -0.13 139 179 7 91 1.98 10 01C 0.09 140 180 11 91 1.74 27 02C 0.00 141 181 12 91 0.65 8 02C -0.05 141 182 12 91 1.15 1 01C 0.03 142 183 13 91 0.47 19 02C -0.05 143 184 1 92 1.08 1 01C 0.11 144 185 3 92 0.67 21 01C 0.06 145 186 7 92 2.06 30 01C 0.00 146 187 9 92 1.01 4 01C 0.11 Page 16 of 115

TABLE 4 Steam Generator 22 - Less than the Technical Specification Repair Limit TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM 147 188 4 93 0.63 15 02C 0.00 147 189 4 93 1.82 14 01C 0.11 148 190 5 93 1.36 21 01C 0.09 149 191 6 93 0.57 10 02C -0.09 Page 17 of 115

TABLE 5 STEAM GENERATOR 21 - HISTORICAL F*0 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1 1 2 1 2.61 SAN TRH -2.49 -2.30 0.19 2 2 1 2 3.65 SAN TRH -2.48 -2.26 0.22 3 3 2 2 1.87 SAN TRH -2.53 -2.42 0.11 4 4 1 4 4.64 SAN TRH -2.63 -2.39 0.24 5 5 2 4 1.17 SAN TRH -2.56 -2.45 0.11 6 6 1 5 3.04 SAN TRH -2.61 -2.34 0.27 7 7 2 5 2.52 SAN TRH -2.71 -2.50 0.21 8 8 2 6 3.13 SAN TRH -2.69 -2.47 0.22 9 9 4 6 1.16 SAI TRH -2.64 -2.54 0.10 10 10 18 6 1.70 SAN TRH -2.52 -2.40 0.12 11 11 21 6 0.70 SAI TRH -2.73 -2.71 0.02 12 12 1 7 3.49 SAN TRH -2.66 -2.55 0.11 13 13 2 7 7.68 MAN TRH -2.69 -2.29 0.40 14 14 4 7 0.56 SAN TRH -2.51 -2.45 0.06 15 15 7 8 2.62 SAN TRH -2.53 -2.39 0.14 16 16 8 8 1.24 MAI TRH -1.68 -1.54 0.14 17 17 25 8 1.95 SAN TRH -2.39 -2.29 0.10 18 18 6 9 1.08 SAN TRH -2.50 -2.42 0.08 19 19 8 9 1.13 SAI TRH -1.61 -1.57 0.04 20 20 20 9 3.05 MAN TRH -2.86 -2.68 0.18 21 21 15 10 3.26 MAN TRH -2.63 -2.46 0.17 22 22 16 10 1.66 SAN TRH -2.49 -2.35 0.14 23 23 22 10 1.34 SAN TRH -2.73 -2.68 0.05 24 24 25 10 2.81 SAN TRH -2.66 -2.58 0.08 25 25 26 10 1.85 SAN TRH -2.64 -2.57 0.07 26 26 28 10 4.22 MAN TRH -2.48 -2.40 0.08 27 27 7 11 3.38 SAN TRH -1.61 -1.46 0.15 28 28 17 11 2.30 SAN TRH -2.42 -2.35 0.07 29 29 19 11 1.69 SAN TRH -2.52 -2.45 0.07 30 30 21 11 2.01 SAN TRH -2.63 -2.54 0.09 31 31 27 11 3.71 MAN TRH -2.48 -2.38 0.10 32 32 15 12 5.61 SAN TRH -2.66 -2.45 0.21 33 33 24 12 0.80 SAI TRH -2.73 -2.67 0.06 34 34 25 12 1.36 MAI TRH -2.70 -2.65 0.05 35 35 27 12 2.35 MAN TRH -2.24 -2.23 0.01 36 36 28 12 4.83 MAN TRH -2.57 -2.27 0.30 37 37 1 13 4.17 MAN TRH -2.68 -2.56 0.12 38 38 6 13 2.84 SAN TRH -2.58 -2.47 0.11 39 39 17 13 1.36 SAN TRH -2.50 -2.42 0.08 40 40 23 13 0.93 MAN TRH -2.50 -2.42 0.08 41 41 1 14 4.70 MAN TRH -2.37 -2.25 0.12 42 42 6 15 3.18 SAN TRH -2.59 -2.47 0.12 43 43 7 15 5.06 SAN TRH -2.74 -2.46 0.28 44 44 25 15 0.96 SAN TRH -2.60 -2.53 0.07 45 45 28 15 2.30 MAN TRH -2.57 -2.47 0.10 46 46 31 15 1.27 SAN TRH -2.42 -2.35 0.07 47 47 5 17 2.15 MAN TRH -2.59 -2.50 0.09 Page 18 of 115

TABLE 5 STEAM GENERATOR 21 - HISTORICAL F*0 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 48 48 6 18 0.92 SAI TRH -2.40 -2.36 0.04 49 49 7 18 2.73 SAN TRH -2.55 -2.28 0.27 50 50 26 19 5.21 MAN TRH -2.57 -2.22 0.35 51 51 8 20 2.02 SAN TRH -2.51 -2.40 0.11 52 52 33 20 4.55 MAN TRH -2.55 -2.44 0.11 53 53 32 21 4.07 MAN TRH -2.57 -2.50 0.07 54 54 7 22 4.16 MAN TRH -2.57 -2.39 0.18 55 55 2 23 1.91 SAN TRH -2.55 -2.34 0.21 56 56 7 23 1.97 SAN TRH -2.45 -2.34 0.11 57 57 28 23 0.97 SAN TRH -2.75 -2.66 0.09 58 58 32 23 1.40 SAN TRH -2.69 -2.60 0.09 59 59 33 23 1.58 MAN TRH -2.73 -2.51 0.22 60 60 33 24 2.74 MAN TRH -2.64 -2.50 0.14 61 61 1 25 3.66 MAN TRH -2.53 -2.44 0.09 62 62 29 25 1.16 SAN TRH -2.75 -2.71 0.04 63 63 33 25 4.97 SAN TRH -2.50 -2.36 0.14 64 64 32 29 1.78 SAN TRH -2.45 -2.39 0.06 65 65 33 29 0.99 SAN TRH -2.52 -2.45 0.07 66 66 29 31 0.72 SAI TRH -2.12 -2.08 0.04 67 67 12 32 1.07 SAN TRH -2.66 -2.62 0.04 68 68 1 35 3.37 SAN TRH -2.63 -2.53 0.10 69 69 26 36 1.25 SAN TRH -2.56 -2.48 0.08 70 70 1 37 1.44 SAN TRH -2.69 -2.62 0.07 71 71 1 40 1.61 SAN TRH -2.70 -2.49 0.21 72 72 28 40 0.98 SAN TRH -2.34 -2.30 0.04 73 73 25 41 3.47 SAN TRH -2.50 -2.33 0.17 74 74 21 47 2.35 MAN TRH -2.51 -2.42 0.09 75 75 1 58 2.09 SAN TRH -2.65 -2.54 0.11 76 76 7 58 1.67 SAN TRH -2.51 -2.43 0.08 77 77 24 58 0.70 SAI TRH -2.45 -2.37 0.08 78 78 27 58 1.40 SAN TRH -2.74 -2.68 0.06 79 79 27 60 2.32 MAN TRH -2.72 -2.61 0.11 80 80 28 60 3.09 MAN TRH -2.75 -2.66 0.09 81 81 26 61 2.09 MAN TRH -2.48 -2.37 0.11 82 82 28 61 1.23 MAI TRH -2.71 -2.60 0.11 83 83 16 62 1.15 SAN TRH -2.45 -2.35 0.10 84 84 20 62 0.54 SAN TRH -2.43 -2.37 0.06 85 85 22 62 0.54 SAN TRH -2.56 -2.49 0.07 86 86 29 62 0.50 SAN TRH -2.65 -2.65 0.00 87 87 32 62 3.06 SAN TRH -2.78 -2.68 0.10 88 88 33 62 4.56 SAN TRH -2.71 -2.62 0.09 89 89 23 64 3.85 MAN TRH -2.56 -2.40 0.16 90 90 25 64 1.45 SAN TRH -2.58 -2.49 0.09 91 91 31 64 1.23 SAN TRH -2.61 -2.58 0.03 92 92 32 64 3.30 MAN TRH -2.72 -2.44 0.28 93 93 33 64 4.18 SAN TRH -2.74 -2.43 0.31 94 94 7 65 1.24 SAN TRH -2.61 -2.52 0.09 95 95 19 65 1.13 SAN TRH -2.53 -2.45 0.08 Page 19 of 115

TABLE 5 STEAM GENERATOR 21 - HISTORICAL F*0 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 96 96 24 65 2.64 SAN TRH -2.56 -2.48 0.08 97 97 26 65 3.85 MAN TRH -2.61 -2.43 0.18 98 98 27 65 1.71 SAN TRH -2.63 -2.56 0.07 99 99 28 65 0.67 SAN TRH -2.52 -2.44 0.08 100 100 30 65 3.99 MAN TRH -2.55 -2.43 0.12 101 101 33 65 0.94 SAN TRH -2.56 -2.48 0.08 102 102 13 66 1.76 SAN TRH -2.58 -2.50 0.08 103 103 20 66 1.36 SAN TRH -2.56 -2.49 0.07 104 104 23 66 1.98 SAN TRH -2.54 -2.40 0.14 105 105 27 66 3.40 SAN TRH -2.50 -2.25 0.25 106 106 32 66 2.76 SAN TRH -2.64 -2.57 0.07 107 107 17 67 2.66 SAN TRH -1.67 -1.59 0.08 108 108 32 67 2.11 SAN TRH -2.51 -2.40 0.11 109 109 33 67 2.57 MAN TRH -2.51 -2.33 0.18 110 110 1 68 4.82 MAN TRH -2.42 -2.30 0.12 111 111 16 68 1.15 SAI TRH -1.59 -1.51 0.08 112 112 27 68 4.57 SAN TRH -2.68 -2.33 0.35 113 113 2 69 1.85 SAN TRH -2.47 -2.33 0.14 114 114 24 69 3.90 MAN TRH -2.50 -2.34 0.16 115 115 1 70 1.32 SAN TRH -2.57 -2.49 0.08 116 116 27 70 3.48 SAN TRH -2.57 -2.36 0.21 117 117 31 70 2.78 SAN TRH -2.57 -2.46 0.11 118 118 19 71 0.54 SAI TRH -2.38 -2.33 0.05 119 119 23 71 3.00 SAN TRH -2.44 -2.32 0.12 120 120 27 71 2.38 SAN TRH -2.61 -2.47 0.14 121 121 32 71 1.59 SAN TRH -2.46 -2.39 0.07 122 122 33 71 2.70 SAN TRH -2.53 -2.35 0.18 123 123 14 72 1.44 SAN TRH -2.38 -2.38 0.00 124 124 27 72 2.52 MAN TRH -2.58 -2.50 0.08 125 125 30 72 0.60 MAN TRH -2.57 -2.50 0.07 126 126 31 72 2.74 MAN TRH -2.56 -2.31 0.25 127 127 20 73 1.14 SAN TRH -2.43 -2.34 0.09 128 128 26 73 0.80 SAI TRH -2.50 -2.45 0.05 129 129 27 73 1.94 SAN TRH -2.55 -2.47 0.08 130 130 28 73 1.14 SAN TRH -2.53 -2.46 0.07 131 131 30 73 1.71 SAN TRH -2.43 -2.36 0.07 132 132 33 73 1.79 SAI TRH -2.60 -2.55 0.05 133 133 26 74 1.47 SAN TRH -2.52 -2.45 0.07 134 134 30 74 2.22 SAN TRH -2.54 -2.47 0.07 135 135 32 74 4.04 SAN TRH -2.59 -2.42 0.17 136 136 33 74 2.46 SAN TRH -2.58 -2.46 0.12 137 137 12 75 0.38 SAN TRH -2.41 -2.36 0.05 138 138 25 75 1.04 SAN TRH -2.47 -2.39 0.08 139 139 27 75 2.21 MAN TRH -2.51 -2.39 0.12 140 140 28 75 1.17 MAN TRH -2.61 -2.54 0.07 141 141 30 75 1.11 SAN TRH -2.57 -2.50 0.07 142 142 31 75 2.67 MAN TRH -2.64 -2.49 0.15 143 143 32 75 2.81 MAN TRH -2.60 -2.47 0.13 Page 20 of 115

TABLE 5 STEAM GENERATOR 21 - HISTORICAL F*0 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 144 144 33 75 1.70 MAN TRH -2.58 -2.48 0.10 145 145 1 76 5.32 SAN TRH -2.72 -2.41 0.31 146 146 13 76 1.29 SAN TRH -2.50 -2.36 0.14 147 147 15 76 0.68 SAI TRH -2.53 -2.46 0.07 148 148 17 76 1.13 SAI TRH -2.70 -2.63 0.07 149 149 20 76 1.41 SAN TRH -2.50 -2.43 0.07 150 150 21 76 3.69 MAN TRH -2.63 -2.45 0.18 151 151 26 76 4.77 MAN TRH -2.68 -2.53 0.15 152 152 27 76 6.77 MAN TRH -2.74 -2.60 0.14 153 153 31 76 1.34 SAI TRH -2.59 -2.52 0.07 154 154 33 76 3.03 MAN TRH -2.60 -2.48 0.12 155 155 14 77 0.71 SAN TRH -2.59 -2.53 0.06 156 156 25 77 0.90 SAI TRH -2.45 -2.40 0.05 157 157 27 77 2.57 MAN TRH -2.53 -2.37 0.16 158 158 1 78 2.75 MAN TRH -2.67 -2.52 0.15 159 159 16 78 3.29 SAN TRH -2.59 -2.41 0.18 160 160 24 78 2.19 MAN TRH -2.51 -2.41 0.10 161 161 25 78 2.27 SAN TRH -2.69 -2.59 0.10 162 162 27 78 2.02 MAN TRH -2.60 -2.51 0.09 163 163 29 78 2.84 SAN TRH -2.50 -2.38 0.12 164 164 31 78 2.33 SAN TRH -2.44 -2.33 0.11 165 165 32 78 1.60 MAN TRH -2.42 -2.33 0.09 166 166 20 79 4.96 SAN TRH -2.65 -2.40 0.25 167 167 22 79 2.18 MAN TRH -2.51 -2.41 0.10 168 168 25 79 2.06 MAN TRH -2.52 -2.43 0.09 169 169 26 79 3.54 MAN TRH -2.71 -2.49 0.22 170 170 27 79 2.14 MAN TRH -2.65 -2.46 0.19 171 171 28 79 0.74 SAI TRH -2.64 -2.57 0.07 172 172 33 79 1.51 SAN TRH -2.66 -2.53 0.13 173 173 24 80 1.54 MAN TRH -2.65 -2.55 0.10 174 174 25 80 3.20 MAN TRH -2.68 -2.47 0.21 175 175 31 80 0.96 SAN TRH -2.62 -2.58 0.04 176 176 5 81 3.06 SAN TRH -2.52 -2.38 0.14 177 177 14 81 2.33 SAN TRH -2.55 -2.43 0.12 178 178 22 81 1.60 SAN TRH -2.60 -2.45 0.15 179 179 23 81 2.48 SAN TRH -2.54 -2.42 0.12 180 180 25 81 4.19 MAN TRH -2.57 -2.45 0.12 181 181 26 81 0.86 MAI TRH -2.61 -2.55 0.06 182 182 17 82 0.71 SAI TRH -2.67 -2.58 0.09 183 183 22 82 3.49 SAN TRH -2.65 -2.29 0.36 184 184 23 82 3.33 MAN TRH -2.54 -2.34 0.20 185 185 30 82 0.96 SAI TRH -2.56 -2.49 0.07 186 186 1 83 4.43 SAN TRH -2.73 -2.32 0.41 187 187 20 83 1.70 SAN TRH -2.51 -2.45 0.06 188 188 1 84 2.30 SAN TRH -2.66 -2.52 0.14 189 189 25 84 1.12 SAN TRH -2.57 -2.50 0.07 190 190 10 86 1.99 SCN TRH -2.49 -2.40 0.09 191 191 25 86 1.67 MAN TRH -2.63 -2.46 0.17 Page 21 of 115

TABLE 5 STEAM GENERATOR 21 - HISTORICAL F*0 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 192 192 18 88 0.88 SCN TRH -2.72 -2.65 0.07 193 193 6 93 2.14 SAN TRH -2.63 -2.46 0.17 Page 22 of 115

TABLE 6 STEAM GENERATOR 22 - HISTORICAL F*0 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1 1 4 1 1.51 SAN TRH -2.25 -2.13 0.12 2 2 1 2 1.94 SAN TRH -2.52 -2.43 0.09 2 3 1 2 1.10 SAN TRH -2.17 -2.10 0.07 2 4 1 2 1.05 SAN TRH -2.00 -1.92 0.08 3 5 11 6 1.94 SCN TRH -2.44 -2.33 0.11 4 6 3 10 2.05 SAN TRH -2.35 -2.15 0.20 5 7 1 16 1.05 MCN TRH -2.61 -2.27 0.34 6 8 2 27 0.71 SAN TRH -2.58 -2.50 0.08 7 9 8 27 SAD TRH -2.57 8 10 1 28 2.37 SAN TRH -2.57 -2.47 0.10 9 11 2 28 1.63 SAN TRH -2.51 -2.36 0.15 10 12 40 28 1.07 SAI TRH -2.41 -2.31 0.10 11 13 2 29 1.91 SAN TRH -2.55 -2.27 0.28 12 14 3 29 2.23 SAN TRH -2.45 -2.21 0.24 13 15 35 29 0.90 SAI TRH -2.54 -2.49 0.05 14 16 2 30 2.00 SAN TRH -2.54 -2.26 0.28 15 17 43 32 0.75 SAI TRH -2.69 -2.61 0.08 16 18 1 33 4.57 MAN TRH -2.67 -2.39 0.28 17 19 1 34 4.30 SAN TRH -2.68 -2.36 0.32 18 20 42 35 2.76 SAN TRH -2.60 -2.44 0.16 19 21 2 39 0.50 SCN TRH -2.56 -2.40 0.16 20 22 4 41 0.84 SAN TRH -2.49 -2.37 0.12 21 23 2 43 1.21 SAN TRH -2.44 -2.33 0.11 22 24 1 46 3.48 SAN TRH -2.73 -2.46 0.27 23 25 7 48 1.86 SAN TRH -2.61 -2.53 0.08 24 26 8 48 1.50 SAI TRH -2.65 -2.57 0.08 25 27 5 49 2.48 SAN TRH -2.64 -2.49 0.15 26 28 7 49 2.98 SAN TRH -2.65 -2.49 0.16 27 29 4 50 2.15 SAN TRH -2.75 -2.64 0.11 28 30 6 50 2.03 SAN TRH -2.87 -2.76 0.11 29 31 7 50 4.14 SAN TRH -2.64 -2.47 0.17 30 32 4 51 2.50 MAN TRH -2.73 -2.62 0.11 31 33 7 51 3.07 SAN TRH -2.64 -2.49 0.15 32 34 39 51 0.80 SAI TRH -2.45 -2.26 0.19 33 35 1 53 2.85 MAN TRH -2.74 -2.58 0.16 34 36 4 53 0.89 SAI TRH -2.82 -2.74 0.08 35 37 5 53 1.03 SAN TRH -2.61 -2.53 0.08 36 38 6 53 1.91 SAN TRH -2.78 -2.65 0.13 37 39 9 53 0.53 SAI TRH -2.63 -2.47 0.16 38 40 34 53 1.21 MAN TRH -2.32 -2.20 0.12 39 41 5 54 2.70 MAN TRH -2.62 -2.45 0.17 40 42 3 55 0.76 SAN TRH -2.60 -2.52 0.08 41 43 6 55 1.37 SAN TRH -2.89 -2.78 0.11 42 44 34 55 3.39 MAN TRH -2.60 -2.35 0.25 43 45 2 56 1.99 MAN TRH -2.75 -2.65 0.10 44 46 3 56 1.01 MAN TRH -2.61 -2.53 0.08 45 47 34 56 3.78 MAN TRH -2.63 -2.41 0.22 Page 23 of 115

TABLE 6 STEAM GENERATOR 22 - HISTORICAL F*0 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 46 48 24 57 0.20 SVN TRH -2.46 -2.24 0.22 47 49 6 58 2.08 SAN TRH -2.82 -2.71 0.11 48 50 9 58 1.44 SAN TRH -2.61 -2.50 0.11 49 51 34 58 4.80 MAN TRH -2.64 -2.27 0.37 50 52 10 59 0.46 SAI TRH -2.53 -2.50 0.03 51 53 26 59 1.79 MAN TRH -2.50 -2.36 0.14 52 54 34 60 2.38 MAN TRH -2.57 -2.44 0.13 53 55 11 61 1.86 SAN TRH -2.54 -2.43 0.11 54 56 35 62 1.01 MAI TRH -2.56 -2.44 0.12 55 57 6 63 0.67 SAI TRH -2.56 -2.49 0.07 56 58 8 63 2.89 SAN TRH -2.64 -2.42 0.22 57 59 9 63 1.36 SAN TRH -2.59 -2.50 0.09 58 60 17 63 2.72 MAN TRH -2.60 -2.42 0.18 59 61 18 63 1.72 MAN TRH -2.52 -2.44 0.08 60 62 34 63 3.04 MAN TRH -2.47 -2.15 0.32 61 63 35 63 1.53 SAI TRH -2.27 -2.19 0.08 62 64 5 64 2.57 SAN TRH -2.55 -2.37 0.18 63 65 6 64 2.45 SAN TRH -2.65 -2.53 0.12 64 66 8 64 2.33 SAN TRH -2.63 -2.48 0.15 65 67 4 65 0.83 MAI TRH -2.57 -2.46 0.11 66 68 35 65 0.95 SAN TRH -2.28 -2.22 0.06 67 69 4 66 0.52 SAN TRH -2.42 -2.35 0.07 68 70 7 66 1.08 SAN TRH -2.47 -2.39 0.08 69 71 8 66 3.45 MAN TRH -2.56 -2.24 0.32 70 72 8 67 2.43 SAN TRH -2.56 -2.28 0.28 71 73 36 67 1.42 MAN TRH -2.31 -2.21 0.10 72 74 7 68 1.45 SAN TRH -2.53 -2.35 0.18 73 75 8 68 4.46 SAN TRH -2.58 -2.23 0.35 74 76 1 69 8.54 MAN TRH -2.65 -2.29 0.36 75 77 8 69 0.88 SAI TRH -2.51 -2.43 0.08 76 78 10 69 1.18 SAN TRH -2.58 -2.50 0.08 77 79 34 69 1.35 SAN TRH -2.53 -2.33 0.20 78 80 35 69 1.17 SAN TRH -2.52 -2.38 0.14 79 81 1 70 5.28 MAN TRH -2.65 -2.22 0.43 80 82 7 70 0.85 SAN TRH -2.60 -2.52 0.08 81 83 8 70 1.60 SAN TRH -2.50 -2.40 0.10 82 84 9 70 1.23 SAN TRH -2.48 -2.41 0.07 83 85 35 70 0.82 SAI TRH -2.60 -2.50 0.10 84 86 36 70 1.07 SAI TRH -2.57 -2.48 0.09 85 87 37 70 2.42 MAN TRH -2.66 -2.35 0.31 86 88 6 71 2.96 SAN TRH -2.52 -2.19 0.33 87 89 7 71 1.54 SAN TRH -2.43 -2.35 0.08 88 90 8 71 1.55 MAN TRH -2.52 -2.36 0.16 89 91 11 71 2.65 SAN TRH -2.58 -2.43 0.15 90 92 24 71 3.69 MAN TRH -2.35 -2.10 0.25 91 93 34 71 1.06 SAI TRH -2.31 -2.25 0.06 92 94 36 71 0.55 SAI TRH -2.26 -2.22 0.04 93 95 1 72 7.53 MAN TRH -2.73 -2.26 0.47 Page 24 of 115

TABLE 6 STEAM GENERATOR 22 - HISTORICAL F*0 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 94 96 2 72 0.93 SAN TRH -2.62 -2.55 0.07 95 97 5 72 1.97 SAN TRH -2.50 -2.40 0.10 96 98 6 72 1.82 SAN TRH -2.50 -2.40 0.10 97 99 7 72 1.02 SAN TRH -2.48 -2.38 0.10 98 100 36 72 2.01 SAN TRH -2.34 -2.26 0.08 99 101 37 72 3.26 SAN TRH -2.40 -2.11 0.29 100 102 5 73 2.13 SAN TRH -2.54 -2.27 0.27 101 103 1 74 9.53 MAN TRH -2.66 -2.30 0.36 102 104 2 74 0.84 SAN TRH -2.44 -2.37 0.07 103 105 5 74 2.29 SAN TRH -2.52 -2.40 0.12 104 106 6 74 2.09 MAN TRH -2.47 -2.34 0.13 105 107 5 75 1.01 SAN TRH -2.50 -2.41 0.09 106 108 6 75 2.86 SAN TRH -2.58 -2.29 0.29 107 109 9 75 0.90 SAI TRH -2.59 -2.51 0.08 108 110 1 76 6.61 MAN TRH -2.67 -2.36 0.31 109 111 6 76 1.05 SAN TRH -2.55 -2.45 0.10 110 112 1 77 7.90 MAN TRH -2.63 -2.40 0.23 111 113 4 77 1.53 MAN TRH -2.46 -2.34 0.12 112 114 6 77 2.23 MAN TRH -2.46 -2.35 0.11 113 115 1 78 6.85 MAN TRH -2.62 -2.29 0.33 114 116 2 78 0.96 SAN TRH -2.49 -2.42 0.07 115 117 4 78 1.57 SAN TRH -2.62 -2.52 0.10 116 118 5 78 1.39 SAN TRH -2.51 -2.45 0.06 117 119 7 78 0.84 SAN TRH -2.48 -2.41 0.07 118 120 1 79 5.34 MAN TRH -2.62 -2.51 0.11 119 121 3 79 3.76 MAN TRH -2.52 -2.41 0.11 120 122 8 79 0.69 SAI TRH -2.49 -2.41 0.08 121 123 1 80 7.07 MAN TRH -2.65 -2.23 0.42 122 124 4 80 1.38 MAN TRH -2.55 -2.49 0.06 123 125 5 80 2.96 SAN TRH -2.58 -2.46 0.12 124 126 7 80 1.07 SAI TRH -2.63 -2.56 0.07 125 127 2 81 1.57 SAN TRH -2.59 -2.51 0.08 126 128 5 81 1.34 SAN TRH -2.58 -2.46 0.12 127 129 6 81 1.51 SAN TRH -2.59 -2.45 0.14 128 130 7 81 1.18 SAN TRH -2.56 -2.44 0.12 129 131 1 82 5.66 MAN TRH -2.65 -2.31 0.34 130 132 3 82 1.05 SAI TRH -2.58 -2.51 0.07 131 133 4 82 1.56 MAN TRH -2.58 -2.47 0.11 132 134 5 82 2.67 SAN TRH -2.57 -2.43 0.14 133 135 7 82 1.33 SAI TRH -2.53 -2.39 0.14 134 136 1 83 8.05 MAN TRH -2.70 -2.27 0.43 135 137 6 83 1.00 SAI TRH -2.57 -2.49 0.08 136 138 7 83 0.90 SAN TRH -2.60 -2.49 0.11 137 139 5 84 2.79 MAN TRH -2.51 -2.41 0.10 138 140 6 84 1.06 SAI TRH -2.55 -2.42 0.13 139 141 6 85 4.06 SAN TRH -2.43 -2.25 0.18 140 142 7 85 2.27 SAN TRH -2.48 -2.32 0.16 141 143 8 85 1.46 SAN TRH -2.63 -2.55 0.08 Page 25 of 115

TABLE 6 STEAM GENERATOR 22 - HISTORICAL F*0 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 142 144 6 86 2.57 SAN TRH -2.55 -2.44 0.11 143 145 1 87 6.55 MAN TRH -2.52 -2.27 0.25 144 146 5 87 1.46 SAN TRH -2.42 -2.35 0.07 145 147 4 88 0.22 SAN TRH -2.62 -2.55 0.07 146 148 9 88 2.12 SAN TRH -2.65 -2.54 0.11 147 149 13 88 1.45 SAN TRH -1.83 -1.75 0.08 148 150 15 88 3.20 MAN TRH -2.71 -2.51 0.20 149 151 6 91 0.87 SAN TRH -2.54 -2.49 0.05 150 152 6 94 1.33 MAN TRH -2.60 -2.49 0.11 151 153 7 94 1.21 SAN TRH -2.54 -2.43 0.11 Page 26 of 115

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1 1 3 3 1.54 SAN 1BH -3.75 -3.56 0.19 1 2 3 3 SAD 1BH -1.53 2 3 5 3 SAD 1BH -1.04 3 4 14 3 4.14 SAN 1BH -3.55 -3.41 0.14 3 5 14 3 MAD 1BH -1.63 4 6 3 4 1.00 SAN 1BH -3.68 -3.57 0.11 4 7 3 4 SAD 1BH -1.01 5 8 4 4 1.57 SAN 1BH -3.54 -3.44 0.10 5 9 4 4 SAD 1BH -0.85 6 10 6 4 2.62 SAN 1BH -3.63 -3.48 0.15 6 11 6 4 SAD 1BH -1.16 7 12 7 4 SAD 1BH -1.00 8 13 3 5 SAD 1BH -1.58 9 14 7 5 2.97 SAN 1BH -3.65 -3.47 0.18 9 15 7 5 MAD 1BH -1.16 10 16 8 5 SAD 1BH -0.98 11 17 1 6 4.66 SAN 1BH -3.73 -3.41 0.32 11 18 1 6 SAD 1BH -1.00 12 19 3 6 5.07 MAN 1BH -3.68 -3.44 0.24 12 20 3 6 SAD 1BH -1.61 13 21 15 6 SAD 1BH -0.88 14 22 7 7 5.43 MAN 1BH -3.60 -3.45 0.15 14 23 7 7 SAD 1BH -1.74 15 24 13 7 2.66 SAN 1BH -3.79 -3.64 0.15 15 25 13 7 MAD 1BH -1.00 16 26 17 7 1.02 SAN 1BH -3.65 -3.57 0.08 16 27 17 7 MAD 1BH -1.16 17 28 1 8 6.84 MAN 1BH -3.66 -3.35 0.31 17 29 1 8 MAD 1BH -1.31 18 30 2 8 5.03 SAN 1BH -3.66 -3.42 0.24 18 31 2 8 SAD 1BH -1.60 19 32 5 8 5.00 MAN 1BH -3.75 -3.64 0.11 19 33 5 8 SAD 1BH -1.05 20 34 10 8 MAD 1BH -0.90 21 35 13 8 2.50 MAN 1BH -3.75 -3.60 0.15 21 36 13 8 MAD 1BH -1.35 22 37 14 8 SAD 1BH -0.85 23 38 24 8 2.16 SAN 1BH -3.69 -3.61 0.08 23 39 24 8 MAD 1BH -0.85 24 40 2 9 MAD 1BH -0.90 25 41 3 9 SAD 1BH -1.60 26 42 4 9 4.98 MAN 1BH -3.75 -3.51 0.24 26 43 4 9 MAD 1BH -1.48 27 44 5 9 SAD 1BH -1.37 28 45 7 9 8.65 MAN 1BH -3.69 -3.30 0.39 28 46 7 9 MAD 1BH -1.22 29 47 11 9 MAD 1BH -1.34 Page 27 of 115

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 30 48 12 9 4.26 SAN 1BH -3.68 -3.51 0.17 30 49 12 9 SAD 1BH -0.84 31 50 18 9 MAD 1BH -1.49 32 51 21 9 MCD 1BH -1.05 32 52 21 9 MAD 1BH -1.04 33 53 25 9 3.85 MAN 1BH -3.54 -3.44 0.10 33 54 25 9 SAD 1BH -0.85 34 55 2 10 4.48 SAN 1BH -3.70 -3.46 0.24 34 56 2 10 SAD 1BH -0.85 35 57 4 10 1.01 SAN 1BH -3.63 -3.53 0.10 35 58 4 10 SAD 1BH -1.39 36 59 5 10 SAD 1BH -1.10 37 60 11 10 SAD 1BH -1.03 38 61 12 10 4.72 SAN 1BH -3.74 -3.46 0.28 38 62 12 10 SAD 1BH -1.25 39 63 14 10 3.93 SAN 1BH -3.57 -3.42 0.15 39 64 14 10 MAD 1BH -0.90 40 65 19 10 1.95 SAN 1BH -3.65 -3.42 0.23 40 66 19 10 SAD 1BH -1.05 41 67 20 10 SAD 1BH -1.33 42 68 1 11 7.52 MAN 1BH -3.73 -3.60 0.13 42 69 1 11 SAD 1BH -1.48 43 70 3 11 3.68 MAN 1BH -3.72 -3.54 0.18 43 71 3 11 SAD 1BH -1.61 43 72 3 11 1.47 MAN 1BH -0.65 -0.29 0.36 44 73 5 11 6.33 SAN 1BH -3.64 -3.52 0.12 44 74 5 11 1.26 MAN 1BH -1.19 -1.12 0.07 45 75 6 11 3.11 MAN 1BH -3.66 -3.54 0.12 45 76 6 11 SAD 1BH -1.40 46 77 10 11 SAD 1BH -1.14 47 78 13 11 3.82 MAN 1BH -3.64 -3.51 0.13 47 79 13 11 SAD 1BH -0.78 48 80 14 11 MAD 1BH -1.12 49 81 15 11 1.46 SAN 1BH -3.59 -3.49 0.10 49 82 15 11 MAD 1BH -1.30 50 83 23 11 2.45 MAN 1BH -3.69 -3.62 0.07 50 84 23 11 MAD 1BH -1.50 51 85 24 11 3.01 MAN 1BH -3.70 -3.62 0.08 51 86 24 11 MAD 1BH -1.30 51 87 24 11 4.04 MAN 1BH -0.45 -0.02 0.43 52 88 1 12 4.29 MAN 1BH -3.74 -3.28 0.46 52 89 1 12 SAD 1BH -1.32 53 90 2 12 4.24 SAN 1BH -3.75 -3.61 0.14 53 91 2 12 SAD 1BH -1.47 54 92 4 12 SAD 1BH -1.06 55 93 5 12 3.01 MAN 1BH -3.71 -3.43 0.28 55 94 5 12 SAD 1BH -1.09 56 95 6 12 IRR 1BH -1.43 Page 28 of 115

