L-08-056, Reactor Protection System High Flux Trip Setpoint Calculation

From kanterella
(Redirected from L-08-056)
Jump to navigation Jump to search

Reactor Protection System High Flux Trip Setpoint Calculation
ML080510247
Person / Time
Site: Davis Besse 
(NPF-003)
Issue date: 02/14/2008
From: Bezilla M
FirstEnergy Nuclear Operating Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
L-08-056, TAC MD5240 C-ICE-058.01-008
Download: ML080510247 (83)


Text

-FENOC

"-*A%

5501 North State Route 2 FirstEnergy Nuclear Operating Company Oak Harbor, Ohio 43449 Mark B. Bezilla 419-321-7676 Vice President - Nuclear Fax: 419-321-7582 February 14, 2008 L-08-056 10 CFR 50.90 ATTN: Document Control Desk United States Nuclear Regulatory Commission Washington, D. C. 20555-0001

SUBJECT:

Davis-Besse Nuclear Power Station, Unit 1 Docket No. 50-346, License No. NPF-3 Reactor Protection System High Flux Trip Setpoint Calculation (TAC No. MD5240)

By letter dated April 12, 2007, the FirstEnergy Nuclear Operating Company (FENOC) submitted an amendment request for Davis-Besse Nuclear Power Station Unit No. 1 (DBNPS) for Measurement Uncertainty Recapture Power Uprate. On July 25, 2007, the Nuclear Regulatory Commission (NRC) staff submitted a request for additional information (RAI) concerning the application. By letter dated September 18, 2007, FENOC provided responses to the RAI, which included a commitment to make the Reactor Protection System High Flux Trip setpoint calculation available for NRC staff review by November 1, 2007. On November 8, 2007, FENOC informed the NRC that FENOC would not be able to produce the calculation until January 2008.

The Reactor Protection System High Flux Trip setpoint calculation has been revised and is provided in the Enclosure. Attachments 5-8 of the calculation are not included in the Enclosure. These Attachments contain spreadsheet formulas that were used for design verification of the information contained in Attachments 1-3. Additionally, the Supporting Documents referenced in the Table of Contents are primarily administrative documents used for review and approval of the setpoint calculations. The Supporting Documents are not included in the Enclosure.

Specific sections of interest include Section 4.5, "As-Left Tolerances (ALT)," Section 4.7, "Limiting Trip Setpoint Calculations," Section 4.8, "Nominal Trip Setpoint Calculations," and Section 4.9, "As-Found Tolerances." As discussed in Section 1.2.2, the calculation contains other setpoints in addition to the High Flux Trip Setpoint. These other setpoints are not relevant to the Measurement Uncertainty Recapture Power Uprate but are included in this correspondence as part of the calculation.

Davis-Besse Nuclear Power Station L-08-056 Page 2 of 2 There are no regulatory commitments contained in this letter. If there are any questions or if additional information is required, please contact Mr. Thomas A. Lentz, Manager -

Fleet Licensing, at (330) 761-6071.

I declare under penalty of perjury that the foregoing is true and correct. Executed on Sincerely, cc:

NRC Region III Administrator NRC Resident Inspector NRR Project Manager Utility Radiological Safety Board Executive Director, Ohio Emergency Management Agency, State of Ohio (NRC Liaison)

/1

Enclosure L-08-056 RPS [Reactor Protection System] Reactor Power Related Field Trip Setpoints

FimdeaePage i

_Rrst~~n CA L CU LATIO N NOP-CC-3002-01 Rev. 03 CALCULATION NO.

INITIATING DOCUMENT

[ ]VENDOR CALC

SUMMARY

C-ICE-058.01-008.

600387414 VENDOR CALCULATION NO. N/A El BV1 EJBV2 I

0DB I

UPY Title/

Subject:

RPS Reactor Power Related Field Trip Setpoints Category 0

Active D Historical F] Study Classification 0 Tier 1 Calculation Z Safety-Related/Augmented Quality

[I Nonsafety-Related Open Assumptions?

C Yes Z No If Yes, Enter Tracking Number N/A System Number 058-01 DB-RPS1 NI1604, DB-RPS2NI1604, DB-RPS3NI1704, DB-RPS4NI 1704, DB-RPS1Ni1607, DB-RPS2NI1607, DB-RPS3NI1707, DB-RPS4NI1707, DB-RPS1NI1701, DB-RPS2NI1701, DB-RPS3NI1801, DB-RPS4NI1801, DB-NSHNI6A-1, DB-NSHNI6A-2, DB-NSHNI5A-1, DB-NSHNI5A-2, DB-NSHNI8A-1, DB-NSHNI8A-2, DB-NSHNI7A-1, DB-NSHNI7A-2, DB-RPS1RC1304, DB-RPS2RC1304, DB-RPS3RC1404, DB-RPS4RC1404, DB-QSNI6-01, DB-QSNI6-02, DB-QSNI6-03, DB-QSNI5-01, DB-QSNI5-02, DB-QSNI5-03, DB-QSNI8-01, DB-QSNI8-02, DB-QSNI8-03, DB-QSNI7-01, DB-QSNI7-02, DB-QSNI7-03, Functional Location DB-FYRCIB1, DB-FYRCIB2, DB-FYRC1B3, DB-FYRC1B4, DB-FYRC1A1, DB-FYRC1A2, DB-FYRC1A3, DB-FYRClA4, DB-RPS1 RC1407, DB-RPS2RC 1407, DB-RPS3RC1507, DB-RPS4RC1507, DB-RPS1 RC1404, DB-RPS2RC1404, DB-RPS3RC1504, DB-RPS4RC1504, DB-RPS1NI1704, DB-RPS2NI1704, DB-RPS3NI1804, DB-RPS4NI1804, DB-,RPS NI1l707, DB-RPS2NI1707, DB-RPS3NI1807, DB-RPS4NI1807, DB-FYRCl-1, DB-FYRC1-2, DB-FYRCl-3, DB-FYRCl-4, DB-QSRC1-1, DB-QSRCl-2, DB-QSRCl-3, DB-QSRCl-4 Commitments:

A21935 (Perry & Davis-Besse Only)

Calculation Type: N/A Referenced In Atlas?

1 Yes 0 No (Perry Only)

Referenced In USAR Validation Database El Yes E] No Computer Program(s)

Program Name Version / Revision Category Status Description MS Office 2003 C

Active Word Processor, Spreadsheets Revision Record Rev.

Affected Pages Originator/Date Reviewer/Design Verifier/Date Approver/Date 1

1,2,4,5,8 & 9 Gabriel Barteck 10/16/01 j R. A. Florian 12/19/01 G. N. Leblanc 1/2/02 Description of Change: Issued to support power uprate for the Caldon Leading Edge Flowmeter (LEFM) allowed by LAR 00-0006.

Describe where the calculation will be evaluated for 10CFR50.59 applicability.

Rev.

Affected Pages Originator/Date Reviewer/Design Verifier/Date Approver/Date 2

1 & 8 1 Gabriel Barteck 3/19/02 R. A. Florian 3/19/02 4

G. N. Leblanc 3/19/02 Description of Change: Issued to correct an editorial error from Rev 1. The Margin parameter was reduced to 0.05% for Overpower only. Margin parameter remains at 0.1% for other functions.

Describe where the calculation will be evaluated for 10CFR50.59 applicability.

Rev.

Affected Pages Originator/Date Reviewer/Design Verifier/Date Approver/Date 3

All R. Mann 02/02/06 W. Brown 02/03/06 Steve Black 02/03/06 Description of Change: Evaluate impact of Cycle 15 new core design on Power/Imbalance Flow setpoints and upgrade entire calculation to current format requirements.

Page ii 5L_nýr CALCULATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.

INITIATING DOCUMENT

[]VENDOR CALC

SUMMARY

C-ICE-058.01-008 600387414 VENDOR CALCULATION NO. N/A Describe where the calculation will be evaluated for 10CFR50.59 applicability. 06-00771 Rev.

Affected Pages Originator Reviewer/Design Verifier Approver (PRAt, Pignator (Prnt Sign & Date)

(Print, Sign & Date) 4 rNumebrs. See C. E. Rupp I-Z -' I.

A,7 rev ba ee 12,7 Description of Change: Incorporate% a' second AV for the RPS High Flux T'rifor LAR 05-0007 Initiating Document: 600387414 and establishes the As-Found and As-Left values in accordance with Technical Specification Task Force (TSTF) Traveler 493 (DIN 64) and Regulatory Issue Summary 2006-17 (DIN 63)

Describe where the calculation will be evaluated for 10CFR50.59 applicability. 07-03797

Page iii CALCULATION NOP-CC-3002-O1 Rev. 03 CALCULATION NO.

C-ICE-058.01-008 INITIATING DOCUMENT 600387414

[ VENDOR CALC

SUMMARY

VENDOR CALCULATION NO. N/A TABLE OF CONTENTS SUBJECT PAGE COVERSHEET:

i OBJECTIVE OR PURPOSE iv SCOPE OF CALCULATION iv

SUMMARY

OF RESULTS/CONCLUSIONS iv LIMITATIONS OR RESTRICTION ON CALCULATION APPLICABILITY v

IMPACT ON OUTPUT DOCUMENTS v

DOCUMENT INDEX vi CALCULATION COMPUTATION (BODY OF CALCULATION):

1 ANALYSIS METHODOLOGY 1

ASSUMPTIONS 5

ACCEPTANCE CRITERIA 5

COMPUTATION 6

RESULTS 28 CONCLUSIONS 29 ATTACHMENTS:

ATTACHMENT 1: Drift Analysis for High Flux 10 Pages ATTACHMENT 2: Drift Analysis for Power / Pumps 8 Pages ATTACHMENT 3: Drift Analysis for Power / Imbalance Flow 19 Pages ATTACHMENT 4: Foxboro Technical Information Document TI-2AI-1 30 for Spec 200 Current to 5 Pages Voltage Converters ATTACHMENT 5: Spreadsheet formulas for High Flux Drift Analysis 6 Pages ATTACHMENT 6: Spreadsheet formulas for Power to Pumps Drift Analysis 6 Pages ATTACHMENT 7: Spreadsheet formulas for Power/Imbalance/Flow Drift Analysis 10 Pages ATTACHMENT 8: Spreadsheet formulas for Calculation of K factor for use in Drift Analysis 18 Pages SUPPORTING DOCUMENTS (For Records Copy Only)

DESIGN VERIFICATION RECORD 1 Pages CALCULATION REVIEW CHECKLIST 3 Pages 10CFR50.59 DOCUMENTATION 4 Pages DESIGN INTERFACE

SUMMARY

1 Pages DESIGN INTERFACE EVALUATIONS 19 Pages OTHER 0 Pages

[]

YES EXTERNAL MEDIA? (MICROFICHE, ETC.) (IF YES, PROVIDE LIST IN BODY OF CALCULATION)

NO TOTAL NUMBER OF PAGES IN CALCULATION (COVERSHEETS + BODY + ATTACHMENTS) 120 Pages

Page iv CALCULATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.

C-ICE-058.01-008 INITIATING DOCUMENT

[ VENDOR CALC

SUMMARY

600387414 VENDOR CALCULATION NO. N/A OBJECTIVE OR PURPOSE:

The purpose of this calculation is to determine the field setpoints for the Reactor Protection System (RPS) Reactor High Flux, Power/Imbalance/Flow and Power/Pumps Trip functions. This includes calculated drift for the associated equipment consistent with the time interval allowed in the Technical Specifications. The As-Found and As-Left equipment performance values are also derived. See Section 1.1 for the affected bistable equipment identification numbers.

SCOPE OF CALCULATION/REVISION:

This revision is needed to support License Amendment Request 05-0007 (Serial 3198) "License Amendment Application for Measurement Uncertainty Recapture Power Uprate" (DIN 55). Revision 04 incorporates a second Allowable Value (AV) for the RPS High Flux Trip. This second AV shall be used when the Ultrasonic Flow Meter instrumentation is inoperable or not used in the performance of the daily heat balance (DIN 55 and 56). Also, former Attachments are being replaced with more current component drift evaluations.

Consistent with Serial 3198, As-Found and As-Left values used for evaluating equipment performance will be derived.

SUMMARY

OF RESULTS/CONCLUSIONS:

The field setpoints for the Reactor Protection System (RPS) Reactor High Flux, Power/Imbalance/Flow and Power/Pumps Trip functions are as follows:

Parameter Nominal Trip Setpoint High Flux (4 Pump Operation WITH Ultrasonic Flow Meter)

High Flux (4 Pump Operation WITHOUT Ultrasonic Flow Meter)'

104.5% Power 102.9% Power 80.1% Power 54.5% Power High Flux (3 Pump Operation)

Power/Pumps Power/Imbalance/Flow First column is % of Axial Power Imbalance Second column is % of Rated Thermal Power

-30.1

-16.5 16.5 30.1 93.5 107.1 107.1 76.2 I

As-Left Tolerances (ALT):

High Flux ALT:

Power/Pumps ALT:

Power/Imbalance/Flow:

Power/Imbalance ALT Power/Flow ALT As-Found Tolerances (AFT):

+1- 0.0875% Power

= +/- 0.225% Power

= +/- 0.15% Power

= +/- 0.5125% Power

= +/- 0.3125% Power High Flux AFT As-Found Acceptance Criteria Band:

previous As-Left - current As-Found

-< 0.3125% Power (or 0.025 Vdc)

Power/Pumps AFT Power/Imbalance/Flow:

Power/Imbalance AFT Power/Flow AFT

= +/- 0.4500% Power

= +/- 0.3750% Power

= +/- 0.7375% Power

Page v Rrst~ne*CALCULATION NOP-CC-3002-01 Rev. 03

  • VENDOR CALCULATION NO. N/A LIMITATIONS OR RESTRICTIONS ON CALCULATION APPLICABILITY:

This calculation is not intended to include accident and abnormal conditions. Those are accounted for in determining the Technical Specification Allowable Values which are determined external to this calculation.

This calculation is not applicable until LAR 05-0007 (DIN 55) is approved by the NRC.

IMPACT ON OUTPUT DOCUMENTS:

A second RPS High Flux Trip Setpoint is being documented in this design basis calculation. The actual field implementation will be provided by an Engineering Change Package tracked by Notification 600387414.

As stated in License Amendment Request 05-0007 (Serial 3198) "License Amendment Application for Measurement Uncertainty Recapture Power Uprate" (DIN 55), an As-Found Acceptance Criteria Band shall be determined for the RPS High Flux string and placed in the Technical Requirements Manual (TRM). The shift ofthe instrument setpoint between calibrations will be compared to the As-Found Acceptance Criteria Band and shall be a requirement in the functional test procedures. Changes to the TRM will be followed by Commitment A21933 (DIN 74).

Page vi Rrst~neCALCULATION NOP-CC-3002-01 Rev. 03 cIE080-0 6o0u03874,14 VENDOR CALCULATION NO. N/A DOCUMENT INDEX 0) z C

S D

Document Number/Title Revision, Edition, Date o0

1.

Davis-Besse Nuclear Power Station, Unit No. 1, Amendment 310 19 0

El Technical Specifications - TABLE 2.2-1.

2.

LAR 90-0002, License Amendment Request to 1990 0

0 Increase the Reactor Protection System (RPS) and Anticipatory Reactor Trip System (ARTS)

Channel Functional Test Surveillance Interval and Channel Bypass Allowed -Out-of-Service Time.

.3.

Updated Safety Analysis Report for Davis-Rev. 25 0

El E".

Besse Nuclear Power Station, Section 7.2

4.

Updated Safety Analysis Report for Davis-Rev. 25 El 0

El Besse Nuclear Power Station, Appendix 4B, Reload Report, ANP-2514, Rev 1, 103-2514-001

5.

Framatome ANP 51-5012682-02, D-B Caldon Rev. 2

[]

El Power Uprate Project Evaluation Summary Report

6.

Regulatory Guide 1.105, Instrument Setpoints Rev. 3 11 E

for Safety Related Instrumentation

7.

System Description for Nuclear Instrumentation Rev. 3 0

E 0

/ Reactor Protection System, SD-044

8.

ISA-67.04.01-2000, Setpoints for Nuclear Jan. 2000 Z

[]

El Safety Related Instrumentation

9.

ISA-RP67.04.02-2000, Determination of Jan. 2000 0

El El Setpoints for Nuclear Safety Related Instrumentation

10.

ISA S51.1-1979, Process Instrumentation 1979 Terminology

11.

Surveillance Procedure DB-SC-04117, RPS Rev. 8 0

El 0

Channel 1 Flow Scaling Factor Determination

12.

Surveillance Procedure DB-SC-04118, RPS Rev. 8 Channel 2 Flow Scaling Factor Determination

13.

Surveillance Procedure DB-SC-041 19, RPS Rev. 8 1

Channel 3 Flow Scaling Factor Determination

14.

Surveillance Procedure DB-SC-04120, RPS Rev. 8 Channel 4 Flow Scaling Factor Determination

15.

B & W 32-1172392-03, TED-1 Reactor Rev. 3 0 L El Protection System String Error Calculations

16.

Framatome Calculation Summary Sheet 32-9/25/96

[]

z El 1257719-02, Davis-Besse Unit 1 RPS Setpoint Allowable Values Calculation (EXT-96-02166)

17.

DWG. M-7201 / SAP - Functional Location Rev. 50 / N/A 1 z 0

Page vii

~CALCULATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.

INITIATING DOCUMENT

[]VENDOR CALC

SUMMARY

C-ICE-058.01-008 600387414 VENDOR CALCULATION NO. N/A DOCUMENT INDEX (Cont.)

18.

AREVA 86-5057366-003, DB Cycle 15 Task 14 Rev. 3

[]

I]

I Input to Fuels

19.

LAR 00-0006, License Amendment Request to 2000 0

El 1:

Increase Allowable Power

20.

Walpole, R.E. & Myers, R. H, Probability and Dated 1998

[]

I]

I Statistics for Engineers and Scientists, New York, NY: Macmillan Publishing Company

21.

Beggs, W.J., "Statistics for Nuclear Engineers Dated February, 1981 ED El El and Scientists, Part 1: Basic Statistical Inference," DOE Research and Development Report No. WAPD-TM-1292

22.

Metrology Specification Sheet: Fluke 8840A/AF Rev. 0 (dated 10/28/94)

El Z

El (applicable to the 8840AF also per T. Baker 1/31/06)

23.

C-ICE-058.01-011, Calculation of Acceptable Rev. 0 z

0 El As-Found Values for Safety Related Trip Setpoints

24.

M-324AQ-331, Composite Instruction Book for Rev 3 LI

[

LI Post Accident Panel

25.

M-536-101, Bailey Meter Company., Nuclear Rev. 9 El 0 0 Instrumentation and Reactor Protection System Technical Data

26.

"Guidelines for Instrumentation Calibration Rev. 1 Dated October 1998

[

L 1

Extension/Reduction Programs", Electrical Power Research Institute, EPRI TR-103335-R1, Final Report

27.

Instrument String Data Package, 58A - NSH-I 0 I NI05A

28.

Instrument String Data Package, 58A - NSH-DLI[

N1O6A

29.

Instrument String Data Package, 58A - NSH-LILI[

NI07A

30.

Instrument String Data Package, 58A - NSH-LI El ED NIO8A

31.

AREVA 32-5057192-00, DB Cycle 15 Task 14 Rev. 0

]

11 El Reload Evaluation

32.

Instrument String Data Package, 58A - QS-1:1 NI05

33.

Instrument String Data Package, 58A - QS-El El 0

N106

34.

Instrument String Data Package, 58A - QS-LI El Z

N107

35.

Instrument String Data Package, 58A - QS-LI L I N108

36.

Instrument String Data Package, 58A - QS-OLI[

RC01-1

37.

Instrument String Data Package, 58A - QS-El J

[0 RC01-2

38.

Instrument String Data Package, 58A - QS-11 El

[

RC01-3

~Page viii RmtF~netCALCULATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.

INITIATING DOCUMENT

[ ]VENDOR CALC

SUMMARY

C-ICE-058.01-008 600387414 VNO ACLTO O

/

VENDOR CALCULATION NO. N/A DOCUMENT INDEX (Cont.)

39.

Instrument String Data Package, 58A - QS-El El 0

RC01-4

40.

Surveillance Test Procedure, DB-MI-03057, El El 0

RPS Channel 1 Calibration of High Flux, Power/Imbalance/Flow, Power/Pumps Trip Functions

41.

Surveillance Test Procedure, DB-MI-03058,

[]

0

[

RPS Channel 2 Calibration of High Flux, Power/Imbalance/Flow, Power/Pumps Trip Functions

42.

Surveillance Test Procedure, DB-MI-03059, El El Z

RPS Channel 3 Calibration of High Flux, Power/Imbalance/Flow, Power/Pumps Trip I Functions 43 Surveillance Test Procedure, DB-MI-3060, El El 0

RPS Channel 4 Calibration of High Flux, Power/Imbalance/Flow, Power/Pumps Trip Functions

44.

System Work Package DB-MI-03057 QTR LiLJ[

45.

System Work Package DB-MI-03058 QTR

[]

El z

46.

System Work Package DB-MI-03059 QTR EJ El Z

47.

System Work Package DB-MI-03060 QTR El El

[

48.

NOP-CC-3002, Nuclear Operating Rev. 4 z

E 13 Administrative Procedure, Calculation

49.

Core Operating Limits Report (COLR)

E]

50.

C-NRE-062.02-164, Cycle 14 RPS Imbalance Rev. 0 0

[]

El Trip Comparison

51.

DB-SC-04121, RPS Channel 1 Power-Flow and 11 C1 0

Power-Imbalance Variable Setpoint Calculations

52.

DB-SC-04122, RPS Channel 2 Power-Flow and El El 0

Power-Imbalance Variable Setpoint Calculations

53.

DB-SC-04123, RPS Channel 3 Power-Flow and C]

El 0

Power-Imbalance Variable Setpoint Calculations

54.

DB-SC-04124, RPS Channel 4 Power-Flow and 0

0 0

Power-Imbalance Variable Setpoint Calculations

55.

Serial 3198 (LAR 05-0007) Measurement 4/12/07 EJ OD Uncertainty Recapture Power Uprate

56.

AREVA 51-9004090-005 Davis-Besse MUR Rev. 005 0

0

[]

Power Uprate Summary Report. (Notification 600376458)

57.

