L-MT-14-002, Deviation from Bwrvi P-181-A Solution Annealing/Weld Inspection Requirement

From kanterella
Jump to navigation Jump to search
Deviation from Bwrvi P-181-A Solution Annealing/Weld Inspection Requirement
ML14021A082
Person / Time
Site: Monticello Xcel Energy icon.png
Issue date: 01/21/2014
From: Fili K
Northern States Power Co, Xcel Energy
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
L-MT-14-002
Download: ML14021A082 (3)


Text

Xcel Energy@

January 21, 2014 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 Monticello Nuclear Generating Plant Docket No. 50-263 Renewed Facility Operating License No. DPR-22 Monticello Nuclear Generating Plant 2807 W County Road 75 Monticello, MN 55362 L -MT 002 Deviation from BWRVI P-181-A Solution Annealing/Weld Inspection Requirement

References:

1) Paul Young (NSPM) to Andrew McGehee, BWRVIP Program Manager-Electric Power Research Institute, "Monticello Nuclear Plant (MNGP)

Technical Justification for Deviation from BWRVIP-181-A," dated December 16, 2013.

2) BWR Vessel and Internals Project, Steam Dryer Repair Design Criteria, EPRI Report 1020997 (BWRVIP-181-A), dated July 2010.
3) BWR Vessel and Internals Project, Program Implementation Guide, EPRI Report 1024452 (BWRVIP-94NP, Revision 2), dated September 2011.
4) BWRVIP Communication 2012-155, "BWRVIP-181-A Requirements for Solution Annealing of Steam Dryer Welds," dated October 3, 2012.

Northern States Power Company, a Minnesota corporation (NSPM), doing business as Xcel Energy, submitted a technical justification for a deviation from Boiling Water Reactor Vessel Internals Project (BWRVIP) guidance to the BWRVIP for the Monticello Nuclear Generating Plant (MNGP) on December 16, 2013 (Reference 1 ). The deviation disposition is in regard to solution annealing or inspection of welds as outlined in BWRVIP-181-A, "Steam Dryer Repair Design Criteria," (Reference 2). In accordance with BWRVIP-94NP, "BWR Vessel Internals Project Program Implementation Guide,"

(Reference 3), NSPM is notifying the U.S. Nuclear Regulatory Commission (NRC) of the deviation from the BWRVIP guidance.

Document Control Desk L-MT-14-002 Page 2 of 3 The deviation is from a "needed" element of the BWRVIP program guidance for replacement steam dryers. BWRVIP-181-A provides two options for replacement steam dryer (RSD) welds: solution anneal welds wherever practical or subject the welds that are not solution annealed to augmented inspections at the next refueling outage.

Solution annealing of steam dryer welds is performed to reduce the likelihood of intergranular stress corrosion cracking (IGSCC). While solution annealing is generally a good practice, it has the potential to cause distortion of the dryer, which could induce additional stresses and affect steam dryer functionality. Additionally, the situation exists where welds that would not be solution annealed may also not be accessible for inspection. This situation was communicated to all BWRVIP members in BWRVIP Communication 2012-155 (Reference 4). Reference 4 also noted that other requirements of the Reference 2 guidelines (e.g., use of IGSCC-resistant materials, proper welding procedures,, minimization of cold work and polishing of all welds) also provide effective protection against IGSCC.

The MNGP RSD was installed in 2011. The fabrication welds were not solution annealed and not all welds were inspected during the 2013 refueling outage. NSPM deviates from the guidance outlined in Reference 2 for solution annealing or inspection of the non-solution annealed welds. In lieu of the Reference 2 requirement, NSPM implemented fabrication requirements for the RSD that remained consistent with the principles that are associated with minimizing the effects of IGSCC and fatigue cracking from Reference 2 for fabrication of a new steam dryer. In addition, NSPM has completed targeted inspections of representative weld locations that revealed no indications. Future inspections are planned. The material selection, fabrication requirements, completed inspections, and planned inspections provide justification for the deviation.

This letter is being submitted in accordance with Section 3.5 of Reference 3 for information only. NSPM is not requesting any action from the NRC Staff.

Please contact Lynne Gunderson at (612) 396-0173 if there are any questions regarding this l~tter.