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 57 96 9 12 SAD 1BH -1.33 58 97 11 12 SAD 1BH -1.06 59 98 13 12 SAD 1BH -0.90 60 99 22 12 0.95 SAN 1BH -3.64 -3.57 0.07 60 100 22 12 SAD 1BH -1.40 61 101 23 12 1.25 MAN 1BH -3.63 -3.56 0.07 61 102 23 12 MAD 1BH -1.43 62 103 26 12 2.09 SAN 1BH -3.54 -3.47 0.07 62 104 26 12 SAD 1BH -0.80 63 105 2 13 8.21 MAN 1BH -3.65 -3.53 0.12 63 106 2 13 4.78 MAN 1BH -1.35 -0.93 0.42 64 107 5 13 SAD 1BH -1.48 65 108 8 13 MAD 1BH -1.12 66 109 11 13 MAD 1BH -1.33 67 110 13 13 1.21 SAN 1BH -3.34 -3.28 0.06 67 111 13 13 SAD 1BH -1.40 68 112 14 13 2.12 MAN 1BH -3.54 -3.43 0.11 68 113 14 13 SAD 1BH -1.33 69 114 15 13 1.86 SAN 1BH -3.59 -3.45 0.14 69 115 15 13 MAD 1BH -1.19 70 116 21 13 0.76 SAN 1BH -3.44 -3.36 0.08 70 117 21 13 SAD 1BH -1.24 71 118 27 13 1.80 MAN 1BH -3.66 -3.58 0.08 71 119 27 13 MAD 1BH -0.88 72 120 2 14 4.84 SAN 1BH -3.75 -3.45 0.30 72 121 2 14 1.38 SAN 1BH -1.06 -0.91 0.15 73 122 4 14 2.37 SAN 1BH -3.74 -3.53 0.21 73 123 4 14 MAD 1BH -1.22 74 124 5 14 2.53 MAN 1BH -3.64 -3.37 0.27 74 125 5 14 SAD 1BH -2.14 75 126 7 14 3.92 MAN 1BH -3.75 -3.59 0.16 76 127 9 14 MAD 1BH -1.35 77 128 13 14 SAD 1BH -1.17 78 129 15 14 MAD 1BH -1.21 79 130 22 14 SAD 1BH -1.17 80 131 23 14 SAD 1BH -1.30 81 132 1 15 2.56 MAN 1BH -1.46 -1.17 0.29 82 133 2 15 4.68 MAN 1BH -3.52 -3.30 0.22 82 134 2 15 SAD 1BH -1.38 83 135 4 15 0.78 SAN 1BH -3.65 -3.58 0.07 83 136 4 15 MAD 1BH -1.02 84 137 5 15 1.66 MAN 1BH -3.59 -3.50 0.09 84 138 5 15 1.50 MAN 1BH -3.58 -3.51 0.07 84 139 5 15 SAD 1BH -1.17 84 140 5 15 SAD 1BH -1.17 85 141 8 15 SAD 1BH -1.21 86 142 10 15 SAD 1BH -1.37 87 143 11 15 SAD 1BH -0.89 Page 29 of 115

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 88 144 14 15 SAD 1BH -1.26 89 145 15 15 1.98 SAN 1BH -3.66 -3.48 0.18 89 146 15 15 SAD 1BH -0.90 90 147 19 15 1.23 SAN 1BH -3.61 -3.42 0.19 90 148 19 15 MAD 1BH -1.21 91 149 20 15 1.23 SAN 1BH -3.66 -3.58 0.08 91 150 20 15 SAD 1BH -0.89 92 151 21 15 MAD 1BH -0.87 93 152 22 15 1.00 SAN 1BH -3.36 -3.32 0.04 93 153 22 15 SAD 1BH -1.22 94 154 23 15 1.63 SAN 1BH -3.34 -3.31 0.03 94 155 23 15 SAD 1BH -1.18 95 156 26 15 2.72 MAN 1BH -3.65 -3.47 0.18 95 157 26 15 SAD 1BH -0.85 96 158 27 15 4.71 MAN 1BH -3.69 -3.48 0.21 96 159 27 15 SAD 1BH -1.31 97 160 1 16 8.76 MAN 1BH -3.62 -3.44 0.18 97 161 1 16 SAD 1BH -1.34 98 162 3 16 2.79 MAN 1BH -3.68 -3.43 0.25 98 163 3 16 SAD 1BH -1.16 99 164 4 16 2.52 MAN 1BH -3.67 -3.51 0.16 99 165 4 16 1.86 MAN 1BH -1.31 -1.10 0.21 100 166 5 16 2.64 SAN 1BH -3.70 -3.50 0.20 100 167 5 16 SAD 1BH -1.16 101 168 6 16 3.73 MAN 1BH -3.71 -3.54 0.17 101 169 6 16 SAD 1BH -0.90 102 170 7 16 5.50 MAN 1BH -3.71 -3.43 0.28 102 171 7 16 SAD 1BH -0.80 103 172 8 16 3.03 SAN 1BH -3.76 -3.55 0.21 103 173 8 16 MAD 1BH -1.20 104 174 10 16 SAD 1BH -0.88 105 175 13 16 2.20 MAN 1BH -3.75 -3.42 0.33 105 176 13 16 MAD 1BH -1.16 106 177 14 16 3.38 SAN 1BH -3.71 -3.42 0.29 106 178 14 16 MAD 1BH -1.35 107 179 15 16 5.01 SAN 1BH -3.73 -3.50 0.23 107 180 15 16 SAD 1BH -0.85 108 181 16 16 2.22 SAN 1BH -3.69 -3.55 0.14 108 182 16 16 MAD 1BH -0.80 109 183 17 16 SAD 1BH -1.28 110 184 18 16 4.74 MAN 1BH -3.71 -3.48 0.23 110 185 18 16 SAD 1BH -1.24 111 186 24 16 3.18 MAN 1BH -3.50 -3.42 0.08 111 187 24 16 MAD 1BH -1.39 112 188 28 16 0.87 MAN 1BH -3.53 -3.48 0.05 112 189 28 16 SAD 1BH -0.90 113 190 29 16 1.56 MAN 1BH -1.20 -1.10 0.10 114 191 30 16 MAD 1BH -0.85 Page 30 of 115

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 115 192 6 17 3.63 MAN 1BH -3.57 -3.48 0.09 115 193 6 17 SAD 1BH -0.92 116 194 7 17 3.57 MAN 1BH -3.57 -3.46 0.11 116 195 7 17 SAD 1BH -1.03 117 196 10 17 SAD 1BH -1.37 118 197 11 17 SAD 1BH -1.32 119 198 13 17 SAD 1BH -1.31 120 199 16 17 MAD 1BH -1.00 121 200 19 17 SAD 1BH -1.32 122 201 22 17 SAD 1BH -1.35 123 202 2 18 1.23 SAN 1BH -3.60 -3.49 0.11 123 203 2 18 SAD 1BH -0.89 124 204 3 18 0.99 SAN 1BH -1.23 -1.15 0.08 124 205 3 18 0.44 SAN 1BH -0.46 -0.38 0.08 125 206 5 18 3.44 MAN 1BH -1.36 -0.93 0.43 126 207 10 18 MAD 1BH -1.25 127 208 11 18 SAD 1BH -1.40 128 209 16 18 SAD 1BH -1.44 129 210 18 18 MAD 1BH -0.82 130 211 20 18 SAD 1BH -0.85 131 212 22 18 SAD 1BH -1.15 132 213 24 18 1.01 SAN 1BH -3.48 -3.45 0.03 132 214 24 18 MAD 1BH -0.80 133 215 25 18 1.55 MAN 1BH -3.45 -3.37 0.08 133 216 25 18 SAD 1BH -2.11 133 217 25 18 0.62 SAN 1BH -0.86 -0.76 0.10 134 218 29 18 SAD 1BH -1.04 135 219 31 18 SAD 1BH -1.22 136 220 1 19 7.90 MAN 1BH -3.70 -3.48 0.22 136 221 1 19 4.81 MAN 1BH -1.21 -1.10 0.11 137 222 2 19 SAD 1BH -1.39 138 223 4 19 SAD 1BH -1.20 139 224 7 19 3.52 MAN 1BH -3.56 -3.46 0.10 139 225 7 19 MAD 1BH -1.04 140 226 8 19 2.72 MAN 1BH -3.65 -3.54 0.11 140 227 8 19 SAD 1BH -1.32 141 228 11 19 MAD 1BH -1.37 142 229 12 19 MAD 1BH -1.20 143 230 14 19 0.76 SAN 1BH -3.61 -3.57 0.04 143 231 14 19 SAD 1BH -0.85 144 232 15 19 SAD 1BH -1.12 145 233 16 19 0.99 SAN 1BH -3.51 -3.43 0.08 145 234 16 19 SAD 1BH -1.20 146 235 17 19 4.07 SAN 1BH -3.62 -3.51 0.11 146 236 17 19 MAD 1BH -0.86 147 237 20 19 SAD 1BH -1.21 148 238 23 19 SAD 1BH -1.06 149 239 24 19 SAD 1BH -0.90 Page 31 of 115

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 150 240 27 19 3.52 SAN 1BH -3.63 -3.30 0.33 150 241 27 19 MAD 1BH -1.10 151 242 30 19 SAD 1BH -1.37 152 243 31 19 2.09 SAN 1BH -3.72 -3.40 0.32 152 244 31 19 MAD 1BH -1.30 153 245 32 19 SAD 1BH -1.42 154 246 6 20 5.07 MAN 1BH -3.76 -3.57 0.19 154 247 6 20 SAD 1BH -0.90 155 248 7 20 4.97 MAN 1BH -3.74 -3.48 0.26 155 249 7 20 3.54 MAN 1BH -1.30 -1.02 0.28 156 250 9 20 SAD 1BH -1.16 157 251 11 20 SAD 1BH -1.06 158 252 12 20 SAD 1BH -0.88 159 253 13 20 2.61 MAN 1BH -1.29 -1.07 0.22 160 254 16 20 SAD 1BH -1.20 161 255 19 20 1.33 SAN 1BH -3.70 -3.62 0.08 161 256 19 20 SAD 1BH -1.40 162 257 20 20 SAD 1BH -1.23 163 258 23 20 2.42 MAN 1BH -3.47 -3.39 0.08 163 259 23 20 MAD 1BH -1.42 164 260 24 20 MAD 1BH -0.80 165 261 25 20 3.47 MAN 1BH -3.63 -3.50 0.13 165 262 25 20 SAD 1BH -0.82 166 263 26 20 SAD 1BH -0.88 167 264 28 20 SAD 1BH -0.80 168 265 29 20 1.27 MAN 1BH -1.19 -1.07 0.12 169 266 30 20 SAD 1BH -1.40 170 267 32 20 SAD 1BH -1.12 171 268 36 20 MAD 1BH -1.37 172 269 37 20 MAD 1BH -1.35 173 270 6 21 4.05 MAN 1BH -3.47 -3.33 0.14 173 271 6 21 0.58 SAN 1BH -1.16 -1.11 0.05 174 272 8 21 3.10 MAN 1BH -3.43 -3.32 0.11 174 273 8 21 SAD 1BH -1.15 175 274 17 21 1.61 SAN 1BH -3.53 -3.42 0.11 175 275 17 21 1.58 MAN 1BH -1.18 -1.09 0.09 176 276 19 21 SAD 1BH -1.03 177 277 20 21 MAD 1BH -0.88 178 278 22 21 MAD 1BH -0.90 179 279 26 21 1.03 MAN 1BH -3.75 -3.69 0.06 179 280 26 21 SAD 1BH -1.25 180 281 27 21 1.38 SAN 1BH -3.73 -3.62 0.11 180 282 27 21 SAD 1BH -1.47 181 283 28 21 SAD 1BH -0.85 182 284 29 21 2.05 SAN 1BH -3.73 -3.65 0.08 182 285 29 21 SAD 1BH -0.85 183 286 30 21 SAD 1BH -1.40 184 287 33 21 5.87 SAN 1BH -3.68 -3.43 0.25 Page 32 of 115

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 184 288 33 21 SAD 1BH -1.26 185 289 36 21 SAD 1BH -1.25 186 290 1 22 8.03 MAN 1BH -3.80 -3.37 0.43 186 291 1 22 3.36 MAN 1BH -1.32 -0.99 0.33 187 292 4 22 1.91 MAN 1BH -1.20 -1.09 0.11 188 293 5 22 4.89 MAN 1BH -3.86 -3.54 0.32 188 294 5 22 SAD 1BH -0.84 189 295 6 22 1.77 MAN 1BH -3.65 -3.53 0.12 189 296 6 22 SAD 1BH -0.89 190 297 9 22 SAD 1BH -1.16 191 298 10 22 MAD 1BH -1.16 191 299 10 22 SAD 1BH -0.90 192 300 12 22 SAD 1BH -0.80 193 301 13 22 MAD 1BH -1.20 194 302 14 22 0.78 MAN 1BH -1.19 -1.04 0.15 195 303 17 22 1.66 MAN 1BH -1.18 -1.01 0.17 196 304 18 22 SAD 1BH -1.16 197 305 19 22 MAD 1BH -1.20 198 306 20 22 SAD 1BH -0.88 199 307 21 22 MAD 1BH -1.31 200 308 22 22 SAD 1BH -0.85 201 309 24 22 MAD 1BH -0.85 202 310 26 22 2.92 MAN 1BH -3.60 -3.49 0.11 202 311 26 22 MAD 1BH -0.87 203 312 28 22 1.11 SAN 1BH -3.61 -3.54 0.07 203 313 28 22 SAD 1BH -1.28 204 314 30 22 MAD 1BH -0.90 205 315 32 22 3.77 MAN 1BH -3.58 -3.45 0.13 205 316 32 22 SAD 1BH -1.39 206 317 37 22 MAD 1BH -1.49 207 318 1 23 6.57 MAN 1BH -3.78 -3.35 0.43 207 319 1 23 MAD 1BH -1.00 208 320 5 23 0.92 SAN 1BH -3.46 -3.42 0.04 208 321 5 23 MAD 1BH -1.40 209 322 6 23 5.55 MAN 1BH -3.58 -3.32 0.26 209 323 6 23 1.22 MAN 1BH -1.18 -0.96 0.22 210 324 8 23 1.87 MAN 1BH -3.58 -3.37 0.21 210 325 8 23 MAD 1BH -1.30 211 326 9 23 SAD 1BH -1.29 211 327 9 23 1.68 MAN 1BH -0.45 -0.18 0.27 212 328 10 23 SAD 1BH -0.87 213 329 12 23 MAD 1BH -1.21 214 330 14 23 2.61 MAN 1BH -1.22 -0.96 0.26 215 331 15 23 MAD 1BH -1.16 216 332 17 23 MAD 1BH -1.30 217 333 18 23 MAD 1BH -0.99 218 334 20 23 SAD 1BH -0.85 219 335 21 23 MAD 1BH -0.98 Page 33 of 115

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 220 336 24 23 3.66 MAN 1BH -3.75 -3.43 0.32 220 337 24 23 MAD 1BH -0.83 221 338 25 23 MAD 1BH -0.78 222 339 26 23 MAD 1BH -0.97 223 340 27 23 1.86 SAN 1BH -3.72 -3.54 0.18 223 341 27 23 SAD 1BH -1.17 224 342 34 23 SAD 1BH -1.17 225 343 35 23 MAD 1BH -1.03 226 344 37 23 SAD 1BH -1.38 227 345 38 23 MAD 1BH -1.29 228 346 2 24 SAD 1BH -1.35 229 347 4 24 2.55 SAN 1BH -3.70 -3.59 0.11 229 348 4 24 MAD 1BH -1.23 230 349 7 24 4.95 MAN 1BH -3.67 -3.51 0.16 230 350 7 24 SAD 1BH -1.32 231 351 8 24 2.91 MAN 1BH -3.71 -3.55 0.16 231 352 8 24 SAD 1BH -1.26 232 353 9 24 1.93 SAN 1BH -1.18 -1.06 0.12 233 354 11 24 MAD 1BH -1.16 234 355 12 24 2.71 MAN 1BH -1.36 -1.07 0.29 235 356 13 24 SAD 1BH -1.01 236 357 15 24 SAD 1BH -0.89 237 358 16 24 MAD 1BH -1.20 238 359 18 24 SAD 1BH -0.80 239 360 19 24 MAD 1BH -0.82 240 361 20 24 MAD 1BH -1.34 241 362 23 24 SAD 1BH -0.94 242 363 25 24 2.79 SAN 1BH -3.73 -3.59 0.14 242 364 25 24 SAD 1BH -1.25 243 365 26 24 MAD 1BH -0.85 244 366 28 24 2.31 SAN 1BH -3.74 -3.64 0.10 244 367 28 24 SAD 1BH -0.93 245 368 29 24 SAD 1BH -1.14 246 369 30 24 2.10 MAN 1BH -3.70 -3.55 0.15 246 370 30 24 MAD 1BH -1.31 247 371 31 24 3.05 MAN 1BH -3.75 -3.62 0.13 247 372 31 24 SAD 1BH -0.98 248 373 32 24 MAD 1BH -0.94 249 374 35 24 SAD 1BH -0.83 250 375 37 24 SAD 1BH -1.32 251 376 5 25 SAD 1BH -1.17 252 377 6 25 MAD 1BH -1.20 253 378 7 25 SAD 1BH -1.30 253 379 7 25 1.05 SAN 1BH -0.39 -0.24 0.15 254 380 9 25 SAD 1BH -0.82 255 381 10 25 SAD 1BH -1.29 256 382 11 25 MAD 1BH -1.00 257 383 13 25 MAD 1BH -0.93 Page 34 of 115

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 258 384 16 25 2.91 SAN 1BH -1.09 -0.98 0.11 259 385 17 25 SAD 1BH -1.21 260 386 20 25 MAD 1BH -1.26 261 387 21 25 MAD 1BH -0.86 262 388 24 25 2.79 MAN 1BH -3.63 -3.53 0.10 262 389 24 25 SAD 1BH -1.00 263 390 25 25 MAD 1BH -1.25 264 391 28 25 2.27 SAN 1BH -3.66 -3.55 0.11 264 392 28 25 SAD 1BH -1.06 265 393 30 25 1.22 SAN 1BH -3.60 -3.47 0.13 265 394 30 25 MAD 1BH -1.39 266 395 31 25 1.34 SAN 1BH -3.70 -3.58 0.12 266 396 31 25 MAD 1BH -0.85 267 397 38 25 MAD 1BH -0.89 268 398 1 26 1.89 SAN 1BH -3.77 -3.58 0.19 268 399 1 26 SAD 1BH -0.95 269 400 3 26 MAD 1BH -0.85 270 401 8 26 SAD 1BH -1.25 271 402 10 26 MAD 1BH -0.91 272 403 11 26 MAD 1BH -0.90 273 404 13 26 MAD 1BH -1.27 274 405 14 26 SAD 1BH -1.02 275 406 15 26 2.06 SAN 1BH -3.67 -3.52 0.15 275 407 15 26 MAD 1BH -0.85 276 408 16 26 SAD 1BH -1.26 277 409 17 26 1.47 MAN 1BH -3.73 -3.65 0.08 277 410 17 26 1.33 SAN 1BH -1.14 -1.10 0.04 278 411 19 26 MAD 1BH -1.27 279 412 21 26 SAD 1BH -1.02 280 413 22 26 SAD 1BH -1.22 281 414 24 26 1.83 SAN 1BH -3.64 -3.53 0.11 281 415 24 26 SAD 1BH -0.85 282 416 25 26 1.25 SAN 1BH -3.68 -3.58 0.10 282 417 25 26 SAD 1BH -1.13 283 418 27 26 SAD 1BH -0.85 284 419 28 26 0.99 SAN 1BH -3.69 -3.62 0.07 284 420 28 26 SAD 1BH -0.93 285 421 30 26 1.74 MAN 1BH -3.63 -3.55 0.08 285 422 30 26 SAD 1BH -0.90 286 423 34 26 SAD 1BH -1.10 287 424 2 27 SAD 1BH -1.20 288 425 3 27 SAD 1BH -1.46 289 426 4 27 MAD 1BH -0.93 289 427 4 27 4.56 MAN 1BH -0.83 -0.15 0.68 290 428 5 27 1.70 SAN 1BH -1.97 -1.60 0.37 291 429 6 27 SAD 1BH -0.87 292 430 8 27 0.79 SAN 1BH -1.20 -1.13 0.07 293 431 9 27 SAD 1BH -1.23 Page 35 of 115

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 294 432 11 27 MAD 1BH -0.85 295 433 13 27 SAD 1BH -1.28 296 434 16 27 SAD 1BH -1.21 297 435 17 27 2.12 MAN 1BH -1.19 -1.04 0.15 298 436 18 27 SAD 1BH -1.33 299 437 19 27 MAD 1BH -0.88 300 438 24 27 SAD 1BH -0.95 301 439 25 27 SAD 1BH -0.99 302 440 27 27 MAD 1BH -1.30 303 441 31 27 MAD 1BH -0.79 304 442 32 27 1.88 MAN 1BH -3.75 -3.64 0.11 304 443 32 27 2.00 SAN 1BH -1.24 -1.17 0.07 305 444 33 27 1.84 MAN 1BH -3.69 -3.59 0.10 305 445 33 27 SAD 1BH -0.85 306 446 34 27 MAD 1BH -0.85 307 447 35 27 SAD 1BH -1.06 308 448 37 27 MAD 1BH -0.90 309 449 39 27 SAD 1BH -0.78 310 450 1 28 4.25 MAN 1BH -1.27 -0.94 0.33 311 451 5 28 0.92 MAN 1BH -1.32 -1.11 0.21 312 452 6 28 SAD 1BH -1.30 313 453 8 28 SAD 1BH -1.20 314 454 10 28 SAD 1BH -1.30 315 455 20 28 SAD 1BH -1.25 316 456 24 28 SAD 1BH -0.92 317 457 28 28 1.17 SAN 1BH -3.68 -3.62 0.06 317 458 28 28 SAD 1BH -1.18 318 459 30 28 2.54 SAN 1BH -3.69 -3.57 0.12 318 460 30 28 SAD 1BH -1.15 319 461 31 28 3.00 SAN 1BH -3.65 -3.50 0.15 319 462 31 28 MAD 1BH -1.19 320 463 32 28 2.80 SAN 1BH -3.74 -3.63 0.11 320 464 32 28 SAD 1BH -0.96 321 465 33 28 2.03 MAN 1BH -3.74 -3.60 0.14 321 466 33 28 SAD 1BH -1.03 322 467 35 28 SAD 1BH -0.85 323 468 39 28 SAD 1BH -1.32 324 469 2 29 MAD 1BH -1.04 325 470 3 29 SAD 1BH -0.98 326 471 5 29 SAD 1BH -0.89 327 472 7 29 0.54 MAN 1BH -1.16 -0.99 0.17 328 473 8 29 MAD 1BH -1.27 329 474 9 29 SAD 1BH -0.90 330 475 10 29 MAD 1BH -1.31 331 476 17 29 MAD 1BH -0.85 332 477 18 29 2.43 MAN 1BH -1.24 -1.07 0.17 333 478 19 29 1.82 SAN 1BH -3.64 -3.53 0.11 333 479 19 29 MAD 1BH -1.30 Page 36 of 115

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 334 480 21 29 MAD 1BH -0.85 335 481 22 29 MAD 1BH -1.09 336 482 25 29 SAD 1BH -1.26 337 483 26 29 1.27 SAN 1BH -3.75 -3.66 0.09 337 484 26 29 SAD 1BH -1.22 338 485 28 29 MAD 1BH -1.16 339 486 31 29 2.75 MAN 1BH -3.74 -3.62 0.12 339 487 31 29 MAD 1BH -1.29 340 488 35 29 SAD 1BH -0.86 341 489 1 30 MAD 1BH -1.42 342 490 3 30 MAD 1BH -1.26 343 491 4 30 1.19 SAN 1BH -3.74 -3.60 0.14 343 492 4 30 2.83 MAN 1BH -1.09 -0.96 0.13 343 493 4 30 3.01 MAN 1BH -0.45 -0.19 0.26 344 494 5 30 0.49 SAN 1BH -3.74 -3.65 0.09 344 495 5 30 SAD 1BH -0.94 345 496 10 30 SAD 1BH -1.12 346 497 22 30 MAD 1BH -1.20 347 498 25 30 MAD 1BH -0.86 348 499 26 30 SAD 1BH -0.79 349 500 29 30 MAD 1BH -0.88 350 501 31 30 MAD 1BH -1.38 351 502 33 30 4.20 SAN 1BH -3.73 -3.58 0.15 351 503 33 30 MAD 1BH -0.80 352 504 36 30 MAD 1BH -1.00 353 505 38 30 SAD 1BH -1.13 354 506 42 30 SAD 1BH -0.88 355 507 1 31 2.78 SAN 1BH -3.69 -3.52 0.17 355 508 1 31 SAD 1BH -1.21 356 509 2 31 MAD 1BH -1.00 357 510 3 31 0.56 MAN 1BH -1.12 -1.09 0.03 358 511 5 31 SAD 1BH -1.51 358 512 5 31 SAD 1BH -1.08 359 513 6 31 2.75 SAN 1BH -1.04 -0.68 0.36 360 514 7 31 MAD 1BH -1.41 361 515 8 31 SAD 1BH -1.09 362 516 10 31 SAD 1BH -1.26 363 517 26 31 SAD 1BH -0.84 364 518 27 31 SAD 1BH -1.29 365 519 32 31 SAD 1BH -1.36 366 520 35 31 SAD 1BH -0.90 367 521 2 32 SAD 1BH -0.87 368 522 5 32 SAD 1BH -1.45 369 523 7 32 MAD 1BH -1.04 370 524 8 32 SAD 1BH -0.97 371 525 9 32 MAD 1BH -0.90 372 526 22 32 MAD 1BH -0.88 373 527 26 32 1.17 SAN 1BH -3.68 -3.62 0.06 Page 37 of 115

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 373 528 26 32 SAD 1BH -1.18 374 529 27 32 SAD 1BH -1.27 375 530 30 32 2.64 SAN 1BH -1.29 -1.15 0.14 376 531 33 32 SAD 1BH -1.26 377 532 36 32 MAD 1BH -0.90 378 533 1 33 2.00 SAN 1BH -3.69 -3.61 0.08 378 534 1 33 SAD 1BH -0.85 379 535 11 33 SAD 1BH -1.24 380 536 23 33 SAD 1BH -0.88 381 537 24 33 SAD 1BH -1.31 382 538 26 33 SAD 1BH -0.85 383 539 31 33 2.01 SAN 1BH -3.55 -3.48 0.07 383 540 31 33 SAD 1BH -0.84 384 541 33 33 1.52 MAN 1BH -3.75 -3.70 0.05 384 542 33 33 MAD 1BH -1.26 385 543 34 33 MAD 1BH -0.80 386 544 36 33 SAD 1BH -0.82 387 545 37 33 MAD 1BH -1.38 388 546 1 34 2.93 MAN 1BH -3.64 -3.49 0.15 388 547 1 34 SAD 1BH -0.85 389 548 2 34 SAD 1BH -1.24 390 549 4 34 SAD 1BH -1.14 391 550 5 34 MAD 1BH -1.00 392 551 8 34 1.65 MAN 1BH -1.23 -1.12 0.11 393 552 9 34 SAD 1BH -0.92 394 553 24 34 MAD 1BH -0.89 395 554 27 34 SAD 1BH -0.87 396 555 28 34 SAD 1BH -0.88 397 556 29 34 MAD 1BH -1.22 398 557 33 34 1.58 MAN 1BH -3.62 -3.54 0.08 398 558 33 34 SAD 1BH -1.26 399 559 36 34 SAD 1BH -0.98 400 560 37 34 MAD 1BH -1.38 401 561 41 34 MAD 1BH -1.22 402 562 43 34 SAD 1BH -0.96 403 563 2 35 SAD 1BH -1.27 404 564 5 35 MAD 1BH -1.18 405 565 8 35 1.38 MAN 1BH -1.16 -1.00 0.16 406 566 9 35 MAD 1BH -0.85 407 567 11 35 SAD 1BH -1.28 408 568 12 35 SAD 1BH -1.29 409 569 13 35 3.87 MAN 1BH -1.33 -1.01 0.32 410 570 21 35 MAD 1BH -1.21 411 571 24 35 SAD 1BH -1.25 412 572 25 35 SAD 1BH -1.00 413 573 27 35 MAD 1BH -1.20 414 574 29 35 SAD 1BH -1.29 415 575 30 35 SAD 1BH -1.31 Page 38 of 115

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 416 576 33 35 SAD 1BH -0.90 417 577 37 35 SAD 1BH -1.45 418 578 2 36 SAD 1BH -1.00 419 579 3 36 SAD 1BH -1.30 420 580 4 36 MAD 1BH -1.27 421 581 9 36 SAD 1BH -1.42 422 582 10 36 SAD 1BH -1.35 423 583 11 36 MAD 1BH -0.86 424 584 12 36 SAD 1BH -1.55 425 585 13 36 SAD 1BH -1.01 426 586 20 36 1.78 MAN 1BH -1.35 -1.20 0.15 427 587 21 36 SAD 1BH -0.87 428 588 22 36 1.27 SAN 1BH -1.20 -1.13 0.07 429 589 23 36 MAD 1BH -1.30 430 590 24 36 MAD 1BH -0.80 431 591 25 36 SAD 1BH -1.40 432 592 27 36 SAD 1BH -1.26 433 593 28 36 SAD 1BH -1.00 434 594 36 36 SAD 1BH -0.90 435 595 37 36 SAD 1BH -1.00 436 596 38 36 MAD 1BH -1.22 437 597 4 37 SAD 1BH -1.33 438 598 8 37 0.59 MAN 1BH -0.91 -0.85 0.06 439 599 9 37 SAD 1BH -0.90 440 600 10 37 SAD 1BH -0.90 441 601 11 37 MAD 1BH -0.92 442 602 22 37 SAD 1BH -0.80 443 603 23 37 SAD 1BH -0.85 444 604 25 37 SAD 1BH -1.20 445 605 27 37 4.25 MAN 1BH -3.75 -3.70 0.05 445 606 27 37 MAD 1BH -1.25 446 607 28 37 MAD 1BH -0.84 447 608 31 37 SAD 1BH -0.98 448 609 32 37 SAD 1BH -1.20 449 610 34 37 SAD 1BH -1.24 450 611 36 37 MAD 1BH -1.27 451 612 37 37 SAD 1BH -0.90 452 613 1 38 MAD 1BH -1.25 453 614 2 38 SAD 1BH -1.02 454 615 5 38 SAD 1BH -1.35 455 616 8 38 MAD 1BH -0.93 456 617 11 38 SAD 1BH -0.88 456 618 11 38 0.23 SAN 1BH -0.57 -0.32 0.25 457 619 12 38 SAD 1BH -1.50 458 620 13 38 1.04 SAN 1BH -3.73 -3.66 0.07 458 621 13 38 2.47 SAN 1BH -1.31 -1.10 0.21 459 622 23 38 MAD 1BH -0.91 460 623 26 38 1.09 SAN 1BH -3.73 -3.63 0.10 Page 39 of 115

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 460 624 26 38 SAD 1BH -1.03 461 625 27 38 MAD 1BH -0.99 462 626 29 38 MAD 1BH -0.85 463 627 30 38 MAD 1BH -1.11 464 628 31 38 SAD 1BH -1.25 465 629 32 38 SAD 1BH -1.40 466 630 36 38 MAD 1BH -0.85 467 631 37 38 MAD 1BH -1.22 468 632 39 38 MAD 1BH -0.85 469 633 40 38 SAD 1BH -0.84 470 634 1 39 MAD 1BH -0.87 471 635 2 39 SAD 1BH -1.36 472 636 3 39 SAD 1BH -0.85 473 637 4 39 3.20 MAN 1BH -1.32 -0.94 0.38 474 638 7 39 SAD 1BH -1.35 475 639 9 39 SAD 1BH -1.24 476 640 11 39 MAD 1BH -0.89 477 641 15 39 SAD 1BH -0.91 478 642 19 39 SAD 1BH -1.29 479 643 24 39 SAD 1BH -1.13 480 644 25 39 2.31 MAN 1BH -3.64 -3.48 0.16 480 645 25 39 0.84 MAN 1BH -1.20 -1.12 0.08 481 646 26 39 SAD 1BH -1.22 482 647 29 39 SAD 1BH -0.95 483 648 32 39 MAD 1BH -1.23 484 649 33 39 SAD 1BH -1.19 485 650 35 39 SAD 1BH -1.13 486 651 36 39 SAD 1BH -1.43 487 652 40 39 MAD 1BH -0.93 488 653 3 40 MAD 1BH -1.26 489 654 7 40 MAD 1BH -0.83 490 655 9 40 SAD 1BH -1.27 491 656 11 40 SAD 1BH -0.80 492 657 13 40 MAD 1BH -1.56 493 658 20 40 SAD 1BH -1.00 494 659 21 40 MAD 1BH -1.26 495 660 24 40 MAD 1BH -1.00 496 661 25 40 SAD 1BH -0.85 497 662 26 40 MAD 1BH -1.28 498 663 29 40 1.11 SAN 1BH -3.53 -3.49 0.04 498 664 29 40 SAD 1BH -1.30 499 665 30 40 SAD 1BH -0.80 500 666 31 40 MAD 1BH -1.10 501 667 32 40 MAD 1BH -1.23 501 668 32 40 2.72 MAN 1BH -1.14 -0.92 0.22 502 669 33 40 SAD 1BH -1.20 503 670 40 40 MAD 1BH -0.82 504 671 1 41 3.48 SAN 1BH -3.61 -3.47 0.14 Page 40 of 115