Vendor Drawing M-536-00039 Rev. 13

58.

Vendor Drawing M-536-00040 Rev. 4 D

El AE]

59.

Vendor Drawing M-536-00042 Rev. 4 0

0 0

60.

Vendor Drawing M-536-00043 Rev. 6 z

[]

C

Page ix 5Wrst CALCULATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.

.INITIATING DOCUMENT

[]VENDOR CALC

SUMMARY

C-ICE-058.01-008

[600387414 V N O A C L TO O

/

VENDOR CALCULATION NO. N/A

61.

Drawing J-0111 sheet 1 Rev. 1

[] O

62.

Drawing J-01 11 sheet 2 Rev. 1 0

0

63.

Regulatory Issue Summary (RIS) 2006-17, 8/24/2006 z

0 NRC Staff Position on the Requirements of 10CFR50.36, "Technical Specifications,"

Regarding Limiting Safety System Settings During Periodic Testing and Calibration of Instrument Channels

64.

Technical Specification Task Force (TSTF)

Rev. 2 0

Improved Standard Technical Specifications Change Traveler 493 (TSTF-493), Rev 2, Dated April 16, 2007 in letter to NRC, Clarify Application of Setpoint Methodology for LSSS Functions

65.

Calculation C-ICE-058.01-005 Rev. 5 0

0

66.

ICDP RPSlNI1704 Rev. 6 z

67.

ICDP RPS2NI1704 Rev. 7 ED 0I L

68.

ICDP RPS3NI1804 Rev. 6 0

69.

ICDP RPS4NI1804 Rev. 7 z

0

70.

ICDP RPSlRC1410 Rev. 5.

ED 0

71.

ICDP RPS2RC1410 Rev. 6 N

0

72.

ICDP RPS3RC1510 Rev. 5 1

73.

ICDP RPS4RC1510 Rev. 6 ED 0E

74.

Commitment A21933 N/A ED 0

75.

0_

0]

[]

Page 1 ArFýLEnew CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

C-ICE-058-01-008 ANALYSIS METHODOLOGY ISA-67.04.01-2000 (DIN 8) develops a basis for establishing setpoints for nuclear safety-related instrumentation. This document was prepared by the Instrument Society of America (ISA) with a goal of providing uniformity in the field of instrumentation. ISA-RP67.04.02-2000 (DIN 9) presents guidelines and examples of methods for the implementation of ISA-67.04.01-2000. Regulatory Guide 1.105 (DIN 6) endorses the use of the 1994 version of the ISA standard as an acceptable method for determining safety-related setpoints. The 2000 version of the ISA standard is identical to the 1994 version with respect to the RG 1.105 technical review issues. While RG 1.105 is specifically applicable to safety-related setpoints, it also recognizes that the standard "is also appropriate for non-safety system instrumentation for maintaining design limits described in the Technical Specifications".

Several methods for determining the Allowable Value (AV) have been developed and are presently in use.

This calculation utilizes Method 1 from ISA-RP67.04.02-2000, Section 7.3. "Method 1" determines the AV by calculating the instrument channel uncertainties that are NOT "tested" during the Channel Functional testing and includes those uncertainties between the Analytical Limit and the AV. All other "tested" uncertainties, including drift of control room cabinet equipment, calibration uncertainties, and uncertainties observed during normal operation are included between the AV and the Limiting Trip Setpoint. Those uncertainties that are NOT "tested" include, but are not limited to, drift of non-control room cabinet equipment such as transmitters, other uncertainties of the equipment that would be tested on a 24 month cycle, and other effects that are not testable by a surveillance test such as DBE effects.

The Limiting Trip Setpoint (LTSP) will be calculated by combining the computed sum of several terms with the Technical Specification Allowable Value. These terms include the As-Left Tolerance (which includes accuracy and Calibration Uncertainty) and Drift Allowance (see Sections 4.5 and 4.4). In addition, margin will be included to establish a Nominal Trip Setpoint (Section 4.8). The sum may be computed by the use of the Square Root Sum of the Squares (SRSS) method (DIN 9), by a simple arithmetic addition of terms or by a combination of both. SRSS is an accepted method for summing independent uncertainties/inaccuracies associated with an instrument setpoint calculation. Arithmetic summation yields a larger number and is used to sum terms which are dependent on the same uncertainty source or as desired.

The As-Left Tolerance is an allowance made for acceptance of the calibration of the instrument string.

The As-Left Tolerance is controlled and declared here, and implemented by the calibration/functional test procedures (DIN 40, 41, 42, and 43).

The As-Found tolerance is an allowance made to determine if the instrument string is exhibiting expected behaviors between calibrations. The As-Found Tolerance is controlled and declared here and implemented by the calibration/functional test procedures (DIN 40, 41, 42, and 43).

Per Serial 3198 (LAR 05-0007), Measurement Uncertainty Recapture Power Uprate, the shift of the RPS High Flux instrument string setpoint shall be evaluated and documented in the surveillance test procedures. The As-Found setpoint will be subtracted from the As-Left setpoint from the previous surveillance and the result shall be less than or equal to the As-Found Acceptance Criteria Band. This comparison shall be contained and documented in the RPS Surveillance Procedures (DIN 40, 41, 42, and 43). The As-Found Acceptance Criteria Band is calculated in Section 4.9.

Drift Allowance will be calculated for 3 month string drift for compliance with the required 92 day Functional testing of the RPS Functional Units. Drift allowances are calculated in Attachments 1, 2, and 3.

Calibration Uncertainty is the inaccuracy of the calibration device and/or reference standard, which in this analysis is a digital multimeter and/or precision resistor. The devices used are declared and controlled in

Page 2 FMstne CALCULATION COMPUTATION NOP-CC-3002-Ql Rev. 03 CALCULATION NO.:

REVISION:

C-lCE-058.01-008 1 4 this calculation. Procedures and Data Packages shall maintain the device inaccuracy to be consistent with or better than the value used in this calculation.

Conservative margin is included, as any setpoint calculation is just a documented use of a selected method to arrive at a best estimate of a field setpoint. Periodic channel functional testing validates the method used. Should a surveillance result in violation of the Technical Specification Limit an evaluation is required to determine that the Safety Limit was being preserved. The evaluation will determine if the problem affects safety and if it is caused by equipment malfunction, calibration method, measurement and test equipment or by an inadequate field setpoint methodology.

The effects of all other sources of instrument inaccuracy are included in the Technical Specification Allowable Values which are determined external to this calculation. Framatome ANP / AREVA reports /

calculations ANP-2514, 51-5012682-02, 32-1172392-03, 32-1257719-02, 86-5057366-003, 32-5057192-00, and 51-9004090-005 (DINs 4, 5, 15, 16, 18, 31, and 56) contain information pertinent to the calculation of those Allowable Values.

This calculation models drift as a linear function of time. In practice this is reasonable and conservative.

Verification of individual string component performance within SAP assigned tolerances is not necessary to support this setpoint calculation provided the overall string performance is within the As-Found and As-Left Setting Tolerances declared in this calculation and implemented in the respective calibration/channel functional procedures.

1.1 Affected Instrument Strings (DIN 17, 44, 45, 46, and 47)

Below is a list of the associated SAP Functional Location numbers (DIN 17) for the trip bistables. See Tables 1, 2, and 3 in Section 4.1 for a complete list of all equipment included in this calculation.

CHANNEL HIGH FLUX

  • POWER/PUMPS
  • POWER/IMBALANCE 1

DB-NSHNI6A-1 DB-QSNI6-01 DB-QSRC1-1 DB-NSHNI6A-2 DB-QSNI6-02 DB-QSNI6-03 2

DB-NSHNI5A-1 DB-QSNI5-01 DB-QSRC1-2 DB-NSHNI5A-2 DB-QSNI5-02 DB-QSNI5-03 3

DB-NSHN18A-1 DB-QSNI8-01 DB-QSRC1-3 DB-NSHNI8A-2 DB-QSNI8-02 DB-QSNI8-03 4

DB-NSHNI7A-1 DB-QSNI7-01 DB-QSRC1-4 DB-NSHNI7A-2 DB-QSNI7-02 DB-QSNI7-03

  • - The High Flux and Power/Pumps bistables are only one bistable. The equipment number is broken into several sub numbers to identify setpoints for different operation configurations, specifically for the number of pumps running.

1.2 Functional Description/Design Basis 1.2.1 Background Discussion This calculation is developed in accordance with the Tier-1 requirements of NOP-CC-3002 (DIN 48);

therefore, information from previous revisions has been design verified.

Page 3 6MYCALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008I 4

This calculation is not intended to include accident and abnormal conditions. Those are accounted for in determining the Technical Specification Allowable Values which are determined external to this calculation. See Section 1.1 for the affected bistable equipment identification numbers and Section 4.1 for all equipment associated with this calculation.

1.2.2 Reactor Protection System (RPS) Function (DIN 3 & 7)

The purpose of the RPS is to initiate a reactor trip when a sensed parameter (or group of parameters) exceeds a setpoint value indicating the approach of an unsafe condition. In this manner, the reactor core is protected from exceeding design limits and the Reactor Coolant System (RCS) is protected from high pressure.

The RPS consists of four identical protection channels which are redundant and independent. Each channel is served by its own independent sensors which are physically isolated from the sensors of the other protective channels. Each sensor supplies an input signal to one or more signal processing strings in the RPS channel. Each signal processing string terminates in a bistable which electronically compares the processed signal with trip setpoints. All bistable trip contacts are connected in series. In the normal untripped state, the contact associated with each bistable will be closed, thereby energizing the channel terminating relay.

Contacts from eight trip bistables are normally in series with the power supply to each of the protective channel trip relays. The trip bistables included are RCS high pressure, low pressure, pressure-temperature, power/imbalance/flow, high flux, power-pumps, high temperature, and containment vessel (CV) high pressure. The first three compare RC pressure with fixed high and low pressure setpoints and a pressure setpoint which is a function of RC outlet temperature. The second three compare the output of the power range neutron flux monitor related to the protective channel with the total RC flow and core imbalance, a fixed high power setpoint, and a high power setpoint which is a function of the pump configuration. The seventh trip bistable compares RC outlet temperature with a high temperature setpoint. The eighth compares the CV pressure with a high pressure setpoint.

The trip functions of RPS which are affected by this calculation are as follows (See Section 4.1 for instrument string diagrams):

A.

High Flux The High Flux trip function, Functional Unit 2 in Technical Specification Section 3/4.3.1, is also referred to as Overpower. For the remainder of the calculation, it will be referred to as High Flux.

Each RPS channel contains a two-section power range neutron flux detector. The signals from each half are summed to produce a total power signal. This power signal is sent to the high flux, power/pump, and power/imbalance/flow bistables. When the total power signal exceeds the high flux trip setpoint of the bistable, its relay contact will open, de-energizing (tripping) the channel terminating relay. During the high flux functional test, the power range test module sends two test signals, which represent power levels in the upper and lower half of the reactor core, to two linear amps. The outputs of the linear amps are then summed in the Sum/Diff amp and its resultant, representing total core power, is sent to the High Flux bistable (DIN 57, 58).

B. Power/Pumps The High Flux / Number of Reactor Coolant Pumps On trip function, Functional Unit 8 in Technical Specification Section 3/4.3.1, is also referred to as Power/Pumps For the remainder of the calculation, it will be referred to as Power/Pumps.

Page 4 FlrstnelzCALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008 1 4 Reactor Coolant Pump (RCP) status (on-off) and information as to the loops in which pumps are operating, is monitored by pump monitors. The pump monitors provide an open or closed contact as the input to the RPS. The pump contact monitor module provides a variable signal which is a function of the number of running pumps and the loop in which they are running. This signal is used as a variable setpoint signal in the power/pumps bistable. If the total reactor power exceeds the power/pumps setpoint, as determined by the pump configuration, the bistable will cause its associated relay contact to open, de-energizing (tripping) the channel terminating relay. During functional tests, test signals are produced in the power range and contact monitor test modules. Similar to the high flux functional test, the power range test module sends two signals to two linear amps and then into one Sum/Diff amp. The contact monitor test module outputs contact logic, simulating Reactor Coolant Pump status, to the contact monitor module. The outputs from the Sum/Diff amp and the contact monitor are then compared in the Power/Pumps bistable (DIN 57 and 59).

C. Power/Imbalance/Flow The Flux / A Flux / Flow trip function, Functional Unit 4 in Technical Specification Section 3/4.3.1, is also referred to as Power/Imbalance/Flow. For the remainder of the calculation, it will be referred to as Power/imbalance/ Flow.

Each RPS channel receives two differential pressure signals (one from each reactor coolant loop) for flow.

The signals are developed by differential pressure transmitters that measure pressure drop across gentile tubes mounted in the two reactor coolant loops. The analog output of the transmitters is proportional to flow squared. The output is processed by a current to voltage (I/E) converter and is input to a square root extractor which converts the signal to one directly proportional to flow. The proportional flow signals from both RC loops are summed to produce a total RC flow signal in the buffer amplifier. Each RPS channel monitors reactor power imbalance. This is the difference between the power measured in the top half of the core and the power measured in the bottom half of the core by the two separate power range neutron flux detectors. The imbalance signal and the flow signal are combined in a Function Generator and the resultant function signal is compared with the total power signal in a bistable. The bistable will trip when the total reactor power signal exceeds the trip envelope limit in the Core Operating Limits Report (DIN 49).

When this bistable trips, its relay contact opens, de-energizing (tripping) the channel terminating relay.

During functional tests, test signals are produced in the power range test module and by two flow transmitter simulators. Similar to the high flux functional test, the power range test module sends two signals to two linear amps. The two linear amps output to a difference amp to determine power imbalance. The flow transmitter simulators, simulating flow in each hot leg, send current signals to two current-to-voltage converters, to two square root extractors, and are~then combined in a buffer amp. The resultants of the difference (power imbalance) and buffer amps (flow) are combined in the function generator. The output of the function generator is finally compared to total flux in the Power/Imbalance/Flow bistable (DIN 57, 58, 60, 61, and 62).

D. Design Requirements The RPS is classified as a "Q" quality system and this calculation is Nuclear Safety Related. The RPS is designed to maintain the capability to perform its protective function during and after an earthquake. The vessel containing the equipment will protect it from flood, lightning, and wind. The RPS cabinets are housed in the control room where they are protected against fire, explosion, and missiles. All sensors and cables are located to minimize damage caused by fire, explosion, or missiles. The redundancy of the system will satisfactorily operate under all conditions. The system cabinets provide protection against mechanical damage and spread of fires between RPS channels. All sensors, signal transmission circuits, and signal conditioning devices are designed to function in postulated deteriorated environments to which they may be subjected for the length of time required to provide the protective action (DIN 3).

Page 5 amLst~

CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008I 4

2.

ASSUMPTIONS Any assumptions, implied or otherwise, are verified each time the respective channel passes its periodic surveillance test. No assumptions are made that require additional activity to verify prior to implementation of these setpoints.

3.

ACCEPTANCE CRITERIA There are no numeric acceptance criteria associated with this calculation. The acceptance criteria are:

1.

The calculation complies with the ISA Standard and Recommended Practice (DINs 8 and 9). The trip setpoints will be derived in accordance with these documents and Acceptance Criteria #2.

The setpoint when combined with the instrument uncertainties contained in B&W/Framatome calculation 32-1172392-03 (DIN 15), include all required instrument uncertainties for the instrument string.

2.

Appropriate Limiting Trip Setpoint, Nominal Trip Setpoint, As-Found value and As-Left value are derived in compliance with the Technical Specification Task Force (TSTF) Traveler 493 (DIN 64) and the NRC Regulatory Issue Summary (RIS) 2006-17 (DIN 63).

3.

There are no unacceptable operational burdens associated with the setpoints.

Page 6 hrstF<emt, CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-I CE -058.01-008 4

4.

COMPUTATION 4.1 Loop Diagrams The loops will be broken into pieces similar to the method used in Framatome calculation 32-1172392-03 (DIN 15). The uncertainties and the testing will be discussed with these diagrams as reference.

Figure 1 - RPS Nuclear High Flux Trip String Figure 1 RPS Nuclear High Flux Trip String II II II

  • Sum/Diff High Flux RTM S

Amplifier Bistable L, -

-=J- -

Not Included in Each Functionally Calculation nChecked CalcuationIndependently Functional Check as String Not Included in Calculation Table I - Equipment List Channel Top Linear Bottom Linear Sum/Diff Amplifier High Flux Bistable Amplifier Amplifier 1

DB-RPSlNI1604 DB-RPSlNI1607 DB-RPSlNI1701 DB-NSHNI6A-1, -2 2

DB-RPS2NI1604 DB-RPS2NI1607 DB-RPS2NI1701 DB-NSHNI5A-1, -2 3

DB-RPS3NI1704 DB-RPS3NI1707 DB-RPS3NI1801 DB-NSHNI8A-1, -2 4

DB-RPS4NI1704 DB-RPS4NI1707 DB-RPS4NI1801 DB-NSHNI7A-1, -2

  • UCIC Uncompensated Ion Chamber

Page 7 PrstEneo CALCULATION COMPUTATION NoP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION.

C-lCE-058.01-008I 4

Figure 2 - RPS Power to Reactor Coolant Pumps Trip String Figure 2 RPS Power to Reactor Cooolant Pumps Trip String Table 2 - Equipment List For Linear Amplifiers and Sum/Diff Amplifier, See Table 1 Channel Contact Monitor Power to Pumps Bistable 1

DB-RPS1RC1304 DB-QSNI6-1, -2, -3 2

DB-RPS2RC1304 DB-QSNI5-1, -2, -3 3

DB-RPS3RC1404 DB-QSNI8-1, -2, -3 4

DB-RPS4RC1404 DB-QSNI7-1, -2, -3

Page 8 RS t Fney CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008 14 Figure 3 - RPS Power/imbalance Trip String Figure 3 RPS Power/Imbalance Trip String P/.F RTM B istable Ii I Functional Check Not Included in as String Calculation Table 3 - Equipment List For Linear Amplifiers and Sum/Diff Amplifier, See Table 1 Channel li/E Converter Loop 1 I/E Converter Loop 2 Square Root Square Root Extractor Extractor Loop 1 Loop 2 1

DB-FYRC1B1 DB-FYRC1A1 DB-RPS1RC1407 DB-RPS1RC1404 2

DB-FYRC1B2 DB-FYRC1A2 DB-RPS2RC1407 DB-RPS2RC1404 3

DB-FYRC1B3 DB-FYRC 1A3 DB-RPS3RC1507 DB-RPS3RC1504 4

DB-FYRC1B4 DB-FYRC1A4 DB-RPS4RC1507 DB-RPS4RC1504 Channel Difference Amplifier Buffer Amplifier Function Generator Imbalance Bistable 1

DB-RPS1NI1704 DB-FYRC1-1 DB-RPSlNI1707 DB-QSRC1-1 2

DB-RPS2NI1704 DB-FYRC1-2 DB-RPS2NI1707 DB-QSRC1-2 3

DB-RPS3NI1804 DB-FYRC1-3 DB-RPS3NI1807 DB-QSRC1-3 4

DB-RPS4NI1804 DB-FYRC1-4 DB-RPS4NI1807 DB-QSRC1-4

  • UCIC = Uncompensated Ion Chamber

Page 9 6mtEým CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008 1 4 Figure 4 - RPS Power/Flow Trip String

... l r - - -

Am n

h ioa Calculation L

I LI Not Included In Each Functionally CalcuationChecked Calcuation Independently Delta Ii

/E Sciw Pressure Converter Ex Loop I Loopi1 L,

Ii Dela

/E Squ; Pressure Con~verter Ex Loop 2 Ig Loop 2 Li Figure 4 RPS Power/Flow Trip String Not Included in Functional Check Calculation as String Equipment List, For Linear Amplifiers and Sum/Diff Amplifier, See Table 1. For all other equipment, See I

Table 3.

I UCIC = Uncompensated Ion Chamber RTM = Reactor Trip Module

Page 10 ftstF CALCULATION COMP.UTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-lCE-058.01-008 4

4.2 Design Information 4.2.1 Units

% Power = Percent Rated Reactor Thermal Power

% Span = Percent uncertainty of the component or string Note: % Span will be converted to % Power for the final calculated values.

4.2.2 Symbology ALT

= As-Left Tolerance AFT

- = As-Found Tolerance CAL

= Calibration Equipment Tolerance Drift

= Drift Allowance 4.2.3 Power - Voltage Conversion Functions The following functions are used to convert from percent power to bistable input voltage. The Bistable input voltage is a 0-10 Vdc signal corresponding to 0-125% Reactor Power.

Vdc

= (% Power/ 125 %)

  • 10 Vdc

% Power

= (Vdc / 10 Vdc)

  • 125 % Power 4.2.4 Testing The testing of the instrument strings for the 92 day Channel Functional test interval is accomplished by procedures DB-MI-03057, DB-MI-03058, DB-MI-03059, and DB-MI-03060 (DINs 40, 41, 42, and 43).

These procedures also perform the Channel Calibration of the instruments, if required by the testing interval. This calculation evaluates the uncertainties associated with the Channel Functional test (92 days) for compliance with the Technical Specifications. Any uncertainty associated with Channel Calibration that is not bounded by the Channel Functional testing is included between the Analytical Limit and the Allowable Value. This calculation establishes the uncertainties between the Allowable Value and the trip setpoints. The Data Packages associated with the 92 day test, DB-MI-03057 QTR, DB-MI-03058 QTR, DB-MI-03059 QTR, and DB-MI-03060 QTR (DINs 44, 45, 46, and 47) compliment the above procedures.

4.2.5 Equipment Location All equipment included in this calculation is located in the controlled environment of the control room cabinet area. No environmental effects will be included in this calculation since they are included, if applicable, in Framatome calculation 32-1172392-03 (DIN 15).

Page 11 CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008 4

4.3 Uncertainties 4.3.1 Component/String Accuracies The accuracies of the equipment included in this calculation are typically included between the Allowable Value and the Limiting Trip Setpoint in compliance with ISA-RP67.04.02 (DIN 9). However, they are included in Framatome calculation 32-1172392-03 (DIN 15), which calculates the uncertainties included between the Analytical Limit and the Allowable Value. Based on this, the accuracies will be included for the establishment of the As-Found and As-Left values, but will not be included as an accuracy value in establishing the Limiting Trip Setpoint. The only effects to be considered in this calculation are the drift and the As-Left values (including accuracies and calibration uncertainties) for establishment of the Limiting Trip Setpoint.

