IR 05000498/2016006

From kanterella
Jump to navigation Jump to search
Annual Assessment Letter for South Texas Project Electric Generating Station, Units 1 and 2 (05000498/2016006 and 05000499/2016006)
ML17059D441
Person / Time
Site: South Texas  
(NPF-076, NPF-080)
Issue date: 03/01/2017
From: Troy Pruett
NRC/RGN-IV/DRP
To: Gerry Powell
South Texas
NICK TAYLOR
References
IR 2016006
Download: ML17059D441 (6)


Text

March 1, 2017

SUBJECT:

ANNUAL ASSESSMENT LETTER FOR SOUTH TEXAS PROJECT ELECTRIC GENERATING STATION, UNITS 1 AND 2 (REPORT 05000498/2016006 AND 05000499/2016006)

Dear Mr. Powell:

On February 16, 2017, the U.S. Nuclear Regulatory Commission (NRC) completed its end-of-cycle performance assessment of South Texas Project Electric Generating Station, Units 1 and 2, reviewing performance indicators (PIs), inspection results, and enforcement actions from January 1, 2016, through December 31, 2016. This letter informs you of the NRCs assessment of your facility during this period and its plans for future inspections at your facility.

The NRC concluded that overall performance at your facility preserved public health and safety.

The NRC determined the performance at South Texas Project Electric Generating Station, Units 1 and 2 during the most recent quarter was within the Regulatory Response Column, the second highest performance column of the NRCs Reactor Oversight Process (ROP) Action Matrix. This conclusion was based on one or more greater-than-Green inspection findings in the Security cornerstone, and all PIs within the expected range (i.e., Green).

Therefore, in addition to ROP baseline inspections, the NRC plans to conduct a supplemental inspection in accordance with Inspection Procedure 95001, Supplemental Inspection Response to Action Matrix Column 2 Inputs. The objective of this supplemental inspection will be to (1) assure that the root causes and contributing causes of significant performance issues are understood; (2) independently assess and assure that the extent of condition and extent of cause of significant performance issues are identified; (3) assure that corrective actions taken to address and preclude repetition of significant performance issues are prompt and effective; and (4) assure that corrective plans direct prompt actions to effectively address and preclude repetition of significant performance issues. This inspection will be scheduled after you notify the NRC of your readiness.

The enclosed inspection plan lists the inspections scheduled through December 31, 2018. The NRC provides the inspection plan to allow for the resolution of any scheduling conflicts and personnel availability issues. Routine inspections performed by resident inspectors are not included in the inspection plan. The inspections listed during the last twelve months of the inspection plan are tentative and may be revised. The NRC will contact you as soon as possible to discuss changes to the inspection plan should circumstances warrant any changes.

This inspection plan does not include the plan for security-related inspections, which will be sent via separate, non-publicly available correspondence. On August 25, 2016, the NRC completed a Problem Identification and Resolution inspection at South Texas Project (Agencywide Documents Access and Management System (ADAMS) Accession No. ML16323A297), which identified safety conscious work environment challenges in the Security Department.

This inspection plan includes an in-depth problem identification and resolution sample that the NRC plans to perform during the week of June 19, 2017 to assess the Security Departments progress in improving the safety conscious work environment.

In accordance with Title 10 of the Code of Federal Regulations (10 CFR) 2.390 of the NRCs Rules of Practice, a copy of this letter will be available electronically for public inspection in the NRC Public Document Room or from the Publicly Available Records (PARS) component of NRC's document system (ADAMS). ADAMS is accessible from the NRC Web site at http://www.nrc.gov/reading-rm/adams.html (the Public Electronic Reading Room).

Please contact Nick Taylor at 817-200-1141 with any questions you have regarding this letter.

Sincerely,

/RA/

Troy W. Pruett, Director Division of Reactor Projects Docket Nos.: 50-498, 50-499 License Nos.: NPF-76 and NPF-80 Enclosure:

South Texas Project Electric Generating Station, Units 1 and 2 Inspection/

Activity Plan

SUNSI Review:

ADAMS:

Non-Publicly Available Non-Sensitive Keyword:

By: NTaylor/dll Yes No Publicly Available Sensitive NRC-002 OFFICE RIV/DRP:C DRS:D DRP:D NAME NTaylor AVegel TPruett SIGNATURE

/RA/

/RA JClark for/

/RA/

DATE 2/23/17 2/23/17 2/27/17

South Texas Project Inspection / Activity Plan 01/01/2017 - 12/31/2018 Unit Number Report 22 No. of Staff on Site Planned Dates Start End Inspection Activity Title Page 1 of 3 02/23/2017 11:47:57

7112407

- REMP INSPECTION 1, 2 01/09/2017 01/13/2017 IP 71124.07 Radiological Environmental Monitoring Program

EB2-05T

- TRIENNIAL FIRE PROTECTION INSPECTION 1, 2 01/23/2017 01/27/2017 IP 7111105T Fire Protection [Triennial]

1, 2 02/06/2017 02/10/2017 IP 7111105T Fire Protection [Triennial]

EXAM

- INITIAL EXAM

08/14/2017 08/18/2017 X02592 INITIAL EXAM STP U1 (09/2017)

08/14/2017 08/18/2017 X02593 INITIAL EXAM STP U2 (09/2017)

09/25/2017 10/04/2017 X02592 INITIAL EXAM STP U1 (09/2017)

09/25/2017 10/04/2017 X02593 INITIAL EXAM STP U2 (09/2017)