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 504 672 1 41 SAD 1BH -1.30 505 673 2 41 SAD 1BH -0.93 506 674 3 41 SAD 1BH -1.31 507 675 4 41 4.81 MAN 1BH -1.34 -0.81 0.53 508 676 5 41 2.20 MAN 1BH -1.10 -1.00 0.10 509 677 7 41 2.68 MAN 1BH -1.09 -0.96 0.13 510 678 8 41 MAD 1BH -1.27 511 679 11 41 SAD 1BH -1.37 512 680 14 41 0.36 MAN 1BH -0.87 -0.13 0.74 513 681 21 41 SAD 1BH -0.86 514 682 22 41 MAD 1BH -0.90 515 683 23 41 2.37 MAN 1BH -3.69 -3.61 0.08 515 684 23 41 SAD 1BH -0.98 516 685 26 41 2.03 SAN 1BH -3.73 -3.58 0.15 516 686 26 41 MAD 1BH -0.88 517 687 28 41 SAD 1BH -1.29 518 688 31 41 SAD 1BH -1.00 519 689 32 41 SAD 1BH -0.95 520 690 34 41 SAD 1BH -1.02 521 691 1 42 0.93 SAN 1BH -3.60 -3.56 0.04 521 692 1 42 SAD 1BH -1.36 522 693 4 42 SAD 1BH -1.30 523 694 5 42 MAD 1BH -0.92 524 695 10 42 SAD 1BH -1.28 525 696 11 42 SAD 1BH -1.05 526 697 12 42 MAD 1BH -1.17 527 698 15 42 1.90 MAN 1BH -1.17 -1.06 0.11 528 699 16 42 SAD 1BH -1.31 529 700 20 42 SAD 1BH -1.30 530 701 24 42 SAD 1BH -1.25 531 702 25 42 2.11 MAN 1BH -3.55 -3.44 0.11 531 703 25 42 SAD 1BH -0.85 532 704 28 42 SAD 1BH -1.05 533 705 36 42 MAD 1BH -1.37 534 706 4 43 MAD 1BH -0.85 535 707 5 43 1.48 SAN 1BH -1.25 -1.17 0.08 536 708 12 43 SAD 1BH -0.93 537 709 21 43 SAD 1BH -1.23 538 710 23 43 2.23 MAN 1BH -1.25 -1.08 0.17 539 711 25 43 MAD 1BH -0.90 540 712 30 43 SAD 1BH -0.80 541 713 32 43 SAD 1BH -1.10 542 714 35 43 SAD 1BH -1.18 543 715 36 43 MAD 1BH -1.00 544 716 42 43 SAD 1BH -0.99 545 717 1 44 2.83 SAN 1BH -3.74 -3.66 0.08 545 718 1 44 MAD 1BH -1.32 546 719 3 44 SAD 1BH -1.30 Page 41 of 115

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 547 720 4 44 MAD 1BH -1.25 548 721 5 44 MAD 1BH -0.85 549 722 6 44 SAD 1BH -1.30 550 723 7 44 SAD 1BH -0.85 551 724 12 44 SAD 1BH -0.95 552 725 13 44 SAD 1BH -0.93 553 726 21 44 SAD 1BH -1.30 554 727 22 44 SAD 1BH -0.90 555 728 25 44 MAD 1BH -0.99 556 729 26 44 0.16 SAN 1BH -0.94 -0.90 0.04 557 730 29 44 MAD 1BH -0.97 558 731 31 44 MAD 1BH -1.02 559 732 32 44 MAD 1BH -1.00 560 733 1 45 1.20 SAN 1BH -3.74 -3.68 0.06 560 734 1 45 SAD 1BH -1.36 561 735 4 45 SAD 1BH -0.86 562 736 6 45 SAD 1BH -1.18 563 737 7 45 SAD 1BH -0.90 564 738 8 45 SAD 1BH -0.89 565 739 9 45 1.99 MAN 1BH -1.01 -0.84 0.17 566 740 10 45 MAD 1BH -0.89 567 741 11 45 SAD 1BH -0.80 568 742 14 45 0.18 SAN 1BH -0.84 -0.81 0.03 569 743 16 45 SAD 1BH -1.30 570 744 18 45 MAD 1BH -1.23 570 745 18 45 0.53 MAN 1BH -0.42 -0.23 0.19 571 746 19 45 SAD 1BH -0.80 572 747 20 45 MAD 1BH -0.97 573 748 21 45 SAD 1BH -1.22 574 749 23 45 SAD 1BH -1.33 575 750 28 45 MAD 1BH -0.96 576 751 32 45 MAD 1BH -1.26 577 752 34 45 SAD 1BH -1.07 578 753 4 46 1.12 MAN 1BH -1.24 -1.10 0.14 579 754 5 46 SAD 1BH -1.35 580 755 7 46 SAD 1BH -1.43 581 756 8 46 1.86 MAN 1BH -1.26 -1.02 0.24 582 757 10 46 MAD 1BH -1.49 583 758 14 46 2.57 MAN 1BH -1.15 -1.04 0.11 584 759 17 46 SAD 1BH -1.25 585 760 18 46 SAD 1BH -1.24 586 761 19 46 5.61 MAN 1BH -3.59 -3.35 0.24 586 762 19 46 SAD 1BH -1.18 587 763 21 46 SAD 1BH -1.25 588 764 24 46 2.49 SAN 1BH -3.58 -3.44 0.14 588 765 24 46 MAD 1BH -1.28 588 766 24 46 5.42 MAN 1BH -0.74 -0.06 0.68 589 767 26 46 MAD 1BH -0.98 Page 42 of 115

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 590 768 27 46 1.85 MAN 1BH -3.74 -3.59 0.15 590 769 27 46 SAD 1BH -0.85 591 770 28 46 1.02 SAN 1BH -3.57 -3.50 0.07 591 771 28 46 MAD 1BH -1.28 592 772 34 46 MAD 1BH -1.27 593 773 1 47 8.99 MAN 1BH -3.65 -3.38 0.27 593 774 1 47 SAD 1BH -1.00 594 775 3 47 MAD 1BH -1.41 595 776 4 47 3.22 MAN 1BH -1.42 -1.04 0.38 596 777 8 47 0.49 SAN 1BH -1.15 -1.05 0.10 597 778 11 47 MAD 1BH -1.18 598 779 12 47 2.54 MAN 1BH -1.40 -1.11 0.29 598 780 12 47 0.25 SAN 1BH -0.90 -0.75 0.15 599 781 17 47 SAD 1BH -0.99 600 782 19 47 3.13 MAN 1BH -3.69 -3.51 0.18 600 783 19 47 MAD 1BH -1.28 601 784 22 47 MAD 1BH -1.27 602 785 24 47 MAD 1BH -1.32 603 786 25 47 MAD 1BH -0.89 604 787 26 47 SAD 1BH -1.25 605 788 27 47 SAD 1BH -1.47 606 789 29 47 MAD 1BH -0.99 607 790 31 47 SAD 1BH -1.31 608 791 34 47 SAD 1BH -1.20 609 792 35 47 SAD 1BH -1.04 610 793 37 47 SAD 1BH -1.60 611 794 1 48 6.23 MAN 1BH -3.75 -3.45 0.30 611 795 1 48 SAD 1BH -1.29 612 796 3 48 SAD 1BH -1.34 613 797 5 48 SAD 1BH -1.36 614 798 6 48 0.74 SAN 1BH -1.18 -1.10 0.08 615 799 9 48 SAD 1BH -1.36 616 800 11 48 MAD 1BH -1.41 617 801 13 48 MAD 1BH -0.94 618 802 15 48 1.66 MAN 1BH -3.70 -3.66 0.04 618 803 15 48 MAD 1BH -0.96 619 804 16 48 0.80 SAN 1BH -3.70 -3.62 0.08 619 805 16 48 SAD 1BH -0.89 620 806 18 48 SAD 1BH -1.34 620 807 18 48 2.68 MAN 1BH -0.49 -0.23 0.26 621 808 20 48 MAD 1BH -1.24 622 809 22 48 MAD 1BH -1.15 623 810 24 48 MAD 1BH -0.85 624 811 25 48 SAD 1BH -0.90 625 812 30 48 MAD 1BH -1.16 626 813 34 48 SAD 1BH -0.85 627 814 36 48 MAD 1BH -0.83 628 815 1 49 2.93 SAN 1BH -3.72 -3.58 0.14 Page 43 of 115

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 628 816 1 49 MAD 1BH -0.91 629 817 3 49 SAD 1BH -1.36 630 818 4 49 MAD 1BH -1.39 631 819 7 49 MAD 1BH -1.39 632 820 9 49 SAD 1BH -0.90 633 821 11 49 MAD 1BH -1.36 634 822 12 49 MAD 1BH -1.45 634 823 12 49 1.37 MAN 1BH -0.35 -0.18 0.17 635 824 20 49 MAD 1BH -0.92 636 825 23 49 SAD 1BH -0.88 637 826 24 49 SAD 1BH -0.87 638 827 27 49 MAD 1BH -0.86 639 828 28 49 SAD 1BH -1.33 640 829 29 49 MAD 1BH -1.26 641 830 31 49 SAD 1BH -1.26 642 831 36 49 SAD 1BH -1.26 643 832 38 49 SAD 1BH -0.81 644 833 40 49 SAD 1BH -0.91 645 834 3 50 SAD 1BH -0.90 646 835 4 50 3.98 MAN 1BH -1.35 -1.06 0.29 647 836 5 50 4.85 MAN 1BH -1.29 -1.11 0.18 648 837 6 50 SAD 1BH -1.41 649 838 8 50 MAD 1BH -0.93 650 839 9 50 MAD 1BH -1.02 651 840 10 50 2.32 MAN 1BH -1.28 -1.13 0.15 652 841 12 50 4.00 MAN 1BH -1.21 -1.06 0.15 652 842 12 50 4.02 MAN 1BH -0.48 -0.25 0.23 653 843 15 50 MAD 1BH -0.89 654 844 19 50 MAD 1BH -0.90 655 845 20 50 SAD 1BH -1.25 656 846 21 50 SAD 1BH -1.30 657 847 22 50 SAD 1BH -1.27 658 848 24 50 MAD 1BH -1.29 658 849 24 50 4.57 MAN 1BH -0.79 -0.08 0.71 659 850 26 50 MAD 1BH -0.92 660 851 28 50 SAD 1BH -1.27 661 852 30 50 MAD 1BH -1.10 662 853 37 50 SAD 1BH -0.90 663 854 1 51 2.10 SAN 1BH -1.17 -1.09 0.08 664 855 2 51 SAD 1BH -1.37 665 856 3 51 SAD 1BH -1.07 665 857 3 51 SAD 1BH -1.07 666 858 4 51 0.70 MAN 1BH -1.24 -1.15 0.09 667 859 6 51 MAD 1BH -1.27 668 860 11 51 SAD 1BH -1.75 669 861 12 51 MAD 1BH -1.30 670 862 13 51 SAD 1BH -1.41 671 863 15 51 SAD 1BH -1.28 Page 44 of 115

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 672 864 16 51 MAD 1BH -1.28 673 865 17 51 SAD 1BH -0.89 674 866 19 51 SAD 1BH -1.21 675 867 20 51 MAD 1BH -0.92 676 868 21 51 SAD 1BH -1.16 677 869 23 51 MAD 1BH -0.88 678 870 26 51 SAD 1BH -1.34 679 871 27 51 MAD 1BH -0.87 680 872 28 51 MAD 1BH -0.92 681 873 29 51 MAD 1BH -1.30 682 874 30 51 MAD 1BH -0.93 683 875 32 51 MAD 1BH -1.23 684 876 33 51 MAD 1BH -0.92 685 877 34 51 MAD 1BH -0.84 686 878 35 51 SAD 1BH -0.86 687 879 36 51 SAD 1BH -0.88 688 880 37 51 MAD 1BH -1.31 689 881 38 51 SAD 1BH -1.32 690 882 39 51 MAD 1BH -0.89 691 883 1 52 1.01 SAN 1BH -1.16 -1.07 0.09 692 884 2 52 4.31 MAN 1BH -1.38 -1.03 0.35 693 885 3 52 2.20 MAN 1BH -1.29 -1.18 0.11 694 886 5 52 MAD 1BH -1.38 695 887 9 52 SAD 1BH -1.34 696 888 10 52 SAD 1BH -1.36 697 889 13 52 SAD 1BH -1.65 698 890 15 52 MAD 1BH -1.31 699 891 16 52 SAD 1BH -0.88 700 892 17 52 SAD 1BH -0.99 701 893 18 52 SAD 1BH -0.90 702 894 19 52 MAD 1BH -1.33 703 895 20 52 MAD 1BH -0.89 704 896 23 52 MAD 1BH -0.91 705 897 25 52 SAD 1BH -1.36 706 898 26 52 SAD 1BH -0.87 707 899 28 52 MAD 1BH -0.89 708 900 30 52 MAD 1BH -1.34 709 901 33 52 SAD 1BH -1.25 710 902 36 52 SAD 1BH -1.05 711 903 37 52 SAD 1BH -1.06 712 904 1 53 MAD 1BH -1.43 713 905 2 53 SAD 1BH -0.93 714 906 3 53 MAD 1BH -1.40 715 907 4 53 2.02 MAN 1BH -1.29 -1.20 0.09 716 908 6 53 MAD 1BH -1.04 717 909 7 53 1.57 SAN 1BH -1.18 -1.10 0.08 717 910 7 53 4.44 MAN 1BH -0.83 -0.22 0.61 718 911 11 53 SAD 1BH -1.42 Page 45 of 115

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 719 912 12 53 SAD 1BH -1.23 720 913 13 53 MAD 1BH -1.33 721 914 14 53 MAD 1BH -1.50 722 915 15 53 MAD 1BH -0.90 723 916 16 53 SAD 1BH -1.00 724 917 17 53 MAD 1BH -0.90 725 918 18 53 SAD 1BH -1.10 726 919 19 53 MAD 1BH -0.91 727 920 20 53 SAD 1BH -1.30 728 921 21 53 SAD 1BH -0.95 729 922 22 53 SAD 1BH -0.85 730 923 24 53 MAD 1BH -0.85 731 924 25 53 MAD 1BH -1.05 732 925 27 53 2.03 SAN 1BH -3.75 -3.69 0.06 732 926 27 53 MAD 1BH -0.88 733 927 28 53 SAD 1BH -0.85 734 928 32 53 SAD 1BH -0.89 735 929 35 53 SAD 1BH -0.84 736 930 42 53 SAD 1BH -0.89 737 931 1 54 0.96 SAN 1BH -1.29 -1.18 0.11 738 932 2 54 SAD 1BH -1.48 739 933 3 54 MAD 1BH -1.06 740 934 4 54 MAD 1BH -0.90 741 935 5 54 SAD 1BH -1.09 742 936 7 54 1.72 MAN 1BH -1.34 -1.14 0.20 743 937 10 54 SAD 1BH -0.92 744 938 13 54 MAD 1BH -1.38 745 939 14 54 SAD 1BH -1.37 746 940 17 54 MAD 1BH -1.16 747 941 18 54 SAD 1BH -1.21 748 942 19 54 1.77 MAN 1BH -1.19 -1.12 0.07 749 943 20 54 SAD 1BH -1.32 750 944 23 54 MAD 1BH -0.85 751 945 27 54 SAD 1BH -1.31 752 946 34 54 SAD 1BH -1.29 753 947 3 55 SAD 1BH -1.06 753 948 3 55 SAD 1BH -1.06 754 949 5 55 MAD 1BH -0.93 755 950 7 55 SAD 1BH -1.58 756 951 9 55 MAD 1BH -0.94 757 952 12 55 SAD 1BH -1.40 758 953 15 55 MAD 1BH -1.33 759 954 17 55 SAD 1BH -1.23 760 955 18 55 MAD 1BH -0.85 761 956 20 55 MAD 1BH -1.00 762 957 22 55 SAD 1BH -1.23 763 958 23 55 MAD 1BH -1.19 764 959 24 55 MAD 1BH -1.01 Page 46 of 115

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 765 960 25 55 SAD 1BH -1.17 766 961 26 55 MAD 1BH -0.90 767 962 27 55 SAD 1BH -1.26 768 963 29 55 SAD 1BH -1.30 769 964 31 55 SAD 1BH -0.85 770 965 33 55 SAD 1BH -0.90 771 966 1 56 MAD 1BH -1.00 772 967 2 56 MAD 1BH -1.23 772 968 2 56 2.64 MAN 1BH -0.49 -0.15 0.34 773 969 3 56 MAD 1BH -0.99 774 970 4 56 MAD 1BH -1.54 775 971 9 56 MAD 1BH -1.27 776 972 13 56 SAD 1BH -0.85 777 973 14 56 SAD 1BH -1.46 778 974 18 56 SAD 1BH -1.35 778 975 18 56 0.96 SAN 1BH -0.31 -0.19 0.12 779 976 19 56 SAD 1BH -0.99 780 977 20 56 SAD 1BH -1.28 781 978 22 56 SAD 1BH -1.35 782 979 27 56 SAD 1BH -0.88 783 980 29 56 SAD 1BH -1.31 784 981 30 56 MAD 1BH -0.85 785 982 31 56 MAD 1BH -0.86 786 983 32 56 MAD 1BH -0.85 787 984 34 56 MAD 1BH -0.85 788 985 43 56 SAD 1BH -1.05 789 986 2 57 MAD 1BH -1.43 790 987 3 57 MAD 1BH -1.29 791 988 4 57 SAD 1BH -1.28 792 989 5 57 SAD 1BH -1.50 793 990 6 57 1.57 MAN 1BH -1.27 -1.15 0.12 794 991 7 57 MAD 1BH -1.36 795 992 8 57 3.59 MAN 1BH -1.21 -0.84 0.37 795 993 8 57 7.89 MAN 1BH -0.75 -0.02 0.73 796 994 12 57 MAD 1BH -1.38 797 995 14 57 SAD 1BH -1.30 798 996 15 57 MAD 1BH -1.37 799 997 17 57 SAD 1BH -1.30 800 998 18 57 MAD 1BH -1.30 801 999 19 57 SAD 1BH -1.28 802 1000 21 57 MAD 1BH -0.87 803 1001 25 57 SAD 1BH -1.31 804 1002 27 57 SAD 1BH -1.11 805 1003 29 57 SAD 1BH -0.85 806 1004 32 57 MAD 1BH -0.85 807 1005 34 57 MAD 1BH -0.85 808 1006 2 58 SAD 1BH -1.39 809 1007 3 58 SAD 1BH -1.00 Page 47 of 115

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 809 1008 3 58 SAD 1BH -1.00 810 1009 4 58 MAD 1BH -1.41 811 1010 11 58 SAD 1BH -1.20 812 1011 12 58 SAD 1BH -0.90 813 1012 14 58 1.75 MAN 1BH -1.23 -1.12 0.11 814 1013 16 58 3.37 MAN 1BH -1.30 -1.05 0.25 815 1014 17 58 SAD 1BH -1.28 816 1015 18 58 SAD 1BH -1.32 817 1016 19 58 MAD 1BH -0.95 818 1017 22 58 SAD 1BH -0.85 819 1018 23 58 SAD 1BH -1.32 820 1019 29 58 SAD 1BH -0.85 821 1020 31 58 MAD 1BH -1.40 822 1021 2 59 SAD 1BH -1.00 823 1022 3 59 SAD 1BH -1.29 824 1023 6 59 MAD 1BH -1.38 825 1024 8 59 4.84 MAN 1BH -3.68 -2.30 1.38 825 1025 8 59 1.76 MAN 1BH -2.48 -2.30 0.18 825 1026 8 59 3.44 MAN 1BH -1.37 -1.01 0.36 826 1027 9 59 5.64 MAN 1BH -3.70 -2.28 1.42 826 1028 9 59 MAD 1BH -1.39 827 1029 10 59 1.43 MAN 1BH -1.14 -1.06 0.08 828 1030 12 59 MAD 1BH -1.44 829 1031 14 59 0.63 MAN 1BH -1.33 -1.26 0.07 830 1032 17 59 SAD 1BH -1.32 831 1033 19 59 MAD 1BH -1.26 832 1034 21 59 SAD 1BH -1.28 833 1035 23 59 SAD 1BH -0.70 834 1036 26 59 SAD 1BH -1.23 835 1037 28 59 SAD 1BH -1.20 836 1038 29 59 SAD 1BH -1.05 837 1039 33 59 SAD 1BH -1.39 838 1040 3 60 2.51 MAN 1BH -1.25 -1.15 0.10 839 1041 7 60 2.38 SAN 1BH -1.19 -0.96 0.23 840 1042 9 60 MAD 1BH -1.23 841 1043 14 60 3.70 MAN 1BH -1.26 -1.12 0.14 842 1044 17 60 MAD 1BH -1.34 843 1045 18 60 SAD 1BH -1.29 844 1046 19 60 SAD 1BH -1.30 845 1047 20 60 MAD 1BH -1.10 846 1048 21 60 SAD 1BH -0.85 847 1049 23 60 2.15 MAN 1BH -3.66 -3.55 0.11 847 1050 23 60 MAD 1BH -1.29 848 1051 24 60 4.55 MAN 1BH -3.62 -3.36 0.26 848 1052 24 60 SAD 1BH -0.93 849 1053 25 60 2.05 SAN 1BH -3.63 -3.45 0.18 849 1054 25 60 MAD 1BH -0.98 850 1055 26 60 SAD 1BH -0.90 Page 48 of 115

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 851 1056 32 60 1.48 MAN 1BH -3.75 -3.63 0.12 851 1057 32 60 SAD 1BH -0.85 852 1058 33 60 2.99 MAN 1BH -3.72 -3.48 0.24 852 1059 33 60 SAD 1BH -0.85 853 1060 36 60 SAD 1BH -1.30 854 1061 37 60 SAD 1BH -1.26 854 1062 37 60 1.73 MAN 1BH -0.54 -0.12 0.42 855 1063 3 61 2.51 MAN 1BH -1.99 -1.87 0.12 855 1064 3 61 1.81 MAN 1BH -1.34 -1.23 0.11 856 1065 5 61 1.30 MAN 1BH -1.34 -1.17 0.17 857 1066 6 61 MAD 1BH -1.95 858 1067 8 61 SAD 1BH -0.99 859 1068 10 61 0.88 MAN 1BH -1.19 -1.07 0.12 860 1069 13 61 SAD 1BH -0.92 860 1070 13 61 3.05 MAN 1BH -0.66 -0.17 0.49 861 1071 14 61 MAD 1BH -1.00 862 1072 18 61 SAD 1BH -1.00 863 1073 19 61 SAD 1BH -1.32 864 1074 23 61 4.01 MAN 1BH -3.68 -3.56 0.12 864 1075 23 61 SAD 1BH -1.35 865 1076 24 61 4.51 MAN 1BH -3.74 -3.59 0.15 865 1077 24 61 SAD 1BH -1.32 866 1078 27 61 4.19 MAN 1BH -3.75 -3.56 0.19 866 1079 27 61 MAD 1BH -1.08 867 1080 31 61 SAD 1BH -3.50 867 1081 31 61 0.17 SVN 1BH -1.63 -1.37 0.26 868 1082 32 61 SAD 1BH -0.81 869 1083 33 61 3.22 MAN 1BH -3.75 -3.59 0.16 869 1084 33 61 MAD 1BH -1.42 870 1085 34 61 MAD 1BH -1.30 871 1086 37 61 SAD 1BH -1.33 872 1087 41 61 SAD 1BH -0.85 873 1088 1 62 4.96 SAN 1BH -3.74 -3.55 0.19 873 1089 1 62 SAD 1BH -1.41 874 1090 2 62 1.58 MAN 1BH -1.32 -1.22 0.10 875 1091 3 62 SAD 1BH -1.36 876 1092 6 62 SAD 1BH -1.47 877 1093 7 62 MAD 1BH -0.96 878 1094 8 62 0.83 MAN 1BH -1.36 -1.28 0.08 879 1095 9 62 MAD 1BH -0.94 880 1096 11 62 MAD 1BH -1.12 881 1097 12 62 1.10 SAN 1BH -1.19 -1.09 0.10 882 1098 13 62 MAD 1BH -1.34 883 1099 15 62 4.50 SAN 1BH -3.64 -3.50 0.14 883 1100 15 62 MAD 1BH -1.00 884 1101 17 62 2.69 SAN 1BH -3.67 -3.56 0.11 884 1102 17 62 MAD 1BH -1.42 885 1103 19 62 SAD 1BH -0.88 Page 49 of 115

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 886 1104 21 62 SAD 1BH -1.10 887 1105 23 62 5.05 MAN 1BH -3.63 -3.47 0.16 887 1106 23 62 SAD 1BH -0.88 888 1107 27 62 1.61 SAN 1BH -3.73 -3.66 0.07 888 1108 27 62 MAD 1BH -0.83 889 1109 28 62 2.78 SAN 1BH -3.74 -3.64 0.10 889 1110 28 62 SAD 1BH -0.91 890 1111 34 62 SAD 1BH -0.86 891 1112 35 62 MAD 1BH -1.35 892 1113 36 62 SAD 1BH -1.35 893 1114 37 62 SAD 1BH -0.90 894 1115 38 62 SAD 1BH -1.32 895 1116 7 63 SAD 1BH -1.40 896 1117 9 63 SAD 1BH -1.34 897 1118 11 63 SAD 1BH -1.39 897 1119 11 63 0.59 MAN 1BH -0.31 -0.18 0.13 898 1120 12 63 SAD 1BH -1.00 899 1121 13 63 MAD 1BH -0.91 900 1122 15 63 SAD 1BH -1.21 901 1123 17 63 MAD 1BH -0.80 902 1124 18 63 SAD 1BH -0.89 903 1125 19 63 2.03 SAN 1BH -3.77 -3.69 0.08 903 1126 19 63 MAD 1BH -1.37 903 1127 19 63 5.39 MAN 1BH -0.94 -0.03 0.91 904 1128 21 63 2.95 SAN 1BH -3.71 -3.57 0.14 904 1129 21 63 SAD 1BH -1.01 905 1130 23 63 SAD 1BH -1.03 906 1131 25 63 3.91 MAN 1BH -3.72 -3.55 0.17 906 1132 25 63 MAD 1BH -1.30 907 1133 26 63 2.55 SAN 1BH -3.69 -3.49 0.20 907 1134 26 63 SAD 1BH -0.81 908 1135 27 63 1.83 SAN 1BH -3.68 -3.57 0.11 908 1136 27 63 SAD 1BH -1.07 909 1137 28 63 3.61 SAN 1BH -3.71 -3.47 0.24 909 1138 28 63 MAD 1BH -1.30 910 1139 29 63 2.49 MAN 1BH -3.71 -3.54 0.17 910 1140 29 63 MAD 1BH -0.92 911 1141 34 63 SAD 1BH -1.32 911 1142 34 63 3.80 MAN 1BH -0.72 -0.13 0.59 912 1143 36 63 SAD 1BH -0.89 913 1144 37 63 MAD 1BH -1.38 914 1145 39 63 SAD 1BH -0.90 915 1146 1 64 6.84 MAN 1BH -3.75 -3.46 0.29 915 1147 1 64 SAD 1BH -1.35 916 1148 3 64 1.73 MAN 1BH -1.30 -1.22 0.08 917 1149 4 64 1.54 MAN 1BH -1.31 -1.21 0.10 918 1150 6 64 1.10 MAN 1BH -1.27 -1.13 0.14 919 1151 10 64 MAD 1BH -1.28 Page 50 of 115

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 920 1152 11 64 MAD 1BH -1.59 920 1153 11 64 1.57 MAN 1BH -0.62 -0.31 0.31 921 1154 13 64 MAD 1BH -0.93 922 1155 14 64 4.66 MAN 1BH -3.64 -3.45 0.19 922 1156 14 64 1.12 MAN 1BH -1.16 -1.08 0.08 923 1157 15 64 2.80 MAN 1BH -3.69 -3.55 0.14 923 1158 15 64 SAD 1BH -1.25 924 1159 18 64 2.48 MAN 1BH -3.63 -3.48 0.15 924 1160 18 64 MAD 1BH -0.87 925 1161 19 64 MAD 1BH -1.38 926 1162 22 64 SAD 1BH -1.35 927 1163 24 64 MAD 1BH -0.87 928 1164 26 64 2.50 MAN 1BH -3.56 -3.40 0.16 928 1165 26 64 SAD 1BH -0.90 929 1166 27 64 SAD 1BH -0.84 930 1167 29 64 2.22 SAN 1BH -3.72 -3.61 0.11 930 1168 29 64 SAD 1BH -0.80 931 1169 35 64 SAD 1BH -1.28 932 1170 37 64 SAD 1BH -1.34 933 1171 1 65 6.23 SAN 1BH -3.75 -3.40 0.35 933 1172 1 65 MAD 1BH -1.25 933 1173 1 65 0.84 MAN 1BH -0.42 -0.22 0.20 934 1174 2 65 3.79 SAN 1BH -3.73 -3.61 0.12 934 1175 2 65 SAD 1BH -1.42 935 1176 3 65 2.00 SAN 1BH -3.67 -3.59 0.08 935 1177 3 65 0.37 MAN 1BH -0.95 -0.94 0.01 936 1178 4 65 SAD 1BH -1.40 936 1179 4 65 1.58 SAN 1BH -0.39 -0.27 0.12 937 1180 8 65 1.36 SAN 1BH -1.31 -1.26 0.05 938 1181 10 65 MAD 1BH -1.24 938 1182 10 65 0.80 MAN 1BH -0.33 -0.19 0.14 939 1183 13 65 MAD 1BH -1.27 939 1184 13 65 2.88 SAN 1BH -0.91 -0.25 0.66 940 1185 15 65 2.44 MAN 1BH -3.57 -3.49 0.08 940 1186 15 65 SAD 1BH -1.02 941 1187 17 65 1.87 SAN 1BH -3.75 -3.67 0.08 941 1188 17 65 MAD 1BH -1.33 942 1189 18 65 4.12 SAN 1BH -3.74 -3.50 0.24 942 1190 18 65 SAD 1BH -1.36 943 1191 20 65 4.62 MAN 1BH -3.74 -3.59 0.15 943 1192 20 65 SAD 1BH -1.00 944 1193 23 65 4.09 MAN 1BH -3.67 -3.45 0.22 944 1194 23 65 MAD 1BH -0.92 945 1195 35 65 MAD 1BH -0.90 946 1196 36 65 MAD 1BH -0.91 947 1197 37 65 SAD 1BH -0.86 948 1198 40 65 MAD 1BH -1.32 949 1199 41 65 MAD 1BH -0.88 Page 51 of 115

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 950 1200 1 66 9.05 MAN 1BH -3.71 -3.38 0.33 950 1201 1 66 MAD 1BH -0.93 951 1202 2 66 3.31 SAN 1BH -3.67 -3.53 0.14 951 1203 2 66 MAD 1BH -0.89 952 1204 3 66 MAD 1BH -1.30 953 1205 4 66 MAD 1BH -0.93 954 1206 5 66 6.31 SAN 1BH -3.68 -3.36 0.32 954 1207 5 66 3.89 MAN 1BH -1.19 -0.97 0.22 955 1208 6 66 2.38 SAN 1BH -3.69 -3.56 0.13 955 1209 6 66 SAD 1BH -1.22 956 1210 8 66 MAD 1BH -1.02 957 1211 9 66 MAD 1BH -0.92 958 1212 11 66 SAD 1BH -0.94 959 1213 12 66 1.86 MAN 1BH -3.66 -3.55 0.11 959 1214 12 66 MAD 1BH -1.33 960 1215 14 66 1.31 MAN 1BH -3.60 -3.55 0.05 960 1216 14 66 SAD 1BH -1.29 961 1217 15 66 3.77 MAN 1BH -3.72 -3.48 0.24 961 1218 15 66 MAD 1BH -1.41 962 1219 18 66 SAD 1BH -1.36 963 1220 19 66 SAD 1BH -0.82 964 1221 21 66 2.28 SAN 1BH -3.68 -3.57 0.11 964 1222 21 66 SAD 1BH -1.24 965 1223 22 66 SAD 1BH -1.23 966 1224 24 66 2.63 SAN 1BH -3.70 -3.59 0.11 966 1225 24 66 MAD 1BH -1.18 967 1226 25 66 4.91 MAN 1BH -3.73 -3.48 0.25 967 1227 25 66 SAD 1BH -1.26 968 1228 28 66 SAD 1BH -0.88 969 1229 30 66 2.10 MAN 1BH -3.74 -3.68 0.06 969 1230 30 66 MAD 1BH -0.88 970 1231 33 66 MAD 1BH -0.91 971 1232 35 66 SAD 1BH -1.35 972 1233 36 66 MAD 1BH -0.90 973 1234 37 66 SAD 1BH -0.89 974 1235 1 67 4.02 SAN 1BH -3.72 -3.58 0.14 974 1236 1 67 MAD 1BH -1.31 975 1237 2 67 SAD 1BH -1.42 976 1238 3 67 MAD 1BH -1.36 977 1239 4 67 SAD 1BH -1.17 978 1240 5 67 MAD 1BH -1.35 979 1241 6 67 SAD 1BH -1.33 980 1242 8 67 SAD 1BH -0.86 981 1243 10 67 SAD 1BH -0.94 982 1244 11 67 SAD 1BH -1.34 983 1245 12 67 MAD 1BH -1.36 984 1246 15 67 1.33 MAN 1BH -3.66 -3.58 0.08 984 1247 15 67 MAD 1BH -0.89 Page 52 of 115