In some cases, the manufacturer has specified a "Typical" (smaller) and a "Worst Case" (larger) accuracy uncertainty. Since the accuracy values being developed in this calculation are for the establishment of As-Found And As-Left values, using either the "Typical" or "Worst Case" accuracy will either increase or reduce the calculated uncertainty. When including the As-Left value in establishing the trip setpoint, larger or "Worst Case" accuracies would be conservative. When using the accuracy for establishing the As-Found and As-Left value for evaluation of the equipment performance, a smaller accuracy would be conservative. Since this calculation is establishing the As-Found and As-Left values, and the accuracy component is already included between the Analytical Limit and the Allowable Value by the Framatome /

AREVA calculations, the smaller accuracy values will be used in the calculations to ensure equipment performance is maintained at the highest level.

The effects of all other sources of instrument uncertainties are included in the Technical Specification Allowable Values which are determined external to this calculation. Framatome ANP / AREVA reports I calculations ANP-2514, 51-5012682-02, 32-1172392-03, 32-1257719-02, 86-5057366-003, 32-5057192-00, and 51-9004090-005 (DINs 4, 5, 15, 16, 18, 31, and 56) contain information pertinent to the calculation of those Allowable Values.

The following accuracies will be used in this calculation:

RPS Component Accuracy Source Comments

(% Full Scale or Span)

Bistable 0.15%

DIN 25, E92-341, page 14 Linear Amp 0.05%

DIN 25, E92-315, page 10 Sum/Diff Amp 0.15%

DIN 25, E92-317, page 12 Scaled output, WO Ref Power Supply Contact Monitor 0.3%

DIN 25, E92-343, page 15 Scaled Difference Amp 0.04%

DIN 25, E92-410, page 7 Function Generator Breakpoints 2 & 3 0.2%

DIN 25, E92-358, page 14 Breakpoints 1 & 4 0.4%

DIN 25, E92-358, page 14 Slope 1.0%

DIN 25, E92-358, page 14 li/E Converter 0.25%, page 2, Buffer Amp 0.05%

DIN 25, E92-316, page10 Square Root Extractor 0.40%

DIN 25, E92-345, page 14

Page 12 Eist-e CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008I 4

4.3.2 Uncertainty Propagation Through Modules Per ISA-RP67.04-02-2000 (DIN 9, Section 6.3.1), if signal conditioning modules are used in the instrument channel, the propagation of uncertainties through the modules must be taken into account. Equations have been developed to determine the output uncertainties for several common types of signal conditioning modules and are presented in ISA-RP67.04-02-2000, Section 6.3.1 Table 1. The following

'equations are applicable to RPS modules included in this calculation:

Fixed Gain Amplifier erandom = K

  • einput Square Root Extraction eranom = (einput) / (2
  • input)11 Where:

K

= multipliers of input signals (dimensionless gain) einput, einputl

= uncertainty of input signal(s) input

= input signal The summing amplifier equation from the ISA Recommended Practice is not included in this calculation since the Sum/Diff Amplifier acts as a fixed gain amplifier (gains are the same) with two inputs. Based on that, the fixed gain amplifier equation will be used with two linear amplifier inputs.

Since the accuracy values being developed in this calculation are for the establishment of As-Found and As-Left values, adjustable gains will either increase or reduce the calculated uncertainty. When including the As-Left value in establishing the trip setpoint, larger gains would be conservative. When using the gain for establishing the As-Found and As-Left value for evaluation of the equipment performance, a smaller gain would be conservative. Since the accuracy values are already included between the Analytical Limit and Allowable Value, a value smaller than the values currently included in the Data Packages (Dins 66, 67, 68, 69, 70, 71, 72, and 73) willbe used to reduce the As-Found and As-Left values to ensure equipment performance is maintained at the highest level.

The function generator is not included in the propagation of uncertainties. For the breakpoints on the sides (See Section 4.10.2), if beyond those points, a saturation value is added to the flow value to produce an output. Based on this, it does not modify the uncertainties input to the module similar to an amplifier.

Similarly, the breakpoints across the top will provide only the flow component as an output, thus not modifying the uncertainties from the flow input. The slopes are the only portion of the function generator that could cause the input uncertainties to be modified. The slope error is discussed in Section 4.5, which determines that a more conservative value than the calculated values will be used. Since the values calculated in Section 4.5, are for the development of an As-Left Tolerance, including additional uncertainty for the function generator slope, then reducing the value back to the same more conservative values is not necessary.

4.3.3 Calculation of String Accuracies The following section will calculate thestring accuracies for use in the As-Found and As-Left tolerance calculations. As stated above, the accuracies will not be specifically included in the Limiting Trip Setpoint development since the accuracies are already included in development of the Allowable Values.

4.3.3.1 High Flux String Accuracy As described in Section 1.2.2 and shown on Figure 1, the High Flux string consists of two signals that represent core power in the top and bottom halves of the core. The signals travel through two separate linear amps, are summed in a sum/diff amp, and the result (total power) is compared to a setpoint in a bistable. The uncertainties of the two signals from the linear amps are considered random and can be

I Page 13 SrstFne ayCALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008 4

combined by SRSS technique. The linear amps are calibrated with unity gain (DIN 40, 41, 42, and 43).

The sum/diff amp has an internal gain of 0.5 (DIN 25).

Sum/Diff Amp Input Uncertainty

= K

  • einput; where K is the gain of the Sum/Diff Amp

= 0.5 * (SRSS (linear amp, linear amp)) % Span

= 0.5 * (SRSS (0.05, 0.05)) % Span

= 0.035 % Span The Sum/Diff Amp Input Uncertainty may now be combined with the Sum/Diff Amp Accuracy and the Bistable Accuracy to calculate a total accuracy of the string. The total reference accuracy for the High Flux string is:

High Flux Accuracy

= SRSS (Sum/Diff Amp Input Uncertainty, Sum/Diff Amp Accuracy, Bistable Accuracy) % Span

= SRSS (0.035, 0.15, 0.15) % Span

= 0.215 % Span 4.3.3.2 Power/Pumps String Accuracy As described in Section 1.2.2 and shown on Figure 2, the Power/Pumps string consists of the High Flux String and input from the contact monitor. The contact monitor represents reactor coolant pump status (on or off). The output of the High Flux string and the contact monitor are compared to a setpoint in a bistable.

As input to the Power/Pumps string, the linear amplifier outputs are identical to the High Flux string.

Based on that, the Sum/Diff Amp Input Uncertainty from above will be used to represent the linear amplifiers. The total reference accuracy for the Power/Pumps string is:

Power/Pumps Accuracy 4.3.3.3 Power/Imbalance/Flow Accuracy

= SRSS (Sum/Diff Amp Input Uncertainty, Sum/Diff Amp, Contact Monitor, Bistable) % Span

= SRSS (0.035, 0.15,0.3, 0.15) % Span

= 0.369 % Span As described in Section 1.2.2 and shown on Figures 3 and 4, the Power/Imbalance/Flow consists of numerous components. The High Flux String is utilized for total reactor power and power imbalance.

Power Imbalance is determined through,the use of the two linear amp signals a~nd a scaled difference amp. The scaled difference amp determines if there are differences in power level between the top and bottom halves of the core then outputs the difference (imbalance) to the function generator. The gain of the scaled difference amp for channels 1 through 4 are 1.442, 1.490, 1.478, and 1.4995 per data packages RPS1NI1704, RPS2NI1704, RPS3NI1804, and RPS4NI1804 (DINs 66, 67, 68, and 69),

respectively. As described in Section 4.3.2, a smaller gain value of 1.25 will be used.

The Function Generator is provided with two accuracies for Breakpoint pairs 1 and 4, and 2 and 3. The calculation will calculate each independently for the Power/Imbalance (0.4%) and the Power/Flow (0.2%).

These breakpoints act independent of each other as described in Section 4.3.2. There is also an accuracy associated with the slope. The slope error will be addressed in Section 4.5.

Difference Amp Input Uncertainty

= K

  • einput; where K is the gain of the Difference Amp

= 1.25

  • SRSS (linear amp, linear amp) % Span

= 1.25 * (SRSS (0.05, 0.05)) % Span

= 0.088 % Span

Page 14 CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008 1 4 Power/Imbalance Accuracy

= SRSS (Difference Amp Input Uncertainty, Difference Amp, Function Generator, Bistable) % Span

= SRSS (0.088, 0.04, 0.4, 0.15) % Span

= 0.438 % Span The reactor coolant flow signal is sent through two separate current to voltage (I/E) converters and square root extractors (DIN 60). The outputs of the two square root extractors are combined in a buffer amp to determine total flow that outputs to the function generator. The gain of the buffer amp for channels 1 through 4 are currently about 0.905, 0.908, 0.904, and 0.907 per data packages RPS1 RC1410, RPS2RC1410, RPS3RC1510, and RPS4RC1510 (DINs 70, 71, 72, and 73). As described in Section 4.3.2, a smaller gain value of 0.75 will be used. The function generator output, representing power imbalance and flow, is sent to a bistable where it is compared to total reactor power from the High Flux string.

Square Root Ext. Input Uncertainty Buffer Amp Input Uncertainty (einp91 ) / 2 (input)

using signal units (Vdc)

= (li/E (Vdc)) / 2 * (I0Vdc)112

= (0.25% Span /100%

  • 1OVdc) /2 * (1OVdc) 1,2

=0.040 Vdc or 0.400 % Span

= K

  • einput; where K is the gain of the Buffer Amp

= 0.75

  • SRSS (Square Root Ext Input Uncert, Square Root Ext Input Uncert) % Span

= 0.75

  • SRSS (0.400, 0.400) % Span

= 0.424 % Span The total reference accuracy for the Power/Flow function is:

Power/Flow Accuracy

= SRSS (Sum/Diff Amp Input Uncertainty, Sum/Diff Amp, Buffer Amp Input Uncertainty, Buffer Amp, Function Generator, Bistable)

= SRSS (0.035, 0.15, 0.424, 0.05, 0.2, 0.15) % Span

= 0.518 % Span 4.3.4 Calibration Uncertainties (CAL)

Digital multimeters (DMM) are used for calibration of the RPS modules and precision resistors are also used during calibration of the RPS flow modules. The precision resistor and the DMM will be included for the Power/Imbalance/Flow portion (DIN 40, 41, 42, and 43). Only the DMM will be used for the other RPS strings.

Precision Resistor: 250 0 +/- 0.01% Span (or 0.001 Vdc on a 0-1OVdc scale)

DMM Accuracy is given as +/- 0.005% of Reading + 3 counts for 6 month calibration interval and 20 Vdc Scale (DIN 20):

DMM Accuracy

= 0.005% of Reading DMM Count Accuracy

= 3 (On 20 Vdc scale a count = 0.0001 Vdc)

Reading

= 0-10 Vdc Maximum Accuracies given in % are divided by 100% to convert to decimal fraction.

Page 15 fts_ý CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008 1 4 DMM Accuracy

= [(DMM Accuracy/ 100)

  • 10] + DMM Count Accuracy

= [(0.005% / 100)

  • 10] + (3
  • 0.0001)

= 0.0008 Vdc The DMM allowance is conservatively increased to 0.003 Vdc or 0.03% Span.

As the DMM uncertainty is conservatively increased, the calibration standard, i.e., the instrument used to calibrate the DMM will not be included in the calculation. Since the calibration standard is typically at least 4 times more accurate than the DMM, the conservative increase of the DMM uncertainty would bound the calibration standard uncertainty.

4.3.4.1 High Flux Calibration Uncertainties In surveillance procedures DB-MI-03057, DB-MI-03058, DB-MI-03059, and DB-MI-03060 (DINs 40, 41, 42, and 43), the linear amplifiers are calibrated with 2 digital multimeters each. The remainder of the high flux string is calibrated with 2 digital multimeters connected to the output of the linear amplifiers. The bistable trip is verified based on the linear amplifier outputs. The multimeters used for the calibrations could be the same devices for each of the linear amplifiers and the high flux string. If the multimeter is off in one direction, then the same effect would be contributed to each calibration. Based on that, the three sets of multimeter uncertainties will be considered to be dependent uncertainties and accounted for as such in the equation. The propagation of the uncertainties through the modules will be combined similar to the accuracies above. This results in:

Sum/Diff Amp Input CAL Uncertainty

= K

  • eiput; where K is the gain of the Sum/Diff Amp

= 0.5 * (SRSS ((DMM11 + DMM21), (DMM12 + DMM22))) %

Span

= 0.5 * (SRSS ((0.03 + 0.03), (0.03 + 0.03))) % Span

= 0.5 * (SRSS ((0.0600), (0.0600))) % Span

= 0.0424 % Span Where:

DMM1 1 = DMM1 used for calibrating Linear Amp 1 DMM21 = DMM2 used for calibrating Linear Amp 1 DMM12 = DMM1 used for calibrating Linear Amp 2 DMM22 = DMM2 used for calibrating Linear Amp 2 The output of the Sum/Diff Amp Input CAL Uncertainty may now be.combined with the Sum/Diff Amp /

Bistable calibration uncertainty. The total calibration uncertainty for the High Flux string is:

High Flux CAL Uncertainty

= SRSS (Sum/Diff Amp Input CAL Uncertainty, Sum/Diff Amp /

Bistable CAL Uncertainty) % Span

= SRSS (0.0424, (DMM1 + DMM2) % Span

= SRSS (0.0424, (0.03 + 0.03) % Span

= 0.0735 % Span 4.3.4.2 Power to Pumps Calibration Uncertainties For the Power to Pumps trip, the value from the High Flux uncertainties for the Sum/Diff Amp Input CAL Uncertainty may be used since the same output from the Sum/Diff Amplifier is input to both the High Flux and Power to Pumps bistables. The remainder of the instrument string is calibrated with two DMMs at the output of the linear amplifiers. Since this is identical to the test configuration for the High Flux Trip, the same value will be used.

Page 16

.6WEnqW CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE -058.01-008 4

Power to Pumps CAL Uncertainty

= 0.0735% Span The Contact Monitor total uncertainty is included in the string uncertainty described above since the dry contact inputs are simulated and included as part of the string calibration.

4.3.4.3 Power/Imbalance/Flow Calibration Uncertainties The Power/Imbalance/Flow will be broken into two strings similar to the function generator curve. The Power/Imbalance is protected by the sides of the function generator curve and the Power/Flow is protected by the top of the function generator curve. The Sum/Diff Amplifier Calibration Uncertainty described above is used as an input to the Power/Imbalance/Flow Bistable. This uncertainty will be identical to the uncertainties calculated above.

Sum/Diff Amp Input CAL Uncertainty

= 0.0424 % Span The Difference Amplifier uses the input from the Linear Amplifiers and inverts one input, sums the two to create the difference and multiplies that value by the gain. The calibration uncertainty associate with that is:

Difference Amp Input CAL Uncertainty

= K

  • einput; where K is the gain of the Difference Amp

= 1.25 * (SRSS ((DMM1 1 + DMM21), (DMM12 + DMM22))) %

Span

= 1.25 * (SRSS ((0.03 + 0.03), (0.03 + 0.03))) % Span

= 1.25 * (SRSS ((0.0600), (0.0600))) % Span

= 0.1061 % Span The reactor coolant flow signal is measured with two DMMs and two precision resistors. The propagation of the uncertainties through the square root extractors results in:

Square Root Ext. CAL Uncertainty Buffer Amp CAL Uncertainty

= (einptl) / 2 * (input)1/2 ; using sighnal units (Vdc)

= (SRSS (DMM1, DMM2, RES1, RES2) (Vdc)) / 2 * (10Vdc) 1 2

= (SRSS (0.03, 0.03, 0.01, 0.01)% Span /100%

  • 1OVdc) / 2 *

(1 OVdc) 1/2 0.007 Vdc or 0.070 % Span

= K

  • einput; where K is the gain of the Buffer Amp

= 0.75

  • SRSS (Square Root Ext CAL Uncert, Square Root Ext CAL Uncert) % Span

= 0.75

  • SRSS (0.070, 0.070) % Span

= 0.074 % Span The total calibration uncertainty for the Power/Imbalance function is:

Power/Imbalance CAL Uncertainty

= SRSS (Sum/Diff Amp Input CAL Uncertainty, Difference Amp Input CAL Uncert)

= SRSS (0.0424, 0.1061) % Span

= 0.114 % Span

Page 17 Flo-com CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008 1 4 The total calibration uncertainty for the Power/Flow function is:

Power/Flow CAL Uncertainty

= SRSS (Sum/Diff Amp Input Uncertainty, Buffer Amp CAL Uncert)

= SRSS (0.035, 0.074) % Span

= 0.082 % Span 4.4 Drift Drift values for the instrument strings are determined in Attachments 1, 2, and 3 of this calculation. The linear amplifier drift is included in calculation 32-1172392-03 (DIN 15). The calculated uncertainty values in that calculation are included between the Analytical Limit and the Allowable Value. Based on that, the drift for the linear amplifiers, although normally included between the Allowable Value and the trip setpoint, will not be included in this calculation. The calculated drift values for the remainders of the instrument strings are:

High Flux Bias: -0.000291 Vdc Random: 0.009346 Vdc Power to Pumps Bias: 0.000249 Vdc Random: 0.012871 Vdc Power/Imbalance/Flow Bias: -0.000094 Vdc Random: 0.008268 Vdc The worst case from above would be Power to Pumps with a summed, total of 0.013120. The Technical Specifications allow the three month surveillance period plus a 25% extension for total time to test. To correct for the extension, the 0.013120 volt value will be multiplied by 1.25. This yields 0.016400 Vdc. A conservative value of 0.018 Vdc will be used. As the drift analysis determined the drifts to be not normally distributed, the drift will be added in the As-Left Tolerance calculation instead of using the square root sum of the squares method.

Drift

=0.018 Vdc Drift

= (0.018 Vdc/ 10 Vdc) 125% Power

= 0.225% Power 4.5 As-Left Tolerances (ALT)

The As-Left Tolerance is controlled and declared here, and implemented by the calibration/functional test procedures and System Work Packages (DIN 40, 41, 42, 43, 44, 45, 46, and 47).

Per the TSTF Improved Technical Specification Traveler 493, (DIN 63, page 7) the As-Left tolerance must be calculated to include only uncertainties of reference accuracy, M&TE accuracy, and M&TE readability.

Regulatory Issue Summary (RIS) 2006-17 (DIN 62) page 5, states:

Additionally, the TSTF did not sufficiently address the NRC staff concern with the practice of using Nominal Setpoints (NSPs) for establishing the test acceptance criteria band for as-found instrument values. The NRC staff concern was that excessive changes in the Trip Setpoints (TSP) could go undetected and also that a high incidence of false detections could result from such a practice.

Subsequently, the NRC staff investigated the acceptability of basing operability determinations for as-found instrument values on NSP values. The NRC staff review concluded that if specific conditions are met, then the NRC staff would find a NSP-based assessment of as-found values acceptable. Those conditions are: (1) the setting tolerance band is less than or equal to the square root of the sum of the squares of reference accuracy, measurement and test equipment, and readability uncertainties; (2) the

F F~ne IPag 1 8 CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008I 4

setting tolerance is included in the total loop uncertainty, and (3) the pre-defined test acceptance criteria band for the as-found value includes either, the setting tolerance or the uncertainties associated with the setting tolerance band, but not both of these.

As described above, the ALT is determined by using the RPS string accuracy calculation (Section 4.2.4) and adding the calibration uncertainty (Section 4.3.4). The values for the accuracy and calibration uncertainty are developed in % Span. They must be converted to % Power by multiplying the values by 1.25 (125%). As discussed in Section 4.4, the drifts will be added since they are not normally distributed.

High Flux ALT Power/Pumps ALT

= High Flux Accuracy +-High Flux CAL Uncertainty

= ((0.215% Span x 1.25) + (0.0735% span x 1.25)) % Power

= 0.3606% Power

= Power/Pumps Accuracy + Power to Pumps CAL Uncertainty

= ((0.369% Span x 1.25) + (0.0735% Span x 1.25))% Power

= 0.5531% Power Power/Imbalance/Flow:

Power/Imbalance ALT Power/Flow ALT

= Power/Imbalance Accuracy + Power/Imbalance CAL Uncert

= ((0.438% Span x 1.25) + (0.114% Span x 1.25)) % Power

= 0.69% Power

= Power/Flow Accuracy + Power/Flow CAL Uncert

= ((0.518% Span x 1.25) + (0.082% Span x 1.25)) % Power

= 0.750% Power As stated in Section 4.3.3.3, the slope accuracy will be included after establishing the As-Left Tolerances and the Breakpoint locations. Instead of using the calculated As-Left Tolerances, the smaller, more restrictive As-Left Tolerances currently in use in the surveillance procedures will be used. This is conservative, since using a smaller As-Left Tolerance ensures the setpoint will be continuously close to its nominal setpoint and poorly performing equipment will be readily detected. Based on this, adding additional uncertainty due to slope to the calculated values, then reducing.the ALT values to provide a more restrictive ALT is unnecessary. This is acceptable since the slope accuracy is already included between the Analytical Limit and the Allowable Value as documented in Framatome calculation 32-1257719-02 (DIN 16), Section 10. As stated above, the more restrictive As-Left Tolerance values currently used in surveillance procedures will be retained. Those ALT values are:

High Flux ALT:

Power/Pumps ALT:

Power/Imbalance/Flow:

+/- 0.0875% Power

+/- 0.225% Power

+/- 0.15% Power

+/- 0.5125% Power Power/Imbalance ALT

=

Power/Flow ALT

=

Page 19 FmLrsTy CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008I 4

4.6 Technical Specification (TS) Allowable Values The following TS Allowable Values will be used in this calculation.

High Flux with ULTRASONIC FLOW METER

< 104.9% Power with 4 pumps operating

  • High Flux without ULTRASONIC FLOW METER

< 103.3% Power with 4 pumps operating

  • High Flux

< 80.6% Power with 3 pumps operating (DIN 16)

Power/Pumps

_5 55.1% Power with one pump in each loop (DIN 16)

NOTE: The Power/Pumps setpoint is < 0% Power for no pumps, one pump/loop or two pumps in one loop operating. This is also the field setpoint for these conditions.