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 985 1248 16 67 3.05 MAN 1BH -3.73 -3.58 0.15 986 1249 18 67 SAD 1BH -1.00 987 1250 19 67 SAD 1BH -0.79 988 1251 20 67 1.97 SAN 1BH -3.69 -3.57 0.12 988 1252 20 67 SAD 1BH -0.92 989 1253 21 67 1.41 SAN 1BH -3.67 -3.59 0.08 989 1254 21 67 MAD 1BH -1.30 990 1255 26 67 SAD 1BH -1.21 991 1256 27 67 SAD 1BH -0.90 992 1257 28 67 SAD 1BH -0.89 993 1258 30 67 2.92 SAN 1BH -3.74 -3.63 0.11 993 1259 30 67 MAD 1BH -1.25 994 1260 34 67 MAD 1BH -1.41 995 1261 2 68 MAD 1BH -0.93 996 1262 6 68 3.04 SAN 1BH -3.66 -3.52 0.14 996 1263 6 68 MAD 1BH -0.92 997 1264 7 68 1.74 SAN 1BH -3.68 -3.59 0.09 997 1265 7 68 3.12 MAN 1BH -1.31 -1.04 0.27 998 1266 8 68 2.91 MAN 1BH -3.66 -3.50 0.16 998 1267 8 68 MAD 1BH -0.85 999 1268 9 68 MAD 1BH -0.92 1000 1269 10 68 MAD 1BH -0.85 1001 1270 12 68 SAD 1BH -1.32 1001 1271 12 68 3.41 MAN 1BH -0.62 -0.17 0.45 1002 1272 13 68 3.70 SAN 1BH -3.62 -3.48 0.14 1002 1273 13 68 MAD 1BH -1.39 1003 1274 14 68 MAD 1BH -1.35 1004 1275 15 68 0.95 SAN 1BH -3.66 -3.59 0.07 1004 1276 15 68 MAD 1BH -1.44 1005 1277 17 68 MAD 1BH -1.25 1006 1278 18 68 MAD 1BH -0.92 1007 1279 19 68 SAD 1BH -0.85 1008 1280 20 68 SAD 1BH -0.85 1009 1281 21 68 1.08 SAN 1BH -3.59 -3.52 0.07 1009 1282 21 68 SAD 1BH -0.85 1010 1283 24 68 1.38 SAN 1BH -3.68 -3.60 0.08 1010 1284 24 68 SAD 1BH -0.83 1011 1285 26 68 MAD 1BH -0.85 1012 1286 30 68 MAD 1BH -0.89 1013 1287 37 68 MAD 1BH -1.05 1013 1288 37 68 1.46 MAN 1BH -0.42 -0.01 0.41 1014 1289 1 69 5.37 MAN 1BH -3.75 -3.63 0.12 1014 1290 1 69 SAD 1BH -1.30 1015 1291 3 69 SAD 1BH -1.01 1016 1292 4 69 MAD 1BH -1.42 1017 1293 5 69 2.10 SAN 1BH -3.75 -3.60 0.15 1017 1294 5 69 SAD 1BH -1.35 1018 1295 6 69 MAD 1BH -1.73 Page 53 of 115

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1018 1296 6 69 SAD 1BH -1.34 1019 1297 7 69 MAD 1BH -1.74 1020 1298 8 69 SAD 1BH -1.40 1021 1299 9 69 SAD 1BH -0.85 1022 1300 13 69 0.92 SAN 1BH -3.74 -3.69 0.05 1022 1301 13 69 SAD 1BH -1.34 1022 1302 13 69 1.49 MAN 1BH -0.59 -0.20 0.39 1023 1303 14 69 SAD 1BH -1.34 1024 1304 15 69 3.16 MAN 1BH -3.74 -3.63 0.11 1024 1305 15 69 MAD 1BH -1.47 1025 1306 16 69 4.14 MAN 1BH -3.75 -3.50 0.25 1025 1307 16 69 SAD 1BH -1.35 1026 1308 17 69 2.83 SAN 1BH -3.71 -3.57 0.14 1026 1309 17 69 SAD 1BH -1.30 1027 1310 18 69 MAD 1BH -0.85 1028 1311 20 69 MAD 1BH -1.41 1029 1312 22 69 SAD 1BH -0.85 1030 1313 23 69 SAD 1BH -1.00 1031 1314 25 69 SAD 1BH -1.42 1032 1315 26 69 1.47 SAN 1BH -3.74 -3.66 0.08 1032 1316 26 69 SAD 1BH -1.41 1033 1317 28 69 SAD 1BH -0.86 1034 1318 32 69 3.20 SAN 1BH -3.69 -3.45 0.24 1034 1319 32 69 SAD 1BH -0.85 1035 1320 33 69 4.25 SAN 1BH -3.72 -3.51 0.21 1035 1321 33 69 SAD 1BH -1.48 1036 1322 34 69 MAD 1BH -0.85 1037 1323 35 69 SAD 1BH -1.32 1038 1324 36 69 MAD 1BH -0.85 1039 1325 37 69 MAD 1BH -0.88 1040 1326 39 69 SAD 1BH -0.85 1041 1327 2 70 3.06 SAN 1BH -3.67 -3.49 0.18 1041 1328 2 70 SAD 1BH -1.23 1042 1329 4 70 SAD 1BH -1.42 1043 1330 6 70 2.73 MAN 1BH -3.70 -3.51 0.19 1043 1331 6 70 SAD 1BH -1.41 1044 1332 7 70 SAD 1BH -0.86 1045 1333 8 70 2.39 SAN 1BH -3.63 -3.44 0.19 1045 1334 8 70 MAD 1BH -0.85 1046 1335 11 70 3.59 SAN 1BH -3.62 -3.45 0.17 1046 1336 11 70 MAD 1BH -0.87 1047 1337 14 70 0.46 SAN 1BH -3.63 -3.59 0.04 1047 1338 14 70 SAD 1BH -0.86 1048 1339 16 70 1.01 SAN 1BH -3.58 -3.50 0.08 1048 1340 16 70 MAD 1BH -1.40 1049 1341 17 70 MAD 1BH -0.78 1049 1342 17 70 3.37 MAN 1BH -0.69 -0.14 0.55 1050 1343 19 70 MAD 1BH -0.85 Page 54 of 115

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1051 1344 21 70 MAD 1BH -0.85 1052 1345 22 70 SAD 1BH -1.05 1053 1346 23 70 3.96 MAN 1BH -3.67 -3.38 0.29 1053 1347 23 70 MAD 1BH -0.92 1054 1348 24 70 3.39 SAN 1BH -3.66 -3.42 0.24 1054 1349 24 70 SAD 1BH -0.85 1055 1350 25 70 3.48 SAN 1BH -3.67 -3.39 0.28 1055 1351 25 70 SAD 1BH -1.49 1056 1352 30 70 2.23 SAN 1BH -3.71 -3.50 0.21 1056 1353 30 70 SAD 1BH -0.99 1057 1354 38 70 MAD 1BH -1.07 1058 1355 1 71 2.38 SAN 1BH -3.68 -3.60 0.08 1058 1356 1 71 SAD 1BH -0.80 1059 1357 2 71 MAD 1BH -0.92 1060 1358 4 71 MAD 1BH -0.96 1061 1359 5 71 MAD 1BH -1.41 1062 1360 6 71 MAD 1BH -1.36 1063 1361 7 71 MAD 1BH -1.55 1064 1362 8 71 MAD 1BH -1.36 1065 1363 9 71 SAD 1BH -1.46 1066 1364 12 71 SAD 1BH -1.28 1067 1365 13 71 MAD 1BH -1.00 1068 1366 15 71 MAD 1BH -0.90 1069 1367 16 71 SAD 1BH -0.87 1070 1368 17 71 2.35 SAN 1BH -3.71 -3.53 0.18 1070 1369 17 71 MAD 1BH -1.34 1071 1370 20 71 SAD 1BH -1.07 1072 1371 21 71 0.70 SAN 1BH -3.73 -3.70 0.03 1072 1372 21 71 MAD 1BH -1.42 1073 1373 22 71 0.79 SAN 1BH -3.74 -3.64 0.10 1073 1374 22 71 MAD 1BH -0.86 1074 1375 29 71 2.98 SAN 1BH -3.64 -3.43 0.21 1074 1376 29 71 SAD 1BH -1.02 1075 1377 30 71 2.04 SAN 1BH -3.73 -3.62 0.11 1075 1378 30 71 SAD 1BH -1.30 1076 1379 31 71 6.95 SAN 1BH -3.64 -3.49 0.15 1076 1380 31 71 SAD 1BH -1.37 1077 1381 35 71 MAD 1BH -0.85 1078 1382 37 71 MAD 1BH -0.85 1079 1383 1 72 MAD 1BH -0.85 1080 1384 2 72 MAD 1BH -1.37 1081 1385 3 72 0.72 SAN 1BH -3.53 -3.45 0.08 1081 1386 3 72 SAD 1BH -1.00 1082 1387 5 72 SAD 1BH -1.41 1083 1388 6 72 SAD 1BH -1.30 1084 1389 9 72 SAD 1BH -0.85 1085 1390 10 72 MAD 1BH -0.93 1086 1391 11 72 1.74 MAN 1BH -1.23 -1.10 0.13 Page 55 of 115

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1087 1392 12 72 SAD 1BH -1.46 1088 1393 15 72 SAD 1BH -1.29 1089 1394 16 72 SAD 1BH -1.42 1090 1395 17 72 4.92 SAN 1BH -3.53 -3.43 0.10 1090 1396 17 72 SAD 1BH -1.39 1091 1397 18 72 MAD 1BH -1.48 1092 1398 23 72 0.66 SAN 1BH -3.66 -3.62 0.04 1092 1399 23 72 SAD 1BH -1.24 1093 1400 35 72 MAD 1BH -1.01 1094 1401 36 72 MAD 1BH -1.46 1095 1402 38 72 SAD 1BH -1.31 1096 1403 2 73 SAD 1BH -0.95 1097 1404 3 73 2.58 MAN 1BH -1.28 -1.16 0.12 1098 1405 4 73 SAD 1BH -0.85 1099 1406 6 73 SAD 1BH -0.82 1100 1407 7 73 SAD 1BH -0.90 1101 1408 12 73 MAD 1BH -0.89 1102 1409 15 73 SAD 1BH -0.99 1103 1410 16 73 MAD 1BH -0.86 1104 1411 17 73 MAD 1BH -0.88 1105 1412 18 73 MAD 1BH -1.45 1106 1413 19 73 MAD 1BH -0.85 1106 1414 19 73 MAD 1BH -0.85 1107 1415 21 73 SAD 1BH -0.85 1108 1416 23 73 2.61 SAN 1BH -3.66 -3.58 0.08 1108 1417 23 73 SAD 1BH -0.82 1109 1418 25 73 4.64 MAN 1BH -3.73 -3.43 0.30 1109 1419 25 73 SAD 1BH -1.09 1110 1420 37 73 MAD 1BH -0.80 1111 1421 1 74 0.59 SAN 1BH -3.66 -3.62 0.04 1111 1422 1 74 SAD 1BH -1.41 1112 1423 2 74 SAD 1BH -1.35 1113 1424 3 74 2.85 SAN 1BH -1.19 -1.08 0.11 1114 1425 4 74 MAD 1BH -1.43 1115 1426 6 74 SAD 1BH -1.32 1116 1427 7 74 MAD 1BH -1.34 1117 1428 8 74 MAD 1BH -0.85 1118 1429 11 74 2.36 MAN 1BH -1.24 -1.07 0.17 1119 1430 13 74 SAD 1BH -1.38 1120 1431 15 74 SAD 1BH -1.37 1121 1432 19 74 SAD 1BH -1.41 1122 1433 25 74 1.59 SAN 1BH -3.70 -3.67 0.03 1122 1434 25 74 SAD 1BH -0.85 1123 1435 29 74 SAD 1BH -1.49 1124 1436 34 74 SAD 1BH -1.01 1125 1437 37 74 SAD 1BH -1.26 1126 1438 1 75 4.94 SAN 1BH -3.66 -3.42 0.24 1126 1439 1 75 MAD 1BH -0.98 Page 56 of 115

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1127 1440 4 75 SAD 1BH -1.34 1128 1441 5 75 2.21 MAN 1BH -1.29 -1.19 0.10 1129 1442 8 75 0.62 SAN 1BH -3.69 -3.64 0.05 1129 1443 8 75 MAD 1BH -0.90 1130 1444 9 75 SAD 1BH -0.85 1131 1445 10 75 MAD 1BH -0.85 1132 1446 11 75 SAD 1BH -1.36 1133 1447 16 75 3.02 MAN 1BH -3.64 -3.52 0.12 1133 1448 16 75 MAD 1BH -0.85 1134 1449 17 75 3.01 MAN 1BH -3.62 -3.54 0.08 1134 1450 17 75 MAD 1BH -1.40 1134 1451 17 75 0.57 SAN 1BH -0.51 -0.39 0.12 1135 1452 21 75 SAD 1BH -1.47 1136 1453 22 75 1.21 SAN 1BH -3.73 -3.68 0.05 1136 1454 22 75 SAD 1BH -1.46 1137 1455 35 75 MAD 1BH -1.04 1138 1456 36 75 SAD 1BH -0.85 1139 1457 2 76 SAD 1BH -1.38 1140 1458 3 76 SAD 1BH -1.37 1141 1459 5 76 1.43 SAN 1BH -3.68 -3.54 0.14 1141 1460 5 76 SAD 1BH -1.31 1142 1461 6 76 3.54 SAN 1BH -3.69 -3.48 0.21 1142 1462 6 76 MAD 1BH -0.85 1143 1463 7 76 2.87 SAN 1BH -3.70 -3.50 0.20 1143 1464 7 76 MAD 1BH -1.41 1144 1465 8 76 1.55 SAN 1BH -3.69 -3.65 0.04 1144 1466 8 76 MAD 1BH -0.85 1145 1467 9 76 MAD 1BH -1.39 1146 1468 10 76 MAD 1BH -1.30 1147 1469 11 76 SAD 1BH -1.38 1147 1470 11 76 1.00 MAN 1BH -0.41 -0.20 0.21 1148 1471 14 76 3.07 MAN 1BH -3.63 -3.45 0.18 1148 1472 14 76 SAD 1BH -0.85 1149 1473 16 76 7.60 MAN 1BH -3.68 -3.48 0.20 1149 1474 16 76 MAD 1BH -0.85 1150 1475 18 76 SAD 1BH -0.87 1151 1476 24 76 3.86 MAN 1BH -3.62 -3.36 0.26 1151 1477 24 76 SAD 1BH -1.33 1152 1478 28 76 SAD 1BH -1.31 1153 1479 1 77 4.80 SAN 1BH -3.70 -3.36 0.34 1153 1480 1 77 SAD 1BH -0.85 1154 1481 3 77 3.29 SAN 1BH -3.77 -3.67 0.10 1154 1482 3 77 MAD 1BH -0.93 1155 1483 4 77 SAD 1BH -1.33 1156 1484 5 77 3.24 SAN 1BH -3.75 -3.58 0.17 1156 1485 5 77 SAD 1BH -1.77 1157 1486 6 77 1.72 SAN 1BH -3.76 -3.67 0.09 1157 1487 6 77 MAD 1BH -1.40 Page 57 of 115

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1158 1488 7 77 2.22 SAN 1BH -1.21 -1.12 0.09 1159 1489 8 77 1.99 SAN 1BH -3.70 -3.62 0.08 1159 1490 8 77 MAD 1BH -0.85 1160 1491 9 77 SAD 1BH -0.85 1161 1492 10 77 MAD 1BH -1.33 1162 1493 16 77 1.91 MAN 1BH -3.66 -3.55 0.11 1162 1494 16 77 SAD 1BH -0.87 1163 1495 20 77 2.13 SAN 1BH -3.74 -3.65 0.09 1163 1496 20 77 SAD 1BH -1.41 1164 1497 22 77 6.51 MAN 1BH -3.86 -3.54 0.32 1164 1498 22 77 SAD 1BH -1.16 1165 1499 32 77 SAD 1BH -0.80 1166 1500 3 78 MAD 1BH -1.53 1167 1501 4 78 3.32 SAN 1BH -3.72 -3.54 0.18 1167 1502 4 78 MAD 1BH -1.08 1168 1503 5 78 1.07 SAN 1BH -3.69 -3.62 0.07 1168 1504 5 78 MAD 1BH -1.44 1169 1505 9 78 MAD 1BH -1.39 1170 1506 11 78 1.17 MAN 1BH -1.02 -0.90 0.12 1171 1507 12 78 0.83 SAN 1BH -3.65 -3.56 0.09 1171 1508 12 78 MAD 1BH -0.80 1172 1509 15 78 MAD 1BH -0.85 1173 1510 23 78 2.60 SAN 1BH -3.65 -3.48 0.17 1173 1511 23 78 SAD 1BH -0.90 1174 1512 2 79 MAD 1BH -1.45 1175 1513 4 79 SAD 1BH -1.37 1175 1514 4 79 SAD 1BH -1.37 1176 1515 5 79 MAD 1BH -1.37 1177 1516 6 79 0.81 SAN 1BH -3.66 -3.61 0.05 1177 1517 6 79 MAD 1BH -1.00 1178 1518 7 79 1.73 MAN 1BH -1.29 -1.20 0.09 1179 1519 8 79 1.03 SAN 1BH -3.74 -3.68 0.06 1179 1520 8 79 SAD 1BH -0.93 1180 1521 10 79 SAD 1BH -1.39 1181 1522 11 79 SAD 1BH -1.47 1182 1523 12 79 SAD 1BH -1.42 1183 1524 14 79 2.39 SAN 1BH -3.68 -3.57 0.11 1183 1525 14 79 MAD 1BH -0.89 1184 1526 21 79 3.51 MAN 1BH -3.70 -3.52 0.18 1184 1527 21 79 SAD 1BH -1.29 1185 1528 1 80 MAD 1BH -1.00 1186 1529 2 80 MAD 1BH -0.85 1187 1530 3 80 SAD 1BH -1.31 1188 1531 5 80 SAD 1BH -1.56 1189 1532 7 80 MAD 1BH -0.99 1190 1533 8 80 SAD 1BH -1.31 1191 1534 9 80 SAD 1BH -1.38 1192 1535 11 80 MAD 1BH -1.37 Page 58 of 115

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1193 1536 12 80 SAD 1BH -1.26 1194 1537 18 80 2.03 SAN 1BH -3.75 -3.71 0.04 1194 1538 18 80 MAD 1BH -0.85 1195 1539 26 80 SAD 1BH -0.80 1196 1540 1 81 3.91 MAN 1BH -3.72 -3.48 0.24 1196 1541 1 81 MAD 1BH -0.90 1197 1542 2 81 MAD 1BH -0.86 1198 1543 8 81 SAD 1BH -1.20 1199 1544 9 81 MAD 1BH -0.86 1200 1545 10 81 SAD 1BH -0.91 1201 1546 11 81 SAD 1BH -1.45 1202 1547 13 81 SAD 1BH -0.85 1203 1548 17 81 SAD 1BH -0.85 1204 1549 19 81 SAD 1BH -1.32 1204 1550 19 81 2.06 MAN 1BH -0.52 -0.13 0.39 1205 1551 21 81 1.40 SAN 1BH -3.78 -3.70 0.08 1205 1552 21 81 SAD 1BH -1.30 1206 1553 27 81 SAD 1BH -1.02 1207 1554 1 82 2.91 SAN 1BH -3.74 -3.43 0.31 1207 1555 1 82 SAD 1BH -1.40 1208 1556 2 82 MAD 1BH -0.85 1209 1557 7 82 SAD 1BH -1.52 1210 1558 8 82 MAD 1BH -0.85 1211 1559 9 82 MAD 1BH -0.88 1212 1560 10 82 SAD 1BH -0.91 1213 1561 11 82 SAD 1BH -1.36 1214 1562 12 82 SAD 1BH -1.44 1215 1563 14 82 MAD 1BH -0.85 1216 1564 15 82 SAD 1BH -0.85 1217 1565 16 82 3.38 SAN 1BH -3.75 -3.61 0.14 1217 1566 16 82 SAD 1BH -0.85 1218 1567 19 82 SAD 1BH -0.85 1219 1568 25 82 1.04 SAN 1BH -3.63 -3.58 0.05 1219 1569 25 82 SAD 1BH -0.98 1220 1570 26 82 SAD 1BH -1.37 1221 1571 2 83 SAD 1BH -0.94 1222 1572 4 83 SAD 1BH -1.30 1223 1573 6 83 MAD 1BH -0.87 1224 1574 7 83 SAD 1BH -0.85 1225 1575 9 83 MAD 1BH -1.52 1226 1576 10 83 SAD 1BH -0.95 1227 1577 11 83 SAD 1BH -1.00 1228 1578 14 83 SAD 1BH -1.00 1229 1579 2 84 MAD 1BH -0.85 1230 1580 4 84 SAD 1BH -1.37 1231 1581 5 84 MAD 1BH -1.00 1232 1582 9 84 SAD 1BH -1.42 1233 1583 10 84 MAD 1BH -1.02 Page 59 of 115

TABLE 7 STEAM GENERATOR 21 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1234 1584 12 84 MAD 1BH -0.90 1234 1585 12 84 1.40 MAN 1BH -0.43 -0.31 0.12 1235 1586 20 84 SAD 1BH -0.80 1236 1587 1 85 MAD 1BH -0.85 1237 1588 3 85 MAD 1BH -0.85 1238 1589 7 85 SAD 1BH -1.49 1239 1590 9 85 1.90 SAN 1BH -3.75 -3.67 0.08 1239 1591 9 85 MAD 1BH -1.35 1240 1592 11 85 SAD 1BH -1.26 1241 1593 13 85 0.86 SAN 1BH -3.73 -3.67 0.06 1241 1594 13 85 MAD 1BH -1.39 1242 1595 1 86 MAD 1BH -0.85 1243 1596 7 86 MAD 1BH -0.85 1243 1597 7 86 0.64 MAN 1BH -0.56 -0.30 0.26 1244 1598 18 86 2.62 SAN 1BH -1.32 -1.04 0.28 1245 1599 3 87 SAD 1BH -1.31 1246 1600 1 88 MAD 1BH -0.95 1247 1601 8 88 SAD 1BH -0.85 1248 1602 9 88 MAD 1BH -0.85 1249 1603 13 88 SAD 1BH -0.85 1250 1604 9 89 SAD 1BH -1.23 1251 1605 10 89 MAD 1BH -1.25 1252 1606 6 90 MAD 1BH -0.80 1253 1607 4 91 SAD 1BH -0.80 1254 1608 9 92 SAD 1BH -1.00 Page 60 of 115

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1 1 4 6 SAD 1BH -0.90 2 2 15 7 SAD 1BH -1.05 3 3 4 8 SAD 1BH -1.40 4 4 4 9 SAD 1BH -0.85 5 5 1 10 1.22 SAN 1BH -2.33 -2.26 0.07 6 6 14 10 MAD 1BH -0.90 7 7 21 11 SAD 1BH -1.42 8 8 15 12 MAD 1BH -0.85 9 9 4 13 SAD 1BH -0.85 10 10 15 13 SAD 1BH -1.11 11 11 20 13 SAD 1BH -0.85 12 12 22 13 SAD 1BH -0.90 13 13 24 13 SAD 1BH -1.46 13 14 24 13 0.72 MAN 1BH -0.66 -0.18 0.48 14 15 27 13 0.36 SAN 1BH -0.93 -0.84 0.09 15 16 4 14 0.90 SAN 1BH -2.34 -2.26 0.08 16 17 17 14 MAD 1BH -1.32 17 18 1 15 MAD 1BH -0.85 18 19 2 15 0.96 SAN 1BH -2.41 -2.30 0.11 19 20 9 15 SAD 1BH -1.16 20 21 14 15 SAD 1BH -1.06 21 22 24 15 3.86 MAN 1BH -1.55 -1.16 0.39 22 23 25 15 SAD 1BH -1.49 23 24 4 16 MAD 1BH -0.85 24 25 17 16 MAD 1BH -0.92 25 26 25 16 SAD 1BH -1.07 26 27 27 16 SAD 1BH -1.17 27 28 4 17 MAD 1BH -1.30 28 29 14 17 SAD 1BH -1.32 29 30 25 17 1.04 SAN 1BH -1.04 -0.97 0.07 30 31 1 18 2.69 MAN 1BH -2.17 -1.92 0.25 31 32 2 18 1.01 MAN 1BH -2.37 -2.05 0.32 32 33 3 18 SAD 1BH -0.91 33 34 4 18 MAD 1BH -1.19 34 35 9 18 SAD 1BH -1.45 35 36 14 18 MAD 1BH -1.37 36 37 15 18 SAD 1BH -0.94 37 38 4 19 0.65 SAN 1BH -2.37 -1.85 0.52 38 39 12 19 MAD 1BH -0.80 39 40 13 19 SAD 1BH -0.96 40 41 15 19 MAD 1BH -1.08 41 42 16 19 MAD 1BH -0.80 42 43 21 19 0.70 SVN 1BH -2.55 -2.34 0.21 43 44 25 19 SAD 1BH -0.92 44 45 1 20 2.34 MAN 1BH -2.35 -2.13 0.22 45 46 3 20 0.77 SAN 1BH -2.19 -2.08 0.11 46 47 9 20 MAD 1BH -0.98 Page 61 of 115

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 47 48 14 20 SAD 1BH -0.91 48 49 24 20 SAD 1BH -1.32 48 50 24 20 2.69 MAN 1BH -0.93 -0.13 0.80 49 51 29 20 SAD 1BH -1.47 50 52 33 20 SAD 1BH -0.96 51 53 37 20 SAD 1BH -1.14 52 54 1 21 2.68 MAN 1BH -2.38 -2.22 0.16 53 55 4 21 1.48 MAN 1BH -2.40 -2.29 0.11 54 56 10 21 SAD 1BH -1.34 55 57 25 21 SAD 1BH -1.04 56 58 31 21 SAD 1BH -1.40 57 59 1 22 MAD 1BH -0.99 58 60 7 22 SAD 1BH -1.27 59 61 13 22 MAD 1BH -0.90 59 62 13 22 0.75 MAN 1BH -0.47 -0.34 0.13 60 63 14 22 MAD 1BH -0.96 61 64 15 22 SAD 1BH -0.85 62 65 18 22 2.30 SAN 1BH -1.45 -1.20 0.25 63 66 23 22 SAD 1BH -1.31 63 67 23 22 0.54 SAN 1BH -0.50 -0.32 0.18 64 68 28 22 SAD 1BH -1.47 65 69 33 22 SAD 1BH -1.28 66 70 35 22 1.17 MAN 1BH -3.58 -3.46 0.12 66 71 35 22 MAD 1BH -0.90 67 72 1 23 MAD 1BH -0.96 68 73 12 23 SAD 1BH -0.85 69 74 21 23 SAD 1BH -0.90 70 75 22 23 1.62 SAN 1BH -1.51 -1.37 0.14 71 76 26 23 SAD 1BH -1.53 72 77 31 23 MAD 1BH -0.93 73 78 32 23 SAD 1BH -1.24 74 79 35 23 1.74 MAN 1BH -3.56 -3.39 0.17 74 80 35 23 MAD 1BH -0.96 75 81 1 24 SAD 1BH -1.36 76 82 7 24 SAD 1BH -0.98 77 83 15 24 MAD 1BH -0.90 78 84 22 24 MAD 1BH -0.87 79 85 27 24 MAD 1BH -1.57 80 86 28 24 4.11 MAN 1BH -1.31 -1.09 0.22 81 87 32 24 SAD 1BH -1.10 82 88 33 24 0.27 MAN 1BH -1.09 -0.99 0.10 83 89 34 24 SAD 1BH -1.02 84 90 35 24 0.80 MAN 1BH -3.56 -3.44 0.12 84 91 35 24 SAD 1BH -1.32 85 92 37 24 1.14 SAN 1BH -3.67 -3.54 0.13 85 93 37 24 SAD 1BH -1.04 86 94 1 25 0.91 SAN 1BH -3.75 -3.66 0.09 86 95 1 25 MAD 1BH -0.85 Page 62 of 115

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 87 96 7 25 SAD 1BH -1.31 88 97 9 25 SAD 1BH -0.85 89 98 14 25 SAD 1BH -1.33 90 99 16 25 SAD 1BH -1.27 91 100 19 25 SAD 1BH -1.24 92 101 21 25 SAD 1BH -1.51 93 102 23 25 2.29 MAN 1BH -1.48 -1.27 0.21 94 103 26 25 0.84 SAN 1BH -1.27 -1.16 0.11 95 104 27 25 SAD 1BH -0.94 96 105 28 25 SAD 1BH -1.27 96 106 28 25 2.61 MAN 1BH -0.86 -0.15 0.71 97 107 31 25 SAD 1BH -1.00 98 108 32 25 SAD 1BH -1.40 99 109 33 25 SAD 1BH -1.00 100 110 35 25 1.60 SAN 1BH -3.59 -3.40 0.19 100 111 35 25 SAD 1BH -1.56 100 112 35 25 1.16 MAN 1BH -0.70 -0.26 0.44 101 113 37 25 1.31 MAN 1BH -3.50 -3.25 0.25 101 114 37 25 SAD 1BH -0.85 102 115 38 25 1.38 SAN 1BH -3.75 -3.63 0.12 103 116 1 26 2.51 SAN 1BH -3.73 -3.68 0.05 103 117 1 26 SAD 1BH -1.47 103 118 1 26 0.24 SAN 1BH -0.54 -0.32 0.22 104 119 7 26 MAD 1BH -0.98 105 120 9 26 MAD 1BH -0.85 106 121 13 26 MAD 1BH -0.85 107 122 19 26 MAD 1BH -1.67 108 123 21 26 SAD 1BH -1.36 108 124 21 26 0.44 SAN 1BH -0.36 -0.13 0.23 109 125 25 26 0.42 SAN 1BH -1.31 -0.78 0.53 110 126 28 26 SAD 1BH -0.96 111 127 31 26 SAD 1BH -0.93 112 128 32 26 SAD 1BH -1.30 113 129 33 26 SAD 1BH -1.33 114 130 1 27 1.64 SAN 1BH -3.75 -3.59 0.16 114 131 1 27 SAD 1BH -0.99 115 132 3 27 SAD 1BH -0.90 116 133 5 27 SAD 1BH -0.85 117 134 7 27 SAD 1BH -0.96 117 135 7 27 0.14 SAN 1BH -0.53 -0.46 0.07 118 136 12 27 MAD 1BH -0.90 119 137 13 27 MAD 1BH -1.29 120 138 14 27 SAD 1BH -0.95 121 139 15 27 SAD 1BH -1.59 122 140 20 27 SAD 1BH -1.52 123 141 24 27 SAD 1BH -1.35 124 142 25 27 SAD 1BH -1.22 125 143 28 27 MAD 1BH -1.24 Page 63 of 115

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 126 144 31 27 MAD 1BH -1.29 127 145 3 28 2.27 SAN 1BH -3.74 -3.63 0.11 127 146 3 28 SAD 1BH -0.98 128 147 7 28 MAD 1BH -1.51 129 148 23 28 SAD 1BH -1.34 130 149 31 28 SAD 1BH -1.34 131 150 38 28 1.64 SAN 1BH -3.75 -3.65 0.10 131 151 38 28 SAD 1BH -2.18 132 152 1 29 MAD 1BH -1.35 133 153 7 29 SAD 1BH -1.18 134 154 19 29 SAD 1BH -1.72 135 155 24 29 SAD 1BH -1.57 136 156 26 29 MAD 1BH -1.44 137 157 27 29 MAD 1BH -1.23 137 158 27 29 1.70 MAN 1BH -0.64 -0.36 0.28 138 159 31 29 MAD 1BH -0.90 139 160 32 29 SAD 1BH -1.52 140 161 33 29 SAD 1BH -0.98 141 162 1 30 MAD 1BH -0.94 142 163 3 30 SAD 1BH -0.90 143 164 5 30 MAD 1BH -1.24 143 165 5 30 0.32 SAN 1BH -0.38 -0.16 0.22 144 166 7 30 SAD 1BH -1.05 145 167 9 30 SAD 1BH -1.61 146 168 21 30 SAD 1BH -1.29 147 169 31 30 SAD 1BH -0.80 148 170 32 30 MAD 1BH -1.40 149 171 33 30 MAD 1BH -0.90 150 172 35 30 0.91 MAN 1BH -3.56 -3.44 0.12 150 173 35 30 SAD 1BH -1.40 151 174 3 31 2.99 MAN 1BH -1.56 -1.10 0.46 152 175 4 31 0.35 SAN 1BH -1.42 -1.35 0.07 153 176 5 31 SAD 1BH -1.02 154 177 10 31 1.15 SAN 1BH -1.02 -0.98 0.04 155 178 27 31 SAD 1BH -1.25 156 179 28 31 SAD 1BH -1.47 157 180 29 31 SAD 1BH -1.25 158 181 31 31 SAD 1BH -0.90 159 182 32 31 SAD 1BH -1.40 160 183 33 31 SAD 1BH -1.32 161 184 35 31 0.95 SAN 1BH -3.53 -3.42 0.11 161 185 35 31 SAD 1BH -1.53 162 186 39 31 SAD 1BH -1.15 163 187 1 32 2.96 MAN 1BH -3.75 -3.52 0.23 163 188 1 32 MAD 1BH -1.34 164 189 3 32 SAD 1BH -0.90 165 190 6 32 SAD 1BH -1.00 166 191 9 32 MAD 1BH -1.18 Page 64 of 115

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 167 192 20 32 1.34 MAN 1BH -1.35 -1.25 0.10 168 193 21 32 SAD 1BH -1.36 169 194 22 32 0.10 SVN 1BH -2.12 -1.99 0.13 170 195 28 32 SAD 1BH -1.17 171 196 31 32 2.37 SAN 1BH -1.50 -1.29 0.21 172 197 32 32 SAD 1BH -1.44 173 198 33 32 MAD 1BH -1.46 174 199 18 33 SAD 1BH -1.41 175 200 23 33 SAD 1BH -1.53 176 201 25 33 SAD 1BH -0.90 177 202 31 33 MAD 1BH -0.98 178 203 32 33 MAD 1BH -1.49 179 204 33 33 SAD 1BH -1.00 180 205 38 33 1.06 SAN 1BH -3.75 -3.67 0.08 180 206 38 33 SAD 1BH -2.03 181 207 3 34 MAD 1BH -0.85 182 208 6 34 SAD 1BH -0.85 183 209 7 34 SAD 1BH -1.25 184 210 23 34 MAD 1BH -0.95 185 211 28 34 2.30 MAN 1BH -1.47 -1.36 0.11 186 212 30 34 0.77 MAN 1BH -1.56 -1.47 0.09 187 213 33 34 SAD 1BH -0.97 188 214 1 35 SAD 1BH -0.85 189 215 3 35 SAD 1BH -1.36 190 216 6 35 SAD 1BH -0.85 191 217 12 35 MAD 1BH -1.21 192 218 13 35 2.56 MAN 1BH -1.38 -1.01 0.37 193 219 22 35 SAD 1BH -0.90 194 220 23 35 MAD 1BH -0.92 195 221 28 35 4.37 MAN 1BH -1.60 -1.30 0.30 196 222 29 35 SAD 1BH -1.27 197 223 30 35 SAD 1BH -1.38 198 224 35 35 0.52 MAN 1BH -1.10 -0.89 0.21 199 225 1 36 2.70 MAN 1BH -3.74 -3.55 0.19 199 226 1 36 SAD 1BH -1.30 200 227 3 36 SAD 1BH -0.85 201 228 5 36 SAD 1BH -0.90 202 229 7 36 SAD 1BH -1.35 203 230 12 36 SAD 1BH -0.95 204 231 20 36 MAD 1BH -1.47 205 232 23 36 4.54 MAN 1BH -1.48 -1.36 0.12 206 233 27 36 SAD 1BH -1.48 207 234 29 36 SAD 1BH -1.22 208 235 32 36 0.57 SAN 1BH -0.99 -0.75 0.24 209 236 33 36 SAD 1BH -1.23 210 237 35 36 SAD 1BH -1.51 211 238 1 37 5.82 MAN 1BH -3.74 -3.47 0.27 211 239 1 37 MAD 1BH -0.94 Page 65 of 115