  • The TS Allowable Values of 104.9% Power and 103.3% Power are contained in Serial 3198 (DIN 55),

'Measurement Uncertainty Recapture Power Uprate.'

Table 2.2-1 of the TS references the Core Operating Limits Report (DIN 49) which contains the TS Allowable Value curve for the Power/Imbalance/Flow (Flux - Delta Flux/Flow). This curve is directly proportional to actual reactor coolant flow. The TS Allowable Value point coordinates are given for 100%

flow:

First column is % of Axial Power Imbalance Second column is % of Rated Thermal Power S-30.6 94.4 1

[Output to the COLR (DIN 49)]

r17 108 30.6 77.1 Note: The TS Allowable Values shown above were determined for Cycle 9 and evaluated in this calculation as being more conservative than the current calculated TS Allowable Values from the Reload Report (DIN 4). See Section 4.10.2 for correlations between current Reload Report calculated values, Cycle 9 values, and field setpoints. Therefore, this calculation declares that Cycle 9 TS Allowable Values will be utilized as the basis for determination of Power/Imbalance/Flow field setpoints in this calculation. As a result, these are the TS Allowable Values to be published in the Core Operating Limits Report (Output DIN 49).

With this additional margin, future cycle analyses that impact the current values in the Reload Report, but that remain bounded by Cycle 9 TS Allowable Values, may not require field setpoint changes for Power/Imbalance/Flow. This calculation shall be updated each Cycle to document that the Cycle 9 values remain bounding, or modify the Tech Spec values accordingly.

Page 20 CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008 1 4 4.7 4.7.1 Limiting Trip Setpoint Calculations.

High Flux Setpoint 4 Pump Operation with ULTRASONIC FLOW METER used for heat balance calculations:

Limiting Trip Setpoint (% Power)

= Tech Spec Allowable Value - ALT - Drift

= 104.9 - 0.0875 - 0.225

= 104.5875% Power 4 Pump Operation without ULTRASONIC FLOW METER for heat balance calculations or inoperable:

Limiting Trip Setpoint (% Power) 3 Pump Operation:

Limiting Trip Setpoint (% Power)

= Tech Spec Allowable Value - ALT-Drift

= 103.3 - 0.0875 - 0.225

= 102.9875% Power

= Tech Spec Allowable Value - ALT - Drift

= 80.6 - 0.0875 - 0.225

= 80.2875% Power 4.7.2 Power/Pumps Setpoint Limiting Trip Setpoint (% Power)

= Tech Spec Allowable Value - ALT - Drift

= 55.1 - 0.225 - 0.,225

= 54.65% Power 4.7.3 Power/Imbalance/Flow Setpoint Power/Imbalance Setpoints for Breakpoints (Bp) 1-4.

BplP/I, Limiting Trip Setpoint BplP/I Bp 2_P/I, Limiting Trip Setpoint Bp 2_P/1 Bp 3_P/I, Limiting Trip Setpoint Bp 3_P/I Bp 4_P/I, Limiting Trip Setpoint Bp 4_P/I

= Tech Spec Allowable Value + ALT + Drift

-30.6 + 0.15 + 0.225

=-30.225% Power Tech Spec Allowable Value + ALT + Drift

= -17 + 0.15 + 0.225

= -16.625% Power

= Tech Spec Allowable Value - ALT - Drift

= 17 - 0.15 - 0.225

= 16.625% Power

= Tech Spec Allowable Value - ALT - Drift

= 30.6 - 0.15 - 0.225

= 30.225% Power

Page 21 CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008 4

1 Power/Flow Setpoints for Breakpoints (Bp) 1-4.

Bp 1_P/F, Limiting Trip Setpoint Bp IP/F Bp 2_P/F, Limiting Trip Setpoint Bp 2_P/F Bp 3_P/F, Limiting Trip Setpoint Bp 3_P/F Bp 4_P/F, Limiting Trip Setpoint Bp 4_P/F

= Tech Spec Allowable Value - ALT - Drift

= 94.4 - 0.5125 - 0.225

= 93.6625% Power

= Tech Spec Allowable Value - ALT - Drift

= 108 - 0.5125 - 0.225

= 107.2625% Power

= Tech Spec Allowable Value - ALT - Drift

= 108 - 0.5125 - 0.225

= 107.2625% Power

= Tech Spec Allowable Value - ALT - Drift

= 77.1 - 0.5125 - 0.225

= 76.3625% Power 4.8 Nominal Trip Setpoint Calculations.

The Nominal Trip Setpoints are calculated by including margin to the Limiting Trip Setpoint in a manner that will move the Nominal Trip Setpoint away from the Analytical Limit. There is no specific basis for the amount of margin included other than toround the values to a more conservative value. The Nominal Trip Setpoints shall be implemented in the field by SAP and M-7201 setpoint data.

4.8.1 High Flux Setpoint 4 Pump Operation with ULTRASONIC FLOW METER used for heat balance calculations:

Nominal Trip Setpoint (%)

= Limiting Trip Setpoint - Margin

= 104.5875 - 0.0875

= 104.5% Power 4 Pump Operation without ULTRASONIC FLOW METER for heat balance calculations or inoperable:

Nominal Trip Setpoint (%)

3 Pump Operation:

= Limiting Trip Setpoint - Margin

= 102.9875- 0.0875

= 102.9% Power

= Limiting Trip Setpoint - Margin

= 80.2875 - 0.1875

= 80.1% Power Nominal Trip Setpoint (%)

Page 22

.8!ýLEýne CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008 4

4.8.2 Power/Pumps Setpoint Nominal Trip Setpoint (%)

= Limiting Trip Setpoint - Margin

= 54.65 - 0.1500

= 54.5% Power 4.8.3 Power/Imbalance/Flow Setpoint Using the Break Points calculated in Section 4.7.3 as the Limiting Trip Setpoints results in:

Power/Imbalance Setpoints for Breakpoints (Bp) 1-4.

BplP/I, Nominal Trip Setpoint BplP/I Bp 2_P/I, Nominal Trip Setpoint Bp 2_P/I Bp 3_P/I, Nominal Trip Setpoint Bp 3_P/I Bp 4_P/I, Nominal Trip Setpoint Bp 4_P/I Power/Flow SetDoints for BreakDoints (B

= Limiting Trip Setpoint + Margin

= -30.225 + 0.1250

= -30.1% Power

= Limiting Trip Setpoint + Margin

= -16.625 + 0.1250

= -16.5% Power

= Limiting Trip Setpoint - Margin

= 16.625 - 0.1250

= 16.5% Power

= Limiting Trip Setpoint - Margin

= 30.225 - 0.1250

= 30.1% Power

'p) 1-4.

= Limiting Trip Setpoint - Margin

= 93.6625 - 0.1625

= 93.5% Power

= Limiting Trip Setpoint - Margin

= 107.2625 - 0.1625

= 107.1% Power

= Limiting Trip Setpoint - Margin

= 107.2625 - 0.1625

= 107.1% Power

= Limiting Trip Setpoint - Margin

= 76.3625 - 0.1625

= 76.2% Power Bp !_P/F, Nominal Trip Setpoint Bp IP/F Bp 2_P/F, Nominal Trip Setpoint Bp 2_P/F Bp 3_P/F, Nominal Trip Setpoint Bp 3_P/F Bp 4_P/F, Nominal Trip Setpoint Bp 4_P/F

Page 23 Rrst~neCALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008 4

4.9 As-Found Tolerances (AFT)

The following As-Found Tolerances account for the uncertainties associated with the As-Left Tolerance plus the Drift Allowance. This is consistent with the guidance in TSTF Improved Technical Specification Traveler 493, (DIN 63, page 7). Per the TSTF Improved Technical Specification Traveler 493, (DIN 63, page 7) the As-Found Tolerance must be calculated to include only uncertainties of reference accuracy, M&TE accuracy, M&TE readability, and drift or the combination of the As-Left Tolerance and drift. The latter approach will be used because using the string accuracies (Section 4.2.4) would allow the as-found setpoint to be non-conservative with respect to the Allowable Value. Using the ALT ensures that the Tech Spec Allowable Value is protected.

Any As-Found value that exceeds the As-Found Tolerance requires recalibration to within the As-Left Tolerance around the Nominal Trip Setpoint prior to return to service.

4.9.1 High Flux As-Found Tolerance r

The As-Found Acceptance Criteria Band is determined by taking the High Flux string As-Left Tolerance (Section 4.2.4) and drift. The equipment accuracies and calibration uncertainties are included in the As-Left Tolerance, so they will not be listed separately. During surveillance testing, the absolute value of the previous As-Left minus the current As-Found shall be less than or equal to the As-Found Acceptance Criteria Band. If outside the As-Found Acceptance Criteria Band, the equipment shall be recalibrated to within the As-Left Tolerance around the Nominal Trip Setpoint and evaluated to verify it is functioning as required prior to return to service.

previous As-Left - current As-Found 1 5 As-Found Acceptance Criteria Band This approach is consistent with the methodology contained in a similar RPS Technical Requirements Manual LCO 3.3.1.2 and ensures that the components are exhibiting expected behaviors. This method for determining compliance with the As-Found Acceptance Criteria Band shall be contained in the RPS Surveillance Procedures (DINs 40, 41, 42, and 43).

As-Found Acceptance Criteria Band

= High Flux ALT + Drift

= 0.0875% + 0.225%

= 0.3125% Power OR

= (0.3125%/125%)

  • 10 Vdc

= 0.025 Vdc 4.9.2 Power/Pumps As-Found Tolerance Power/Pumps AFT

= Power/Pumps ALT + Drift

= 0.225% + 0.225%

= 0.4500% Power 4.9.3 Power/Imbalance/Flow As-Found Tolerance Power/Imbalance As-Found Tolerance Power/Imbalance

= Power/Imbalance ALT + Drift

= 0.15% + 0.225%

= 0.3750% Power

I Page 24 5mrstF_nec CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008,I 4

Power/Flow As-Found Tolerance Power/Flow

= Power/Flow ALT + Drift

= 0.5125% + 0.225%

= 0.7375% Power Y

Page 25 CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008 4

4.10 Illustrations 4.10.1 Locations of Calculated Uncertainties This figure illustrates the methodology/location of uncertainties and margins used to calculation the Limiting and Nominal Trip Setpoints for the High Flux, Power/Pumps, and Power/Imbalance/Flow with respect to the Analytical Limits.

Analytical Limit String Errors and Margin A

Allowable Value As-Found Tolerance As-Found Tolerance Drift As-Left Tolerance Limiting Trip Setpoint Drift As-Left Tolerance Margin As-Left Tolerance Drift Nominal Trip Setpoint

Page 26

~CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C;-ICE-058.01-008 4

4.10.2 Power/Imbalance/Flow Trip Curve The following two graphs are developed with the Calculated Allowable Values from the Reload Report, Figure 8-14 (DIN 4); the Allowable Values from Section 4.6; and the Setpoints from Section 4.8.3. Graphs have been provided for both the current 2772MWt licensed power level, as well as the proposed 2817MWt power uprate. Therefore, Allowable Values and field setpoints are demonstrated as conservative and bounding for both cases. This is consistent with the approach documented in AREVA Document 86-5057366-003 (DIN 18).

Thermal Power of 2772 MWt:

B3

--- --- Calculated AV Cycle 9 AV (bounding)

Setpoint B4

-40

-30

-20

-10 0

10 20 30 40

%Axial Power Imbalance Where at each point of interest, the breakpoint values for the Calculated AVs are on top, the AVs are below the Calculated AVs, and the Setpoint Values are below the AVs.

  • rst~etc~yCALCULATION COMPUTATION Pae2 NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-lCE-058.01-008 1 4 Thermal Power of 2817 MWt:

r-25.04, 108 21.42, 108 A nn#

B2-0 BI

-17, 108 17, 108 L-16.5, 107.1 16.5, 107.1 110

//-

I,&

90

-32.3, 93.91

-30.6, 94.4 k-30.1, 93.5 37.09, 93.91 7O 730.6, 77.1 30.1, 76.2 60 1 I

i

}-B3 B4 I

-40

-30

-20

-10 0

10 20 30 40 50

%Axial Power Imbalance From the above graphs, it is evident that the values are equivalent orý there is margin between the Calculated AV and the Cycle 9 AV.

Page 28 Rrst CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-O08I 4

5. RESULTS Nominal Trip Setpoints for the Reactor Protection System (RPS) Reactor High Flux, Power/Imbalance/Flow and Power/Pumps Trip functions are as follows:

Parameter Nominal Trip Setpoint High Flux WITH Ultrasonic Flow Meter (4 Pump Operation)

High Flux WITHOUT Ultrasonic Flow Meter (4 Pump Operation) 104.5% Power 102.9% Power 80.1% Power 54.5% Power High Flux (3 Pump Operation)

Power/Pumps Power/Imbalance/Flow First column is % of Axial Power Imbalance Second column is % of Rated Thermal Power

(ý30.1

-16.5 116.5 30.1 As-Left Tolerances:

93.5 107.1I 107.1 76.29 High Flux ALT:

Power/Pumps ALT:

Power/Imbalance/Flow:

Power/Imbalance ALT Power/Flow ALT

=

+/-. 0.0875% Power

=

+/- 0.225% Power

=

+/- 0.15% Power

=

+/- 0.5125% Power As-Found Tolerances:

High Flux AFT

= +/7 0.3125% Power As-Found Acceptance Criteria Band (High Flux String):

I previous As-Left - current As-Found I -< 0.3125% Power (or 0.025 Vdc)

Power/Pumps Power/Imbalance/Flow Power/Imbalance Power/Flow

- +/- 0.4500% Power

= +/- 0.3750% Power

= +/- 0.7375% Power

Page 29 Rrstý CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008I 4

6. CONCLUSIONS The Nominal Trip Setpoints identified above are based on Allowable Values from Serial 3198 (DIN 55) and AREVA 51-9004090-005 (DIN 56) with the exception of the Allowable Values for Power/Imbalance/Flow which are based on the Reload Report (DIN 4). The methodology for determining the setpoints is in compliance with ISA 67.04 requirements. Additionally, the As-Left and As-Found Tolerances are calculated based on the Technical Specification Task Force (TSTF) Traveler 493 (DIN 62) and the NRC Regulatory Issue Summary (RIS) 2006-17 (DIN 61). The calculated values are identical to the current operating values and no operator burdens have been identified with the setpoints. Based on this, the acceptance criteria outlined in Section 3 have been met.

Page 30 F5rsEner :

CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008 4

Attachment I - Drift Analysis for High Flux Analysis Methodology The method used to determine the drift for the bistables is to analyze the as-found as-left (AFAL) setpoint data of the subject instruments. The statistical analysis will be based on TR-103335-R1, "Guidelines for Instrument Calibration Extension Reduction Programs -

Revision 1: Statistical Analysis of Instrument Calibration Data" (DIN 26), with the following clarifications:

1.

The calibration data was taken during a functional check. The procedures from which the data was retrieved are:

DB-MI-03057, RPS Channel 1 Calibration of High Flux, Power/Imbalance/Flow, Power/Pumps Trip Functions (Din 40) 0 DB-MI-03058, RPS Channel 2 Calibration of High Flux, Power/Imbalance/Flow, Power/Pumps Trip Functions (Din 41) 0 DB-MI-03059, RPS Channel 3 Calibration of High Flux, Power/Imbalance/Flow, Power/Pumps Trip Functions (Din 42)

DB-MI-03060, RPS Channel 4 Calibration of High Flux, Power/Imbalance/Flow, Power/Pumps Trip Functions (Din 43)

The instrument was adjusted if the as-found data was outside the tolerance and, in some cases, was adjusted even when within the tolerance.

2.

The three-month drift was calculated using the following formula for a time period for which no replacements were made to the instrument. If adjustments were made, these were factored into the formula as follows:

Di = AF - AFi.92 + Adjustment(s)

Where:

D,

= Drift for the time period AF

= As-Found during current calibration check ALi92

= As-Left of approximately 92 days previous

3.

Since the duration (di) of the calculated three-month drift (Di) was not always comprised of the same number of days and the Technical Specification defines three months as 92 days, for all durations less than or equal to 92 days, the calculated three-month drift was corrected based on the following equation:

Dci = Di (92/di) ; where Dci is corrected drift If the duration was greater than 92 days, the value would be decreased if the above equation were used. For conservatism, the value collected during the surveillance test was used as the normalized data (i.e., no interpolation of data).

For durations that were less than 46 days (92/2) or greater than 115 days (92 x 1.25) the data was not used since it would not be reflective of the 92 day drift.

4.

The data will be evaluated for outliers and for normality.

F mtF~nerCALCULATION COMPUTATION Pae3

.NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008 4

5.

The tolerance interval will be calculated for a confidence level of 95% with 95% of the population contained within the tolerance interval (TI) using the following equation:

TI(95/95)

= xbar + ks

Where, TI(gs/ 95)

= Tolerance interval for 95%/95%

xbar

= Sample mean k

= Tolerance factor (95/95) s

= Sample standard. deviation

6.

The following equations will be used to determine the mean and standard deviation:

Mean

= xbar = (7 Dc, ) N, where N = sample count, and I = 1 to N Sample standard deviation = s = [(I/(N - 1)) ((1 (Da )2 ) - N (xbar)2)]1' 2

Page 32 FnstF__ner CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

IREVISION:

C-ICE-O58.01-008I 4

Compilation of Drift Data - High Flux Channel1 Channel2 Channel3 Channel4 0.000000 0.003680 0.003366 0.003286

-0.002190

-0.001095

-0.003286

-0.002190

-0.001095

-0.002190 0.000000 **

-0.002190 0.000000

-0.020092 **

0.000000 **

-0.001136 0.000000

-0.002272 **

-0.002190 0.006732

-0.001057 0.001082 0.008762 0.009200

-0.001136 **

-0.002190 0.001704 0.001095 0.004381 0.001070

-0.015153

-0.001095 0.001095

-0.001122 0.003325 0.000000

-0.003286 0.002140

-0.003286 0.001095 **

0.014071

-0.001000

-0.001095 0.002000 **

0.000000 0.000000

-0.001000

-0.002000 0.000000

-0.002272 0.000000....

-0.002190 **

0.000000 0.000000 0.000000 **

0.001108

-0.005412 0.000000 0.001070

-0.004279 0.001095 0.000000

-0.002244 0.000000

-0.003366

-0.001122 0.001095 0.001082 0.002244

-0.001095

-0.001095 0.001122

-0.001057

-0.001000 0.001057 0.001122 **

0.004678 0.001000

-0.001057 0.003407 0.000000

-0.005041 **

0.004000 0.000000 0.005041

-0.006571 0.001227

-0.001000

-0.001108

-0.012000 0.000000 0.002000

-0.002190 1

Calculation of Mean and Standard Deviation - High Flux Mean (Drift (Bias))I

-0.000291 Standard Dev.1 0.0041601 Sample Size 93 K Factor 2.2468 Drift (Random) 0.009346

Page 33 5rst' CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008I 4

T-Test - High Flux The T-Test determines if a data point is able to be considered an outlier from all other data. This is accomplished by finding the worst case value in either the positive or negative direction, subtracting the mean from that value, taking the absolute value of the results, and dividing the resulting value by the standard deviation. This gives a result of the number of standard deviations the value is away from the mean. If the value is determined to be greater than the "Critical Value", the data point may be considered an outlier and removed from the data if there is a basis for removal. If the data is removed, the T-Test is repeated with revised worst case value, mean, and standard deviation, until the worst case data point is either less than the Critical Value or has no basis for removal.

Max value from Table =

0.014071 Min value from Table =

-0.020092 Critical value for T-Test with a sample size of 96 and a Upper 5% Significance =

3.21 Standard Dev =

0.004160 Mean=

-0.000291 T-Test for Max value 0.014071 T-Test for Min value

-0.020092 T-Test =

3.4523 T-Test =

4.7601 Because the T-Test for both the Max and the Min values is higher than the 3.21 value,.they could be considered outliers and excluded from the sample. Due to there being no basis for removal, they will not be excluded. No further tests for outliers are required.

I Page 34 flfrA ne g CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION N6.:

REVISION:

C-ICE-058.01-008I 4

Normalcy Test - High Flux Using the Chi-squared test for normalcy results in:

47.64 based on groupings of bins below.

As there are 8 bins, a normal distributed data set would be below 8. Since it is above 8, the data is determined to be NOT normally distributed. Graphing the data results in a display of data that has a high kurtosis (middle peak) and 3 data values outside of 3 standard deviations. To graphically display the data, a series is established starting at the Mean and moving away from the Mean by the Standard Deviation.

The number of data sets in each series are determined to be able to plot a normalcy graph. The following table displays the series boundaries and the number of data sets in each series and compares that to the normal distribution value. Due to the high kurtosis and the 3 values that are more than 3 standard deviations away from the mean, the data will be considered to be NOT normally distributed and will be included as a bias in the calculation.

Actual Dist Normal Dist Chi-Squared Data Sets between 0.024669 and

.0.012189 1

0.14 5.31 Data Sets between 0.012189 and 0.008029 2

1.98 0.00 Data Sets between 0.008029 and 0.003869 5

12.64 4.62 Data Sets between 0.003869 and

-0.000291 44 31.74 4.73 Data Sets between

-0.000291 and

-0.004450 35 31.74 0.33 Data Sets between

-0.004450 and

-0.008610 3

12.64 7.35 Data Sets between

-0.008610 and

-0.012770 1

1.98 0.49 Data Sets between

-0.012770 and

-0.025250 2

0.14 24'81 47.64 Determination of Normalcy 50 O 40

.N 30

'D 20

.~10 0I-0 U)

~Actual data

  • 0 U Normal data

ý 73 Actual data

'10 Normal data 3

4 5

6 7

8 1

2 3

Actual data versus normal distribution V

Page 35 F rst~enWj CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008I 4

Time Dependency Analysis - High Flux Time dependency analysis is used to determine if there is a correlation between the period between calibrations and the resulting change in setpoint. Each data point has been calculated along with the associated time duration between calibrations. Each of the data points used have been included in the plot below. As can be seen from the plot, there are no discernable indications that the drift is in any one direction based on a given time period. For example, if there were a significant number of data points in the positive region from the period of 100 - 150 days with no corresponding data points in the negative region, this would indicate a time dependency with respect to the drift. Since this, nor any other similar correlation is evident, it is concluded there is no time dependency to the drift.

Time Dependency Analysis Normalized Data 0.02 0.0 15,,*

'FA 0.01.

0

-0.005 5

+

1

  • Seriesl

~-0.01

~

~JY~<?

-L -0.015

0)

-0.02 i.

-0.025 Days

Page 36 Fust~nerCALCU LATION COM PUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008I 4

A B

C D

E F

G H

I I

1

.High Flux Trip - Channel 1

-2 Di di Dci 3

Re-3 Month

'3 Month Corrected 3 calibrated Re-

'Drift Value Duration Month Drift 4

Date Desired As-Found As-Left Difference calibrated (Voc)

(Days)

Value (VDC)

Comments 5

7113/99 8.360 8.361 8.361 6

10/5/99 8.360 8.361 8.361 0.00000 84 0.000000 7

12/28/99 8.360 8.359 8.359 1

-0.00200 84

-0.002190 1 8

3/21/00 8.360 8.358 8.358

-0.00100 84

-0.001095 9

6/13/oo 8.360 8.356 8.356

-0.00200 84

-0.002190 10 918/00 8.360 8.356 8.356 0.00000 87 0.000000 11 11/28/O 8.360 8.354 8.354

-0.00200 81

-0.002272 12 2/23(01 8.360 8.353 8.353

-0.00100 87

-0.001057 13 5/15/01 8.360 8.352 8.352

-0.00100 81

-0.001136 14 8/7/01 8.360 8.353 8.353 0.00100 84 0.001095 1 15 I0/30/01 8.360 8.352 8.352

-0.00100 84

-0.001095 16 1/22/02 8.360 8.352 8.352 0.00000 84 0,000000 17 6/27/03 0.320 0.326 0.326 Desired Value Char e 18 11/11/03 0.320 0.325 0.325

-0.00100 137

-0.001000 19 2/20(04 0.320 0.325 0.325 0.00000 101 0.000000 20 5/14/04 8.360 8.369 8.369 Desired Value Char e 21 8/3/04 8.360 8.367 8.367

-0.00200 81

-0.002272 1 22 10/26/04 8.360 8.365 8.365 1

-0.00200 84

-0.002190 23 2/15/2005 8.360 8.365 8.365 0.00000 112 0.000000 24 4/12/2005 8.360 8.365 8.365 0.00000 56 0.000000 25 7/8/2005 8.360 8.365 8.365 0.00000 87 0.000000 26 1

9/28/2005 8.360 8.364 8.364

-0.00100 82

-0.001122 27 12/21/2005 8.360 8.363 8.363

-0.00100 84

-0.001095 28 4/9/2006 8.360 8.362 8.362

-0.00100 109

-0.001000 1 29 6r7r2006 8.360 8.365 8.365 0.00300 59 0.004678 30 8/29/2006 8.360 8.365 8.365 0.00000 83 0.000000 31 11/29/2006 8.360 8.365 8.365 0.00000 92 0.000000 1

Page 37 6rst~e_.

CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-lCE-058.01-008 1 4 A

B C

D E

I F

G H

I I

T

_High Flux Trip - Channel 2 2

Di di Da 3

Re-3 Month 3 Month Corrected 3 calibrated Re-Drift Value Duration Month Drift 4

Date Desired As-Found As-Left Difference calibrated (Voc)

(Days)

Value (VDC)

Comments 5

6/1011999 8.360

,8.364 8.364 6

8/24/1999 8.360 8.367 8.367 0.00300 75.00 0.003680 7

11/16/1999 8.360 8.366 8.366

-0.00100 84.00

-0.001095 8

2/8/2000 8.360 8.364 8.364

-0.00200 84.00

-0.002190 9

3/6/2ooo 8.360 8.364 8.364 0.00000 27.00 0.000000 10 5/512000 7.969 7.970 7.970 Desired Value Char e 11 712412000 8.360 8.363 8.363 Desired Value Char e 12 10/17/2000 8.360 8.364 8.364 0.00100 85.00 0.001082 13 1113/2000 8.360 8.365 8.365 17.00 Duration too short 14 1/9/2001 8.360 8.368 8.361

-0.00700 X

0.00400 84.00 0.004381 Uses 10/17/2000 de a 15 413/2001 8.360 8.362 8.362 0,00100 84.00 0.001095 16 6/26/2001 8.360 8.359W 8.359

-0.00300 84.00

-0.003286 17 9/18/2001 8.360 8.360 8.360 0.00100 84.00 0.001095 18 12/11/2001 8.360 8.359 8.359

-0.00100 84.00

-0.001095 19 7/3/2003 0.320 0.322 0.322 Desired Value Char ge 20 11/13/2003 0.320 0.321 0.321

-0.00100 133.00

-0.001000 21 2/12/2004 0.320 0.321 0.321 0.00000 91.00 0.000000 22 3/14/2004 4.800 4.798 4.800 0.00200 X

Desired Value Char ]e 23 6/22/2004 8.360 8.360 8.360 Desired Value Char ;e 24 9/16/2004 8.360 8.361 8.361 0.00100 86.00 0.001070 25 12/7/2004 8.360 8.359 8.359

-0.00200 82.00

-0.002244 26 3/112005 8.360 8.360 8.360 0.00100 84.00 0.001095 27 5/24/2005 8.360 8.359 8.359

-0.00100 84.00

-0.001095 28 8/19/2005 8.360 8.360 8.360 0.00100 87.00 0.001057 29 11/19/2005 8.360 8.361 8.361 0.00100 92.00 0.001000 30 1131/2006 8.360 8.357 8.357

-0.00400 73.00

-0.005041 31 4114/2006 8.360 8.361 8.361 0.00400 73.00 0.005041 32 7/1812006 8.360 8.360 8.360

-0.00100 95.00

-0.001000 33 10/11/2006 8.360 8.360 8.360 0.00000 85.00 0.000000 34 1/3/2007 8.360 8.358 8.358

-0.00200 84.00

-0.002190

Page 38 RrstEneW CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

IREVISION:

C-ICE-058.01-008I 4

A B

C D

E F

G H

I J

1__High Flux Trip - Channel 3

-2 D.

di D_ _

3 Re-3 Month 3 Month Corrected 3 calibrated Re-Drift Value Duration Month Drift 4

Date Desired As-Found As-Left Difference calibrated (Voc)

(Days)

Value (VDC)

Comments 5

612411999 8.360 8.357 8.357 6

9114/1999 8.360 8.360 8.360 0.00300 82.00 0.003366 7

12/7/1999 8.360 8.357 8.357

-0.00300 84.00

-0.003286 8

2129/2000 8.360 8.357 8.367 0.01000 X

0.00000 84.00 0.000000 9

5/26/2000 8.360 8.348 8.348

-0.01900 87.00

-0.020092 I

10 8/15/2000 8.360 8.347 8.347

-0.00100 81.00

-0.001136 11 11/7/2000 8.360 8.345 8:368 0.02300 X

-0.00200 84.00

-0.002190 12 1/30/2001 8,360 8.376 8.361

-0.01500 X

0.00800 84.00 0.008762 13 412412001 8.360 8.359 8.359

-0.00200 84.00

-0.002190 14 7/1912001 8.360 8.360 8.360 0.00100 86.00 0.001070 15 10/9/2001 8.360 8.359 8.359

-0.00100 82.00

-0.001122 16 1/3/2002 8.360 8.361 8.361 0.00200 86.00 0.002140 17 7/4/2003 0.320 0.314 0.314 Desired Value Char le 18 11/12/2003 0.320 0.316 0.316 0.00200 131.00 0.002000 19 11/20/2003 0.320 0.315 0.315 8.00 Duration too short 20 2/2612004 0.320 0.314 0.314

-0.00200 106.00

-0.002000 Uses 11/12/2003 dw a 21 4/22/2004 8.360 8.369 8.369 Desired Value Char je 22 7/14/2004 8.360 8.369 8.369 0.00000 83.00 0.000000 23 10/5/2004 8.360 8.370 8.370 0.00100 83.00 0.001108 24 12130/2004 8.360 8.366 8.366

-0.00400 86.00

-0.004279 25 3/24/2005 8.360 8.366 8.366 0.00000 84.00 0.000000 26 6/17/2005 8.360 8.367 8.367 0.00100 85.00 0.001082 1 27 9/7/2o05 8,360 8.368 8.368 0.00100 82.00 0.001122 28 11/28/2005 8.360 8.369 8.369 0.00100 82.00 0.001122 29 2123/2006 8.360 8.368 8.368

-0.00100 87.00

-0.001057 30 4/10/2006 8.360 8.361 8.361 1

46.00 Duration too short 31 5/18/200o 8.360 8.362 8.362 1

-0.00600 84.00

-0.006571 Uses 2/23/2006 dat :

32 6/9/2006 8.360 8.361 8.361

-0.00100 83.00

-0.001108 33 1/25/2007 8.360 8.363 8.363

  • 0.00200 169.00 0.002000 1

Page 39 Fn-stne wCALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

IREVISION.

C-lCE-058.01-008I 4

A B

C D

E I

F I

G H

I I

1

__High Flux Trip - Channel 4 2

Di di D_

3 Re-3 Month 3 Month Corrected 3 calibrated Re-Drift Value Duration Month Drift 4

Date Desired As-Found As-Left Difference calibrated (Voc)

(Days)

Value (VDC)

Comments 5

81311999 8.360 8.351 8.351 6

10126/1999 8.360 8.354 8.354 0.00300 84.00 0.003286 7

1/1820ooo 8.360 8.352 8.352 1

-0.00200 84.00

-0.002190 8

5/8/2000 7.969 7.971 7.971 Desired Value Char le 9

7/6/2000 8.360 8.359 8.359 Desired Value Char ge 10 9/28/2000 8.360 8.359 8,366 0.00700 0.00000 84.00 0.000000 11 12/19/200o 8.360 8.372 8.372 0.00600 82.00 0,006732 12 1/18/2001 8.360 8.375 8.369

-0.00600 X

0.00300 30.00 0.009200 13 3/1312001 8.360 8.370 8.370 0.00100 54.00 0.001704 14 6/6/2001 8.360 8.356 8.356

-0.01400 85.00

-0.015153 15 8/28/2001 8.360 8.359 8.359 0.00300 83.00 0.003325 16 11120/2001 8.360 8.356 8.356

-0,00300 84.00

-0.003286 17 2/13/2002 8.360 8.369 8.369 0.01300 85.00 0.014071 18 7/9/2003 0.320 0.325 0.325 Desired Value Char e 19 11/17/2003 0.320 0.325 0.325 0.00000 131.00 0.000000 20 2/27/2004 0.320 0.325 0.325 0.00000 102.00 0.000000 21 5/25/2004 8.360 8.360 8.360 Desired Value Char e 22 8/26/2004 8.360 8.360 8.360 0.00000 93.00 0.000000 23 11/1912004 8.360 8.355 8.355

-0.00500 85.00

-0.005412 24 2111/2005 8.360 8.356 8.356 0.00100 84.00 0.001095 25 5/4/2005 8.360 8.353 8.353

-0.00300 82.00

-0.003366 26 7/2512005 8.360 8.355 8.355 0.00200 82.00 0.002244 27 10/20/2005 8.360 8.354 8.354

-0.00100 87.00

-0.001057 28 1119/2005 8.360 8.355 8.355 20.00 Duration too short 29 1/9/2006 8.360 8.357 8.357 0.00300 81.00 0.003407 Uses 10/20/2005 d a 30 4/14/2006 8.360 8.361 8.361 0.00400 95.00 0.004000 31 6/28/2006 8.360 8.362 8.362 1

0.00100 75.00 0.001227 1 1

32 12/13/2006 8.360 8.350 8.350 1

-0.01200 168.00

-0.012000 1 1

1

Page 40 Rtstne~yCALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008I 4 - Drift Analysis for Power/Pumps (See Attachment 1 for Methodology)

Compilation of Drift Data - Power/Pumps Channell Channel2 Channel3 Channel4 0.004381 0.000000

-0.002244 0.004381

    • -0.001095

-0.002190

-0.006571

-0.005476 0.000000 0.009000

-0.005000

-0.001095 0.000000

-0.003407 0.008903 0.000000

-0.018098 0.002190 0.000000 0.000000 0.014950 0.001095 0.001095 0.002115

-0.009741

-0.002044 **

-0.002272 **

-0.001150 0.002190 0.001095 **

-0.001122

-0.007576 0.000000 0.004381 0.003209 0.000000

-0.002190 0.001095 **

0.000000

-0.004381 0.007000 0.007576 0.001000 0.000000 0.004000 **

0.003000 0.002190

-0.003286 0.002000 0.002190 **

0.002217 0.003000

-0.002272 0.001000 0.000000 0.000000 0.000000 0.013289

-0.002140

-0.002000

-0.001000 0.002968 0.000000 0.001082 0.001643

-0.003000 0.000000

-0.001095

-0.003172 0.003172 0.002244

-0.002244 0.002244

-0.002272

-0.003366 0.002244 0.000000 0.001095 0.001057 0.000000

-0.004000

-0.002190

-0.012000**

0.004678 0.001057 0.007263

-0.001136 0.002217 0.002000 0.002217

-0.005000

-0.001000

-0.001260

-0.001000 0.006133

-0.020164 0.002000 0.030000

-0.010824 1

0.001095 1

Calculation of Mean and Standard Deviation - Power/Pumps I

Mean Drift (Bias))i 0.0002491 Standard Dev.1 0.0057721 Sample Size 100 K Factor 2.2300 Drift (Random) 0.012871 D

Page 41 FigLhwCALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

/REVISION:

C-ICE-058.01-008I 4

T-Test - PowerlPumps The T-Test determines if a data point is able to be considered an outlier from all other data. This is accomplished by finding the worst case value in either the positive or negative direction, subtracting the mean from that value, taking the absolute value of the results, and dividing the resulting value by the standard deviation. This gives a result of the number of standard deviations the value is away from the mean. If the value is determined to be greater than the "Critical Value", the data point may be considered an outlier and removed from the data if there is a basis for removal. If the data is removed, the T-Test is repeated with revised worst case value, mean, and standard deviation, until the worst case data point is either less than the Critical Value or has no basis forremoval.

Max value from Table =

0.030000 Min value from Table =

-0.020164 Critical value for T-Test with a sample size of 96 and a Upper 5% Significance 3.21 Standard Dev =

0.005772 Mean=

0.000249 T-Test for Max value 0.030000 T-Test for Min value

-0.020164 T-Test =

5.1547 T-Test =

3.5368 Because the T-Test for the Min and Max values are higher than the 3.21 value, they could be considered outliers and excluded from the sample. Due to there being no basis for removal, they will not be excluded.

No further tests for outliers are required.

Page 42

.Rrst~ne yCALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-1CE-058.01-008 "I4 Normalcy Test - Power/Pumps Using the Chi-squared test for normalcy results in:

44.99 based on groupings of bins below.

As there are 8 bins, a normal distributed data set would be below 8. Since it is above 8, the data is determined to be NOT normally distributed. Graphing the data results in a display of data that has a high kurtosis (middle peak) and 3 data values outside of 3 standard deviations. To graphically display the data, a series is established starting at the Mean and moving away from the Mean by the Standard Deviation.

The number of data sets in each series are determined to be able to plot a normalcy graph. The following table displays the series boundaries and the number of data sets in each series and compares that to the normal distribution value. Due to the high kurtosis and the 3 values that are more than 3 standard deviations away from the mean, the data will be considered to be NOT normally distributed and will be included as a bias in the calculation.

Actual Dist Normal Dist Chi-Squared Data Sets between 0.034879 and 0.017564 1

0.15 4.82 Data Sets between 0.017564 and 0.011792 2

2.13 0.01 Data Sets between 0.011792 and 0.006020 6

13.59 4.24 Data Sets between 0.006020 and 0.000249 36 34.13 0.10 Data Sets between 0.000249 and

-0.005523 48 34.13 5.64 Data Sets between

-0.005523 and

-0.011295 4

13.59 6.77 Data Sets between

-0.011295 and

-0.017066 1

2.13 0.60 Data Sets between

-0.017066 and

-0.034381 2

0.15 22.82 44.99 Determination of Normalcy 60 C.2 50 940 30 G Actual data U)30

___dt N Normal data

.E 20 10 I--

1 2

3 4

5 6

7 8

Actual data versus normal distribution

Page 43 Rrst~neCALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008I 4

Time Dependency Analysis - Power/Pumps Time dependency analysis is used to determine if there is a correlation between the period between calibrations, and the resulting change in setpoint. Each data point has been calculated along with the associated time duration between calibrations. Each of the data points used have been included in the plot below. As can be seen from the plot, there are no discernable indications that the drift is in any one direction based on a given time period. For example, if there were a significant number of data points in the positive region from the period of 100 - 150 days with no corresponding data, points in the negative region, this would indicate a time dependency with respect to the drift. Since this, nor any other similar correlation is evident, it is concluded there is no time dependency to the drift.

Time Dependency Analysis Normalized Data 0.04

._ 0.03 CL 0.02 -":

0.01

  1. Series1 I 0.0 eies

-0.01 1

co -0.02

-0.03 L Days

Page 44 Rrst~nert:*yCALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008I 4

A B

C I

D E

F G

H I

I 1

Power/Pumps Trip - Channel 1 2

Di di D.

3 Re-3 Month 3 Month Corrected 3 calibrated Re-Drift Value Duration Month Drift 4

Date Desired As-Found As-Left Difference calibrated (VDC)

(Days)

Value (VDC)

Comments 5

10/5/1999 4.360 4.353 4.353 6

12/28/1999 4.360 4.357 4.357 0.00400 84 0.004381 7

1/2o/20oo 4.360 4.354 4.354 23 Duration too short 8

3/21/2000 4.360 4.352 4.352

-0.00500 84

-0.005476 Uses 12/28/1999 da A 9

6/13/2000 4.360 4.351 4.351

-0.00100 84

-0.001095 10 9/8/2000 4.360 4.351 4.351 0.00000 87 0.000000 11 11/2/000 4.360 4.351 4.351 0.00000

81.

0.000000 12 2/23/2001 4.360 4.353 4.353 0.00200 87 0.002115 13 5/15/2001 4.360 4.351 4.351

-0.00200 81

-0.002272 14 8r7/2001 4.360 4.352 4.352 1

0.00100

.84 0.001095 15 10o30/2001 4,360 4.352 4.352 0.00000 84 0.000000 16 1/22/2002 4.360 4.350 4.350

-0.00200 84

-0.002190 17 6/27/2003 4.360 4.348 4.348 521 Extended Outage 18 11/11/2003 4.360 4.349 4.347

-0.00200 0.00100 137 0.001000 19 2/20/2004 4.360 4.350 4.350 0.00300 101 0.003000 20 5114/2004 4.360 4.352 4.352 0.00200 84 0.002190 21 813/2004 4.360 4.350 4.350 1

-0.00200 81

-0.002272 22 10126/2004 4.360 4.350 4.350 0.00000 84 0.000000 23 2/15/2oo5 4.360 4.349 4.349

-0.00100 112

-0.001000 24 4/12/2005 4.360 4.350 4.350 0.00100 56 0.001643 25 7/8/2005 4.360 4.347 4.347

-0.00300 87

-0.003172 26 9128/2005 4.360 4.349 4.349 0.00200 82 0.002244 1 27 12/21/2005 4.360 4.349 4.349 0.00000 84 0.000000 28 4/9/2006 4.360 4.345 4.345 1

1

-0.00400 109

-0.004000 29 6/7r200o 4.360 4.348 4.348 0.00300 59 0.004678 301 8/29/2006 4.360 4.350 4.350

_0.00200 83 0.002217 311 11/29/2006 4.360 4.349 4.349

-0.00100 92

-0.001000

Page 45 EwsttF_

CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008I 4

A B

C D

E F

I G

H I

1 PowerlPumps Trip - Channel 2 2

Di di Di 3

Re-3 Month 3 Month Corrected 3 calibrated Re-Drift Value Duration Month Drift 4

Date Desired As-Found As-Left Difference calibrated (Voc)

(Days)

Value (VDC)

Comments 5

6/lO/1999 4,360 4.367 4.367 6

8/2411999 4,360 4.367 4.367 0.00000 75.00 0.000000 7

'1/16/1999 4,360 4.366 4.366

-0.00100 84.00

-0.001095 1 8

2/8/2000 4,360 4.366 4.366 0.00000 84.00 0.000000 9

3/5/2000 4,360 4.366 4.366 0.00000 26.00 0.000000 10 5/5/2000 4,360 4.354 4.358 0.00400 X

-0.01200 61.00

-0.018098 11 7/2412000 4,360 4.371 4.365

-0.00600 X

0.01300 80.00 0.014950 12 10/17/2000 4,360 4.356 4.365 0.00900 X

-0.00900 85.00

-0.009741 13 11/3/2000 4,360 4.366 4.366 17.00 Duration too short 14 11/15/2000 4,360 4.368 4.368 12.00 Duration too short 15 1/9/2OOl 4,360 4.369 4.364

-0.00500 X

0.00400 84.00 0.004381 Uses 10/17/2000 d a 16 4/3/2001 4,360 4.365 4.365 0.00100 84.00 0.001095 17 6/26/2001 4,360 4.361 4.361

-0.00400 84.00

-0.004381 18 9/18/2001 4,360 4.361 4.361 0.00000 84.00 0.000000 19 12/11/2001 4,360 4.363 4.363 0.00200 84.00 0.002190 20 7/2/2003 4,360 4.349 4.362 0.01300 X

568.00 1 Extended Outage 21 11113/2003 4.360 4.363 4.363 0.00100 134.00 0.001000 22 2/11/2004 4.360 4.376 4.359

-0.01700 X

0.01300 90.00 0.013289 23 3/13/2004 4.360 4.360 4.360 0.00100 31.00 0.002968 24 6/22/2004 4,360 4.357 4.357

-0.00300 101.00

-0.003000 25 9/17/2004 4.360 4.360 4.360 0.00300 87.00 0.003172 26 12/7/2004 4.360 4.358 4.358

-0.00200 81.00

-0.002272 27 3/1/2005 4.360 4.359 4.359 0.00100 84.00 0.001095 28 5/24/2005 4,360 4.357 4.357

-0.00200 84.00

-0.002190 29 8/19/2005 4.360 4.358 4.358 0.00100 87.00 0.001057 30 11/19/2005 4.360 4.360 4.360 0.00200 92.00 0.002000 31 1/31/2006 4.360 4.359 4.359

-0.00100 73.00

-0.001260 32 4/14120o6 4.360 4.343 4.343

-0.01600 73.00

-0.020164 33

.7/18/2006 4.360 4.373 4.373 0.03000 95.00 0.030000 34 1O/11/2006 4.360 4.363 4.363

-0.01000 85.00

-0.010824 35 113/2007 4,360 4.364 4.364 0.00100 84.00 0.001095

Page 46

.Rrst9nerW CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

IREVISION:

C-ICE-058,01-008I 4

A B

C D

E F

G H

I I

1 PowerlPumps Trip - Channel 3 2

Di di D.