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 212 240 2 37 SAD 1BH -1.25 213 241 3 37 SAD 1BH -0.80 214 242 5 37 SAD 1BH -0.90 215 243 7 37 SAD 1BH -0.80 216 244 20 37 SAD 1BH -1.48 217 245 21 37 MAD 1BH -1.23 218 246 22 37 SAD 1BH -0.94 219 247 23 37 SAD 1BH -1.51 220 248 24 37 0.88 SAN 1BH -1.55 -1.48 0.07 221 249 30 37 SAD 1BH -1.29 222 250 37 37 SAD 1BH -1.40 223 251 11 38 SAD 1BH -0.85 224 252 19 38 2.07 MAN 1BH -1.40 -1.18 0.22 225 253 23 38 SAD 1BH -1.00 226 254 33 38 MAD 1BH -1.50 226 255 33 38 2.59 MAN 1BH -0.83 -0.05 0.78 227 256 42 38 SAD 1BH -1.11 228 257 1 39 MAD 1BH -1.55 228 258 1 39 3.78 MAN 1BH -0.89 -0.13 0.76 229 259 3 39 SAD 1BH -1.41 230 260 6 39 SAD 1BH -0.90 231 261 9 39 SAD 1BH -1.50 232 262 20 39 SAD 1BH -1.11 233 263 21 39 MAD 1BH -1.07 234 264 23 39 SAD 1BH -1.50 235 265 33 39 SAD 1BH -1.31 236 266 37 39 SAD 1BH -1.33 237 267 40 39 SAD 1BH -1.02 238 268 1 40 MAD 1BH -1.34 239 269 3 40 SAD 1BH -1.08 240 270 4 40 SAD 1BH -0.80 241 271 6 40 SAD 1BH -1.07 242 272 9 40 SAD 1BH -0.85 243 273 12 40 1.28 SAN 1BH -3.73 -3.65 0.08 243 274 12 40 SAD 1BH -1.03 244 275 20 40 SAD 1BH -1.41 245 276 21 40 SAD 1BH -1.36 246 277 22 40 MAD 1BH -0.95 247 278 23 40 SAD 1BH -1.00 248 279 30 40 MAD 1BH -0.94 249 280 32 40 SAD 1BH -1.52 250 281 33 40 SAD 1BH -1.00 251 282 1 41 4.08 MAN 1BH -3.75 -3.42 0.33 251 283 1 41 MAD 1BH -1.63 252 284 6 41 SAD 1BH -0.85 253 285 9 41 SAD 1BH -0.85 254 286 19 41 SAD 1BH -1.54 255 287 21 41 SAD 1BH -1.58 Page 66 of 115

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 256 288 22 41 SAD 1BH -1.47 257 289 23 41 MAD 1BH -1.22 258 290 27 41 2.31 MAN 1BH -1.51 -1.40 0.11 259 291 28 41 SAD 1BH -0.92 260 292 29 41 SAD 1BH -1.28 261 293 30 41 SAD 1BH -0.99 262 294 33 41 MAD 1BH -1.41 263 295 34 41 SAD 1BH -0.95 264 296 1 42 2.31 SAN 1BH -3.75 -3.64 0.11 264 297 1 42 SAD 1BH -1.35 265 298 2 42 2.37 SAN 1BH -3.79 -3.64 0.15 265 299 2 42 SAD 1BH -1.32 266 300 5 42 SAD 1BH -0.85 267 301 9 42 MAD 1BH -0.85 268 302 10 42 SAD 1BH -1.10 269 303 13 42 SAD 1BH -1.28 270 304 21 42 MAD 1BH -0.95 271 305 22 42 SAD 1BH -1.49 272 306 23 42 SAD 1BH -1.07 273 307 24 42 SAD 1BH -1.71 274 308 28 42 0.59 SAN 1BH -1.55 -1.46 0.09 275 309 29 42 SAD 1BH -1.50 276 310 32 42 0.48 SAN 1BH -1.40 -1.29 0.11 277 311 33 42 2.08 MAN 1BH -1.28 -1.14 0.14 278 312 35 42 SAD 1BH -1.13 278 313 35 42 0.22 SAN 1BH -0.51 -0.34 0.17 279 314 1 43 6.12 MAN 1BH -3.75 -3.39 0.36 279 315 1 43 SAD 1BH -1.63 279 316 1 43 0.46 SAN 1BH -0.63 -0.49 0.14 280 317 3 43 SAD 1BH -1.22 281 318 5 43 SAD 1BH -0.85 282 319 12 43 MAD 1BH -1.17 283 320 13 43 SAD 1BH -1.18 284 321 27 43 MAD 1BH -1.06 285 322 30 43 SAD 1BH -1.07 286 323 33 43 2.07 MAN 1BH -1.49 -1.25 0.24 287 324 37 43 1.78 MAN 1BH -1.56 -1.25 0.31 287 325 37 43 1.87 MAN 1BH -0.44 -0.20 0.24 288 326 2 44 SAD 1BH -0.83 289 327 6 44 SAD 1BH -1.07 290 328 13 44 1.81 MAN 1BH -1.18 -0.98 0.20 291 329 14 44 SAD 1BH -1.58 292 330 17 44 1.00 MAN 1BH -1.38 -1.28 0.10 293 331 18 44 SAD 1BH -0.93 294 332 22 44 MAD 1BH -1.05 295 333 23 44 MAD 1BH -1.52 296 334 27 44 SAD 1BH -1.55 297 335 30 44 SAD 1BH -1.50 Page 67 of 115

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 298 336 33 44 SAD 1BH -1.36 299 337 35 44 0.43 SAN 1BH -1.42 -1.17 0.25 300 338 37 44 SAD 1BH -1.14 301 339 1 45 5.43 MAN 1BH -3.74 -3.42 0.32 301 340 1 45 MAD 1BH -0.75 302 341 6 45 SAD 1BH -1.34 303 342 12 45 SAD 1BH -0.90 304 343 13 45 1.89 SAN 1BH -1.25 -1.08 0.17 305 344 15 45 MAD 1BH -1.52 306 345 19 45 MAD 1BH -0.90 307 346 23 45 SAD 1BH -1.00 308 347 28 45 MAD 1BH -1.57 309 348 29 45 SAD 1BH -1.40 310 349 34 45 MAD 1BH -1.40 311 350 7 46 SAD 1BH -0.85 312 351 9 46 SAD 1BH -1.03 313 352 10 46 SAD 1BH -1.18 314 353 12 46 SAD 1BH -1.38 315 354 16 46 MAD 1BH -1.35 316 355 17 46 2.32 MAN 1BH -3.61 -3.44 0.17 316 356 17 46 0.39 SAN 1BH -1.18 -1.07 0.11 317 357 18 46 SAD 1BH -0.95 318 358 19 46 SAD 1BH -1.47 319 359 26 46 1.64 MAN 1BH -1.55 -1.34 0.21 320 360 28 46 0.51 SAN 1BH -1.38 -1.28 0.10 321 361 1 47 0.88 SAN 1BH -4.07 -3.99 0.08 321 362 1 47 SAD 1BH -1.19 322 363 6 47 SAD 1BH -1.29 323 364 12 47 SAD 1BH -1.43 324 365 20 47 SAD 1BH -0.93 325 366 28 47 SAD 1BH -0.99 326 367 33 47 MAD 1BH -1.05 327 368 35 47 SAD 1BH -1.09 328 369 1 48 SAD 1BH -1.07 329 370 2 48 1.90 MAN 1BH -1.10 -1.02 0.08 330 371 3 48 0.76 SAN 1BH -3.65 -3.58 0.07 330 372 3 48 MAD 1BH -1.17 331 373 9 48 3.36 SAN 1BH -3.69 -3.47 0.22 331 374 9 48 MAD 1BH -0.89 332 375 10 48 1.60 SAN 1BH -3.75 -3.65 0.10 332 376 10 48 MAD 1BH -0.89 333 377 11 48 SAD 1BH -0.90 334 378 21 48 SAD 1BH -1.00 335 379 22 48 SAD 1BH -1.52 336 380 23 48 3.62 MAN 1BH -1.60 -1.23 0.37 337 381 28 48 2.82 MAN 1BH -1.54 -1.17 0.37 338 382 29 48 SAD 1BH -1.59 339 383 37 48 3.00 MAN 1BH -3.74 -3.54 0.20 Page 68 of 115

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 339 384 37 48 SAD 1BH -1.43 340 385 1 49 4.12 SAN 1BH -3.75 -3.55 0.20 340 386 1 49 2.54 SAN 1BH -1.19 -1.11 0.08 341 387 4 49 1.29 MAN 1BH -3.74 -3.63 0.11 341 388 4 49 SAD 1BH -1.28 342 389 6 49 1.14 SAN 1BH -3.71 -3.60 0.11 342 390 6 49 SAD 1BH -0.93 343 391 8 49 1.08 SAN 1BH -3.75 -3.66 0.09 343 392 8 49 SAD 1BH -1.04 344 393 9 49 1.18 SAN 1BH -3.55 -3.41 0.14 344 394 9 49 SAD 1BH -1.32 345 395 10 49 1.86 SAN 1BH -3.75 -3.55 0.20 345 396 10 49 SAD 1BH -1.35 346 397 11 49 MAD 1BH -1.36 347 398 12 49 2.44 MAN 1BH -1.05 -0.90 0.15 347 399 12 49 1.64 SAN 1BH -0.18 -0.01 0.17 348 400 14 49 3.50 MAN 1BH -1.24 -1.02 0.22 349 401 21 49 SAD 1BH -0.86 350 402 23 49 4.26 MAN 1BH -1.64 -1.20 0.44 351 403 27 49 SAD 1BH -1.15 352 404 28 49 1.66 SAN 1BH -1.36 -1.28 0.08 353 405 32 49 3.70 MAN 1BH -1.65 -1.23 0.42 354 406 40 49 SAD 1BH -1.19 355 407 41 49 2.56 MAN 1BH -1.36 -1.19 0.17 356 408 1 50 9.13 MAN 1BH -3.75 -3.44 0.31 356 409 1 50 SAD 1BH -1.44 357 410 2 50 SAD 1BH -1.15 358 411 9 50 1.90 MAN 1BH -3.57 -3.46 0.11 358 412 9 50 2.24 MAN 1BH -1.16 -1.03 0.13 359 413 11 50 SAD 1BH -1.18 360 414 13 50 MAD 1BH -1.05 361 415 15 50 SAD 1BH -1.20 362 416 18 50 MAD 1BH -0.94 363 417 22 50 SAD 1BH -0.99 364 418 24 50 2.86 MAN 1BH -1.45 -1.34 0.11 365 419 25 50 1.33 SAN 1BH -2.39 -2.34 0.05 366 420 27 50 MAD 1BH -1.51 367 421 28 50 0.93 SAN 1BH -1.36 -1.28 0.08 368 422 29 50 SAD 1BH -1.60 369 423 30 50 SAD 1BH -1.22 370 424 31 50 SAD 1BH -1.00 371 425 32 50 3.26 MAN 1BH -1.45 -1.11 0.34 372 426 33 50 2.67 SAN 1BH -1.46 -1.39 0.07 373 427 34 50 SAD 1BH -1.55 374 428 35 50 SAD 1BH -1.56 375 429 1 51 6.30 MAN 1BH -3.70 -3.51 0.19 375 430 1 51 SAD 1BH -1.13 376 431 3 51 2.18 MAN 1BH -3.64 -3.53 0.11 Page 69 of 115

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 376 432 3 51 SAD 1BH -1.35 377 433 10 51 1.63 SAN 1BH -3.75 -3.65 0.10 377 434 10 51 SAD 1BH -1.19 378 435 12 51 SAD 1BH -1.17 379 436 13 51 MAD 1BH -1.21 380 437 14 51 SAD 1BH -1.06 381 438 15 51 SAD 1BH -1.09 382 439 16 51 SAD 1BH -1.22 383 440 19 51 MAD 1BH -1.03 384 441 21 51 SAD 1BH -1.33 385 442 28 51 SAD 1BH -1.47 386 443 32 51 3.12 SAN 1BH -1.40 -1.26 0.14 387 444 33 51 MAD 1BH -0.90 388 445 37 51 0.87 SAN 1BH -3.74 -3.66 0.08 388 446 37 51 SAD 1BH -1.57 388 447 37 51 0.72 MAN 1BH -0.53 -0.27 0.26 389 448 3 52 SAD 1BH -1.35 390 449 9 52 2.87 SAN 1BH -3.66 -3.54 0.12 390 450 9 52 SAD 1BH -1.15 391 451 10 52 1.27 SAN 1BH -3.75 -3.65 0.10 391 452 10 52 SAD 1BH -1.07 392 453 12 52 SAD 1BH -1.18 393 454 14 52 MAD 1BH -1.02 394 455 20 52 SAD 1BH -1.28 395 456 28 52 2.66 SAN 1BH -1.40 -1.29 0.11 396 457 29 52 1.25 SAN 1BH -1.46 -1.39 0.07 397 458 33 52 2.42 SAN 1BH -1.54 -1.23 0.31 398 459 34 52 0.87 MAN 1BH -3.80 -3.70 0.10 398 460 34 52 SAD 1BH -0.90 399 461 7 53 1.66 SAN 1BH -3.64 -3.54 0.10 399 462 7 53 SAD 1BH -1.02 400 463 14 53 SAD 1BH -1.09 401 464 18 53 SAD 1BH -1.33 402 465 19 53 SAD 1BH -1.12 403 466 21 53 MAD 1BH -1.00 404 467 24 53 SAD 1BH -1.46 405 468 25 53 0.74 SAN 1BH -1.60 -1.47 0.13 406 469 29 53 MAD 1BH -1.53 407 470 30 53 SAD 1BH -1.60 407 471 30 53 3.86 MAN 1BH -1.10 -0.13 0.97 408 472 32 53 SAD 1BH -1.35 409 473 33 53 SAD 1BH -1.34 410 474 37 53 2.16 MAN 1BH -3.74 -3.46 0.28 410 475 37 53 MAD 1BH -0.93 411 476 40 53 SAD 1BH -1.36 411 477 40 53 2.47 MAN 1BH -0.84 -0.25 0.59 412 478 1 54 3.63 MAN 1BH -3.75 -3.55 0.20 412 479 1 54 1.61 MAN 1BH -1.00 -0.84 0.16 Page 70 of 115

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 413 480 7 54 0.75 SAN 1BH -3.64 -3.57 0.07 413 481 7 54 SAD 1BH -1.06 414 482 9 54 MAD 1BH -1.18 415 483 10 54 SAD 1BH -1.24 416 484 13 54 SAD 1BH -1.31 417 485 15 54 SAD 1BH -1.07 418 486 16 54 SAD 1BH -1.29 418 487 16 54 5.70 MAN 1BH -0.64 -0.04 0.60 419 488 22 54 MAD 1BH -1.28 420 489 23 54 1.61 SAN 1BH -1.45 -1.37 0.08 421 490 24 54 SAD 1BH -1.46 422 491 25 54 SAD 1BH -1.33 423 492 27 54 SAD 1BH -1.45 424 493 30 54 MAD 1BH -0.85 425 494 34 54 3.09 MAN 1BH -3.73 -3.58 0.15 425 495 34 54 0.92 SAN 1BH -1.03 -0.96 0.07 426 496 37 54 0.76 SAN 1BH -3.74 -3.60 0.14 426 497 37 54 SAD 1BH -1.41 427 498 1 55 0.17 SAN 1BH -0.66 -0.59 0.07 428 499 5 55 SAD 1BH -0.93 429 500 9 55 0.95 SAN 1BH -3.61 -3.57 0.04 429 501 9 55 SAD 1BH -1.36 430 502 10 55 1.49 MAN 1BH -1.23 -1.07 0.16 431 503 14 55 SAD 1BH -1.20 432 504 16 55 SAD 1BH -1.09 433 505 17 55 SAD 1BH -1.19 434 506 19 55 MAD 1BH -1.25 435 507 20 55 SAD 1BH -1.23 436 508 21 55 MAD 1BH -1.41 437 509 22 55 2.15 SAN 1BH -1.44 -1.33 0.11 438 510 23 55 0.55 SAN 1BH -1.50 -1.44 0.06 439 511 24 55 SAD 1BH -1.53 440 512 28 55 0.18 SVN 1BH -2.49 -2.27 0.22 440 513 28 55 0.10 SVN 1BH -1.56 -1.38 0.18 441 514 29 55 SAD 1BH -1.39 442 515 32 55 SAD 1BH -1.30 443 516 33 55 2.57 SAN 1BH -1.54 -1.34 0.20 444 517 4 56 0.88 SAN 1BH -3.75 -3.68 0.07 444 518 4 56 4.42 MAN 1BH -1.22 -1.07 0.15 445 519 6 56 SAD 1BH -1.26 446 520 7 56 SAD 1BH -1.36 447 521 9 56 SAD 1BH -1.28 448 522 10 56 MAD 1BH -1.20 449 523 11 56 MAD 1BH -1.19 450 524 12 56 MAD 1BH -1.24 451 525 13 56 SAD 1BH -1.41 452 526 16 56 SAD 1BH -1.25 453 527 27 56 SAD 1BH -1.60 Page 71 of 115

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 454 528 28 56 SAD 1BH -1.55 455 529 29 56 SAD 1BH -1.50 456 530 32 56 SAD 1BH -1.28 457 531 2 57 SAD 1BH -0.81 458 532 3 57 1.38 MAN 1BH -3.60 -3.52 0.08 458 533 3 57 SAD 1BH -1.28 459 534 5 57 SAD 1BH -1.37 460 535 7 57 1.26 SAN 1BH -3.63 -3.55 0.08 460 536 7 57 2.47 SAN 1BH -1.15 -1.01 0.14 461 537 10 57 SAD 1BH -1.24 462 538 13 57 MAD 1BH -1.31 463 539 14 57 MAD 1BH -1.04 464 540 15 57 SAD 1BH -1.06 465 541 16 57 SAD 1BH -1.06 466 542 18 57 MAD 1BH -0.92 467 543 20 57 SAD 1BH -1.05 468 544 23 57 SAD 1BH -1.51 469 545 25 57 SAD 1BH -1.44 470 546 27 57 SAD 1BH -1.37 471 547 28 57 MAD 1BH -1.41 472 548 32 57 SAD 1BH -1.28 473 549 34 57 1.37 SAN 1BH -3.68 -3.58 0.10 473 550 34 57 SAD 1BH -1.45 474 551 37 57 2.33 MAN 1BH -3.74 -3.55 0.19 474 552 37 57 SAD 1BH -0.85 475 553 1 58 SAD 1BH -1.30 476 554 3 58 1.66 SAN 1BH -3.78 -3.57 0.21 476 555 3 58 SAD 1BH -1.27 477 556 7 58 0.90 SAN 1BH -3.62 -3.51 0.11 477 557 7 58 MAD 1BH -1.21 478 558 12 58 SAD 1BH -1.00 479 559 14 58 SAD 1BH -1.31 480 560 16 58 SAD 1BH -1.20 481 561 18 58 MAD 1BH -1.31 482 562 19 58 SAD 1BH -0.98 483 563 20 58 SAD 1BH -1.40 484 564 21 58 SAD 1BH -1.01 485 565 23 58 3.86 SAN 1BH -1.52 -1.41 0.11 486 566 24 58 SAD 1BH -1.51 487 567 37 58 1.86 MAN 1BH -3.74 -3.55 0.19 487 568 37 58 2.65 SAN 1BH -1.57 -1.32 0.25 488 569 4 59 2.20 MAN 1BH -3.77 -3.66 0.11 488 570 4 59 SAD 1BH -1.26 489 571 5 59 0.94 SAN 1BH -3.63 -3.56 0.07 489 572 5 59 SAD 1BH -1.42 490 573 9 59 SAD 1BH -1.30 491 574 13 59 SAD 1BH -1.01 492 575 15 59 MAD 1BH -1.34 Page 72 of 115

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 493 576 16 59 MAD 1BH -1.16 493 577 16 59 0.44 SAN 1BH -0.45 -0.30 0.15 494 578 17 59 SAD 1BH -1.04 495 579 18 59 SAD 1BH -1.03 496 580 19 59 MAD 1BH -1.01 497 581 20 59 SAD 1BH -1.43 498 582 22 59 SAD 1BH -1.43 499 583 23 59 0.48 SAN 1BH -1.43 -1.26 0.17 500 584 24 59 SAD 1BH -1.51 501 585 25 59 SAD 1BH -1.40 502 586 27 59 SAD 1BH -1.41 503 587 28 59 3.70 MAN 1BH -1.50 -1.23 0.27 504 588 29 59 SAD 1BH -1.51 504 589 29 59 1.46 MAN 1BH -0.69 -0.21 0.48 505 590 30 59 2.06 MAN 1BH -1.40 -1.32 0.08 506 591 32 59 MAD 1BH -0.85 507 592 34 59 1.25 MAN 1BH -3.61 -3.50 0.11 507 593 34 59 SAD 1BH -1.39 508 594 37 59 0.62 MAN 1BH -3.93 -3.78 0.15 508 595 37 59 SAD 1BH -1.01 509 596 5 60 SAD 1BH -1.35 510 597 6 60 0.72 SAN 1BH -3.65 -3.58 0.07 510 598 6 60 SAD 1BH -1.34 511 599 7 60 1.96 SAN 1BH -3.67 -3.54 0.13 511 600 7 60 SAD 1BH -1.35 512 601 13 60 SAD 1BH -1.43 512 602 13 60 2.35 MAN 1BH -0.67 -0.08 0.59 513 603 15 60 SAD 1BH -1.26 513 604 15 60 0.52 MAN 1BH -0.43 -0.18 0.25 514 605 17 60 SAD 1BH -0.99 515 606 18 60 SAD 1BH -1.42 516 607 19 60 MAD 1BH -1.41 517 608 23 60 SAD 1BH -1.48 518 609 27 60 SAD 1BH -1.26 519 610 32 60 2.24 SAN 1BH -1.41 -1.34 0.07 520 611 37 60 SAD 1BH -1.45 521 612 7 61 5.07 SAN 1BH -3.65 -3.54 0.11 521 613 7 61 MAD 1BH -1.26 522 614 12 61 SAD 1BH -1.29 523 615 13 61 MAD 1BH -1.53 524 616 14 61 MAD 1BH -1.11 525 617 15 61 SAD 1BH -0.85 526 618 16 61 SAD 1BH -1.10 527 619 18 61 MAD 1BH -1.43 528 620 19 61 SAD 1BH -1.02 529 621 20 61 SAD 1BH -1.35 530 622 23 61 2.43 SAN 1BH -1.43 -1.27 0.16 531 623 25 61 SAD 1BH -1.50 Page 73 of 115

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 532 624 26 61 SAD 1BH -1.14 533 625 27 61 MAD 1BH -1.44 533 626 27 61 1.82 MAN 1BH -0.63 -0.20 0.43 534 627 32 61 SAD 1BH -1.47 535 628 37 61 SAD 1BH -0.85 536 629 5 62 MAD 1BH -1.62 537 630 7 62 0.86 SAN 1BH -3.58 -3.52 0.06 537 631 7 62 SAD 1BH -1.23 538 632 10 62 SAD 1BH -1.38 539 633 12 62 SAD 1BH -1.42 540 634 16 62 MAD 1BH -1.17 540 635 16 62 0.91 MAN 1BH -0.54 -0.34 0.20 541 636 18 62 SAD 1BH -1.34 542 637 19 62 3.71 MAN 1BH -1.26 -1.12 0.14 543 638 23 62 MAD 1BH -1.55 544 639 24 62 SAD 1BH -1.36 545 640 25 62 0.93 MAN 1BH -3.11 -2.93 0.18 545 641 25 62 SAD 1BH -1.45 545 642 25 62 2.76 SAN 1BH -0.76 -0.19 0.57 546 643 29 62 SAD 1BH -1.16 547 644 34 62 2.87 MAN 1BH -3.65 -3.51 0.14 547 645 34 62 SAD 1BH -1.46 548 646 37 62 2.50 MAN 1BH -3.61 -3.31 0.30 548 647 37 62 1.59 SAN 1BH -1.42 -1.21 0.21 549 648 42 62 SAD 1BH -1.26 549 649 42 62 3.21 MAN 1BH -0.75 -0.18 0.57 550 650 1 63 2.58 SAN 1BH -3.67 -3.57 0.10 550 651 1 63 SAD 1BH -1.24 551 652 7 63 2.29 SAN 1BH -3.78 -3.67 0.11 551 653 7 63 SAD 1BH -1.19 552 654 11 63 SAD 1BH -1.30 553 655 12 63 SAD 1BH -1.41 554 656 23 63 SAD 1BH -1.16 555 657 24 63 SAD 1BH -1.38 556 658 25 63 0.43 SAN 1BH -1.66 -1.58 0.08 557 659 31 63 SAD 1BH -1.08 558 660 33 63 SAD 1BH -1.52 559 661 37 63 1.94 MAN 1BH -3.75 -3.52 0.23 559 662 37 63 1.27 SAN 1BH -1.47 -1.39 0.08 560 663 42 63 SAD 1BH -1.15 561 664 1 64 3.34 MAN 1BH -3.66 -3.56 0.10 561 665 1 64 SAD 1BH -1.21 562 666 4 64 SAD 1BH -1.14 563 667 7 64 6.74 SAN 1BH -3.66 -3.38 0.28 563 668 7 64 0.69 SAN 1BH -1.71 -1.50 0.21 564 669 9 64 2.03 SAN 1BH -3.63 -3.49 0.14 564 670 9 64 3.29 SAN 1BH -1.20 -1.08 0.12 565 671 15 64 SAD 1BH -1.06 Page 74 of 115

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 566 672 18 64 SAD 1BH -1.30 567 673 19 64 MAD 1BH -1.26 568 674 32 64 MAD 1BH -1.50 569 675 34 64 3.26 MAN 1BH -3.58 -3.34 0.24 569 676 34 64 1.73 MAN 1BH -1.50 -1.23 0.27 570 677 37 64 2.65 MAN 1BH -3.64 -3.34 0.30 570 678 37 64 SAD 1BH -1.18 571 679 6 65 MAD 1BH -1.27 572 680 7 65 4.19 MAN 1BH -3.62 -3.45 0.17 572 681 7 65 SAD 1BH -0.72 573 682 8 65 2.77 SAN 1BH -3.63 -3.49 0.14 573 683 8 65 SAD 1BH -1.18 574 684 9 65 MAD 1BH -1.00 575 685 10 65 2.75 MAN 1BH -1.20 -1.09 0.11 576 686 11 65 SAD 1BH -1.33 577 687 12 65 1.64 MAN 1BH -1.35 -1.09 0.26 578 688 17 65 SAD 1BH -1.01 579 689 19 65 SAD 1BH -1.29 580 690 25 65 SAD 1BH -0.98 581 691 26 65 SAD 1BH -1.26 582 692 27 65 2.23 SAN 1BH -1.46 -1.38 0.08 583 693 33 65 SAD 1BH -1.49 584 694 34 65 4.55 MAN 1BH -3.95 -3.61 0.34 584 695 34 65 SAD 1BH -1.23 585 696 36 65 1.89 SAN 1BH -3.49 -3.35 0.14 585 697 36 65 SAD 1BH -1.56 585 698 36 65 2.79 MAN 1BH -0.51 -0.01 0.50 586 699 9 66 2.02 MAN 1BH -3.74 -3.46 0.28 586 700 9 66 SAD 1BH -1.15 587 701 11 66 2.19 MAN 1BH -1.27 -1.12 0.15 588 702 13 66 SAD 1BH -1.28 589 703 19 66 SAD 1BH -1.00 590 704 20 66 MAD 1BH -1.27 591 705 21 66 MAD 1BH -1.03 592 706 22 66 SAD 1BH -1.47 593 707 31 66 SAD 1BH -1.50 594 708 34 66 SAD 1BH -0.90 595 709 37 66 2.40 MAN 1BH -3.72 -3.44 0.28 595 710 37 66 0.27 SVN 1BH -1.49 -1.31 0.18 595 711 37 66 SAD 1BH -1.31 596 712 7 67 SAD 1BH -1.31 597 713 9 67 4.35 MAN 1BH -1.41 -0.98 0.43 598 714 12 67 SAD 1BH -1.02 599 715 16 67 2.27 SAN 1BH -1.16 -0.94 0.22 600 716 17 67 SAD 1BH -1.39 601 717 18 67 SAD 1BH -0.98 602 718 20 67 SAD 1BH -1.27 603 719 24 67 3.05 MAN 1BH -1.63 -1.26 0.37 Page 75 of 115

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 604 720 27 67 3.39 MAN 1BH -1.51 -1.24 0.27 605 721 30 67 0.49 SAN 1BH -1.53 -1.44 0.09 606 722 31 67 SAD 1BH -1.00 607 723 32 67 SAD 1BH -1.22 608 724 34 67 3.83 MAN 1BH -3.67 -3.36 0.31 608 725 34 67 SAD 1BH -1.48 609 726 37 67 3.93 MAN 1BH -3.49 -3.17 0.32 609 727 37 67 SAD 1BH -1.45 609 728 37 67 0.43 MAN 1BH -0.35 -0.23 0.12 610 729 9 68 SAD 1BH -1.59 610 730 9 68 1.63 SAN 1BH -0.49 -0.03 0.46 611 731 10 68 SAD 1BH -1.24 612 732 13 68 SAD 1BH -1.17 613 733 21 68 MAD 1BH -1.33 614 734 24 68 2.93 MAN 1BH -1.43 -1.32 0.11 615 735 27 68 4.16 SAN 1BH -1.42 -1.34 0.08 616 736 31 68 SAD 1BH -0.90 617 737 32 68 SAD 1BH -1.32 618 738 33 68 SAD 1BH -1.27 619 739 34 68 3.73 MAN 1BH -3.62 -3.25 0.37 619 740 34 68 0.50 MAN 1BH -1.03 -0.87 0.16 620 741 37 68 5.04 MAN 1BH -3.68 -3.30 0.38 620 742 37 68 2.34 MAN 1BH -1.50 -1.32 0.18 621 743 7 69 SAD 1BH -0.75 622 744 9 69 1.04 MAN 1BH -3.80 -3.68 0.12 622 745 9 69 SAD 1BH -1.34 623 746 14 69 SAD 1BH -0.99 624 747 15 69 MAD 1BH -0.94 625 748 16 69 MAD 1BH -1.30 626 749 25 69 1.83 MAN 1BH -1.35 -1.27 0.08 627 750 27 69 SAD 1BH -1.51 628 751 31 69 SAD 1BH -1.46 629 752 32 69 SAD 1BH -1.15 630 753 37 69 2.48 MAN 1BH -3.71 -3.55 0.16 630 754 37 69 SAD 1BH -1.43 631 755 4 70 SAD 1BH -1.06 632 756 10 70 1.74 SAN 1BH -3.74 -3.68 0.06 632 757 10 70 SAD 1BH -1.10 633 758 11 70 SAD 1BH -0.95 634 759 14 70 MAD 1BH -1.00 635 760 16 70 SAD 1BH -1.07 636 761 21 70 SAD 1BH -1.47 637 762 22 70 SAD 1BH -1.19 638 763 23 70 SAD 1BH -1.14 639 764 24 70 SAD 1BH -1.57 640 765 27 70 2.58 SAN 1BH -1.52 -1.38 0.14 641 766 31 70 0.21 SAN 1BH -1.14 -1.04 0.10 641 767 31 70 1.48 MAN 1BH -0.49 -0.19 0.30 Page 76 of 115

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 642 768 9 71 1.98 SAN 1BH -3.77 -3.48 0.29 642 769 9 71 MAD 1BH -0.90 643 770 12 71 MAD 1BH -1.11 644 771 13 71 MAD 1BH -0.98 645 772 14 71 SAD 1BH -1.36 646 773 17 71 MAD 1BH -1.35 647 774 18 71 SAD 1BH -1.28 648 775 22 71 2.84 MAN 1BH -3.77 -3.55 0.22 648 776 22 71 MAD 1BH -1.24 649 777 23 71 2.85 MAN 1BH -3.75 -3.52 0.23 649 778 23 71 MAD 1BH -1.42 650 779 27 71 SAD 1BH -0.90 651 780 32 71 SAD 1BH -1.17 652 781 37 71 SAD 1BH -1.05 653 782 8 72 SAD 1BH -1.28 654 783 9 72 MAD 1BH -1.20 655 784 11 72 MAD 1BH -1.28 656 785 12 72 4.51 MAN 1BH -1.30 -1.19 0.11 657 786 13 72 SAD 1BH -1.37 658 787 15 72 SAD 1BH -1.09 659 788 17 72 SAD 1BH -1.26 660 789 24 72 0.74 SAN 1BH -1.52 -1.48 0.04 660 790 24 72 0.56 SAN 1BH -0.50 -0.15 0.35 661 791 27 72 MAD 1BH -1.32 662 792 31 72 SAD 1BH -0.91 663 793 9 73 SAD 1BH -1.27 664 794 13 73 MAD 1BH -1.30 665 795 14 73 MAD 1BH -1.13 666 796 15 73 1.82 MAN 1BH -1.14 -1.01 0.13 667 797 17 73 0.35 MAN 1BH -2.72 -2.65 0.07 667 798 17 73 MAD 1BH -1.30 668 799 18 73 SAD 1BH -1.30 669 800 25 73 SAD 1BH -1.49 670 801 31 73 SAD 1BH -1.01 671 802 4 74 1.00 MAN 1BH -3.48 -3.41 0.07 671 803 4 74 MAD 1BH -0.90 672 804 12 74 SAD 1BH -1.34 672 805 12 74 2.56 MAN 1BH -0.77 -0.38 0.39 673 806 14 74 MAD 1BH -1.34 674 807 18 74 SAD 1BH -0.94 674 808 18 74 2.04 MAN 1BH -0.66 -0.29 0.37 675 809 24 74 SAD 1BH -1.54 676 810 25 74 SAD 1BH -0.97 677 811 27 74 MAD 1BH -1.14 678 812 4 75 1.49 MAN 1BH -3.75 -3.67 0.08 678 813 4 75 SAD 1BH -1.39 679 814 10 75 MAD 1BH -1.24 680 815 12 75 MAD 1BH -1.22 Page 77 of 115