3 Re-3 Month 3 Month Corrected 3 calibrated Re-Drift Value Duration Month Drift 4

Date Desired As-Found As-Left Difference calibrated (VDc)

(Days)

Value (VDC)

Comments 5

6/24/1999 4.360 4.341 4.341 6

9/14/1999 4.360 4.339 4.339

-0.00200 82.00

-0.002244 7

12/7/1999 4.360 4.337 4.337

-0.00200 84.00

-0.002190 8

5/26/2000 4.360 4.346 4.346 0.00900 171.00 0.009000 9

8/15/2000 4.360 4.343 4.343

-0.00300 81.00

-0.003407 10 11/7/2000 4.360 4.345 4.345 0.00200 84.00 0.002190 11 1/3012001 4.360 4.346 4.346 0.00100 84.00 0.001095 12 4/30/2001 4.360 4.344 4.344

-0.00200 90.00

-0.002044 13 7/19/2001 4.360 4.343 4.343

-0.00100 80.00

-0.001150 14 10/9/2001 4.360 4.342 4.342

-0.00100 82.00

-0.001122 15 1/3/2002 4.360 4.345 4.345 0.00300 86.00 0.003209 16 7/1/2003 4.360 4.341 4.341 544.00 Extended Outage 17 11/19/2003 4.360 4.348 4.348 0.00700 141.00 0.007000 18 2/26/2004 4.360 4.352 4.352 0.00400 99.00 0.004000 19 4/22/2004 4.360 4.350 4.350

-0.00200 56.00

-0.003286 1 20 7/14/20041 4.360 4.352 4.352 0.00200 83.00 0.002217 21 10/5/2004 4.360 4.352 4.352 0.00000 83.00 0.000000 22 12/30/2004 4.360 4.350 4.350

-0.00200

.86.00

-0.002140 23 3/24/2005 4.360 4.350 4.350 0.00000 84.00 0.000000 24 6/17/2005 4.360 4.350 4.350 0.00000 85.00 0.000000 25 917/2005 4.360 4.352 4.352 0.00200 82.00 0.002244 26 11/28/2005 4.360 4.349 4.349

-0.00300 82.00

-0.003366 27 2/23/2006 4.360 4.350 4.350 0.00100 87.00.

0.001057 28 4/10/2006 4.360 4.344 4.344 1

1

-0.00600 46.00

-0.012000 29 5/18/2006 4.360 4.347 4.347 1

___L 0.00300 38.00 0.007263 3

8 9/20061 4.360 1

4.349 4.349 1

0.00200 83.00 0.002217 31 1/25/2007 4.360 4.348 4.3481

-0.00100 169.00

-0.001000

I Page 47 FwstF~erl yCALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

IREVISION:

C-ICE-058.01-008I 4

A B

C D

E F

G H

I I

1 Power/Pumps Trip - Channel 4 2

Di d_

D.

3 Re-3 Month 3 Month Corrected 3 calibrated Re-Drift Value Duration Month Drift 4

Date Desired As-Found As-Left Difference calibrated (Voc)

(Days)

Value (VDC)

Comments-5 813/1999 4.360 4.356 4.356 6

10/26/1999 4.360 4.360 4.360 0.00400 84.00 0.004381 7

1/18/2ooo 4.360 4.354 4.354

-0.00600 84.00

-0.006571 8

5/520ooo 4.360 4.349 4.349

-0.00500 108.00

-0.005000 9

7/6/2oOO 4.360 4.355 4.355 0.00600 62.00 0.008903 10 9/26/2000 4.360 4.355 4.359 0,00400 X

0.00000 82.00 0.000000 11 12/19/2000 4.360 4.360 4.360 0.00100 84.00 0.001095 12 1/18/2001 4.360 4.362 4.362 1" 30.00 Duration too short 13 3/13/2001 4.360 4.362 4.362 1

0.00200 84.00 0.002190 Uses 12/19/2000 da ýa 14 6/6/2001 4.360 4.355 4.355

-0.00700 85.00

-0.007576 15 8/2a/2001 4.360 4.355 4.355 0.00000 83.00 0.000000 16 11/20/2001 4.360 4.355 4.355 0.00000 84.00 0.000000 17 2/13/2002 4.360 4.362 4.362 0.00700 85.00 0.007576 18 717/2003 4.360 4.352 4.356 0.00400 X

509.00 Extended Outage 19 1111712003 4.360 4.358 4.358 0.00200 133.00 0.002000 20 2/27/2004 4.360 4.361 4.353

-0.00800 1 0.00300 102.00 0.003000 1 21 5/25/2004 4.360 4.353 4.353 0.00000 88.00 0.000000 22 8/26/2004 4.360 4.351 4.351

-0.00200 93.00

-0.002000 23 11/19/2004 4.360 4.352 4.352 0.00100 85.00 0.001082 24 2/11/2005 4.360 4.351 4.351

-0.00100 84.00

-0.001095 25 5/4/2005 4.360 4.349 4.349

-0.00200 82.00

-0.002244 26 7/25/2005 4.360 4.351 4.351 0.00200 82.00 0.002244 27 10/20/2005 4.360 4.351 4.351 1

0.00000 87.00 0.000000 1 28 11/9/2005 4.360 4.351 4.351 1

20.00 Duration too short 29 1/9/2006 4.360 4.350 4.350

-0.00100 81.00

-0.001136 Uses 10/20/2005 d :a 30 4/14/2006 4.360 4.345 4.345

-0.00500 95.00

-0.005000 31 6/28/2006 4.360 4.350 4.350 0.00500 75.00 0.006133 32 12/13/2006 4.360 4.352 4.352 0.002001 168.00 0.002000

Page 48

  • rst~ner~jyCALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-lCE-058.01-008 4 - Drift Analysis for Power I Imbalance I Flow (See Attachment 1 for Methodology)

Compilation of Drift Data - P/I/F Channel 1

-0.001095 0.003286

-0.001095 0.001095 0.000000

-0.001095 0.004381 0.004381 0.000000 0.000000 0.007667 0.003286

-0.005476

-0.004381 0.001095

-0.001095

-0.009857

-0.004381 N/A N/A 0.001095 0.002190 0.001095 0.002190 0.000000

-0.001057

-0.001057 0.000000 0.001057 0.001057 0.002272 0.002272

-0.001136

-0.001136

-0.002272

-0.004543 0.002115 0.001057 0.000000

-0.001057

-0.001057 0.001057

-0.006815

-0.005679 0.002272 0.002272 0.000000

-0.001136

-0.002190

-0.002190' 0.001095 0.001095 0.003286 0.003286 0.002190 0.003286

-0.003286

-0.003286

-0.003286

-0.002190 0.006571 0.004381 0.000000 0.000000 0.000000

-0.001095 rN/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

-0.005000

-0.005000 0.006000 0.001000 0.000000 0.001000 N/A N/A N/A N/A N/A N/A

-0.003407

-0.002272

-0.002272 0.004543 0.000000 0.000000

-0.003286

-0.006571 0.002190 0.005476 0.004381 0.005476 0.004000 0.008000

-0.002000

-0.002000

-0.002000

-0.001000

-0.001643 0.000000 0.001643

-0.001643

-0.001643

-0.003286

_-0.006345

-0.006345 0.000000 0.001057

-0.001057

-0.001057 0.000000 0.001122 0.000000 0.000000

-0.001122 0.000000 0.007667 0.005476

-0.001095 0.000000 0.002190 0.002190 0.000000 0.000000

-0.001000

-0.002000

-0.003000

-0.004000 N/A N/A

-0.004678

-0.004678

-0.009356

-0.009356 1 -0.003325

-0.001108

-0.002217

-0.002217

-0.003325

-0.004434 0.002000 0.000000 0.001000 0.001000 0.003000 0.004000

Page 49 CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008 4

Channel 2

-0.006133

-0.002453 0.006133 0.001227 0.001227 0.003680 0.014238 0.000000

-0.003286

-0.001095

-0.002190

-0.002190

-0.007667 0.004381

-0.001095 0.001095 0.003286 0.002190 N/A N/A N/A N/A N/A N/A 0.003172 0.001057 0.001057

-0.001057 0.000000 0.000000 N/A N/A 0.001150 0.002300

-0.001150

-0.001150 0.001082

-0.001082 0.000000

-0.001082 0.000000 0.001082 N/A N/A N/A N/A N/A N/A 0.003286 0.003286 0.007667 0.009857 0.013143 0.013143

-0.005476

-0.003286 0.000000 0.002190 0.000000

-0.001095 0.001095 0.000000

-0.001095

-0.007667

-0.008762

-0.008762 0.000000 0.001095

-0.001095 0.002190

-0.002190

-0.001095

-0.001095 0.000000 0.001095 0.002190 0.001095 0.000000 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

-0.007077 0.001011 0.002022 0.000000 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

-0.001095 0.000000 0.000000 0.000000 0.001070 0.000000 0.004279 0.001070 0.000000 0.001070 0.000000

-0.002244

-0.001122 0.000000

-0.001122

-0.001122 0.002190 0.002190

-0.003286

-0.002190 0.000000 0.000000 0.002190 N/A

-0.001095 0.001095 0.000000

-0.001095

-0.006345

-0.005287 0.003172 0.002115 0.000000 0.001057 0.004000 0.002000

-0.001000

-0.001000 0.000000 0.001000 0.000000 0.001260

-0.001260 0.003781 0.001260 0.000000 0.001260 0.001260

-0.002521

-0.001260

-0.003781 0.000000 N/A N/A

-0.001000

-0.001000 0.002000 0.000000

-0.001082

-0.002165 0.004329

-0.008659 0.000000

-0.001082

-0.001095

-0.002190

-0.002190 0.007667

-0.001095 0.001095

Page 50 CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008 4

Channel 3 0.001122 0.001122 0.001122 0.000000 0.000000 0.001122

-0.001095

-0.002190

-0.001095

-0.001095 0.000000

-0.001095 0.001095 0.002190 0.000000 0.001095 0.000000 0.000000 N/A N/A 0.002115 0.002115 0.001057 0.001057

-0.001136

-0.013630

-0.002272

-0.005679

-0.002272

-0.004543 0.000000 0.001095 0.005476 0.005476

-0.001095 0.003286 0.002190 0.000000

-0.003286

-0.001095 0.002190 0.000000

-0.003286

-0.002190 0.001095 0.000000 0.000000 0.000000 0.001070 0.002140

-0.001070 0.001070 0.000000 0.000000

-0.001122

-0.002244 0,000000

-0.001122

-0.001122 0.000000 0.002140

-0.004279 0.000000 0.001070 0.000000 0.000000 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

-0.003000 0.000000 0.000000 0.000000 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

_-0.011084

-0.007759 0.001108 0.000000 0.000000 0.000000 0.004434 0.002217 0.000000 0.000000 0.000000 0.000000

-0.001070

-0.002140 0.000000 0.001070 0.000000

-0.001070 0.000000 0.001095 0.000000. -0.001095

-0.001095 0.001095

-0.003247

-0.001082 0.000000

-0.001082 0.001082

-0.001082 0.001122 0.000000 0.000000 0.001122 0.000000 0.001122 0.002244 0.001122 0.001122 0.001122 0.000000 0.000000 0.001057 0.000000

-0.002115

-0.001057

-0.001057

-0.001057

-0.004000 0.002000 0.002000 0.000000 0.000000 0.000000 N/A N/A N/A N/A N/A N/A 0.001108 0.002217 0.000000

-0.001108 0.000000 0.00000o N/A IN/A N/A N/A N/A N/A

Page 51

.5rt~n~e CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008 14 Channel 4 Channel 4 (10043811 0.0032861

-0.0032861 0.0000001

-0.0010951 0.001095 0.009857 0.003286 0.001095 0.000000

-0.001095 0.002190

-0.001000 0.003000

-0.011000

-0.005000 0.002000

-0.003000 N/A N/A 0.017806 0.001484 0.001484 0.000000 0.001122 0.002244

-0.001122 0.001122 0.001122

-0.002244

-0.004381

-0.002190 0.001095 0.002190

-0.005476 0.000000 N/A N/A N/A N/A N/A N/A

-0.026286

-0.020810 0.010952 0.003286 0.001095 0.000000 0.012988 0.008659

-0.005412

-0.003247 0.003247

-0.001082

-0.005542

-0.004434 0.000000 0.005542 0.002217 0.001108

-0.005476

-0.003286 0.002190

-0.002190

-0.004381

-0.001095

-0.005412

-0.001082 0.002165 0.000000

-0.001082 0.000000 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

-0.001000

-0.002000

-0.001000 0.001000 N/A N/A N/A N/A N/A N/A N/A N/A 0.016727 0.001673

-0.001673

-0.003345 0.009000 0.008000

-0.013000

-0.002000 0.001000

-0.001000

-0.015153

-0.012988 0.006494 0.003247

-0.001082 0.002165 0.016429 0.014238

-0.005476

-0.002190

-0.001095 0.000000

-0.004488

-0.005610 0.002244 0.001122 0.006732 0.001122

-0.003366

-0.001122

-0.002244

-0.001122

-0.006732 0.002244

-0.002115

-0.003172 0.001057

-0.001057 0.000000

-0.006345 N/A N/A N/A N/A N/A N/A 0.005679 0.004543

-0.002272 0.001136 0.000000 0.001136 0.003000 0.003000 0.001000

-0.001000 0.000000 0.000000 N/A N/A 0.002453 0.002453 0.000000

-0.001227 N/A N/A N/A N/A N/A N/A

Page 52 Bts-ý,

CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008 4

Calculation of Mean and Standard Deviation - P/I/F I

Mean (Drift (Bias))l

-0.000094 Standard Dev.1 0.0039981 Sample Size 521 K Factor 2.0679 Drift (Random) 0.008268 T-Test - P/I/F The T-Test determines if a data point is able to be considered an outlier from all other data. This is accomplished by finding the worst case value in either the positive or negative direction, subtracting the mean from that value, taking the absolute value of the results, and dividing the resulting value by the standard deviation. This gives a result of the number of standard deviations the value is away from the mean. If the value is determined to be greater than the "Critical Value", the data point may be considered an outlier and removed from the data if there is a basis for removal. If the data is removed, the T-Test is repeated with revised worst case value, mean, and standard deviation, until the worst case data point is either less than the Critical Value or has no basis for removal.

Max value from Table =

0.017806 Min value from Table =

-0.026286 Critical value for T-Test with a sample size of 521 and a Upper 5% Significance 3.33 Standard Dev =

0.003998 Mean=

-0.000094 T-Test for Max value 0.017806 T-Test for Min value

-0.026286 T-Test =

4.4771 T-Test =

6.5507 Because th e T-Test for both the Max and Min values are higher than the 3.33 value, they could be considered outliers and excluded from the sample. Due to there being no basis for removal, they will not be excluded. No further tests for outliers are required.

Page 53 CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008 4

Normalcy Test - P/I/F Using the Chi-squared test for normalcy results in:

178.29 based on groupings of bins below.

As there are 8 bins, a normal distributed data set would be below 8. Since it is above 8, the data is determined to be NOT normally distributed. Graphing the data results in a display of data that has a high kurtosis (middle peak) and 13 data values outside of 3 standard deviations. To graphically display the data, a series is established starting at the Mean and moving away from the Mean by the Standard Deviation. The number of data sets in each series are determined to be able to plot a normalcy graph.

The following table displays the series boundaries and the number of data sets in each series and compares that to thenormal distribution value. Due to the high kurtosis and the 13 values that are more than 3 standard deviations away from the mean, the data will be considered to be NOT normally distributed and will be included as a bias in the calculation.

Actual Dist Normal Dist Chi-Squared Data Sets between 0.023896 and 0.011901 8

0.78 66.68 Data Sets between 0.011901 and 0.007902 7

11.10 1.51 Data Sets between 0.007902 and 0.003904 30 70.80 23.52 Data Sets between 0.003904 and

-0.000094 268 177.82 45.74 Data Sets between

-0.000094 and

-0.004093 155 177.82 2.93 Data Sets tOetween

-0.004093 and

-0.008091 39 70.80 14.29 Data Sets between

-0.008091 and

-0.012089 8

11.10 0.86 Data Sets between

-0.012089 and

-0.024084 5

0.78 22.77 178.29 Determination of Normalcy 300 C.2 250 I2Actual 1 Normal 100 1

2 3

4 5

6 7

8 Actual data versus normal distribution

Page 54 ft CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01.008I 4

Time Dependency Analysis - P/I/F Time dependency analysis is used to determine if there is a correlation between the period between calibrations and the resulting change in setpoint. Each data point has been calculated along with the associated time duration between calibrations. Each of the data points used have been included in the plot below. As can be seen from the plot, there are no discernable indications that the drift is in any one direction based on a given time period. For example, if there were a significant number of data points in the positive region from the period of 100 - 120 days with no corresponding data points in the negative region, this would indicate a time dependency with respect to the drift. Since this, nor any other similar correlation is evident, it is concluded there is no time dependency to the drift.

Time Dependency Analysis Normalized Data 0.03 0.

0.01

0.

,2-

" -0.01 O

-0.02 -

-0.03 -

Days

Page 55 frstne CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-0084 Power I Imbalance I Flow - Channel 1 Data Point Data Point Data Point Channell 1

2 3

Date Desired As-Found As-Left Desired As-Found As-Left Desired As-Found As-Left 7/13/1999 4.193 4.198 4.198 2.796 2.793 2.793 8.678 8.674 8.674 10/511999 4.193 4.197 4.197 2.796 2.796 2.796 8.678 8.673 8.673 12/28/1999 4.193 4.201 4.201 2.796 2.800 2.800 8.678 8.673 8.673 3/21/2000 4.193 4.196 4.196 2.796 2.796 2.796 8.678 8.674 8.674 6/13/2000 4.190 4.190 4.190 2.795 2.793 2.793 8.678 8.675 8.675 9/8/2000 4.190 4.190 4.190 2.795 2.792 2.792 8.678 8.674 8.674 11/28/2000 4.190 4.192 4.192 2.795 2.794 2.794 8.678 8.673 8.673 2/23/2001 4.190 4.194 4.194 2.795 2.795 2.795 8.678 8.673 8.673 5/15/2001 4.190 4.188 4.188 2.795 2.790 2.790 8.678 8.675 8.675 817/2001 4.190 4.186 4.186 2.795 2.788 2.788 8.678 8.676 8.676 10/30/2001 4.190 4.188 4.188 2.795 2.791 2.791 8.678 8.673 8.673 1/22/2002 4.190 4.194 4.194 2.795 2.795 2.795 8.678 8.673 8.673 6/26/2003 4.190 4.201 4.201 2.795 2.805 2.805 8.678 8.678 8.678 11/11/2003 4.190 4.199 4.200 2.795 2.800 2.801 8.678 8.674 8.674 2/20/2004 4.190 4.195 4.195 2.795 2.796 2.796 8.678 8.680 8.680 5/14/2004 4.137 4.138 4.138 2.764 2.766 2.766 8.654 8.654 8.654 8/3/2004 4.137 4.135 4.135 2.764 2.764 2.763 8.654 8.652 8.653 10/26/2004 4.137 4.132 4.132 2.764 2.757 2.757 8.654 8.655 8.655 2/15/2005 4.137 4.136 4.136 2.764 2.765 2.765 8.654 8.653 8.653 4/12/2005 4.137 4.135 4.135 2.764 2.765 2.765 8.654 8.654 8.654 7/8/2005 4.137 4.129 4.129 2.764 2.759 2.759 8.654 8.654 8.654 9/28/2005 4.137 4.129 4.129 2.764 2.760 2.760 8.654 8.654 8.654 12/21/2005 4.137 4.136 4.136 2.764 2.765 2.765 8.654 8.653 8.653 4/9/2006 4.137 4.136 4.136 2.764 2.765 2.763 8.654 8.652 8.655 6/7/2006 4.129 4.131 4.131 2.760 2.761 2.761 8.654 8.652 8.652 8/29/2006 4.129 4.128 4.128 2.760 2.760 2.760 8.654 8.650 8.650 11/29/2006 4.129 4.130 4.130 2.760 2.760 2.760 8.654 8.651 8.651 Bold Denotes change in !"Desired" value from previous test

Page 56 5msaeW yCALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008 4

Data Point Data Point Data Point Channel 1 4

15 6

Date Desired As-Found As-Left Desired As-Found As-Left Desired As-Found As-Left 7/13/1999 8.564 8.561 8.561 5.665 5.664 5.664 5.665 5.669 5.669 10/5/1999 8.564 8.562 8.562 5.665 5.664 5.664 5.665 5.668 5.668 12/28/1999 8.564 8.562 8.562 5.665 5.671 5.671 5.665 5.671 5.671 3/21/2000 8.564 8.561 8.561 5.665 5.662 5.662 5.665 5.667 5.667 6/13/2000 8.564 8.563 8.563 5.665 5.663 5.663 5.665 5.669 5.669 9/8/2oo0 8.564 8.563 8,563 5.665 5.664 5.664 5.665 5.670 5.670 11/28/2000 8.564 8.562 8.562 5.665 5.662 5.662 5.665 5.666 5.666 2/23/2001 8.564 8.561 8.561 5.665 5,661 5.661 5.665 5.667 5.667 5/15/2001 8.564 8.563 8.563 5.665 5.661 5.661 5.665 5.666 5.666 8/7/2001 8.564 8.564 8.564 5.665 5.664 5.664 5.665 5.669 5.669 10/30/2001 8.564 8.561 8.561 5.665 5.661 5.661 5.665 5.667 5.667 1/22/2002 8.564 8.561 8.561 5.665 5.661 5.661 5.665 5.666 5.666 61/26/2003 8.564 8.561 8.561 5.665 5.663 5.663 5.665 5.669 5.669 11/11/2003 8.564 8.561 8.561 5.665 5.662 5.668 5.665 5.667 5.670 21/20/2004 8.564 8.562 8.562 5.665 5.668 5.668 5.665 5.671 5.671 5/14/2004 8.544 8.543 8.543 5.635 5.636 5.636 5.635 5.639 5.639 8/3/2004 8.544 8.547 8.541 5.635 5.636 5.635 5.635 5.639 5.637 1012612004 8.544 8.546 8.546 5.635 5.639 5.639 5.635 5.642 5.642 2/15/2005 8.544 8.544 8.544 5.635 5.637 5.637 5.635 5.641 5.641 4/12/2005 8.544 8.543 8.543 5.635 5.636 5.636 5.635 5.639 5.639 7/8/2005 8.544 8.544 8.544 5.635 5.635 5.635 5.635 5.638 5.638 9/2812005 8.544 8.544 8.544 5.635 5.634 5.634 5.635 5.638 5.638 12/21/2005 8.544 8.544 8.544 5.635 5.636 5.636 5.635 5.640 5.640 4/9/2006 8.544 8.542 8.545 5.635 5.633 5.639 5.635 5.636 5.643 6/7/2006 8.544 8.542 8.542 5.635 5.633 5.633 5.635 5.637 5.637 8/29/2006 8.544 8.540 8.540 5.635 5.630 5.630 5.635 5.633 5.633 11/29/200o6 8.544 8.541 8.541 5.635 5.633 5.633 5.635 5.637 5.637 Bold Denotes change in "Desired" value from previous test

Page 57 frstE~ne 'yCALCULATION COMPUTATION NOPw-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-lCE-058.01-008I 4

Channel 1 Data Point Days Point 1 -

Point 2 -

Point 3 -

Point 4 -

Point 5 -

Point 6 -

Date Between 3 month 3 month 3 month 3 month 3 month 3 month Comments 7/1311999 1015/1999 84

-0.001095 0.003286 -0.001095 0.001095 0.000000 -0.001095 12/28/1999 84 0.004381 0.004381 0.000000 0.000000 0.007667 0.003286 3/21/2000 84

-0.005476 -0.004381 0.001095 -0.001095 -0.009857 -0.004381 6/13/2000 84 N/A N/A 0.001095 0.002190 '0.001095 0.002190 Note 1 918/2000 87 0.000000 -0.001057 -0.001057 0.000000 0.001057 0.001057 11/28/2000 81 0.002272 0.002272 -0.001136 -0.001136 -0.002272 -0.004543 2/23/2001 87 0.002115 0.001057 0.000000 -0.001057 -0.001057 0.001057 5/15/2001 81

-0.006815 -0.005679 0.002272 0.002272 0.000000 -0.001136 8/7/2001 84

-0.002190 -0.002190 0.001095 0.001095 0.003286 0.003286 10/30/2001 84 0.002190 0.003286 -0.003286 -0.003286 -0.003286 -0.002190 1/22/2002 84 0.006571 0.004381 0.000000 0.000000 0.000000 -0.001095 6/26/2003 520 N/A N/A N/A N/A N/A N/A Note 2 11/11/2003 138 N/A N/A N/A N/A N/A N/A Note 2 2120/2004 101

-0.005000 -0.005000 0.006000 0.001000 0.000000 0.001000 5/14/2004 84 N/A N/A N/A,

N/A N/A N/A Note 1 8/312004 81

-0.003407 -0.002272 -0.002272 0.004543 0.000000 0.000000 10/26/2004 84

-0.003286 -0.006571 0.002190 0.005476.0.004381 0.005476 2/15/2005 112 0.004000 0.008000 -0.002000 -0.002000 -0.002000 -0.001000 4/12/2005 56

-0.001643 0.000000 0.001643 -0.001643 -0.001643 -0.003286 7/8/2005 87

-0.006345 -0.006345 0.000000 0.001057 -0.001057 -0.001057 9/28/2005 82 0.000000 0.001122 0.000000 0.000000 -0.001122 0.000000 12/21/2005 84 0.007667 0.005476 -0.001095 0.000000 0.002190 0.002190 4/9/2006 109 0.000000 0.000000 -0.001000 -0.002000 -0.003000 -0.004000 6/7/2006 59 N/A N/A

-0.004678 -0.004678 -0.009356 -0.009356 Note 1 8/29/2006 83

-0.003325 -0.001108 -0.002217 -0.002217 -0.003325 -0.004434 11/29/2006 92 0.002000 0.000000 0.001000 0.001000 0.003000 0.004000 Note 1:

Any surveillances immediately following a change in desired values are not considered.

Note 2:

Periods over 115 days (92

  • 1.25 TS Extension Allowance) or less than 46 days (92/2) are not considered since they could skew the calculated drift data.

-N

Page 58

=F EnerCALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008 4

Power / Imbalance I Flow - Channel 2 Data Point Data Point Data Point Channel 2 1

2 3

Date Desired As-Found As-Left Desired As-Found As-Left Desired As-Found As-Left 6/10/1999 4.186 4.185 4.185 2.792 2.793 2.793 8.674 8.671 8.671 8/24/1999 4.186 4.180 4.180 2.792 2.791 2.791 8.674 8.676 8.676 11/16/1999 4.186 4.193 4.193 2.792 2.791 2.791 8.674 8.673 8.673 2/8/2000 4.186 4.186 4.186 2.792 2.795 2.795 8.674 8.672 8.672 3/6/2000 4.186 4.186 4.186 2.792 2.792 2.792 8.674 8.671 8.671 5/5/2000 4.186 4.189 4.182 2.792 2.796 2.791 8.674 8.673 8.671 7/24/2000 4.155 4.151 4.151 2.775 2.774 2.774 8.674 8.672 8.672 10/17/2000 4.155 4.152 4.152 2.775 2.773 2.773 8.674 8.672 8.672 11/3/2000 4.155 4.151 4.154 2.775 2.773 2.776 8.674 8.674 8.676 11912001 4.155 4.155 4.161 2.775 2.776 2.779 8.674 8.679 8.674 4/3/2001 4.155 4.156 4.156 2.775 2.776 2.776 8.674 8.674 8.674 6/26/2001 4.155 4.157 4.157 2.775 2.776 2.776 8.674 8.673 8.673 9/18/2001 4.155 4.157 4.157 2.775 2:777 2.777 8.674 8.672 8.676 12/11/2001 4.155 4.156 4.156 2.775 2.777 2.777 8.674 8.677 8.677 7/2/2003 4.155 4:153 4.157 2.775 2.773 2.777 8.674 8.677 8.675 11/13/2003 4.155 4.164 4.164 2.775 2.781 2.781 8.674 8.679 8.679 2/12/2004 4.239 4.251 4.251 2.822 2.831 2.831 8.674 8.672 8.672 3/13/2004 4.239 4.249 4.249 2.822 2.830 2.830 8.674 8.674 8.674 3/3012004 4.239 4.245 4.245 2.822 2.826 2.826 8.633 8.634 8.634 6/22/2004 4.139 4.140 4.140 2.765 2.770 2.770 8.633 8.633 8.633 9/16/2004 4.139 4.141 4.141 2.765 2.770 2.770 8.633 8.637 8.637 12/7/2004 4.139 4.141 4.141 2.765 2.768 2.768 8.633 8.636 8,636 3/1/2005 4.139 4.143 4.143 2.765 2.770 2.770 8.633 8.633 8.633 5/24/2005 4.139 4.145 4.145 2.763 2.773 2.773 8.633 8.632 8.632 8/19/2005 4.139 4.139 4.139 2.763 2.768 2.768 8.633 8.635 8.635 11/19/2005 4.139 4.143 4.143 2.763 2.770 2.770 8.633 8.634 8.634 1/31/2006 4.139 4.143 4.143 2.763 2.771 2.771 8.633 8.633 8.633 4/14/2006 4.139 4.144 4.144 2.763 2.772 2.772 8.633 8.631 8.631 7/18/2006 4.106 4.112 4.112 2.747 2.754 2.754 8.633 8.630 8.630 10/11/2006 4.106 4.111 4.111 2.747 2.752 2.752 8.633 8.634 8.634 1/3/2007 4.106 4.110 4.110 2.747 2.750 2.750 8.633 8.632 8.632 Bold Denotes change in "Desired" value from previous test

Data Point Data Point Data Point Channel2 4

5 6

Date Desired As-Found As-Left Desired As-Found As-Left Desired As-Found As-Left 6/10/1999 8.561 8.556 8.556 5.660 5.653 5.653 5.660 5.653 5.653 8/24/1999 8.561 8.557 8.557 5.660 5.654 5.654 5.660 5.656 5.656 11/16/19991 8.561 8.556 8.556 5.660 5.652 5.652 5.660 5.654 5.654 2/8/2000 8.561 8.557 8.557 5.660 5.655 5.655 5.660 5.656 5.656 3/6/2000 8.561 8.555 8.555 5.660 5.653 5.653 5.660 5.654 5.654 5/5/2000 8.561 8.556 8.555 5.660 5.655 5.654 5.660 5.656 5.655 7/24/2000 8.561 8.557 8.557 5.660 5.653 5.653 5.660 5.654 5.6541 10/17/2000 8.561 8.556 8.556 5.6601 5.653 5.653 5.660 5.655 5.655 11/3/20001 8.561 8.556 8.561 5.6601 5.653 5.661 5.660 5.654 5.662 1/9/2001 8.561 8.565 8.560 5.6601 5.665 5.660 5.660 5.667 5.661 4/3/2001 8.561 8.562 8.562 5.660 5.660 5.660 5.660 5.660 5.660 6/26/2001 8.561 8.555 8.555 5.660 5.652 5.652 5.660 5.652 5.652 9/18/2001 8.561 8.557 8.560 5.660 5.650 5.662 5.660 5.651 5.6621 12/11/2001 8.561 8.562 8.562 5.660 5.663 5.663 5.660 5.662 5.6621 7/2/20031 8.561 8.561 8.559 5.660 5.661 5.660 5.660 5.659 5.658 11/13/2003 8.561 8.557 8.557 5.6601 5.661 5.661 5.660 5.660 5.660 2/12/2004 8.561 8.558 8.558 5.660 5.663 5.663 5.660 5.660 5.660 3/13/2004 8.561 8.560 8.560 5.660 5.662 5.662 5.660 5.661 5.661 3/30/2004 8.527 8.525 8.525 5.608 5.610 5.610 5.608 5.608 5.608 6/22/2004 8.527 8.525 8.525 5.608 5.610

-5.610 5.608 5.608 5.608 9/16/2004 8.527 8.526 8,526 5.608 5.610 5.610 5.608 5.609 5.609 12/7/2004 8.527 8.526 8.526 5.6081 5.609 5.609 5.608 5.608 5.608 3/1/2005 8.527 8.524 8.524 5.6081 5.609 5.609 5.608 5.608 5.608 5/24/2005 8.527 8.525 8.525 5.6081 5.609 5.609 5.608 5.607 5.607 8/19/2005 8.527 8.527 8.527 5.608 5.609 5.609 5.608 5.608 5.6081 11/19/20051 8.527

8. 526 8.526 5.608 5.609 5.609 5.608 5.609 5.609 1/31/2006 8.527 8.529 8.529 5.608 5.610 5.610

.5.608 5.609 5.609 4/14/2006 8.527 8.528 8.528 5.608 5.607:

5.607 5.608 5.609 5.609 7/18/2006 8.527 8.52L7 M8.527 5.608 5.609 5.609 5.608 5.609 5.609 10/11/2006 8.527 8.519 8.51 5.6081 5.6091 5.6091 5.608 5.608 5.608' 1/3/2007 8.5271 852 8.526 5.6081 5.6081 5.6081 5.608+

5.6091 5.609 Bold Denotes change in "Desired" value from previous test

Page 60 Rrst~neCALCULATION' COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008J 4

Channel 2 Data Point Days Point 1 -

Point 2 -

Point 3 -

Point 4 -

Point 5 -

Point6 -

Date Between 3 month 3 month 3 month 3 month 3 month 3 month Comments 6/10/1999 8/24/1999 75

-0.006133 -0.002453 0.006133 0.001227 0.001227 0.003680 11/16/1999 84 0.014238 0.000000 -0.003286 -0.001095 -0.002190 -0.002190 2/8/2000 84

-0.007667 0.004381 -0.001095.0.001095 0.003286 0.002190 3/6/2000 27 N/A N/A N/A N/A N/A N/A Note 2 5/5/2000 87 0.003172 0.001057 0.001057 -0.001057 0.000000 0.000000 Note 3 7/24/2000 80 N/A N/A 0.001150 0.002300 -0.001150 -0.001150 Note 1 10/17/2000 85 0.001082 -0.001082 0.000000 -0.00-1082 0.000000 0.001082 11/3/2000 17 N/A N/A N/A N/A N/A N/A Note 2 1/9/2001 84 0.003286 0.003286 0.007667 0.009857 0.013143 0.013143 Note 4 4/3/2001 84

-0.005476 -0.003286 0.000000 0.002190 0.000000 -0.001095 6/26/2001 84 0.001095 0.000000 -0.001095 -0.007667 -0.008762 -0.008762 9/18/2001 84 0.000000 0.001095 -0.001095 0.002190 -0.002190 -0.001095 12/11/2001 84

-0.001095 0.000000 0.001095 0.0021.90 0.001095 0.000000 7/2/2003 568 N/A N/A N/A N/A N/A N/A Note 2 11/13/2003 134 N/A N/A N/A N/A N/A N/A Note 2 2/12/2004 91 N/A N/A

-0.007077 0.001011 0.002022 0.000000 Note 1 3/13/2004 30 N/A N/A N/A N/A N/A N/A Note 2 3/30/2004 17 N/A N/A N/A N/A N/A N/A Notes 1&2 6/22/2004 84 N/A N/A

-0.001095 0.000000 0.000000 0.000000 Note 1 9/16/2004 86 0.001070 0.000000 0.004279 0.001070 0.000000 0.001070 12f7/2004 82 0.000000 -0.002244 -0.001122 0.000000 -0.001122 -0.001122 3/1/2005 84 0.002190 0.002190 -0.003286 -0.002190 0.000000 0.000000 5/24/2005 84 0.002190 N/A

-0.001095 0.001095 0.000000 -0.001095 Note 1 8/19/2005 87

-0.006345 -0.005287 0.003172 0.002115 0.000000 0.001057 11/19/2005 92 0.004000 0.002000 -0.001000 -0.001000 0.000000 0.001000 1/31/2006 73 0.000000 0.001260 -0.001260 0.003781 0.001260 0.000000 4/14/2006 73 0.001260 0.001260 -0.002521 -0.001260 -0.003781 0.000000 7/18/2006

. 95 N/A N/A

-0.001000 -0.001000 0.002000 0.000000 Note 1 10/11/2006 85

-0.001082 -0.002165 0.004329 -0.008659 0.0000001-0.001082 1/3/2007 84

-0.001095 -0.002190 -0.002190 0.007667-0.001095 0.001095 Note 1:

Any surveillances immediately following a change in desired values are not considered.

Note 2:

Periods over 115 days (92

  • 1.25 TS Extension Allowance) or less than 46 days (92/2) are not considered since they could skew the calculated drift data.

Note 3:

Uses data from 2/8/2000 Note 4:

Uses data from 10/17/2000

Page 61 SrstEne y CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058,01-008 4

Power / Imbalance I Flow - Channel 3 Data Point Data Point Data Point Channel 3 1

2 3

Date Desired As-Found As-Left Desired As-Found As-Left Desired As-Found As-Left 6/24/1999 4.172 4.159 4.159 2.784 2.781 2.781 8.671 8.674 8.674 9/1411999 4.172 4.160 4.160 2.784 2.782 2.782 8.671 8.675 8.675 12/7/1999 4.172 4.159 4.159 2.784 2.780 2.780 8.671 8.674 8.674 2/29/2000 4.172 4.160 4.156 2.784 2.782 2.780 8.671 8.674 8.676 5/26/2000 4.151 4.130 4.130 2.772 2.776 2.776 8.671 8.678 8.678 8/15/2000 4.151 4.129 4.129 2.772 2.764 2.764 8.671 8.676 8.676 11/712000 4.151 4.129 4.129 2.772 2.765 2.765 8.671 8.681 8.681 1/30/2001 4.151 4.131 4.131 2.772 2.765 2.765 8.671 8.678 8.678 4/24/2001 4.151 4.128 4.128 2.772 2.763 2.763 8.671 8.679 8.679 7/19/2001 4.151 4.129 4.129 2.772 2.765 2.765 8.671 8.678 8.678 1019/2001 4.151 4.128 4.128 2.772 2.763 2.763 8.671 8.678 8.678 1/3/2002 4.151 4.130 4.130 2.772 2.759 2.759 8.671 8.678 8.678 7/4/2003 4.151 4.131 4.131 2.772 2.766 2.766 8.671 8.679 8.679 11/19/2003 4.151 4.130 4.128 2.772 2.764 2.765 8.671 8.677 8.678 2/26/2004 4.230 4.215 4.215 2.817

-2.815 2.815 8.671 8.675 8.675 3/30/2004 4.230 4.215 4.215 2.817 2.815 2.815 8.639 8.643 8.643 4/22/2004 4.143 4.126 4.126 2.768 2.763 2.763 8.639 8.644 8.644 7/14/2004 4.143 4.116 4.116 2.768 2.756 2.756 8.639 8.645 8.645 10/5/2004 4.143 4.120 4.120 2.768 2.758 2.758 8.639 8.645 8.645 12/30/2004 4.143 4.119 4.119 2.768 2.756 2.756 8.639 8.645 8.645 3/24/2005 4.143 4.119 4.119 2.768 2.757 2.757 8.639 8.645 8.645 6/17/2005 4.143 4.116 4.116 2.768 2.756 2.756 8.639 8.645 8.645 9/7/2005 4.143 4.117 4.117 2.768 2.756 2.756 8.639 8.645 8.645 11/28/2005 4.143 4.119 4.119 2.768 2.757 2,757 8.639 8.646 8.646 2/23/2006 4.143 4.120 4.120 2.768 2.757 2.757 8.639 8.644 8.644 4/10/2006 4.143 4.118 4.118 2.768 2.758 2.758 8.639 8.645 8.645 5/18/2006 4.133 4.108 4.108 2.762 2.751 2.751 8.639 8.645 8.645 8/9/2006 4.133 4.109 4.109 2.762 2.753 2.753 8.639 8.645 8.645 1/25/2007 4.133 4.109 4.109 2.762 2.750 2.750 8.639 8.644 8.644 Bold Denotes change in "Desired" value from previous test

Page 62 CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008 4

Data Point Data Point Data Point Channel 3 4

5 6

Date Desired As-Found As-Left Desired As-Found As-Left Desired As-Found As-Left 6/24/1999 8.558 8.558 8.558 5.656 5.656 5.656 5.656 5.655 5.655 9/14/1999 8.558 8.558 8.558 5.656 5.656 5.656 5.656 5.656 5.656 12/7/1999 8.558 8.557 8.557 5.656 5.656 5.656 5.656 5.655 5.655 2/29/2000 8.558 8.558 8.558 5.656 5.656 5.656 5.656 5.655 5.655 5/26/2000 8.558 8.560 8.560 5.656 5.657 5.657 5.656 5.656 5.656 8/15/2000 8.558 8.555 8.555 5.656 5.655 5.655 5.656 5.652 5.652 11/7/2000 8.558 8.560 8.560 5.656 5.654 5.654 5.656 5.655 5.655 1/30/2001 8.558 8.559 8.559 5.656 5.656 5.656 5.656 5.655 5.655 4/24/2001 8.558 8.559 8.559 5.656 5.656 5.656 5.656 5.655 5.655 7/19/2001 8.558 8.560 8.560 5.656 5.656 5.656 5.656 5.655 5.655 10/9/2001 8.558 8.559 8.559 5.656 5.655 5.655 5.656 5.655 5.655 1/3/2002 8.558 8.560 8.560 5.656 5.655 5.655 5.656 5.655 5.655 7/4/2003 8.558 8.560 8.560 5.656 5.656 5.656 5.656 5.655 5.655 11/19/2003 8.558 8.558 8.559 5.656 5.656 5.657 5.656 5.655 5.657 2/26/2004 8.558 8.559 8.559 5.656 5.657 5.657 5.656 5.657 5.657 3/3012004 8.531 8.532 8.532 5.614 5.615 5.615 5.614 5.615 5.615 4/22/2004 8.531 8.533 8.533 5.614 5.615 5.615 5.614 5.615 5.615 7/14/2004 8.531 8.533 8.533 5.614 5.615 5.615 5.614 5.615 5.615 10/5/2004 8.531 8.533 8.533 5.614 5.615 5.615 5.614 5.615 5.615 12/30/2004 8.531 8.534 8.534 5.614 5.615 5.615 5.614 5.614 5.614 3/24/2005 8.531 8.533 8.533 5.614 5.614 5.614 5.614 5.615 5.615 6/17/2005 8.531 8.532 8.532 5.614 5.615 5.615 5.614 5.614 5.614 9/7/2005 8.531 8.533 8.533 5.614 5.615 5.615 5.614 5.615 5.615 11/28/2005 8.531 8.534 8.534 5.614 5.615 5.615 5.614 5.615 5.615 2/23/2006 8.531 8.533 8.533 5.614 5.614 5.614 5.614 5.614 5.614 4/10/2006 8.531 8.533 8.533 5.614 5.614 5.614 5.614 5.614 5.614 5/18/2006 8.531 8.533 8.533 5.614 5.614 5.614 5.614 5.614 5.614 8/9/20061 8.531 8.532 8.532 5.614 5.614 5.614 5.614 5.614 5.614 1/25/2007 8.531 8.533 8.533 5.614 5.614 5.614 5.614 5.614 5.614 Bold Denotes change in "Desired" value from previous test

Page 63 Srsine CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008I 4

Channel 3 Data Point Days Point 1 -

Point 2 -

Point 3 -

Point 4 -

Point 5 -

Point 6 -

Date Between 3 month 3 month 3 month 3 month 3 month 3 month Comments 6/24/1999 9/14/1999 82 0.001122 0.001122 0.001122 0.000000 0.000000 0.001122 12/7/1999 84

-0.0010951-0.002190 -0.001095 -0.001095 0.000000 -0.001095 2/29/2000 84 0.001095 0.002190 0.000000 0.001095 0.000000 0.000000 5/26/2000 87 N/A N/A 0.002115 0.002115 0.001057 0.001057 Note 1 8/15/2000 81

-0.001136 -0.013630 -0.002272 -0.005679 -0.002272 -0.004543 11/7/2000 84 0.000000 0.001095 0.005476 0.005476 -0.001095 0.003286 1/30/2001 84 0.002190 0.000000 -0.003286 -0.001095 0.002190 0.000000 4/24/2001 84

-0.003286 -0.002190 0.001095 0.000000 0.000000 0.000000 7/19/2001 86 0,001070 0.002140 -0.001070 0.001070 0.000000 0.000000 10/9/2001 82

-0.001122 -0.002244 0.000000 -0.001122 -0.001122 0.000000 1/3/2002 86 0.002140 -0.004279 0.000000 0.001070 0.000000 0.000000 7/4/2003 547 N/A N/A N/A N/A N/A N/A Note 2 11/19/2003 138 N/A N/A N/A N/A N/A N/A Note 2 2/26/2004 99 N/A N/A

-0.003000 0.000000 0.000000 0.000000 Note 1 3/30/2004 33 N/A N/A N/A N/A N/A N/A Notes 1&2 4/22/2004 23 N/A N/A N/A N/A N/A N/A Notes 1&2 7/14/2004 83

-0.011084 -0.007759 0.001108 0.000000 0.000000 0.000000 10/5/2004 83 0.004434 0.002217 0.000000 0.000000 0.000000 0.0000001 12/30/2004 86

-0.001070 -0.002140 0.000000 0.001070 0.000000 -0.001070 3/24/2005 84 0.000000 0.001095 0.000000 -0.001095 -0.001095 0.001095 6/17/2005 85

-0.003247 -0.001082 0.000000 -0.001082 0.001082 -0.001082 9/7/2005 82 0.001122 0.000000 0.000000 0.001122 0.000000 0.001122 11/28/2005 82 0.002244 0.001122 0.001122 0.001122 0.000000 0.000000 2/23/2006 87 0.001057 0.000000 -0.002115 -0.001057 -0.001057 -0.001057 4/10/2006 46

-0.004000 0.002000 0.002000 0.000000 0.000000 0.000000 5/18/2006 38 N/A N/A N/A N/A N/A N/A Notes 1&2 8/9/20061 83 0.001108 0.002217 0.000000 -0.001108 0.000000 0.000000 1/25/2007 169 N/A N/A N/A N/A N/A N/A Note 1:

Any surveillances immediately following a change in desired values are not considered.