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 681 816 13 75 2.10 SAN 1BH -1.26 -1.05 0.21 682 817 14 75 MAD 1BH -1.33 683 818 15 75 MAD 1BH -1.30 684 819 17 75 SAD 1BH -1.07 685 820 19 75 SAD 1BH -0.99 686 821 27 75 MAD 1BH -0.90 687 822 4 76 0.86 SAN 1BH -3.54 -3.47 0.07 687 823 4 76 MAD 1BH -0.85 688 824 8 76 SAD 1BH -1.29 689 825 9 76 1.38 SAN 1BH -3.49 -3.40 0.09 689 826 9 76 SAD 1BH -1.18 690 827 13 76 SAD 1BH -1.48 691 828 18 76 SAD 1BH -1.42 692 829 20 76 SAD 1BH -1.38 693 830 26 76 MAD 1BH -1.50 694 831 8 77 SAD 1BH -1.26 695 832 9 77 SAD 1BH -0.85 696 833 11 77 SAD 1BH -1.39 697 834 13 77 2.79 SAN 1BH -1.25 -1.17 0.08 698 835 14 77 SAD 1BH -1.30 698 836 14 77 2.26 SAN 1BH -0.49 -0.12 0.37 699 837 15 77 SAD 1BH -1.33 700 838 16 77 MAD 1BH -1.27 701 839 17 77 MAD 1BH -1.10 702 840 18 77 MAD 1BH -1.43 703 841 25 77 SAD 1BH -0.94 704 842 11 78 SAD 1BH -1.36 705 843 12 78 SAD 1BH -0.95 706 844 14 78 SAD 1BH -0.85 707 845 17 78 SAD 1BH -1.40 708 846 22 78 SAD 1BH -1.53 709 847 26 78 4.56 MAN 1BH -1.43 -1.35 0.08 710 848 27 78 SAD 1BH -0.95 711 849 13 79 2.08 MAN 1BH -3.81 -3.72 0.09 711 850 13 79 4.38 MAN 1BH -1.27 -1.19 0.08 712 851 14 79 3.69 MAN 1BH -3.81 -3.64 0.17 712 852 14 79 1.17 MAN 1BH -1.17 -1.07 0.10 713 853 17 79 MAD 1BH -1.12 714 854 19 79 SAD 1BH -1.20 715 855 20 79 SAD 1BH -0.80 716 856 22 79 SAD 1BH -1.31 717 857 25 79 SAD 1BH -1.36 718 858 26 79 SAD 1BH -1.49 719 859 9 80 2.16 MAN 1BH -3.60 -3.50 0.10 719 860 9 80 2.34 MAN 1BH -1.15 -1.06 0.09 720 861 10 80 MAD 1BH -1.36 721 862 12 80 MAD 1BH -1.36 722 863 15 80 SAD 1BH -1.32 Page 78 of 115

TABLE 8 STEAM GENERATOR 22 - HISTORICAL F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 723 864 18 80 SAD 1BH -1.02 724 865 22 80 MAD 1BH -1.00 725 866 23 80 SAD 1BH -1.40 726 867 26 80 SAD 1BH -0.95 727 868 4 81 0.59 SAN 1BH -3.52 -3.43 0.09 727 869 4 81 SAD 1BH -0.85 728 870 9 81 MAD 1BH -1.30 729 871 12 81 SAD 1BH -0.88 730 872 15 81 MAD 1BH -0.94 731 873 17 81 SAD 1BH -1.06 732 874 9 82 MAD 1BH -1.04 733 875 12 82 SAD 1BH -1.30 734 876 13 82 MAD 1BH -1.00 735 877 17 82 MAD 1BH -1.30 736 878 4 83 1.18 SAN 1BH -3.61 -3.54 0.07 736 879 4 83 SAD 1BH -0.85 737 880 5 83 MAD 1BH -0.80 738 881 15 83 SAD 1BH -0.90 739 882 17 83 SAD 1BH -0.86 740 883 22 83 0.71 SAN 1BH -3.70 -3.63 0.07 740 884 22 83 SAD 1BH -1.44 741 885 10 84 SAD 1BH -1.48 742 886 12 84 SAD 1BH -0.95 743 887 15 84 SAD 1BH -1.48 744 888 16 84 SAD 1BH -0.95 745 889 18 84 MAD 1BH -0.92 746 890 22 84 SAD 1BH -0.95 747 891 12 85 SAD 1BH -1.45 748 892 13 85 SAD 1BH -1.16 749 893 4 86 SAD 1BH -0.80 750 894 10 86 SAD 1BH -0.80 751 895 13 86 SAD 1BH -1.32 752 896 16 86 SAD 1BH -1.11 753 897 18 86 SCD 1BH -1.02 754 898 15 87 SAD 1BH -1.05 755 899 17 87 SAD 1BH -1.42 Page 79 of 115

TABLE 9 STEAM GENERATOR 21 - HISTORICAL F*2 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1 1 1 10 8.53 MAN 2BH -5.66 -5.27 0.39 1 2 1 10 MAD 2BH -3.39 1 3 1 10 0.83 SAN 2BH -0.79 -0.77 0.02 2 4 2 11 5.62 MAN 2BH -5.66 -5.47 0.19 2 5 2 11 SAD 2BH -2.90 2 6 2 11 1.91 SAN 2BH -0.91 -0.76 0.15 3 7 12 11 SAD 2BH -2.99 3 8 12 11 0.36 SAN 2BH -1.44 -1.14 0.30 4 9 14 12 5.97 MAN 2BH -5.67 -5.31 0.36 4 10 14 12 3.79 MAN 2BH -3.20 -2.81 0.39 4 11 14 12 2.59 SAN 2BH -0.93 -0.64 0.29 5 12 6 14 4.11 MAN 2BH -5.71 -5.42 0.29 5 13 6 14 SAD 2BH -3.30 5 14 6 14 1.07 SAN 2BH -1.00 -0.89 0.11 6 15 11 14 2.15 MAN 2BH -3.10 -2.92 0.18 6 16 11 14 2.63 SAN 2BH -1.00 -0.68 0.32 7 17 16 15 6.70 SAN 2BH -5.63 -5.20 0.43 7 18 16 15 2.63 MAN 2BH -3.10 -2.88 0.22 7 19 16 15 2.27 SAN 2BH -0.92 -0.71 0.21 8 20 18 15 2.22 MAN 2BH -3.05 -2.86 0.19 8 21 18 15 1.20 SAN 2BH -0.90 -0.72 0.18 9 22 12 16 1.91 SAN 2BH -5.71 -5.63 0.08 9 23 12 16 MAD 2BH -3.23 9 24 12 16 0.80 SAN 2BH -0.96 -0.77 0.19 10 25 26 16 0.90 MAN 2BH -5.47 -5.41 0.06 10 26 26 16 MAD 2BH -3.40 10 27 26 16 2.15 SAN 2BH -0.98 -0.81 0.17 11 28 1 17 5.12 MAN 2BH -3.44 -3.00 0.44 11 29 1 17 1.11 MAN 2BH -0.88 -0.80 0.08 12 30 4 17 4.67 SAN 2BH -5.35 -5.24 0.11 12 31 4 17 SAD 2BH -3.11 13 32 18 17 SAD 2BH -3.29 13 33 18 17 3.23 SAN 2BH -0.76 -0.68 0.08 14 34 1 18 4.17 MAN 2BH -5.52 -5.40 0.12 14 35 1 18 MAD 2BH -3.21 14 36 1 18 1.04 SAN 2BH -0.80 -0.69 0.11 15 37 19 18 SAD 2BH -3.27 15 38 19 18 4.06 MAN 2BH -0.91 -0.75 0.16 16 39 33 18 2.08 SAN 2BH -5.54 -5.45 0.09 16 40 33 18 0.66 SAN 2BH -3.22 -3.14 0.08 16 41 33 18 0.69 SAN 2BH -2.18 -2.09 0.09 17 42 6 19 4.30 MAN 2BH -5.54 -5.39 0.15 17 43 6 19 SAD 2BH -3.47 17 44 6 19 1.22 SAN 2BH -0.79 -0.74 0.05 18 45 9 19 MAD 2BH -3.20 18 46 9 19 2.65 SAN 2BH -0.84 -0.73 0.11 19 47 19 19 0.50 SAN 2BH -5.39 -5.35 0.04 Page 80 of 115

TABLE 9 STEAM GENERATOR 21 - HISTORICAL F*2 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 19 48 19 19 1.42 MAN 2BH -3.00 -2.90 0.10 19 49 19 19 3.62 MAN 2BH -0.96 -0.55 0.41 20 50 22 19 3.94 MAN 2BH -5.75 -5.52 0.23 20 51 22 19 MAD 2BH -2.93 20 52 22 19 1.28 SAN 2BH -0.79 -0.69 0.10 21 53 25 19 MAD 2BH -3.25 21 54 25 19 1.43 SAN 2BH -0.87 -0.77 0.10 22 55 4 20 SAD 2BH -2.95 22 56 4 20 1.46 SAN 2BH -0.89 -0.78 0.11 23 57 34 20 SAD 2BH -3.34 23 58 34 20 2.18 MAN 2BH -0.82 -0.75 0.07 24 59 12 21 MAD 2BH -3.27 24 60 12 21 0.48 SAN 2BH -0.84 -0.79 0.05 25 61 16 21 3.61 SAN 2BH -5.75 -5.61 0.14 25 62 16 21 1.37 MAN 2BH -3.21 -3.05 0.16 25 63 16 21 3.10 SAN 2BH -0.85 -0.71 0.14 26 64 23 21 1.82 MAN 2BH -5.73 -5.65 0.08 26 65 23 21 MAD 2BH -3.41 26 66 23 21 1.53 MAN 2BH -0.72 -0.60 0.12 27 67 24 21 1.50 MAN 2BH -5.74 -5.47 0.27 27 68 24 21 2.75 MAN 2BH -3.24 -3.11 0.13 27 69 24 21 2.88 SAN 2BH -1.06 -0.81 0.25 28 70 8 22 5.54 MAN 2BH -5.68 -5.48 0.20 28 71 8 22 2.55 MAN 2BH -3.19 -2.98 0.21 28 72 8 22 2.19 SAN 2BH -0.85 -0.77 0.08 29 73 16 22 MAD 2BH -3.33 29 74 16 22 3.53 SAN 2BH -0.96 -0.63 0.33 30 75 16 23 2.19 MAN 2BH -3.09 -2.92 0.17 30 76 16 23 1.38 SAN 2BH -0.83 -0.75 0.08 31 77 19 23 0.99 MAN 2BH -3.05 -2.96 0.09 31 78 19 23 1.09 SAN 2BH -0.84 -0.76 0.08 32 79 23 23 1.38 SAN 2BH -5.73 -5.64 0.09 32 80 23 23 MAD 2BH -3.22 32 81 23 23 3.09 SAN 2BH -0.79 -0.67 0.12 33 82 31 23 SAD 2BH -3.23 33 83 31 23 1.94 MAN 2BH -0.63 -0.55 0.08 34 84 5 24 0.93 SAN 2BH -5.67 -5.63 0.04 34 85 5 24 2.05 MAN 2BH -3.31 -3.19 0.12 34 86 5 24 1.46 SAN 2BH -0.79 -0.69 0.10 35 87 6 24 3.32 MAN 2BH -5.71 -5.53 0.18 35 88 6 24 0.26 MAN 2BH -3.14 -3.08 0.06 35 89 6 24 1.91 SAN 2BH -0.86 -0.76 0.10 36 90 14 25 MAD 2BH -3.29 36 91 14 25 1.96 MAN 2BH -0.84 -0.55 0.29 37 92 23 25 SAD 2BH -3.21 37 93 23 25 1.67 SAN 2BH -0.70 -0.58 0.12 38 94 4 26 SAD 2BH -3.52 38 95 4 26 4.07 SAN 2BH -1.04 -0.56 0.48 Page 81 of 115

TABLE 9 STEAM GENERATOR 21 - HISTORICAL F*2 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 39 96 18 26 0.52 SAN 2BH -5.77 -5.62 0.15 39 97 18 26 SAD 2BH -3.60 39 98 18 26 2.03 SAN 2BH -0.79 -0.64 0.15 40 99 12 27 MAD 2BH -2.61 40 100 12 27 3.01 SAN 2BH -0.74 -0.38 0.36 41 101 9 28 0.26 MAN 2BH -3.21 -3.11 0.10 41 102 9 28 1.16 MAN 2BH -2.12 -1.92 0.20 42 103 16 28 2.38 MAN 2BH -3.29 -3.00 0.29 42 104 16 28 0.99 SAN 2BH -0.92 -0.68 0.24 43 105 18 28 MAD 2BH -3.23 43 106 18 28 1.82 SAN 2BH -0.98 -0.68 0.30 44 107 21 28 3.34 MAN 2BH -3.52 -3.05 0.47 44 108 21 28 3.28 SAN 2BH -0.87 -0.75 0.12 45 109 23 28 3.19 MAN 2BH -3.24 -3.07 0.17 45 110 23 28 2.25 MAN 2BH -0.88 -0.74 0.14 46 111 38 28 MAD 2BH -3.29 46 112 38 28 2.60 SAN 2BH -0.94 -0.80 0.14 47 113 4 29 0.29 MAN 2BH -3.10 -2.98 0.12 47 114 4 29 4.49 MAN 2BH -0.97 -0.58 0.39 48 115 16 29 1.66 MAN 2BH -3.11 -3.00 0.11 48 116 16 29 1.69 SAN 2BH -0.90 -0.82 0.08 49 117 6 30 3.76 MAN 2BH -3.17 -2.94 0.23 49 118 6 30 1.50 SAN 2BH -0.79 -0.68 0.11 50 119 15 30 MAD 2BH -2.90 51 120 18 30 SAD 2BH -3.18 51 121 18 30 0.21 SAN 2BH -1.90 -1.52 0.38 51 122 18 30 0.36 SAN 2BH -0.92 -0.79 0.13 52 123 15 31 MAD 2BH -2.94 53 124 1 32 1.14 SCN 2BH -4.69 -4.39 0.30 53 125 1 32 3.22 MAN 2BH -3.03 -2.76 0.27 53 126 1 32 3.14 SAN 2BH -0.81 -0.48 0.33 54 127 3 32 MAD 2BH -3.50 54 128 3 32 3.69 SAN 2BH -0.93 -0.75 0.18 55 129 6 32 4.29 MAN 2BH -3.20 -2.84 0.36 55 130 6 32 1.89 SAN 2BH -0.79 -0.68 0.11 56 131 25 32 1.22 MAN 2BH -5.72 -5.65 0.07 56 132 25 32 SAD 2BH -3.26 56 133 25 32 1.21 SAN 2BH -0.93 -0.86 0.07 57 134 32 32 3.43 MAN 2BH -5.75 -5.57 0.18 57 135 32 32 1.07 MAN 2BH -3.24 -3.16 0.08 57 136 32 32 1.08 SAN 2BH -0.90 -0.83 0.07 58 137 3 33 2.07 MAN 2BH -3.12 -3.01 0.11 58 138 3 33 1.16 MAN 2BH -0.85 -0.80 0.05 59 139 4 33 SAD 2BH -3.30 59 140 4 33 1.63 SAN 2BH -0.80 -0.73 0.07 60 141 7 33 2.62 MAN 2BH -3.10 -2.96 0.14 60 142 7 33 1.22 MAN 2BH -0.89 -0.85 0.04 61 143 8 33 2.51 MAN 2BH -3.16 -3.02 0.14 Page 82 of 115

TABLE 9 STEAM GENERATOR 21 - HISTORICAL F*2 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 61 144 8 33 1.31 SAN 2BH -0.77 -0.67 0.10 62 145 22 33 SAD 2BH -3.27 62 146 22 33 3.10 SAN 2BH -1.03 -0.67 0.36 63 147 27 33 1.58 MAN 2BH -3.21 -3.12 0.09 63 148 27 33 0.73 SAN 2BH -0.84 -0.77 0.07 64 149 3 34 2.75 MAN 2BH -3.15 -3.04 0.11 64 150 3 34 0.78 SAN 2BH -0.83 -0.76 0.07 65 151 7 34 SAD 2BH -3.42 65 152 7 34 0.75 SAN 2BH -0.87 -0.79 0.08 66 153 10 34 1.57 MAN 2BH -3.24 -2.90 0.34 66 154 10 34 0.67 SAN 2BH -0.85 -0.75 0.10 67 155 5 36 1.65 MAN 2BH -3.07 -2.97 0.10 67 156 5 36 3.11 MAN 2BH -2.63 -1.90 0.73 68 157 7 36 SAD 2BH -3.23 68 158 7 36 0.78 SAN 2BH -0.78 -0.74 0.04 69 159 8 36 0.22 MAN 2BH -3.06 -2.97 0.09 69 160 8 36 1.23 SAN 2BH -0.83 -0.73 0.10 70 161 14 36 MAD 2BH -3.00 71 162 35 36 MAD 2BH -2.86 71 163 35 36 1.86 SAN 2BH -0.85 -0.74 0.11 72 164 13 37 2.51 MAN 2BH -3.20 -2.99 0.21 72 165 13 37 1.43 MAN 2BH -0.82 -0.71 0.11 73 166 9 38 2.62 MAN 2BH -3.11 -3.00 0.11 73 167 9 38 1.48 MAN 2BH -0.84 -0.79 0.05 74 168 21 39 1.01 SAN 2BH -3.49 -3.42 0.07 74 169 21 39 3.06 SAN 2BH -0.85 -0.72 0.13 75 170 22 39 SAD 2BH -3.28 75 171 22 39 2.51 SAN 2BH -1.10 -0.78 0.32 76 172 2 40 SAD 2BH -3.36 76 173 2 40 2.35 SAN 2BH -0.92 -0.65 0.27 77 174 6 40 SAD 2BH -3.30 77 175 6 40 1.64 SAN 2BH -0.85 -0.69 0.16 78 176 10 40 1.96 MAN 2BH -3.12 -2.97 0.15 78 177 10 40 1.77 SAN 2BH -0.88 -0.67 0.21 79 178 12 40 MAD 2BH -3.30 79 179 12 40 3.31 SAN 2BH -0.79 -0.65 0.14 80 180 37 40 MAD 2BH -3.14 80 181 37 40 1.96 SAN 2BH -0.82 -0.71 0.11 81 182 33 41 MAD 2BH -3.61 81 183 33 41 1.34 SAN 2BH -0.84 -0.76 0.08 82 184 3 42 MAD 2BH -3.22 82 185 3 42 0.77 SAN 2BH -0.73 -0.69 0.04 83 186 21 42 SAD 2BH -3.33 83 187 21 42 2.88 SAN 2BH -2.52 -2.20 0.32 83 188 21 42 0.60 SAN 2BH -0.91 -0.84 0.07 84 189 7 43 1.91 MAN 2BH -3.21 -3.11 0.10 84 190 7 43 0.55 SAN 2BH -0.78 -0.69 0.09 85 191 8 43 1.82 SAN 2BH -3.17 -3.04 0.13 Page 83 of 115

TABLE 9 STEAM GENERATOR 21 - HISTORICAL F*2 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 85 192 8 43 2.16 SAN 2BH -0.81 -0.69 0.12 86 193 9 43 2.67 MAN 2BH -3.19 -2.98 0.21 86 194 9 43 1.35 SAN 2BH -0.81 -0.71 0.10 87 195 24 43 13.34 MAN 2BH -3.38 -2.71 0.67 87 196 24 43 2.00 SAN 2BH -0.76 -0.66 0.10 88 197 8 44 SAD 2BH -2.90 88 198 8 44 0.87 SAN 2BH -0.77 -0.69 0.08 89 199 9 44 MAD 2BH -2.92 89 200 9 44 2.48 SAN 2BH -0.79 -0.71 0.08 90 201 19 44 SAD 2BH -3.50 90 202 19 44 1.17 SAN 2BH -1.94 -1.77 0.17 91 203 24 44 3.54 MAN 2BH -3.29 -3.08 0.21 91 204 24 44 1.84 SAN 2BH -0.89 -0.81 0.08 92 205 13 45 10.75 MAN 2BH -3.37 -2.81 0.56 92 206 13 45 0.89 MAN 2BH -0.67 -0.60 0.07 93 207 3 46 0.33 MAN 2BH -3.02 -2.96 0.06 93 208 3 46 1.26 SAN 2BH -0.81 -0.66 0.15 94 209 9 46 SAD 2BH -3.58 94 210 9 46 0.17 SAN 2BH -1.99 -1.21 0.78 95 211 16 46 MAD 2BH -3.36 95 212 16 46 0.59 SAN 2BH -0.74 -0.71 0.03 96 213 20 46 1.51 SAN 2BH -5.61 -5.50 0.11 96 214 20 46 0.91 MAN 2BH -3.13 -3.02 0.11 96 215 20 46 SAD 2BH -1.50 97 216 22 46 SAD 2BH -3.24 97 217 22 46 3.82 MAN 2BH -2.50 -2.04 0.46 97 218 22 46 1.18 MAN 2BH -1.88 -1.41 0.47 98 219 6 47 0.34 SAN 2BH -2.76 -2.02 0.74 99 220 23 47 1.07 SAN 2BH -5.61 -5.57 0.04 99 221 23 47 MAD 2BH -3.19 99 222 23 47 1.17 SAN 2BH -0.85 -0.78 0.07 100 223 36 47 MAD 2BH -3.10 100 224 36 47 1.67 SAN 2BH -0.81 -0.74 0.07 101 225 4 48 5.61 MAN 2BH -3.20 -3.08 0.12 101 226 4 48 0.59 SAN 2BH -0.77 -0.73 0.04 102 227 12 48 MAD 2BH -3.31 102 228 12 48 2.30 SAN 2BH -0.59 -0.49 0.10 103 229 23 48 MAD 2BH -3.31 103 230 23 48 1.36 SAN 2BH -0.74 -0.47 0.27 104 231 14 49 2.91 MAN 2BH -3.29 -3.16 0.13 104 232 14 49 0.17 SAN 2BH -2.75 -2.43 0.32 104 233 14 49 2.72 SAN 2BH -0.84 -0.74 0.10 105 234 15 49 MAD 2BH -3.35 106 235 17 49 SAD 2BH -2.88 107 236 2 50 12.02 MAN 2BH -3.35 -2.88 0.47 107 237 2 50 1.53 SAN 2BH -0.78 -0.71 0.07 108 238 7 50 6.61 MAN 2BH -3.36 -3.04 0.32 108 239 7 50 1.03 MAN 2BH -0.83 -0.73 0.10 Page 84 of 115

TABLE 9 STEAM GENERATOR 21 - HISTORICAL F*2 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 109 240 17 50 SAD 2BH -3.58 110 241 5 51 3.18 MAN 2BH -3.25 -3.09 0.16 110 242 5 51 2.03 MAN 2BH -0.80 -0.68 0.12 111 243 8 51 8.35 MAN 2BH -3.42 -2.94 0.48 111 244 8 51 0.75 SAN 2BH -0.87 -0.71 0.16 112 245 18 51 MAD 2BH -3.30 112 246 18 51 1.55 MAN 2BH -1.97 -1.85 0.12 113 247 4 52 1.14 MAN 2BH -3.23 -3.12 0.11 113 248 4 52 0.90 SAN 2BH -0.75 -0.70 0.05 114 249 7 52 SAD 2BH -3.31 114 250 7 52 0.72 SAN 2BH -0.69 -0.63 0.06 115 251 11 52 SAD 2BH -3.34 115 252 11 52 1.13 SAN 2BH -0.85 -0.77 0.08 116 253 12 52 SAD 2BH -3.04 116 254 12 52 0.23 SAN 2BH -2.33 -2.22 0.11 116 255 12 52 SAD 2BH -1.81 117 256 22 52 SAD 2BH -3.27 117 257 22 52 1.54 SAN 2BH -0.79 -0.70 0.09 118 258 35 52 SAD 2BH -2.90 118 259 35 52 0.93 SAN 2BH -0.83 -0.80 0.03 119 260 15 54 MAD 2BH -2.94 119 261 15 54 0.31 SAN 2BH -2.81 -2.47 0.34 119 262 15 54 SAD 2BH -0.80 120 263 21 54 MAD 2BH -3.22 120 264 21 54 1.06 SAN 2BH -0.90 -0.83 0.07 121 265 2 55 SAD 2BH -3.01 122 266 10 55 3.10 MAN 2BH -3.39 -3.01 0.38 122 267 10 55 1.67 SAN 2BH -0.74 -0.62 0.12 123 268 11 55 MAD 2BH -2.98 123 269 11 55 1.94 MAN 2BH -0.67 -0.59 0.08 124 270 6 56 2.40 MAN 2BH -3.28 -3.13 0.15 124 271 6 56 1.78 SAN 2BH -0.89 -0.80 0.09 125 272 7 56 MAD 2BH -3.08 125 273 7 56 3.19 SAN 2BH -0.83 -0.71 0.12 126 274 8 56 MAD 2BH -2.91 127 275 1 57 0.29 SAN 2BH -3.13 -3.08 0.05 127 276 1 57 0.87 SAN 2BH -0.79 -0.70 0.09 128 277 13 57 6.75 MAN 2BH -3.30 -2.87 0.43 128 278 13 57 1.35 MAN 2BH -0.89 -0.81 0.08 129 279 23 57 1.58 SAN 2BH -5.67 -5.57 0.10 129 280 23 57 2.35 MAN 2BH -3.13 -3.01 0.12 129 281 23 57 1.90 SAN 2BH -0.87 -0.80 0.07 130 282 5 58 0.36 MAN 2BH -3.40 -3.24 0.16 130 283 5 58 2.74 SAN 2BH -0.95 -0.83 0.12 131 284 1 59 MAD 2BH -3.34 131 285 1 59 3.45 SAN 2BH -0.95 -0.76 0.19 132 286 11 59 4.10 MAN 2BH -3.19 -3.07 0.12 132 287 11 59 2.35 MAN 2BH -0.89 -0.74 0.15 Page 85 of 115

TABLE 9 STEAM GENERATOR 21 - HISTORICAL F*2 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 133 288 13 59 3.91 MAN 2BH -3.27 -3.02 0.25 133 289 13 59 0.82 SAN 2BH -0.93 -0.86 0.07 134 290 31 59 MAD 2BH -3.34 134 291 31 59 0.86 SAN 2BH -0.78 -0.64 0.14 135 292 2 60 3.42 SAN 2BH -5.62 -5.40 0.22 135 293 2 60 MAD 2BH -3.04 135 294 2 60 5.08 MAN 2BH -0.73 -0.55 0.18 136 295 5 60 0.54 MAN 2BH -3.21 -3.11 0.10 136 296 5 60 2.36 MAN 2BH -0.89 -0.76 0.13 137 297 6 60 2.26 SAN 2BH -5.68 -5.61 0.07 137 298 6 60 MAD 2BH -3.35 137 299 6 60 SAD 2BH -1.11 138 300 29 60 MAD 2BH -3.27 138 301 29 60 1.89 SAN 2BH -0.91 -0.83 0.08 139 302 2 61 2.79 MAN 2BH -3.47 -3.17 0.30 139 303 2 61 5.87 SAN 2BH -0.92 -0.66 0.26 140 304 9 61 1.14 MAN 2BH -3.36 -3.20 0.16 140 305 9 61 1.97 SAN 2BH -0.98 -0.77 0.21 141 306 4 62 2.50 SAN 2BH -5.57 -5.36 0.21 141 307 4 62 MAD 2BH -2.84 141 308 4 62 3.34 SAN 2BH -1.03 -0.57 0.46 142 309 5 62 0.81 MAN 2BH -3.26 -3.17 0.09 142 310 5 62 0.42 SAN 2BH -0.89 -0.83 0.06 143 311 10 62 MAD 2BH -3.50 143 312 10 62 1.42 SAN 2BH -1.00 -0.89 0.11 144 313 14 62 5.98 MAN 2BH -5.74 -5.48 0.26 144 314 14 62 1.81 MAN 2BH -3.38 -3.17 0.21 144 315 14 62 1.01 SAN 2BH -0.86 -0.78 0.08 145 316 25 62 3.99 SAN 2BH -5.66 -5.51 0.15 145 317 25 62 0.35 SAN 2BH -3.27 -3.19 0.08 145 318 25 62 2.67 SAN 2BH -1.05 -0.80 0.25 145 319 25 62 3.46 MAN 2BH -0.58 -0.01 0.57 146 320 3 63 3.38 MAN 2BH -3.43 -3.27 0.16 146 321 3 63 5.60 SAN 2BH -0.90 -0.78 0.12 147 322 5 63 1.35 MAN 2BH -3.32 -3.24 0.08 147 323 5 63 0.96 SAN 2BH -0.99 -0.88 0.11 148 324 8 63 0.42 MAN 2BH -3.43 -3.33 0.10 148 325 8 63 2.85 MAN 2BH -1.02 -0.82 0.20 149 326 14 63 MAD 2BH -3.73 149 327 14 63 2.11 MAN 2BH -0.95 -0.69 0.26 150 328 16 63 4.07 SAN 2BH -5.75 -5.50 0.25 150 329 16 63 SAD 2BH -3.33 150 330 16 63 3.56 SAN 2BH -0.99 -0.74 0.25 151 331 5 64 3.30 MAN 2BH -3.73 -3.16 0.57 151 332 5 64 0.81 SAN 2BH -0.98 -0.87 0.11 152 333 7 64 2.42 MAN 2BH -3.38 -3.17 0.21 152 334 7 64 0.84 SAN 2BH -0.92 -0.86 0.06 153 335 8 64 SAD 2BH -3.05 Page 86 of 115

TABLE 9 STEAM GENERATOR 21 - HISTORICAL F*2 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 153 336 8 64 1.98 SAN 2BH -0.89 -0.70 0.19 154 337 34 64 MAD 2BH -3.22 154 338 34 64 1.34 SAN 2BH -0.86 -0.72 0.14 155 339 5 65 3.34 MAN 2BH -3.38 -3.16 0.22 155 340 5 65 3.26 SAN 2BH -0.89 -0.81 0.08 156 341 14 65 SAD 2BH -3.19 156 342 14 65 1.04 SAN 2BH -0.86 -0.78 0.08 157 343 16 65 SAD 2BH -3.23 157 344 16 65 2.34 MAN 2BH -1.04 -0.54 0.50 158 345 25 65 0.93 SAN 2BH -5.74 -5.70 0.04 158 346 25 65 SAD 2BH -2.79 158 347 25 65 1.57 SAN 2BH -0.82 -0.58 0.24 159 348 16 66 5.79 SAN 2BH -5.66 -5.41 0.25 159 349 16 66 0.96 SAN 2BH -4.00 -3.94 0.06 159 350 16 66 1.27 SAN 2BH -0.72 -0.64 0.08 160 351 17 66 1.36 SAN 2BH -5.72 -5.64 0.08 160 352 17 66 SAD 2BH -3.40 160 353 17 66 2.25 SAN 2BH -0.71 -0.56 0.15 161 354 14 67 SAD 2BH -3.02 162 355 24 67 1.31 SAN 2BH -5.71 -5.61 0.10 162 356 24 67 1.37 MAN 2BH -3.08 -2.92 0.16 162 357 24 67 MAD 2BH -2.19 162 358 24 67 0.78 SAN 2BH -0.72 -0.63 0.09 163 359 25 67 4.13 SAN 2BH -5.75 -5.61 0.14 163 360 25 67 0.88 SAN 2BH -0.81 -0.76 0.05 164 361 5 68 6.70 SAN 2BH -5.91 -5.58 0.33 164 362 5 68 4.63 MAN 2BH -3.53 -3.23 0.30 164 363 5 68 1.23 SAN 2BH -0.99 -0.92 0.07 165 364 11 69 1.01 SAN 2BH -3.35 -3.28 0.07 165 365 11 69 2.97 SAN 2BH -0.94 -0.70 0.24 166 366 5 70 5.03 SAN 2BH -5.74 -5.45 0.29 166 367 5 70 2.46 MAN 2BH -3.45 -3.23 0.22 166 368 5 70 0.70 SAN 2BH -1.05 -0.90 0.15 167 369 9 70 MAD 2BH -3.20 167 370 9 70 1.52 SAN 2BH -0.99 -0.84 0.15 168 371 13 70 1.44 SAN 2BH -5.68 -5.63 0.05 168 372 13 70 MAD 2BH -3.40 168 373 13 70 1.07 MAN 2BH -0.89 -0.81 0.08 169 374 10 71 2.21 MAN 2BH -3.32 -3.18 0.14 169 375 10 71 1.51 SAN 2BH -1.00 -0.89 0.11 170 376 34 71 MAD 2BH -3.33 170 377 34 71 4.49 MAN 2BH -2.74 -1.94 0.80 171 378 4 72 1.07 SAN 2BH -5.68 -5.64 0.04 171 379 4 72 SAD 2BH -3.00 171 380 4 72 0.86 SAN 2BH -0.97 -0.89 0.08 172 381 8 72 1.18 MAN 2BH -3.20 -3.12 0.08 172 382 8 72 1.63 SAN 2BH -0.89 -0.82 0.07 173 383 25 72 1.31 SAN 2BH -5.55 -5.48 0.07 Page 87 of 115

TABLE 9 STEAM GENERATOR 21 - HISTORICAL F*2 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 173 384 25 72 SAD 2BH -2.84 174 385 9 73 SAD 2BH -2.80 175 386 11 73 1.44 MAN 2BH -3.17 -3.09 0.08 175 387 11 73 1.60 MAN 2BH -0.87 -0.74 0.13 176 388 5 74 1.78 MAN 2BH -3.27 -3.18 0.09 176 389 5 74 1.26 SAN 2BH -0.99 -0.87 0.12 177 390 9 74 MAD 2BH -3.31 177 391 9 74 2.96 SAN 2BH -1.01 -0.77 0.24 178 392 11 77 SAD 2BH -3.44 178 393 11 77 0.95 MAN 2BH -0.94 -0.85 0.09 179 394 17 77 SAD 2BH -3.36 179 395 17 77 4.67 MAN 2BH -2.79 -2.12 0.67 180 396 2 78 SAD 2BH -2.98 180 397 2 78 SAD 2BH -0.97 181 398 7 78 2.61 MAN 2BH -5.72 -5.62 0.10 181 399 7 78 3.90 MAN 2BH -3.39 -3.07 0.32 181 400 7 78 0.85 MAN 2BH -0.85 -0.72 0.13 182 401 13 83 MAD 2BH -2.85 182 402 13 83 SAD 2BH -0.90 Page 88 of 115

TABLE 10 STEAM GENERATOR 22 - HISTORICAL F*2 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1 1 18 14 2.65 MAN 2BH -3.22 -2.89 0.33 1 2 18 14 2.10 SAN 2BH -0.87 -0.72 0.15 2 3 25 14 SAD 2BH -3.58 2 4 25 14 13.83 MAN 2BH -2.96 -2.04 0.92 3 5 4 15 SAD 2BH -3.25 3 6 4 15 2.18 MAN 2BH -2.22 -1.76 0.46 4 7 13 16 SAD 2BH -3.32 4 8 13 16 4.23 MAN 2BH -2.62 -1.40 1.22 5 9 18 16 SAD 2BH -3.34 5 10 18 16 1.48 SAN 2BH -0.74 -0.60 0.14 6 11 1 17 2.23 MAN 2BH -4.24 -3.99 0.25 6 12 1 17 1.03 MAN 2BH -0.85 -0.69 0.16 7 13 18 20 SAD 2BH -3.57 7 14 18 20 5.73 MAN 2BH -2.73 -1.76 0.97 8 15 18 21 SAD 2BH -3.55 8 16 18 21 SAD 2BH -1.48 9 17 32 22 SAD 2BH -3.22 9 18 32 22 7.64 MAN 2BH -2.82 -1.90 0.92 10 19 16 23 SAD 2BH -3.23 10 20 16 23 2.08 MAN 2BH -2.67 -1.92 0.75 11 21 21 24 MAD 2BH -3.31 11 22 21 24 7.26 MAN 2BH -2.64 -1.85 0.79 12 23 25 24 MAD 2BH -3.37 12 24 25 24 5.41 MAN 2BH -2.53 -1.90 0.63 13 25 20 25 SAD 2BH -2.96 13 26 20 25 2.21 SAN 2BH -0.81 -0.73 0.08 14 27 24 26 MAD 2BH -3.39 14 28 24 26 3.84 MAN 2BH -2.73 -2.17 0.56 14 29 24 26 2.77 MAN 2BH -0.97 -0.82 0.15 15 30 27 26 SAD 2BH -3.50 15 31 27 26 2.18 MAN 2BH -2.28 -1.76 0.52 15 32 27 26 1.57 SAN 2BH -0.78 -0.57 0.21 16 33 9 28 SAD 2BH -2.95 16 34 9 28 2.29 SAN 2BH -2.45 -1.84 0.61 17 35 17 28 MAD 2BH -3.19 17 36 17 28 SAD 2BH -2.12 18 37 20 28 SAD 2BH -3.21 18 38 20 28 1.58 SAN 2BH -0.78 -0.67 0.11 19 39 20 29 SAD 2BH -3.16 20 40 29 29 MAD 2BH -3.58 20 41 29 29 5.64 MAN 2BH -2.95 -1.88 1.07 21 42 27 30 MAD 2BH -3.34 21 43 27 30 2.82 SAN 2BH -2.07 -1.78 0.29 22 44 15 31 2.43 MAN 2BH -3.26 -3.04 0.22 22 45 15 31 SAD 2BH -0.31 23 46 17 33 SAD 2BH -3.08 24 47 22 34 MAD 2BH -3.27 Page 89 of 115

TABLE 10 STEAM GENERATOR 22 - HISTORICAL F*2 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 24 48 22 34 1.62 MAN 2BH -2.11 -1.65 0.46 24 49 22 34 0.69 MAN 2BH -0.72 -0.66 0.06 25 50 14 35 1.52 SAN 2BH -3.13 -2.91 0.22 26 51 19 35 SAD 2BH -3.18 27 52 37 35 SAD 2BH -3.48 27 53 37 35 SAD 2BH -0.88 28 54 19 36 SAD 2BH -3.32 29 55 12 37 SAD 2BH -3.28 30 56 14 37 SAD 2BH -2.90 31 57 33 37 MAD 2BH -3.44 31 58 33 37 4.22 MAN 2BH -2.30 -1.77 0.53 32 59 37 38 SAD 2BH -3.37 32 60 37 38 1.70 SAN 2BH -0.94 -0.69 0.25 33 61 18 39 SAD 2BH -3.16 34 62 19 39 SAD 2BH -3.21 35 63 15 40 SAD 2BH -2.90 36 64 18 40 MAD 2BH -3.00 37 65 5 41 SAD 2BH -3.17 37 66 5 41 1.16 MAN 2BH -2.26 -1.69 0.57 38 67 6 43 MAD 2BH -2.85 39 68 15 43 SAD 2BH -3.57 39 69 15 43 0.25 SAN 2BH -2.04 -1.82 0.22 39 70 15 43 0.82 MAN 2BH -0.33 -0.05 0.28 40 71 20 43 0.58 SAN 2BH -3.19 -3.08 0.11 41 72 23 43 MAD 2BH -3.02 42 73 1 44 4.79 MAN 2BH -5.75 -5.52 0.23 42 74 1 44 MAD 2BH -3.24 43 75 10 44 SAD 2BH -2.85 44 76 9 45 MAD 2BH -2.85 45 77 16 45 SAD 2BH -2.85 46 78 37 45 SAD 2BH -3.48 47 79 39 45 SAD 2BH -3.15 48 80 14 46 SAD 2BH -3.20 48 81 14 46 1.80 MAN 2BH -2.04 -1.47 0.57 49 82 22 46 SAD 2BH -2.98 50 83 23 46 SAD 2BH -3.38 51 84 11 47 MAD 2BH -2.80 52 85 18 47 MAD 2BH -3.37 53 86 21 47 SAD 2BH -3.20 54 87 18 48 SAD 2BH -2.96 55 88 19 48 SAD 2BH -2.86 56 89 27 48 SAD 2BH -3.08 57 90 3 49 0.20 SAN 2BH -3.13 -3.06 0.07 57 91 3 49 2.25 MAN 2BH -2.04 -1.80 0.24 57 92 3 49 1.78 SAN 2BH -0.75 -0.64 0.11 58 93 13 49 SAD 2BH -3.53 58 94 13 49 2.47 SAN 2BH -0.69 -0.58 0.11 59 95 10 50 1.95 SAN 2BH -5.85 -5.74 0.11 Page 90 of 115

TABLE 10 STEAM GENERATOR 22 - HISTORICAL F*2 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 59 96 10 50 SAD 2BH -2.97 60 97 26 50 MAD 2BH -3.14 61 98 8 51 SAD 2BH -3.12 62 99 9 51 2.33 SAN 2BH -5.64 -5.52 0.12 62 100 9 51 MAD 2BH -3.22 62 101 9 51 0.48 MAN 2BH -2.42 -2.17 0.25 63 102 11 51 SAD 2BH -3.16 64 103 20 51 MAD 2BH -3.03 64 104 20 51 1.05 SAN 2BH -2.02 -1.89 0.13 65 105 18 52 SAD 2BH -3.10 66 106 24 52 3.85 MAN 2BH -3.41 -2.99 0.42 67 107 10 53 1.31 SAN 2BH -5.91 -5.82 0.09 67 108 10 53 MAD 2BH -3.29 68 109 12 53 1.54 SVN 2BH -4.39 -4.03 0.36 68 110 12 53 2.17 SAN 2BH -3.01 -2.94 0.07 69 111 16 53 SAD 2BH -3.48 69 112 16 53 1.06 MAN 2BH -2.11 -1.90 0.21 70 113 20 53 MAD 2BH -3.16 71 114 12 54 MAD 2BH -3.04 72 115 18 54 MAD 2BH -3.41 72 116 18 54 1.26 SAN 2BH -0.84 -0.68 0.16 73 117 28 54 SAD 2BH -3.41 73 118 28 54 7.75 MAN 2BH -2.73 -1.88 0.85 74 119 37 55 1.20 MAN 2BH -5.91 -5.83 0.08 74 120 37 55 MAD 2BH -3.46 74 121 37 55 2.71 MAN 2BH -2.67 -2.14 0.53 75 122 15 56 MAD 2BH -3.17 75 123 15 56 2.10 MAN 2BH -0.66 -0.59 0.07 76 124 20 56 SAD 2BH -3.21 77 125 37 56 1.88 MAN 2BH -5.72 -5.50 0.22 77 126 37 56 SAD 2BH -3.00 78 127 21 57 0.25 MAN 2BH -3.06 -2.91 0.15 78 128 21 57 3.38 MAN 2BH -0.89 -0.63 0.26 79 129 2 58 SAD 2BH -3.23 80 130 11 58 SAD 2BH -3.08 81 131 13 58 MAD 2BH -2.99 81 132 13 58 2.09 SAN 2BH -0.69 -0.42 0.27 82 133 21 59 MAD 2BH -2.90 83 134 9 60 1.68 SAN 2BH -5.57 -5.48 0.09 83 135 9 60 0.41 SAN 2BH -1.63 -1.49 0.14 84 136 20 60 SAD 2BH -3.25 85 137 13 62 MAD 2BH -3.26 85 138 13 62 2.67 MAN 2BH -2.57 -1.83 0.74 86 139 15 65 1.00 MAN 2BH -2.98 -2.80 0.18 86 140 15 65 2.17 SAN 2BH -0.75 -0.28 0.47 87 141 16 65 MAD 2BH -3.04 88 142 12 66 MAD 2BH -3.50 88 143 12 66 1.43 SAN 2BH -0.81 -0.65 0.16 Page 91 of 115

TABLE 10 STEAM GENERATOR 22 - HISTORICAL F*2 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 89 144 24 66 1.13 SAN 2BH -3.60 -3.52 0.08 89 145 24 66 1.66 SAN 2BH -0.93 -0.85 0.08 90 146 24 69 0.35 MAN 2BH -3.49 -3.41 0.08 90 147 24 69 1.47 SAN 2BH -0.79 -0.68 0.11 90 148 24 69 0.45 SAN 2BH -0.19 -0.11 0.08 91 149 32 70 MAD 2BH -3.39 91 150 32 70 5.95 MAN 2BH -2.55 -1.70 0.85 92 151 20 71 5.84 MAN 2BH -5.65 -5.36 0.29 92 152 20 71 SAD 2BH -3.29 92 153 20 71 1.53 SAN 2BH -0.75 -0.63 0.12 93 154 26 71 SAD 2BH -3.51 93 155 26 71 3.86 MAN 2BH -2.69 -2.00 0.69 94 156 16 72 SAD 2BH -3.40 94 157 16 72 0.89 SAN 2BH -0.69 -0.58 0.11 95 158 12 73 1.03 MAN 2BH -3.15 -3.00 0.15 95 159 12 73 2.22 SAN 2BH -0.77 -0.66 0.11 96 160 16 73 MAD 2BH -3.43 96 161 16 73 5.03 MAN 2BH -2.46 -1.80 0.66 97 162 19 73 SAD 2BH -3.22 97 163 19 73 1.41 SAN 2BH -0.82 -0.71 0.11 98 164 15 74 MAD 2BH -3.29 98 165 15 74 2.40 SAN 2BH -0.97 -0.89 0.08 99 166 22 75 SAD 2BH -3.12 99 167 22 75 3.51 MAN 2BH -2.48 -1.81 0.67 100 168 11 76 2.35 MAN 2BH -3.25 -3.10 0.15 100 169 11 76 3.33 SAN 2BH -0.80 -0.68 0.12 101 170 17 76 MAD 2BH -3.13 101 171 17 76 1.66 MAN 2BH -0.95 -0.79 0.16 102 172 12 77 MAD 2BH -3.49 102 173 12 77 0.53 MAN 2BH -0.75 -0.67 0.08 103 174 22 77 4.06 SAN 2BH -3.54 -3.36 0.18 103 175 22 77 1.60 MAN 2BH -0.93 -0.83 0.10 104 176 23 78 SAD 2BH -3.46 104 177 23 78 8.35 MAN 2BH -2.67 -1.70 0.97 105 178 12 79 3.25 MAN 2BH -3.40 -3.26 0.14 105 179 12 79 5.49 SAN 2BH -2.87 -2.30 0.57 105 180 12 79 1.46 MAN 2BH -0.95 -0.85 0.10 106 181 17 80 SAD 2BH -3.27 106 182 17 80 2.30 SAN 2BH -0.93 -0.75 0.18 107 183 13 81 SAD 2BH -3.38 107 184 13 81 1.03 SAN 2BH -2.05 -1.84 0.21 108 185 18 81 SAD 2BH -3.26 108 186 18 81 1.50 SAN 2BH -0.74 -0.65 0.09 109 187 22 81 1.74 SAN 2BH -3.48 -3.38 0.10 109 188 22 81 1.69 SAN 2BH -0.88 -0.79 0.09 110 189 26 81 MAD 2BH -3.34 110 190 26 81 4.31 MAN 2BH -2.42 -1.95 0.47 111 191 15 85 SAD 2BH -3.25 Page 92 of 115

TABLE 10 STEAM GENERATOR 22 - HISTORICAL F*2 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 111 192 15 85 3.96 MAN 2BH -2.53 -1.91 0.62 112 193 15 86 MAD 2BH -3.42 112 194 15 86 4.27 MAN 2BH -2.51 -1.93 0.58 113 195 14 88 SAD 2BH -3.42 113 196 14 88 5.89 MAN 2BH -2.62 -1.88 0.74 Page 93 of 115

TABLE 11 STEAM GENERATOR 21 - HISTORICAL EF*

TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1 1 2 21 SAD EBH -14.11 1 2 2 21 1.45 SAN EBH -11.42 -11.28 0.14 1 3 2 21 1.11 MAN EBH -10.99 -10.81 0.18 1 4 2 21 2.13 MAN EBH -9.09 -8.86 0.23 2 5 3 24 SAD EBH -14.03 2 6 3 24 2.22 SAN EBH -11.17 -11.03 0.14 2 7 3 24 0.74 SAN EBH -9.08 -8.94 0.14 3 8 30 27 MAD EBH -13.33 3 9 30 27 2.67 SAN EBH -11.14 -11.05 0.09 3 10 30 27 2.57 MAN EBH -9.54 -9.01 0.53 4 11 9 30 1.82 SAN EBH -16.35 -16.27 0.08 4 12 9 30 0.15 MAN EBH -13.70 -13.61 0.09 4 13 9 30 2.93 SAN EBH -11.34 -11.01 0.33 4 14 9 30 1.39 SAN EBH -9.50 -9.31 0.19 5 15 13 30 0.43 SAN EBH -16.13 -16.09 0.04 5 16 13 30 SAD EBH -13.71 6 17 13 32 SAD EBH -13.67 7 18 17 32 0.95 SAN EBH -16.21 -16.01 0.20 7 19 17 32 SAD EBH -13.48 8 20 13 34 MAD EBH -13.48 9 21 22 38 SAD EBH -13.57 9 22 22 38 MAD EBH -12.50 9 23 22 38 MAD EBH -11.00 10 24 14 40 2.61 MAN EBH -13.43 -13.35 0.08 10 25 14 40 0.20 SAN EBH -11.99 -11.62 0.37 10 26 14 40 0.74 SAN EBH -9.06 -8.98 0.08 11 27 17 41 SAD EBH -13.48 12 28 6 43 SAD EBH -13.48 12 29 6 43 0.33 MAN EBH -13.31 -13.23 0.08 12 30 6 43 SAD EBH -11.20 13 31 28 43 SAD EBH -13.51 13 32 28 43 0.65 SAN EBH -13.27 -10.41 2.86 14 33 10 44 2.31 MAN EBH -13.60 -13.44 0.16 14 34 10 44 SAD EBH -13.53 14 35 10 44 0.48 SAN EBH -9.26 -9.19 0.07 15 36 30 45 0.25 SAN EBH -13.65 -13.61 0.04 15 37 30 45 1.20 MAN EBH -11.34 -11.26 0.08 15 38 30 45 0.83 SAN EBH -9.12 -8.99 0.13 16 39 1 46 1.38 SAN EBH -16.27 -16.12 0.15 16 40 1 46 SAD EBH -13.41 16 41 1 46 0.50 MAN EBH -13.33 -11.80 1.53 16 42 1 46 0.43 SAN EBH -0.05 -0.01 0.04 17 43 28 48 SAD EBH -13.43 17 44 28 48 0.23 SAN EBH -13.31 -9.94 3.37 18 45 14 50 1.60 MAN EBH -13.70 -13.62 0.08 18 46 14 50 0.11 SAN EBH -12.89 -12.49 0.40 18 47 14 50 1.25 SAN EBH -9.41 -9.21 0.20 Page 94 of 115

TABLE 11 STEAM GENERATOR 21 - HISTORICAL EF*

TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 19 48 28 55 SAD EBH -13.90 20 49 4 60 MAD EBH -13.54 20 50 4 60 2.46 SAN EBH -11.63 -11.50 0.13 20 51 4 60 0.77 SAN EBH -9.58 -9.36 0.22 21 52 7 61 MAD EBH -13.42 21 53 7 61 3.10 SAN EBH -11.54 -11.22 0.32 21 54 7 61 2.48 SAN EBH -9.62 -9.26 0.36 22 55 10 66 1.57 SAN EBH -16.38 -16.28 0.10 22 56 10 66 MAD EBH -13.84 22 57 10 66 3.16 SAN EBH -11.45 -11.17 0.28 22 58 10 66 1.16 SAN EBH -9.25 -9.07 0.18 23 59 22 72 SAD EBH -13.52 23 60 22 72 0.28 SAN EBH -13.39 -10.26 3.13 Page 95 of 115

TABLE 12 STEAM GENERATOR 22 - HISTORICAL EF*

TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1 1 21 22 SAD EBH -14.14 1 2 21 22 1.78 MAN EBH -9.46 -9.14 0.32 2 3 13 41 MAD EBH -14.15 2 4 13 41 0.45 SAN EBH -10.36 -10.22 0.14 3 5 12 42 SAD EBH -13.64 3 6 12 42 2.53 SAN EBH -11.08 -10.90 0.18 3 7 12 42 0.64 SAN EBH -9.19 -9.00 0.19 4 8 16 44 SAD EBH -14.03 4 9 16 44 1.15 SAN EBH -8.80 -8.72 0.08 5 10 17 45 4.90 MAN EBH -13.90 -13.41 0.49 5 11 17 45 0.54 SAN EBH -9.44 -9.36 0.08 Page 96 of 115

TABLE 13 STEAM GENERATOR 21 - NEW F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1 1 7 1 0.56 SAI TRH 0.04 0.21 0.17 2 2 3 2 0.77 SAI TRH 0.03 0.11 0.08 3 3 11 2 0.42 SAI TRH 0.13 0.22 0.09 4 4 4 3 1.19 MAN TRH -2.46 -2.39 0.07 4 5 4 3 0.93 MAI TRH 0.05 0.16 0.11 5 6 9 3 0.37 SAI TRH 0.15 0.18 0.03 6 7 3 7 0.60 SAI TRH 0.38 0.43 0.05 6 8 3 7 0.68 SAN TRH -2.56 -2.52 0.04 7 9 21 7 0.67 SAI TRH 0.07 0.14 0.07 8 10 15 9 0.48 SAI TRH 0.12 0.16 0.04 9 11 10 10 0.43 SAI TRH 0.11 0.22 0.11 10 12 27 10 0.34 MAI TRH 0.25 0.35 0.10 10 13 27 10 2.52 MAN TRH -2.69 -2.61 0.08 11 14 18 11 0.41 SAI TRH 0.11 0.16 0.05 12 15 26 11 0.51 SAI TRH 0.10 0.17 0.07 12 16 26 11 2.36 SAN TRH -2.30 -2.22 0.08 13 17 29 11 0.58 SAI TRH 0.07 0.21 0.14 13 18 29 11 2.90 MAN TRH -2.44 -2.33 0.11 14 19 20 12 0.58 MAI TRH 0.01 0.11 0.10 14 20 20 12 1.36 SAI TRH -2.59 -2.52 0.07 15 21 3 13 0.91 SAI TRH 0.04 0.12 0.08 16 22 7 13 5.23 MAN TRH -2.57 -2.41 0.16 16 23 7 13 0.91 MAI TRH 0.01 0.10 0.09 17 24 12 13 1.10 MAI TRH 0.06 0.14 0.08 17 25 12 13 1.85 SAN TRH -2.54 -2.47 0.07 18 26 20 13 0.76 MAI TRH 0.07 0.16 0.09 19 27 25 13 0.72 MAI TRH 0.09 0.16 0.07 19 28 25 13 1.81 SAN TRH -2.54 -2.44 0.10 20 29 3 15 1.43 SAI TRH 0.00 0.08 0.08 21 30 2 16 4.43 SAN TRH -2.60 -2.28 0.32 21 31 2 16 1.01 MAI TRH 0.06 0.18 0.12 22 32 19 16 0.54 MAI TRH 0.03 0.09 0.06 22 33 19 16 1.37 MAI TRH -2.52 -2.42 0.10 23 34 22 16 0.73 SAI TRH 0.05 0.14 0.09 24 35 20 17 0.77 MAI TRH -0.01 0.10 0.11 25 36 15 18 0.62 MAI TRH 0.05 0.14 0.09 26 37 21 18 0.80 MAI TRH 0.00 0.06 0.06 27 38 32 18 0.68 SAI TRH 0.14 0.21 0.07 28 39 18 19 0.48 SAI TRH 0.09 0.13 0.04 29 40 22 20 0.33 SAI TRH 0.12 0.15 0.03 30 41 31 20 0.45 SAI TRH 0.15 0.20 0.05 30 42 31 20 2.03 SAN TRH -2.40 -2.30 0.10 31 43 23 22 0.27 SAI TRH 0.16 0.23 0.07 32 44 29 22 0.35 SAI TRH 0.14 0.19 0.05 33 45 36 22 0.46 SAI TRH 0.12 0.19 0.07 34 46 15 25 0.68 MAI TRH -0.03 0.08 0.11 35 47 18 25 0.38 SAI TRH 0.13 0.20 0.07 Page 97 of 115

TABLE 13 STEAM GENERATOR 21 - NEW F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 36 48 2 26 0.73 MAI TRH 0.10 0.17 0.07 37 49 33 26 0.74 SAI TRH 0.12 0.19 0.07 38 50 1 27 1.39 SAN TRH -2.65 -2.52 0.13 38 51 1 27 0.79 SAI TRH 0.00 0.15 0.15 39 52 14 27 0.30 SAI TRH 0.08 0.15 0.07 40 53 4 28 0.46 SAI TRH 0.12 0.16 0.04 41 54 36 29 0.43 MAI TRH 0.05 0.15 0.10 42 55 2 30 0.59 MAI TRH 0.10 0.21 0.11 43 56 19 30 0.55 MAI TRH 0.14 0.24 0.10 44 57 35 30 0.78 MAI TRH 0.09 0.20 0.11 45 58 41 31 0.57 SAI TRH 0.11 0.15 0.04 46 59 42 31 0.57 SAI TRH 0.16 0.22 0.06 47 60 4 32 0.66 SAI TRH 0.12 0.23 0.11 48 61 20 32 0.51 MAI TRH 0.09 0.24 0.15 49 62 25 33 0.39 SAI TRH 0.18 0.22 0.04 50 63 30 41 0.41 SAI TRH 0.12 0.19 0.07 51 64 26 43 0.32 SAI TRH 0.08 0.15 0.07 52 65 22 45 0.68 MAI TRH 0.07 0.19 0.12 53 66 31 48 0.83 MAI TRH 0.11 0.24 0.13 54 67 39 48 0.55 SAI TRH 0.09 0.13 0.04 55 68 1 50 1.33 SAN TRH -2.66 -2.58 0.08 55 69 1 50 0.64 SAI TRH 0.09 0.19 0.10 56 70 36 50 0.38 SAI TRH 0.11 0.23 0.12 57 71 42 51 0.29 SAI TRH 0.10 0.14 0.04 58 72 37 53 0.80 MAI TRH 0.10 0.28 0.18 59 73 38 53 0.95 MAI TRH 0.09 0.22 0.13 60 74 16 54 0.26 SAI TRH 0.22 0.25 0.03 61 75 15 56 0.79 MAI TRH 0.03 0.13 0.10 62 76 17 56 0.67 MAI TRH 0.07 0.16 0.09 63 77 40 57 0.35 MAI TRH 0.07 0.14 0.07 64 78 7 59 0.69 MAI TRH -0.10 0.10 0.20 65 79 30 59 0.34 MAI TRH 0.03 0.14 0.11 66 80 36 59 0.45 SAI TRH 0.02 0.12 0.10 67 81 8 60 0.85 MAI TRH 0.00 0.23 0.23 68 82 12 60 0.83 MAI TRH 0.10 0.21 0.11 69 83 20 61 1.17 SAI TRH 0.04 0.12 0.08 70 84 36 61 0.61 SAI TRH 0.05 0.17 0.12 71 85 30 63 0.52 SAI TRH 0.05 0.13 0.08 71 86 30 63 1.47 SAN TRH -2.51 -2.44 0.07 72 87 31 63 0.91 MAI TRH 0.13 0.19 0.06 73 88 22 65 0.69 SAI TRH 0.20 0.34 0.14 74 89 13 67 1.05 MAI TRH -0.02 0.17 0.19 75 90 23 67 1.28 MAI TRH 0.15 0.20 0.05 76 91 30 69 0.41 SAI TRH 0.23 0.28 0.05 77 92 25 71 0.69 SAI TRH 0.10 0.17 0.07 77 93 25 71 0.52 SAI TRH -2.44 -2.38 0.06 78 94 1 73 2.56 MAN TRH -2.64 -2.46 0.18 78 95 1 73 0.22 SAI TRH 0.10 0.14 0.04 Page 98 of 115

TABLE 13 STEAM GENERATOR 21 - NEW F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 79 96 8 73 0.93 MAI TRH 0.07 0.20 0.13 80 97 34 73 0.51 SAI TRH -0.05 0.02 0.07 81 98 16 74 0.48 SAI TRH 0.00 0.05 0.05 81 99 16 74 2.39 SAN TRH -2.65 -2.52 0.13 82 100 17 74 0.34 SAI TRH 0.14 0.21 0.07 83 101 23 74 0.53 SAI TRH 0.10 0.16 0.06 83 102 23 74 0.58 SAI TRH -2.46 -2.41 0.05 84 103 23 75 0.42 SAI TRH 0.08 0.33 0.25 84 104 23 75 2.94 SAN TRH -2.42 -2.30 0.12 85 105 29 76 0.42 SAI TRH 0.13 0.21 0.08 85 106 29 76 3.03 SAN TRH -2.63 -2.40 0.23 86 107 15 77 0.66 MAI TRH 0.05 0.19 0.14 87 108 8 78 0.63 SAI TRH -0.07 0.00 0.07 88 109 17 78 0.61 SAI TRH 0.15 0.25 0.10 88 110 17 78 1.62 SAN TRH -2.59 -2.51 0.08 89 111 22 78 0.88 MAI TRH 0.06 0.13 0.07 89 112 22 78 2.90 MAN TRH -2.57 -2.41 0.16 90 113 24 81 0.50 SAI TRH 0.14 0.19 0.05 91 114 6 82 0.52 SAI TRH -0.20 -0.15 0.05 92 115 8 83 0.52 MAI TRH -0.03 0.14 0.17 93 116 18 83 1.00 MAI TRH 0.10 0.22 0.12 94 117 7 84 0.32 SAI TRH 0.01 0.05 0.04 95 118 5 85 0.81 MAI TRH 0.03 0.20 0.17 95 119 5 85 0.54 SAI TRH -2.54 -2.50 0.04 96 120 2 86 0.47 SAI TRH 0.13 0.22 0.09 97 121 10 88 0.86 SAI TRH 0.27 0.35 0.08 98 122 7 89 0.84 MAI TRH 0.00 0.17 0.17 99 123 8 89 0.95 SAI TRH 0.09 0.14 0.05 100 124 6 91 0.47 SAI TRH -0.07 -0.02 0.05 101 125 8 91 0.42 MAI TRH -0.04 0.12 0.16 Page 99 of 115

TABLE 14 STEAM GENERATOR 22 - NEW F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1 1 1 6 2.68 SAN TRH -2.47 -2.36 0.11 1 2 1 6 0.49 MAI TRH 0.10 0.18 0.08 2 3 1 7 4.92 SAN TRH -2.38 -2.09 0.29 2 4 1 7 0.41 MAI TRH 0.16 0.27 0.11 3 5 1 8 0.32 SAI TRH 0.12 0.19 0.07 4 6 21 9 0.48 SAI TRH 0.13 0.20 0.07 5 7 1 11 0.59 MAI TRH 0.08 0.23 0.15 6 8 1 12 1.32 SAN TRH -2.62 -2.44 0.18 6 9 1 12 0.38 MAI TRH 0.04 0.14 0.10 7 10 1 13 0.44 SAI TRH 0.09 0.16 0.07 8 11 16 13 0.43 MAI TRH 0.09 0.16 0.07 9 12 9 14 0.32 MAI TRH 0.07 0.23 0.16 10 13 23 17 0.13 SAI TRH -0.04 0.03 0.07 11 14 29 18 0.44 SAI TRH -0.03 0.04 0.07 12 15 31 19 0.39 MAI TRH 0.09 0.17 0.08 13 16 7 20 0.50 SAI TRH 0.13 0.21 0.08 14 17 25 20 0.38 MAI TRH 0.08 0.17 0.09 15 18 31 20 0.38 MAI TRH 0.03 0.17 0.14 16 19 35 20 1.48 MAN TRH -2.41 -2.12 0.29 16 20 35 20 0.42 MAI TRH -0.09 0.16 0.25 17 21 2 21 0.45 SAI TRH 0.10 0.24 0.14 18 22 7 21 0.62 SAI TRH 0.07 0.22 0.15 19 23 20 21 0.37 SAI TRH 0.09 0.19 0.10 20 24 20 23 0.73 SAI TRH 0.08 0.16 0.08 21 25 33 23 0.52 MAI TRH 0.01 0.20 0.19 22 26 37 23 0.85 MAN TRH -2.43 -2.33 0.10 22 27 37 23 0.44 SAI TRH 0.02 0.15 0.13 23 28 20 24 0.52 SAI TRH 0.10 0.18 0.08 24 29 27 27 0.89 SAI TRH -0.03 0.04 0.07 25 30 33 27 0.64 MAI TRH 0.02 0.12 0.10 26 31 35 27 0.84 SAI TRH -0.08 0.02 0.10 27 32 22 28 0.74 SAI TRH -0.06 0.06 0.12 28 33 33 28 0.94 SAI TRH 0.04 0.19 0.15 29 34 28 29 0.35 SAI TRH 0.12 0.16 0.04 30 35 35 37 1.25 MAI TRH -0.06 0.00 0.06 31 36 3 38 0.41 SAI TRH 0.13 0.18 0.05 32 37 4 39 1.26 SVI TRH -0.25 0.34 0.59 32 38 4 39 1.06 SVI TRH -0.25 0.34 0.59 33 39 30 39 0.76 SAI TRH 0.09 0.18 0.09 34 40 35 39 0.47 SAI TRH -0.06 0.03 0.09 35 41 34 42 0.76 MAI TRH -0.06 0.03 0.09 36 42 38 43 0.29 MAI TRH -0.05 0.02 0.07 37 43 38 44 0.50 SAI TRH -0.07 0.02 0.09 38 44 2 45 2.24 SAN TRH -2.53 -2.34 0.19 38 45 2 45 0.81 MAI TRH 0.05 0.18 0.13 39 46 33 45 0.25 SAI TRH 0.05 0.14 0.09 40 47 3 47 0.37 SAI TRH 0.15 0.20 0.05 Page 100 of 115

TABLE 14 STEAM GENERATOR 22 - NEW F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 41 48 4 47 0.51 SAI TRH 0.15 0.19 0.04 42 49 15 47 0.38 SAI TRH 0.10 0.21 0.11 43 50 13 48 0.69 MAI TRH -0.06 0.12 0.18 44 51 22 49 0.74 MAI TRH 0.00 0.23 0.23 45 52 3 50 1.27 SAN TRH -2.64 -2.56 0.08 45 53 3 50 0.36 SAI TRH 0.05 0.17 0.12 46 54 37 50 0.34 SAI TRH 0.09 0.13 0.04 46 55 37 50 0.94 SAN TRH -2.35 -2.24 0.11 47 56 27 51 0.77 SAI TRH 0.00 0.17 0.17 48 57 32 52 0.96 MAI TRH 0.10 0.22 0.12 49 58 37 52 0.93 SAN TRH -2.33 -2.23 0.10 49 59 37 52 0.41 SAI TRH 0.14 0.18 0.04 50 60 2 55 0.32 SAI TRH 0.10 0.14 0.04 51 61 7 55 0.59 SAI TRH -0.02 0.15 0.17 51 62 7 55 1.51 SAN TRH -2.64 -2.53 0.11 52 63 11 55 0.54 SAI TRH 0.09 0.22 0.13 53 64 1 56 2.94 MAN TRH -2.66 -2.51 0.15 53 65 1 56 0.43 SAI TRH 0.17 0.21 0.04 54 66 5 56 0.67 SAI TRH 0.04 0.18 0.14 55 67 14 56 0.62 SAI TRH 0.15 0.23 0.08 56 68 18 56 0.25 SAI TRH 0.18 0.22 0.04 57 69 12 57 0.32 SAI TRH 0.09 0.15 0.06 58 70 36 57 0.43 SAI TRH -0.02 0.02 0.04 59 71 43 57 0.95 SAI TRH -0.09 0.03 0.12 60 72 10 58 0.45 SAI TRH 0.01 0.06 0.05 61 73 27 58 0.28 SAI TRH -0.06 0.18 0.24 62 74 33 58 0.43 MAI TRH 0.12 0.21 0.09 63 75 2 59 0.37 SAI TRH 0.08 0.23 0.15 64 76 7 59 1.50 SAN TRH -2.49 -2.41 0.08 64 77 7 59 0.50 MAI TRH 0.13 0.26 0.13 65 78 11 59 0.36 MAI TRH -0.03 0.18 0.21 66 79 12 59 0.30 SAI TRH 0.07 0.18 0.11 67 80 10 60 0.39 SAI TRH -0.04 0.00 0.04 67 81 10 60 1.07 SAI TRH -2.62 -2.55 0.07 68 82 11 60 0.37 SAI TRH -0.03 0.16 0.19 69 83 12 60 0.63 SAI TRH -0.06 0.02 0.08 69 84 12 60 1.80 MVI TRH -1.82 -1.44 0.38 70 85 14 60 0.86 SAI TRH -0.07 0.05 0.12 71 86 6 61 1.91 SAN TRH -2.62 -2.53 0.09 71 87 6 61 0.50 MAI TRH 0.17 0.31 0.14 72 88 9 61 0.49 SAI TRH 0.12 0.20 0.08 72 89 9 61 0.80 SAI TRH -2.59 -2.55 0.04 73 90 21 61 0.61 SAI TRH 0.08 0.17 0.09 74 91 39 61 0.85 SAI TRH -0.01 0.04 0.05 75 92 1 62 0.57 MAI TRH 0.01 0.16 0.15 75 93 1 62 5.30 MAN TRH -2.74 -2.49 0.25 76 94 11 62 0.34 SAI TRH -0.02 0.05 0.07 76 95 11 62 0.88 SAI TRH -2.59 -2.52 0.07 Page 101 of 115