Note 2:

Periods over 115 days (92

  • 1.25 TS Extension Allowance) or less than 46 days (92/2) are not considered since they could skew the calculated drift data.

Page 64 5S CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-lCE-058.01-008 4

Power I Imbalance I Flow - Channel 4 Data Point Data Point Data Point Channel 4 1

2 3

Date Desired As-Found As-Left Desired As-Found As-Left Desired As-Found As-Left 8/3/1999 4.139 4.128 4.128 2.766 2.752 2.752 8.679 8.692 8.692 10/26/1999 4.139 4.132 4.132 2.766 2.755 2.755 8.679 8.689 8.689 1/18/2000 4.139 4.141 4.141 2.766 2.758 2.758 8.679 8.690 8.690 5/5/2000 4.139 4.140 4.140 2.766 2.761 2.761 8.679 8.679 8.679 7/6/2000 4.180 4.178 4.178 2.789 2.782 2.782 8.679 8.691 8.691 9/2612000 4.180 4.179 4.181 2.789 2.784 2.790 8.679 8.690 8.678 12/19/2000 4.180 4.177 4.177 2.789 2.788 2.788 8.679 8.679 8.679 1/17/2001 4.180 4.155 4.155 2.789 2.772 2.772 8.679 8.688 8.688 3/13/2001 4.180 4.153 4.153 2.789 2.769 2.769 8.679 8.689 8.689 6/6/2001 4.180 4.165 4.165 2.789 2.777 2.777 8.679 8.684 8.684 8/28/2001 4.180 4.160 4.160 2.789 2.773 2.773 8.679 8.684 8.684 11/20/2001 4.180 4.155 4.155 2.789 2.770 2.770 8.679 8.686 8.686 2/13/2002 4.180 4.150 4.150 2.789 2.769 2.769 8.679 8.688 8.688 7/4/2003 4.180 4.161 4.154 2.789 2.774 2.769 8.679 8.685 8.690 11/16/2003 4.180 4.156 4.156 2.789 2.771 2.771 8.679 8.687 8.687 2/27/2004 4.243 4.223 4.223 2.824 2.812 2.812 8.679 8.686 8.686 3/31/2004 4.243 4.233 4.233 2.824 2.820 2.820 8.629 8.633 8.633 5/25/2004 4.138 4,120 4.120 2.765 2.751 2.751 8.629 8.643 8.643 8/26/2004 4.138 4.129 4.129 2.765 2.759 2.759 8.629 8.630 8.630 11/19/2004 4.138 4.115 4.115 2.765 2.747 2.747 8.629 8.636 8.636 2/11/2005 4.138 4.130 4.130 2.765 2.760 2.760 8.629 8.631 8.631 5/4/2005 4.138 4.126 4.126 2.765 2.755 2.755 8.629 8.633 8.633 7/25/2005 4.138 4.123 4.123 2.765 2.754 2.754 8.629 8.631 8.631 10/20/2005 4.138 4,121 4.121 2.7651 2.751 2.751 8.629 8.632 8.632 11/9/2005 4.138 4.125 4.125 2.765 2.755 2.755 8.629 8.632 8.632 1/9/2006 4.138 4.126 4.126 2.765 2.755 2.755 8.629 8.630 8.630 4/14/2006 4.138 4.129 4.128 2.765 2.758 2.754 8.629 8.631 8.633 6/28/2006 4.114 4.099 4.099 2.752 2.740 2.740 8.629 8.635 8.635 12/13/2006 4.114 4.090 4.090 2.752 2.733 2.733 8.629 8.635 8.635 Bold Denotes change in "Desired" value from previous test

Page 65 F-WsErme y CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008 4

Data Point Data Point Data Point Channel 4 4

5 6

Date Desired As-Found As-Left Desired As-Found As-Left Desired As-Found As-Left 8/3/1999 8.565 8.563 8.563 5.667 5.672 5.672 5.667 5.660 5.660 10/26/1999 8.565 8.563 8.563 5.667 5.671 5.671 5.667 5.661 5.661 1/1812O0O 8.565 8.563 8.563 5.667 5.670 5.670 5.667 5.663 5.663 5/5/2000 8.565 8.558 8.558 5.667 5.672 5.672 5.667 5.660 5.660 7/6/2000 8.565 8.559 8.559 5.667 5.673 5.673 5.667 5.660 5.660 9126/2000 8.565 8.560 8.566 5.667 5.674 5.667 5.667 5.658 5.667 12/19/2000 8.565 8.568 8.568 5.667 5.662 5.662 5.667 5.667 5.667 1/17/2001 8.565 8.573 8.573 5.6671 5.664 5.664 5.667 5.667 5.667 3/13/2001 8.565 8.571 8.571 5.667 5.663 5.663 5.667 5.667 5.667 6/6/2001 8.565 8.568 8.568 5.667 5.666 5.666 5.667 5.666 5.666 8/28/2001 8.565 8.573 8.573 5.667 5.668 5.668 5.667 5.667 5.667 11/20/2001 8.565 8.571 8.571 5.667 5.664 5.664 5.667 5.666 5.666 2/13/2002 8.565 8.571 8.571 5.667 5.663 5.663 5.667 5.666 5.666 7/4/2003 8.565 8.567 8.570 5.667 5.666 5.669 5.667 5.663 5.664 11/16/2003 8.565 8.571 8.571 5.667 5.666 5.666 5.667 5.663 5.663 2/27/2004 8.565 8.569 8.569 5.667 5.665 5.665 5.667 5,664 5.664 3/31/2004 8.523 8.524 8.524 5.603 5.602 5.602 5.603 5.600 5.600 5/25/2004 8.523 8.525 8.525 5.603 5.601 5.601 5.603 5.598 5.598 8/26/2004 8.523 8.523 8.523 5.603 5.602 5.602 5.603 5.597 5.597 11/19/2004 8.523 8.526 8.526 5.6031 5.601 5.601 5.603 5.599 5.599 2/11r2005 8.523 8.524 8.524 5.603 5.600 5.600 5.603 5.599 5.599 5/41/2005 8.523 8.525 8.525 5.603 5.606 5.606 5.603 5.600 5.600 7/25/2005 8.523 8.524 8.524 5.603 5.600 5.600 5.603 5.602 5.602 10/20/2005 8.523 8.523 8.523 5.603 5.600 5.600 5.603 5.596 5.596 11/9/2005 8.523 8.523 8.523 5.603 5.600 5.600 5.603 5.597 5.597 1/9/2006 8.523 8.524 8.524 5.603 5.600 5.600 5,603 5.597 5.597 4/14/2006 8.523 8.523 8.523 5.603 5.600 5.602 5.603 5.597 5.598 6/281/2006 8.523 8.525 8.525 5.603 5.602 5.602 5.603 5.597 5.587 12/13/2006 8.523 8.524, 8.524 5,603 5.608 5.608 5.603 5.598 5.598 Bold Denotes change in "Desired" value from previous test

Page 66 5rs~tEnemg CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008 4

Channel 4 Data Point Days Point 1 -

Point 2 -

Point 3 -

Point 4 -

Point 5 -

Point6 -

Date Between 3 month 3 month 3 month 3 month 3 month 3 month Comment 8/3/1999 10/26/1999 84 0.004381 0.003286 -0.003286 0.000000 -0.001095 0.001095 1/18/2000 84 0.009857 0.003286 0.001095 0.000000 -0.001095 0.002190 5/5/2000 108

-0.001000 0.003000 -0.011000 -0.005000 0.002000 -0.003000 7/6/2000 62 N/A N/A 0.017806 0.001484 0.001484 0.000000 Note 1 9/26/2000 82 0.001122 0.002244 -0.001122 0.001122 0.001122 -0.002244 12/19/2000 84

-0.004381 -0.002190 0.001095 0.002190 -0.005476 0.000000 1/17/2001 29 N/A N/A N/A N/A N/A N/A Note 2 3/13/2001 84

-0.0262861-0.020810 0.010952 0.003286 0.001095 0.000000 Note 3 6/6/2001 85 0.012988 0.008659 -0.005412 -0.003247 0.003247 -0.001082 8/28/2001 83

-0.005542 -0.004434 0.000000 0.005542 0.002217 0.001108 11/20/2001 84

-0.005476 -0.003286 0.002190 -0.002190 -0.004381 -0.001095 2/13/2002 85

-0.005412 -0.001082 0.002165 0.000000 -0.001082 0.000000 7/4/2003 506 N/A N/A N/A N/A N/A N/A Note 2 11/16/2003 135 N/A N/A N/A N/A N/A N/A Note 2 2/27/2004 103 N/A N/A

-0.001000 -0.002000 -0.001000 0.001000 Note 1 3/31/2004 33 N/A N/A N/A N/A N/A N/A Notes 1&2 5125/2004 55 N/A N/A 0.016727 0.001673 -0.001673 -0.003345 Note 1 8/26/2004 93 0.009000 0.008000 -0.013000 -0.002000 0.001000 -0.001000 11/19/2004 85

-0.015153 -0.012988 0.006494 0.003247 -0.001082 0.002165 2/11/2005 84 0.016429 0.014238 -0.005476 -0.002190 -0.001095 0.000000 5/4/2005 82

-0.004488 -0.005610 0.002244 0.001122 0.006732 0.001122 7/25/2005 82

-0.003366 -0.001122 -0.002244 -0.001122 -0.006732 0.002244 10/20/2005 87

-0.002115 -0.003172 0.001057 -0.001057 0.000000 -0.006345 11/9/2005 20 N/A N/A N/A N/A N/A N/A Note 2 1/9/2006 81 0.005679 0.004543 -0.002272 0.001136 0.000000 0.001136 Note4 4/14/2006 95 0.003000 0.003000 0.001000 -0.001000 0.000000 0.000000 6/28/2006 75 N/A N/A 0.002453 0.002453 0.000000 -0.001227 Note 1 12/13/2006 168 N/A N/A N/A N/A N/A N/A Note 2 Note 1:

Any surveillances immediately following a change in desired values are not considered.

Note 2:

Periods over 115 days (92

  • 1.25 TS Extension Allowance) or less than 46 days (92/2) are not considered since they could skew the calculated drift data.

Note 3:

Uses data from 12/19/2000 Note 4:

Uses data from 10/20/2005

Page 67

!rstýEner

~

CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-lCE-058.01-008 1 4 - Foxboro Technical Information Document TI-2AI-130

Page 68 CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008 4

( STechnical Information SPEC 200 CURRENT TO VOLTAGE CONVERTERS

TI'I 2A1-130 March 1972

/I 5/72

(.

Figure 1 GENERAL SPEC 200 Current-to-Voltage Conveners, Figure 1.

provide.the interface between field current signals (4-20 rnA dc or 10-50 mA dc) and SPEC 200 System Voltage Signals(0-10 V dc).

There are four versions of the con-verters which will be identified for discussion purposes by the following partial model numbers.

For complete model numbers. see Specifications section.

12V: 4-20 mA dc to 0-10 V dc Dual Converter with inputs galvanically isolated from outputs.

Transmitter is powered from +18 and -15 V dc nest field bus or external power supply in series with field transmitters.

13V:

4-20-mA dc to 0-10 V dc Dual Converter with nonisolated inputs and outputs. Transmitter is powered from +15 and -15V dc nest field bus or external power supply in series with field transmitter.

H2V: 10-50 mA dc to 0-10 V dc Dual Converter with inputs galvanically isolated from outputs.

Trans REFERENCE DOCUMENT TI 200-205 mitter is powered from 40-100 V -dc nest field bus or from 40- 100 V remote power supply in series with field transmitter.

14V: 4-20 mA dc to 0-10 V dc Dual Converter with nonisolated inputs and outputs. Transmitter is powered from 24 V dc nest field bus or from 24 V dc remote power supply in series with field transmitter.

12V and I3V Converters require, when used with Foxboro E Series Transmitters, that at least 30 V dc

(+15 and - 15 V) be used to power the transmitter circuit. At this voltage the load in series with the associated transmitter (including lead resistance) may be up to 65 ohms maximum. The 14V Converter requires that a minimum 24 V dc be used to power an E Series Transmitter. When it is powered by 30 V dc(+15 and -15 V),

the external load (including lead resistance) that may be added in series with the transmitter is 300 ohms maximum.

H2V Converters with transmitters powered from 40 V de may have up to 150 ohms (including lead resistance) in series with E Series Transmitters.

POX"ORO Printed In U.S.A

r Page 69 Firs~nenCALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008 1 4 TI 2AI-130 Page 2 Two of the converters. the 12V and the ISV, with load circuits powered from a nest mounted DP1O-ULB Power Distribution Panel via the nest field bus, limit energy to the field transmitters to intrinsically safe levels. For a discussion on SPEC 200 Intrinsically Safe Systems, see TI 200-255.

SPECIFICATIONS Model Number:

2AI-I2V:

4-20 mA to 0-10 V (Isolated) 2AI-12V-ULB: 4-20 mA to 0-10 V Intrinsically Safe (Isolated) 2AI-13V: 4-20 mA to 0-10 V (Nonisolated) 2AI-I3V-ULB: 4-20 mA to 0-10 V Intrinsically Safe (Nonisolated) 2AI-H2V; 10-60 mA to 0-10 V (Isolated) 2AI-14V: 4-20 mA to 0-10 V (Nonisolated),

24 V dc Power Mounting:

Mounts directly in SPEC 200 Nest and occupies one nest space.

See Mounting Equipment.

TI 200-215.

Electrical Classification:

Ordinary locations. Suitable for Class I, Groups B. C, D,' Division 2. if suitably enclosed.

For suitable enclosures, see TI 200-250.

Intrinsic Safety:

See prior text and-TI 200-255.

Power Requirements:

(For both converters nor including transmitter overrange requirements) 12V:

415 V dc i6% at 1 0 mA, and -15 V dc *5% at 80 mA when totally powered from system supply via nest bus.

+15 V dc *5% at 40 mA required from com-ponent bus in nest when external power supply in series with field transmitter is used.

13V:

+15 V dc *6% at 44 mA. and -15 V dc *5% at 52 mA when totally powered from system supply via nest bus.

+15 V dc 15% at 4 mA, and -15 V dc t5% at 12 mA from component bus in nest when external power supply in series with field transmitter is used.

H2V: +15 V dc i*

at 15 mA. and -15 V dc 15% at 25 mA from nest component bus.40-200 V dc at 100 mA from nest field bus or power supply in series with field transmitter.

14V:

+15 V dc *5%at4 mA. and -15 V dc *% at 12 mA from component bus in nest. 24 V dc at 40 mA from nest field bus or power supply in series with field transmitter.

Input Signals:

12V, IMV 14V: 4-20 mA dc H2V: 10-50 mA dc Input Resistance:

When powered from power supplies in series with transmitter.

12V: 40 ohms maximum 13V: 250 ohms H2V: 35 ohms maximum 14V: 250 ohms Output Signals:

0-10 V dc Output Loads:

2000 ohms minimum Adjustments: (Located at front panel) 12V: Zero (each input) *2% of output span minimum Span (each input) k5% of output span minimum 13V: Zero (each input) 3. 5% of output span minimum H2V: Zero (each input) :k2. 5 of output span minimum Span (each input) 03. 5% of output span minimum 14V: Zero (each input) +/-3. 5% of output span minimum Open Circuit Conditions:

When inputs are open circuited, the corresponding outputs will go to -2.5 V dc *0.2 V.

Accuracy:

  • 0. 25% of output span Supply Voltage Effect:

12V:

  • 0. 2% of output span maximum for a 15%

change within normal operating units.

13V, H2V, 14V: *0. 1% of output span maximum for a :016 change within normal operating limits.

Ambient Temperature Range:

+40 to 120 F(+5Sto 50 C)

Ambient Temperature Error:

  • 0. 51% of output span maximum for a 50 F (28 C) change within normal operating limits.

--C-C (I-

Page 70 Fest~mCALCULATION COMPUTATION SNOP-CC-3002-01 Rev. 03 CALCULATION NO.:

IREVISION:

C-ICE-058.01-008, 4

TI 2AI-130 Page 3

{ f

+V FIELD BUS SRb

+

TRANSMITTER I (f

E,

_ BUS POWERED ZERO

(

EXTERNAL POWER SUPPLY EXTERNALLY POWERED Eo ZERO Figure 2.

13V and 14V Converter Schematic

(

PRINCIPLE OF OPERATION 13V and 14V: The principle of operation for these converters is basically the same. The differences are

'certain component values and the power to the field circuits.

Figure 2 shows one simplified schematic for the Current-to-Voltage Converters when the field circuit is bus powered and another one when they are powered externally.

The arrangement desired is selected by jumpers on the printed circuit board. The +V and - V field bus supply is +16 and -15 V dc.minimum for the i1V and 24 V dc minimum for the 14V.

Note: There is only one field bus in the SPEC 200 nest. One cannot mix +15 and - 15 V and any other field bus voltage such as 24 V de in the same nest.

The transmitted current~in both diagrams in Figure 2,develops a voltage across Resistor R which is proportional to the measuremeni signal. Ths voltage is biased to take out the elevation of the input signal and attentuated in the integrated circuit amplifier to produce an output (E0 ) of 0-10 V dc.

For intrinsic safety applications, only the bus powered version of the ISV may be used. The +15 and -15 V bus voltage is limited by a specially designed high voltage limiting circuit in the power distribution panel which distributes the power to the nest field bus. The current is limited by Resistors Rh and Ra.

Resistors Rc and Rd protect the field circuit from accidental fault voltages up to 250 volts nominal from the amplifier circuits.

Page 71 5Ma0_Rn39.y CALCULATION COMPUTATION NOP-CC-3002-01 Rev. 03 CALCULATION NO.:

REVISION:

C-ICE-058.01-008 4

TI 2AI-130 Page 4 R

C E

Rb 0

  • TC TRANSMITTER I

MEAS.

0

.P F

0 E

E e

R R 4

-R V PULSES THIS BLOCK IS A PULSE GENERATOR AND A DC/DC CONVERTER FOR THE MODEL 12V BUS POWERED IT IS A PULSE GENERATOR ONLY FOR THE MODEL, H2V

+V

-V R

C E

R TRANSMITTER P

A A%"-

0 R

1E cEE EXTERNAL RI POWER SUPPLY EXTERNALLY POWERED P

E S

E S

E.

N Figure 3.

12V and H2V Converter Schematic I2V and H2V: The principle of operation for these field bus and requiresthe4l5 and -15 V dc powerfor pulse converters is basically the same.

Referring to Figure 3, generation. Here again,it is important to remember the main difference between the two is that when bus that only one voltage may exist on a field bus in a powered, in the 12V, the voltage (+V and -V) feeding the given SPEC 200 Nest. Note that H2V's and 12V's may field circuit is 24 V dc as developed in the DC/DC never be combined in the same nest.

Converter which is powered by the +15 and -15 V nest field bus.

The H2V~on the other hand, eceives power for the field In the intrinsically safe version of the 12V (bus circuit directly from the field bus (40-100 V dc).

Also

\\

powered only), Resistor Ra limits the current, from the the pulses to the chopper are developed by different voltage limited field bus. that can flow in the field circuits in the two units.

circuit.

Isolation and Resistors Rb and Rc limit the energy that can reach the field circuits to intrinsically The transmitted current is converted in the chopper safe levels from the amplifier circuits. This protection circuits to a square wave signal which can be transformer included accidental fault voltages up to 250 volts coupled (providing isolation) to the rectifier circuit.

The nominalh rectified signal is connected to the amplifier which pro-duces output signal Eo (0-10 V dc).

All of the SPEC 200 Voltage-t- Current Converters have a nominal frequency response such that the output When the circuits are externally powered, the is down 3 dB at 10 Hz.

This response may be altered principle of operation is similar. In this mode of by changing capacitor values on the printed circuit card.

operation the H2V is totally disconnected from the nest Additional details are given in the master'instructions for field bus.

The 12V, however, still is connected to the the various converters.