TABLE 14 STEAM GENERATOR 22 - NEW F*1 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 77 96 15 62 0.61 SAI TRH 0.04 0.11 0.07 78 97 10 63 0.74 SAI TRH 0.08 0.19 0.11 79 98 13 63 0.48 SAI TRH 0.07 0.18 0.11 80 99 15 63 0.65 SAI TRH 0.07 0.14 0.07 81 100 13 64 0.61 MAI TRH 0.07 0.19 0.12 82 101 21 64 0.86 SAI TRH -0.05 -0.01 0.04 83 102 31 65 0.75 MAI TRH -0.01 0.22 0.23 84 103 15 66 0.56 MAI TRH 0.10 0.21 0.11 85 104 18 66 1.26 SAN TRH -1.75 -1.57 0.18 85 105 18 66 0.65 SAI TRH 0.06 0.22 0.16 86 106 32 66 0.39 MAI TRH -0.02 0.09 0.11 87 107 3 67 0.74 MAI TRH 0.07 0.19 0.12 88 108 19 67 0.30 SAI TRH 0.08 0.16 0.08 89 109 21 67 0.54 SAI TRH 0.09 0.18 0.09 90 110 3 69 0.42 MAI TRH 0.07 0.19 0.12 90 111 3 69 0.80 SAN TRH -2.44 -2.36 0.08 91 112 13 69 0.48 MAI TRH 0.18 0.32 0.14 92 113 19 69 0.24 SAI TRH 0.10 0.28 0.18 93 114 21 69 0.67 SAI TRH 0.12 0.19 0.07 94 115 36 69 0.66 SAI TRH -0.05 0.04 0.09 95 116 3 70 0.32 SAI TRH 0.14 0.19 0.05 96 117 18 70 0.60 SAI TRH 0.12 0.19 0.07 97 118 19 70 0.41 SAI TRH 0.08 0.15 0.07 98 119 28 71 0.37 SAI TRH 0.16 0.22 0.06 99 120 35 71 0.43 SAI TRH 0.00 0.03 0.03 100 121 20 72 0.57 MAI TRH 0.14 0.26 0.12 101 122 34 72 0.42 SAI TRH -0.03 0.07 0.10 101 123 34 72 2.10 SAN TRH -2.49 -2.38 0.11 102 124 23 73 0.67 SAI TRH -0.08 0.02 0.10 103 125 13 74 0.39 SAI TRH 0.00 0.10 0.10 104 126 34 74 1.23 SAI TRH 0.01 0.09 0.08 105 127 10 76 0.50 SAI TRH 0.11 0.18 0.07 106 128 19 78 0.58 SAI TRH 0.09 0.15 0.06 107 129 10 81 0.34 SAI TRH 0.11 0.18 0.07 108 130 11 81 0.43 SAI TRH -0.06 0.03 0.09 109 131 13 83 0.88 MAI TRH -0.01 0.15 0.16 110 132 14 83 0.76 MAI TRH 0.10 0.16 0.06 111 133 26 83 1.19 SAI TRH 0.00 0.09 0.09 112 134 9 84 0.66 SAI TRH -0.04 0.08 0.12 113 135 12 86 0.62 SAI TRH 0.09 0.19 0.10 114 136 12 88 0.22 SAI TRH 0.15 0.20 0.05 Page 102 of 115

TABLE 15 STEAM GENERATOR 21 - NEW F*2 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1 1 4 2 MAD 1BH -1.06 1 2 4 2 0.94 MAI 1BH -0.18 0.16 0.34 2 3 13 9 1.80 SAN 1BH -3.61 -3.54 0.07 2 4 13 9 SAD 1BH -1.27 2 5 13 9 0.89 MAI 1BH 1.28 1.39 0.11 3 6 7 12 3.65 MAN 1BH -3.62 -3.34 0.28 3 7 7 12 SAD 1BH -1.07 3 8 7 12 0.50 SAI 1BH 1.09 1.20 0.11 4 9 4 13 1.00 SAN 1BH -1.19 -1.08 0.11 4 10 4 13 0.32 SAI 1BH 1.18 1.25 0.07 5 11 13 15 3.44 MAN 1BH -1.43 -0.87 0.56 5 12 13 15 0.45 SAI 1BH 1.13 1.25 0.12 6 13 2 17 3.93 MAN 1BH -3.54 -3.23 0.31 6 14 2 17 SAD 1BH -1.40 6 15 2 17 0.82 SAI 1BH 1.24 1.34 0.10 7 16 25 17 5.49 SAN 1BH -3.75 -3.55 0.20 7 17 25 17 MAD 1BH -1.75 7 18 25 17 3.27 SAN 1BH -1.11 -0.86 0.25 7 19 25 17 0.69 MAI 1BH 1.16 1.27 0.11 8 20 13 18 SAD 1BH -1.30 8 21 13 18 0.40 SAI 1BH 1.12 1.23 0.11 9 22 33 19 SAD 1BH -1.38 9 23 33 19 0.52 MAI 1BH 0.96 1.08 0.12 10 24 17 20 1.52 MAN 1BH -1.23 -1.12 0.11 10 25 17 20 0.74 SAI 1BH 1.15 1.22 0.07 11 26 18 20 3.18 SAN 1BH -3.72 -3.55 0.17 11 27 18 20 SAD 1BH -1.29 11 28 18 20 0.48 SAI 1BH 1.25 1.35 0.10 12 29 35 20 0.54 SAI 1BH 1.36 1.50 0.14 12 30 35 20 SAD 1BH -1.27 13 31 11 21 SAD 1BH -1.21 13 32 11 21 0.50 SAI 1BH 1.28 1.33 0.05 14 33 14 21 SAD 1BH -1.28 14 34 14 21 2.84 SAN 1BH -0.54 -0.15 0.39 14 35 14 21 0.46 SAI 1BH 1.23 1.33 0.10 15 36 31 21 4.44 SAN 1BH -3.75 -3.61 0.14 15 37 31 21 SAD 1BH -1.27 15 38 31 21 0.80 SAI 1BH 1.07 1.18 0.11 16 39 2 22 2.79 MAN 1BH -1.18 -1.00 0.18 16 40 2 22 0.46 MAI 1BH 1.33 1.41 0.08 17 41 3 23 4.69 MAN 1BH -1.32 -0.90 0.42 17 42 3 23 0.40 MAI 1BH 1.29 1.36 0.07 18 43 30 23 1.92 SAN 1BH -3.75 -3.60 0.15 18 44 30 23 MAD 1BH -0.97 18 45 30 23 0.63 MAI 1BH 1.13 1.28 0.15 19 46 39 23 0.68 SAI 1BH 1.13 1.21 0.08 19 47 39 23 MAD 1BH -1.38 Page 103 of 115

TABLE 15 STEAM GENERATOR 21 - NEW F*2 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 20 48 8 25 SAD 1BH -1.49 20 49 8 25 0.18 SAI 1BH 1.25 1.31 0.06 21 50 5 26 SAD 1BH -1.27 21 51 5 26 0.42 SAI 1BH 1.23 1.30 0.07 22 52 7 26 MAD 1BH -1.32 22 53 7 26 0.37 MAI 1BH 1.26 1.43 0.17 23 54 26 27 MAD 1BH -1.27 23 55 26 27 0.34 MAI 1BH 1.14 1.26 0.12 24 56 36 27 MAD 1BH -1.18 24 57 36 27 0.45 SAI 1BH 1.13 1.24 0.11 25 58 3 28 3.59 MAN 1BH -1.28 -0.92 0.36 25 59 3 28 0.38 SAI 1BH 1.22 1.33 0.11 26 60 15 28 0.90 SAN 1BH -1.20 -1.11 0.09 26 61 15 28 0.71 SAI 1BH 1.15 1.29 0.14 27 62 17 28 MAD 1BH -1.17 27 63 17 28 0.30 SAI 1BH 1.27 1.31 0.04 28 64 19 28 4.65 MAN 1BH -1.43 -0.91 0.52 28 65 19 28 0.61 MAI 1BH 1.28 1.42 0.14 29 66 23 29 MAD 1BH -1.26 29 67 23 29 0.40 MAI 1BH 1.07 1.17 0.10 30 68 27 29 MAD 1BH -1.27 30 69 27 29 0.61 MAI 1BH 1.17 1.28 0.11 31 70 8 30 1.94 MAN 1BH -3.73 -3.64 0.09 31 71 8 30 1.32 SAN 1BH -1.17 -1.08 0.09 31 72 8 30 0.47 SAI 1BH 1.20 1.38 0.18 32 73 37 31 0.47 SAI 1BH 1.15 1.19 0.04 32 74 37 31 2.27 SAN 1BH -3.74 -3.67 0.07 32 75 37 31 MAD 1BH -1.23 33 76 24 32 MAD 1BH -1.29 33 77 24 32 0.44 SAI 1BH 1.20 1.24 0.04 34 78 21 33 1.55 MAN 1BH -1.20 -1.10 0.10 34 79 21 33 0.34 SAI 1BH 1.28 1.33 0.05 35 80 34 34 0.86 MAN 1BH -1.29 -1.18 0.11 35 81 34 34 0.59 MAI 1BH 1.12 1.28 0.16 36 82 4 35 MAD 1BH -0.95 36 83 4 35 0.39 SAI 1BH 1.42 1.46 0.04 37 84 31 35 SAD 1BH -1.36 37 85 31 35 0.83 MAI 1BH 0.94 1.07 0.13 38 86 6 36 2.41 MAN 1BH -1.21 -1.11 0.10 38 87 6 36 0.82 SAI 1BH 1.07 1.18 0.11 39 88 29 36 SAD 1BH -1.31 39 89 29 36 0.46 SAI 1BH 1.07 1.14 0.07 40 90 6 37 1.80 MAN 1BH -1.14 -1.07 0.07 40 91 6 37 0.32 SAI 1BH 1.23 1.27 0.04 41 92 21 37 0.84 MAN 1BH -1.20 -1.10 0.10 41 93 21 37 0.62 SAI 1BH 1.26 1.33 0.07 42 94 33 37 SAD 1BH -0.88 42 95 33 37 0.45 SAI 1BH 1.15 1.19 0.04 Page 104 of 115

TABLE 15 STEAM GENERATOR 21 - NEW F*2 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 43 96 3 38 0.90 MAN 1BH -1.11 -1.05 0.06 43 97 3 38 0.51 MAI 1BH 1.23 1.30 0.07 44 98 24 38 SAD 1BH -1.18 44 99 24 38 0.57 SAI 1BH 1.18 1.25 0.07 45 100 35 38 0.74 SAI 1BH 1.25 1.32 0.07 45 101 35 38 MAD 1BH -1.26 46 102 12 39 2.07 SAN 1BH -1.11 -1.00 0.11 46 103 12 39 0.50 SAI 1BH 1.36 1.43 0.07 47 104 20 39 1.79 MAN 1BH -1.25 -1.15 0.10 47 105 20 39 0.34 SAI 1BH 1.20 1.21 0.01 48 106 30 39 MAD 1BH -1.17 48 107 30 39 0.46 SAI 1BH 1.17 1.25 0.08 49 108 12 41 2.26 MAN 1BH -1.17 -1.06 0.11 49 109 12 41 0.65 MAI 1BH 1.24 1.34 0.10 50 110 8 42 MAD 1BH -1.23 50 111 8 42 0.36 SAI 1BH 1.23 1.27 0.04 51 112 17 42 SAD 1BH -0.80 51 113 17 42 0.51 SAI 1BH 1.30 1.34 0.04 52 114 6 46 MAD 1BH -1.55 52 115 6 46 0.51 SAI 1BH 1.25 1.33 0.08 53 116 9 47 1.56 MAN 1BH -1.27 -1.14 0.13 53 117 9 47 SAD 1BH -0.75 53 118 9 47 0.46 MAI 1BH 1.26 1.31 0.05 54 119 13 49 2.77 MAN 1BH -1.22 -1.13 0.09 54 120 13 49 0.48 SAI 1BH 1.18 1.26 0.08 55 121 25 50 0.46 SAI 1BH 1.42 1.49 0.07 55 122 25 50 SAD 1BH -1.26 56 123 14 51 SAD 1BH -1.35 56 124 14 51 2.41 SAN 1BH -0.50 -0.22 0.28 56 125 14 51 0.57 SAI 1BH 1.20 1.30 0.10 57 126 10 53 3.39 SAN 1BH -1.34 -1.17 0.17 57 127 10 53 0.43 SAI 1BH 1.24 1.28 0.04 58 128 29 54 0.33 SAI 1BH 1.27 1.35 0.08 58 129 29 54 MAD 1BH -1.32 59 130 10 56 4.11 MAN 1BH -1.33 -0.91 0.42 59 131 10 56 0.26 SAI 1BH 1.38 1.43 0.05 60 132 21 58 2.00 MAN 1BH -1.26 -1.11 0.15 60 133 21 58 0.47 SAI 1BH 1.24 1.35 0.11 61 134 16 60 1.76 SAN 1BH -3.62 -3.52 0.10 61 135 16 60 2.83 MAN 1BH -1.13 -1.02 0.11 61 136 16 60 0.72 SAI 1BH 1.15 1.22 0.07 62 137 4 61 SAD 1BH -1.26 62 138 4 61 0.42 SAI 1BH 1.36 1.47 0.11 63 139 17 61 2.11 MAN 1BH -1.25 -1.04 0.21 63 140 17 61 0.77 SAI 1BH 1.13 1.21 0.08 64 141 12 64 1.99 MAN 1BH -1.20 -1.05 0.15 64 142 12 64 1.06 SAI 1BH 1.29 1.58 0.29 65 143 7 66 2.50 SAN 1BH -3.70 -3.53 0.17 Page 105 of 115

TABLE 15 STEAM GENERATOR 21 - NEW F*2 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 65 144 7 66 SAD 1BH -1.27 65 145 7 66 0.38 SAI 1BH 1.32 1.45 0.13 66 146 12 69 1.41 MAN 1BH -3.75 -3.68 0.07 66 147 12 69 MAD 1BH -1.33 66 148 12 69 0.54 SAI 1BH 1.37 1.45 0.08 67 149 5 73 1.21 SAN 1BH -3.61 -3.53 0.08 67 150 5 73 1.77 MAN 1BH -1.26 -1.05 0.21 67 151 5 73 0.29 SAI 1BH 1.18 1.22 0.04 68 152 28 74 SAD 1BH -0.94 68 153 28 74 0.40 SAI 1BH 1.26 1.33 0.07 69 154 19 79 0.96 SAN 1BH -3.67 -3.59 0.08 69 155 19 79 MAD 1BH -1.52 69 156 19 79 0.59 SAI 1BH 1.44 1.51 0.07 70 157 28 80 2.13 SAN 1BH -1.37 -1.15 0.22 70 158 28 80 0.63 SAI 1BH 1.00 1.19 0.19 71 159 11 84 MAD 1BH -1.45 71 160 11 84 0.41 SAI 1BH 1.31 1.35 0.04 Page 106 of 115

TABLE 16 STEAM GENERATOR 22 - NEW F*2 TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1 1 20 20 1.22 MAI 1BH 1.35 1.49 0.14 1 2 20 20 MAD 1BH -1.40 2 3 25 22 0.64 SAI 1BH 1.22 1.33 0.11 2 4 25 22 MAD 1BH -1.30 3 5 18 26 0.79 SAI 1BH 1.25 1.39 0.14 3 6 18 26 SAD 1BH -1.27 4 7 22 26 0.87 SAI 1BH -0.08 0.02 0.10 4 8 22 26 SAD 1BH -1.56 5 9 37 41 0.57 MAI 1BH 0.07 0.43 0.36 5 10 37 41 0.80 SAN 1BH -3.75 -3.69 0.06 5 11 37 41 MAD 1BH -1.45 6 12 22 43 0.81 SAI 1BH 1.24 1.34 0.10 6 13 22 43 MAD 1BH -1.44 7 14 18 49 0.40 SAI 1BH 1.23 1.32 0.09 7 15 18 49 2.91 MAN 1BH -1.21 -1.06 0.15 8 16 23 50 0.91 SAI 1BH 1.19 1.34 0.15 8 17 23 50 MAD 1BH -0.97 9 18 18 51 0.34 SAI 1BH 1.31 1.46 0.15 9 19 18 51 MAD 1BH -1.37 10 20 7 52 0.69 SAI 1BH 1.14 1.22 0.08 10 21 7 52 SAD 1BH -1.03 11 22 13 53 0.48 SAI 1BH 1.34 1.41 0.07 11 23 13 53 4.61 MAN 1BH -1.29 -0.84 0.45 12 24 13 55 0.62 SAI 1BH 1.02 1.10 0.08 12 25 13 55 10.56 MAN 1BH -1.34 -0.68 0.66 13 26 22 61 1.13 MAI 1BH 1.12 1.33 0.21 13 27 22 61 1.43 MAN 1BH -1.41 -1.27 0.14 14 28 24 65 0.66 SAI 1BH 1.24 1.28 0.04 14 29 24 65 1.96 MAN 1BH -1.60 -1.39 0.21 15 30 37 65 0.39 SAI 1BH 1.20 1.28 0.08 15 31 37 65 2.88 MAN 1BH -3.85 -3.53 0.32 15 32 37 65 SAD 1BH -1.28 16 33 18 78 0.65 MAI 1BH 1.66 1.74 0.08 16 34 18 78 SAD 1BH -1.38 17 35 15 79 0.51 SAI 1BH 1.32 1.40 0.08 17 36 15 79 4.68 MAN 1BH -3.73 -3.58 0.15 17 37 15 79 MAD 1BH -1.29 18 38 13 80 0.56 SAI 1BH 1.30 1.43 0.13 18 39 13 80 4.86 MAN 1BH -1.23 -1.05 0.18 19 40 13 37 0.54 SAI TRH -0.01 0.14 0.15 20 41 16 43 0.45 SAI TRH 0.01 0.15 0.14 21 42 20 46 0.51 SAI TRH 0.06 0.20 0.14 Page 107 of 115

TABLE 17 STEAM GENERATOR 21 - NEW EF*

TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1 1 4 18 3.79 MAN 2BH -3.41 -3.10 0.31 1 2 4 18 3.28 SAN 2BH -0.89 -0.64 0.25 1 3 4 18 0.28 SAI 2BH 1.19 1.26 0.07 2 4 27 18 0.68 SAI 2BH 1.43 1.57 0.14 2 5 27 18 0.84 SAN 2BH -5.41 -5.37 0.04 2 6 27 18 SAD 2BH -3.50 2 7 27 18 3.40 SAN 2BH -0.88 -0.73 0.15 3 8 9 21 0.29 MAN 2BH -3.01 -2.92 0.09 3 9 9 21 4.54 SAN 2BH -0.92 -0.56 0.36 3 10 9 21 0.30 SAI 2BH 1.36 1.40 0.04 4 11 4 38 0.30 MAN 2BH -3.22 -3.18 0.04 4 12 4 38 0.44 SAN 2BH -0.89 -0.85 0.04 4 13 4 38 0.76 MAI 2BH 1.20 1.28 0.08 5 14 2 42 MAD 2BH -3.12 5 15 2 42 0.73 SAN 2BH -0.86 -0.82 0.04 5 16 2 42 0.78 SAI 2BH 1.33 1.40 0.07 6 17 9 42 SAD 2BH -3.17 6 18 9 42 1.31 MAN 2BH -0.75 -0.68 0.07 6 19 9 42 0.61 SAI 2BH 1.25 1.33 0.08 7 20 12 46 MAD 2BH -2.91 7 21 12 46 0.75 MAN 2BH -2.58 -1.84 0.74 7 22 12 46 0.48 SAI 2BH 1.13 1.28 0.15 8 23 13 47 5.39 MAN 2BH -3.30 -2.84 0.46 8 24 13 47 1.20 SAN 2BH -0.84 -0.55 0.29 8 25 13 47 0.35 SAI 2BH 1.13 1.38 0.25 9 26 10 48 0.98 MAN 2BH -3.13 -3.04 0.09 9 27 10 48 0.39 SAI 2BH 1.27 1.32 0.05 10 28 11 56 MAD 2BH -3.17 10 29 11 56 1.24 SAN 2BH -0.74 -0.65 0.09 10 30 11 56 0.43 SAI 2BH 1.23 1.31 0.08 11 31 17 64 0.26 SAN 2BH -3.27 -3.21 0.06 11 32 17 64 1.34 SAN 2BH -0.91 -0.80 0.11 11 33 17 64 0.36 SAI 2BH 1.32 1.42 0.10 12 34 12 65 2.29 MAN 2BH -5.73 -5.59 0.14 12 35 12 65 0.27 MAN 2BH -3.34 -3.28 0.06 12 36 12 65 1.69 MAN 2BH -0.97 -0.69 0.28 12 37 12 65 0.79 SAI 2BH 1.34 1.48 0.14 13 38 3 71 0.82 MAN 2BH -3.39 -3.24 0.15 13 39 3 71 2.48 MAN 2BH -0.97 -0.88 0.09 13 40 3 71 0.30 SAI 2BH 1.49 1.54 0.05 14 41 11 71 2.27 MAN 2BH -3.37 -3.25 0.12 14 42 11 71 1.60 SAN 2BH -0.85 -0.73 0.12 14 43 11 71 0.61 SAI 2BH 1.15 1.37 0.22 15 44 10 73 SAD 2BH -3.37 15 45 10 73 1.90 SAN 2BH -0.88 -0.76 0.12 15 46 10 73 0.53 SAI 2BH 1.22 1.34 0.12 Page 108 of 115

TABLE 18 STEAM GENERATOR 22 - NEW EF*

TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1 1 14 40 0.42 SAI 2BH 1.19 1.34 0.15 1 2 14 40 SAD 2BH -3.17 1 3 14 40 0.23 SAN 2BH -1.18 -1.03 0.15 2 4 17 53 0.51 SAI 2BH 1.47 1.56 0.09 2 5 17 53 MAD 2BH -3.17 2 6 17 53 1.35 MAN 2BH -2.05 -1.71 0.34 3 7 19 74 0.27 SAI 2BH 1.19 1.23 0.04 3 8 19 74 SAD 2BH -2.76 3 9 19 74 0.29 SAN 2BH -2.13 -1.98 0.15 Page 109 of 115

TABLE 19 STEAM GENERATOR 21 - NEW PLUGS TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1 1 3 17 1.01 SAN EBH -16.08 -16.01 0.07 1 2 3 17 SAD EBH -13.35 1 3 3 17 0.56 SAI EBH 1.97 2.08 0.11 2 4 9 18 SAD EBH -13.43 2 5 9 18 0.74 MAN EBH -0.38 -0.29 0.09 2 6 9 18 0.88 SAI EBH 1.81 1.92 0.11 3 7 7 28 MAD 1BH -1.17 3 8 7 28 3.30 MAN 1BH -0.70 -0.15 0.55 3 9 7 28 0.17 SAI 1BH 16.85 17.04 0.19 4 10 11 28 3.74 SAN 2BH -4.19 -3.80 0.39 4 11 11 28 SAD 2BH -2.77 4 12 11 28 0.95 SAN 2BH -0.83 -0.76 0.07 4 13 11 28 0.16 SAI 2BH 14.77 15.20 0.43 5 14 13 29 0.86 MAN EBH -13.60 -13.54 0.06 5 15 13 29 3.83 MAN EBH -9.35 -8.92 0.43 5 16 13 29 0.52 MAI EBH -0.06 0.03 0.09 6 17 15 29 MAD 1BH -0.92 6 18 15 29 0.08 SAI 1BH 16.51 16.85 0.34 7 19 21 30 0.11 SAI 2BH 15.43 15.71 0.28 7 20 21 30 MAD 2BH -3.25 7 21 21 30 0.80 SAN 2BH -0.80 -0.72 0.08 7 22 21 30 1.24 SAI 2BH 1.28 1.52 0.24 8 23 12 31 0.10 SAI TRH 17.33 18.13 0.80 9 24 22 31 SAD 1BH -1.27 9 25 22 31 0.13 SAI 1BH 16.69 16.95 0.26 10 26 18 41 SAD EBH -13.44 10 27 18 41 0.24 SAI EBH 3.67 4.86 1.19 11 28 15 46 SAD 1BH -0.93 11 29 15 46 0.21 SAI 1BH 16.45 17.17 0.72 12 30 18 50 MAD 2BH -3.21 12 31 18 50 0.85 SAN 2BH -0.85 -0.70 0.15 12 32 18 50 0.10 SAI 2BH 15.34 15.59 0.25 13 33 27 59 0.88 MAI EBH -0.03 0.10 0.13 13 34 27 59 3.41 MAN EBH -16.20 -15.96 0.24 13 35 27 59 SAD EBH -13.59 13 36 27 59 0.11 SAN EBH -13.37 -10.33 3.04 14 37 36 67 0.13 SAI TRH 17.79 18.08 0.29 15 38 17 79 MAD 1BH -1.42 15 39 17 79 4.24 MAN 1BH -0.73 -0.08 0.65 15 40 17 79 0.17 SAI 1BH 16.70 17.07 0.37 16 41 14 17 0.23 SAN 2BH -3.08 -3.01 0.07 16 42 14 17 1.63 SAN 2BH -0.89 -0.78 0.11 16 43 14 17 0.96 SAI 2BH 1.36 1.47 0.11 17 44 27 20 1.42 SAI 2BH 1.19 1.40 0.21 17 45 27 20 3.20 MAN 2BH -5.57 -5.43 0.14 17 46 27 20 0.35 MAN 2BH -3.12 -2.97 0.15 17 47 27 20 3.22 MAN 2BH -1.00 -0.76 0.24 Page 110 of 115

TABLE 19 STEAM GENERATOR 21 - NEW PLUGS TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 18 48 4 31 7.07 MAN 2BH -3.26 -2.83 0.43 18 49 4 31 0.17 SCN 2BH -1.02 -0.94 0.08 18 50 4 31 1.73 SAN 2BH -0.77 -0.70 0.07 18 51 4 31 0.34 MAI 2BH 1.22 1.34 0.12 Page 111 of 115

TABLE 20 STEAM GENERATOR 22 - NEW PLUGS TUBE # IND # ROW COL VOLTS PCT LOCATION ELEV-FROM ELEV-TO LENGTH 1 1 12 31 0.14 SAI TRH 18.63 18.73 0.10 1 2 12 31 0.60 SAI TRH 0.08 0.16 0.08 2 3 43 56 1.79 52 02C -0.14 2 4 43 56 2.07 26 01C -0.11 3 5 2 64 0.11 SAI 1BH 16.91 17.30 0.39 3 6 2 64 1.10 SAN 1BH -3.84 -3.74 0.10 3 7 2 64 SAD 1BH -1.26 4 8 17 74 0.15 SAI 1BH 17.09 18.10 1.01 4 9 17 74 0.17 SAI 1BH 17.04 17.19 0.15 4 10 17 74 8.31 MAN 1BH -0.80 -0.32 0.48 5 11 22 76 0.12 SAI 1BH 17.04 17.29 0.25 5 12 22 76 0.06 SAI 1BH 16.64 16.96 0.32 5 13 22 76 2.55 MAN 1BH -1.42 -1.27 0.15 5 14 22 76 5.34 SAN 1BH -0.73 -0.01 0.72 6 15 1 52 5.01 MAN TRH -2.70 -2.50 0.20 6 16 1 52 0.57 MAI TRH 0.13 0.24 0.11 7 17 11 53 0.62 SAI TRH -0.01 0.08 0.09 8 18 1 57 0.62 SAI TRH 0.14 0.18 0.04 Page 112 of 115

5. Number of tubes plugged or repaired during the inspection outage for each active degradation mechanism, Table 21 provides the number of tubes plugged and repaired during 2R25.

TABLE 21 REPAIRED PLUGGED AR1 AR2 ARE MECHANISM SG 21 SG 22 SG 21 SG 22 SG 21 SG 22 SG 21 SG 22 AVB Wear 0 0 0 0 0 0 0 0 Cold Leg Thinning 0 1 0 0 0 0 0 0 ODSCC 11 4 0 0 0 0 0 0 PWSCC 7 3 101 114 71 21 15 3

6. Total number and percentage of tubes plugged or repaired to date, Table 22 provides the total number and percentage of tubes plugged and repaired to date.

TABLE 22 PLUG F*0 F*1 F*2 EF*

S/G SG 21 SG 22 SG 21 SG 22 SG 21 SG 22 SG 21 SG 22 SG 21 SG 22 TOTAL 279 274 193 151 1355 869 253 134 38 8 PERCENT 8.23% 8.09% 5.70% 4.46% 39.99% 25.65% 7.47% 3.96% 1.12% 0.24%

7. The results of condition monitoring, including the results of tube pulls and in-situ testing, Condition monitoring and operational assessment of steam generator tubing at PINGP Unit 2 was performed without a need for tube pulls or in-situ testing. The observed severity of degradation at the end of Cycle 24 was evaluated to determine if structural and leakage integrity requirements were maintained. The expected severity of tubing degradation at the end of Cycle 25 was projected to determine if required structural and leakage integrity margins will be maintained during the next cycle of operation. The scope of this evaluation included all forms of observed degradation.

The observed degradation at the EOC 24 outage was evaluated in a manner consistent with NEI 97-06 and EPRI guidance. Observed degradation did not present serious challenges to the deterministic (3P or 1.4 SLB) structural margin requirement at the end of the last cycle of operation or challenge required leakage integrity limits under postulated accident conditions. A conservative approach to operational assessment leads to a similar expectation for the next cycle of operation.

Projected leakage for the F*or EF* criteria is not an issue for upcoming Cycle 25 (at 0.85 gpm - 21 Steam Generator).

Page 113 of 115

8. The effective plugging percentage for all plugging and tube repairs in each SG, There have been no repairs performed on these SGs that affect the heat transfer area; therefore the effective plugging percentage is equivalent to that reported in Table 22.
9. Repair method utilized and the number of tubes repaired by each repair method, and During 2R25 the Technical Specification (T.S.5.5.8.c.2 (b)) approved repair method of hardroll expanding non-sleeved portions of tubes in the (hot leg) tubesheet in order to apply the F* and EF* criteria was applied. Table 23 summarizes the number of tubes repaired at each elevation during 2R25.

TABLE 23 ELEVATION SG 21 SG 22 st 1 Repair Location 101 114 2nd Repair Location 71 21 Elevated Repair Location 15 3

10. The results of inspections performed under Specification 5.5.8.d.3 for all tubes that have flaws below the F* or EF* distance, and were not plugged. The report shall include: a) identification of F* and EF* tubes, and b) location and extent of degradation.

The inspection results of tubes returned to service using the F* and EF* ARCs were provided in Tables 5 through 18 of item 4 above. Table 24 summarizes the current cumulative number of tubes with the F* and EF* ARC applied and returned to service.

TABLE 24 ELEVATION SG 21 SG 22 F*0 193 151 F*1 1355 869 F*2 253 134 EF* 38 8 Page 114 of 115

LEGEND OF FIELDS AND CODES FIELD EXPLANATION TUBE # Distinct ROW/COL combination within each Table IND # Distinct ROW/COL/LOCATION combination within each Table ROW Row number of tube location COL Column number of tube location VOLTS Measured Voltage PCT Measured percent or three digit code - see below LOCATION Affected landmark - see below ELEV-FROM Measurement in inches from the centerline of the landmark to the center of the bobbin coil indication or the lower edge of the rotating coil indication ELEV-TO Measurement in inches from the centerline of the landmark to the upper edge of the rotating coil indication LENGTH Calculated Length (ELEV-TO - ELEV-FROM)

FIELD CODE EXPLANATION PERCENT DNT Dent DSI Distorted Support signal with Indication INR Indication Not Reportable IRR Inadvertent ReRoll MAD Multiple Axial indications not Detectable MAI Multiple Axial Indications MAN Multiple Axial indications No change MBM Manufacturing Burnish Mark MCD Multiple Circumferential indications not Detectable MVI Multiple Volumetric Indications NQI Non-Quantifiable Indication PLP Possible Loose Part PSI Possible Support Indication SAD Single Axial indication not Detectable SAI Single Axial Indication SAN Single Axial indications No change SCD Single Circumferential indication not Detectable SCN Single Circumferential indication No change SVI Single Volumetric Indication SVN Single Volumetric indication No change 0-100 As measured percent through wall LOCATION TEH Tube end hot (primary face)

TRH original Tube Roll Hot leg 1BH 1st additional reroll Bottom roll transition Hot leg 2BH 2nd additional reroll Bottom roll transition Hot leg EBH Elevated reroll Bottom roll transition Hot leg TSH Tube sheet hot (secondary face) 0?H  ? = First through Seventh tube support plate on hot leg side NV?  ? = First through Fourth anti-vibration bar 0?C  ? = First through Seventh tube support plate on cold leg side TSC Tube sheet cold (secondary face)

TEC Tube end cold (primary face)

Page 115 of 115