RS 13 PI

- RADIATION SAFETY 1, 2 03/27/2017 03/31/2017 IP 71124.01 Radiological Hazard Assessment and Exposure Controls 1, 2 03/27/2017 03/31/2017 IP 71124.03 In-Plant Airborne Radioactivity Control and Mitigation 1, 2 03/27/2017 03/31/2017 IP 71151-OR01 Occupational Exposure Control Effectiveness 1, 2 03/27/2017 03/31/2017 IP 71151-PR01 RETS/ODCM Radiological Effluent Occurrences

71111.08

- INSERVICE INSPECTION UNIT 1

03/27/2017 04/07/2017 IP 7111108P Inservice Inspection Activities - PWR

EP-1

- BIENNIAL EP PROGRAM INSPECTION 1, 2 05/08/2017 05/12/2017 IP 7111402 Alert and Notification System Testing 1, 2 05/08/2017 05/12/2017 IP 7111403 Emergency Preparedness Organization Staffing and Augmentation System 1, 2 05/08/2017 05/12/2017 IP 7111404 Emergency Action Level and Emergency Plan Changes 1, 2 05/08/2017 05/12/2017 IP 7111405 Correction of Emergency Preparedness Weaknesses and Deficiencies

EP-2

- EP PERFORMANCE INDICATOR VERIFICATION 1, 2 05/08/2017 05/12/2017 IP 71151-EP01 Drill/Exercise Performance 1, 2 05/08/2017 05/12/2017 IP 71151-EP02 ERO Readiness 1, 2 05/08/2017 05/12/2017 IP 71151-EP03 Alert & Notification System Reliability

EB1-17T

- STP 50.59 EVALUATIONS OF CHANGES, TESTS 1, 2 05/22/2017 05/26/2017 IP 7111117T Evaluations of Changes, Tests, and Experiments and Permanent Plant Modifications

STP-SCWE - SUPPLEMENTAL INSP - STP SECURITY SCWE 1, 2 06/19/2017 06/23/2017 IP 71152-Trends Semi-annual Trends

RS 24

- RADIATION SAFETY 1, 2 07/31/2017 08/04/2017 IP 71124.02 Occupational ALARA Planning and Controls 1, 2 07/31/2017 08/04/2017 IP 71124.04 Occupational Dose Assessment This report does not include INPO and OUTAGE activities.

This report shows only on-site and announced inspection procedures.

South Texas Project Inspection / Activity Plan 01/01/2017 - 12/31/2018 Unit Number Report 22 No. of Staff on Site Planned Dates Start End Inspection Activity Title Page 2 of 3 02/23/2017 11:47:57

BRQ

- BRQ INSPECTION 1, 2 08/28/2017 09/01/2017 IP 7111111B Licensed Operator Requalification Program

EB1-21N

- STP DESIGN BASES PROGRAMS INSPECTION 1, 2 01/22/2018 02/09/2018 IP 7111121N Component Design Bases Inspection (Programs)

RS 12PI

- RAD SAFETY 1, 2 04/02/2018 04/06/2018 IP 71124.01 Radiological Hazard Assessment and Exposure Controls 1, 2 04/02/2018 04/06/2018 IP 71124.02 Occupational ALARA Planning and Controls 1, 2 04/02/2018 04/06/2018 IP 71151-OR01 Occupational Exposure Control Effectiveness 1, 2 04/02/2018 04/06/2018 IP 71151-PR01 RETS/ODCM Radiological Effluent Occurrences

7111108

- INSERVICE INSPECTION UNIT 2

04/02/2018 04/13/2018 IP 7111108P Inservice Inspection Activities - PWR

EXAM

- INITIAL EXAM

09/17/2018 09/21/2018 X02626 INITIAL EXAM STP U1(11/18)

09/17/2018 09/21/2018 X02627 INITIAL EXAM STP U2(11/2018)

10/22/2018 10/26/2018 X02626 INITIAL EXAM STP U1(11/18)

10/22/2018 10/26/2018 X02627 INITIAL EXAM STP U2(11/2018)

EB1-07T

- STP HEAT SINK PERFORMANCE 1, 2 06/11/2018 06/15/2018 IP 7111107T Heat Sink Performance

EP-1

- EP EXERCISE INSPECTION 1, 2 06/11/2018 06/15/2018 IP 7111401 Exercise Evaluation 1, 2 06/11/2018 06/15/2018 IP 7111404 Emergency Action Level and Emergency Plan Changes 1, 2 06/11/2018 06/15/2018 IP 71151-EP01 Drill/Exercise Performance 1, 2 06/11/2018 06/15/2018 IP 71151-EP02 ERO Readiness 1, 2 06/11/2018 06/15/2018 IP 71151-EP03 Alert & Notification System Reliability

RS 5678

- RAD SAFETY 1, 2 07/30/2018 08/03/2018 IP 71124.05 Radiation Monitoring Instrumentation 1, 2 07/30/2018 08/03/2018 IP 71124.06 Radioactive Gaseous and Liquid Effluent Treatment 1, 2 07/30/2018 08/03/2018 IP 71124.07 Radiological Environmental Monitoring Program 1, 2 07/30/2018 08/03/2018 IP 71124.08 Radioactive Solid Waste Processing and Radioactive Material Handling, Storage, and Transportation This report does not include INPO and OUTAGE activities.

This report shows only on-site and announced inspection procedures.

South Texas Project Inspection / Activity Plan 01/01/2017 - 12/31/2018 Unit Number Report 22 No. of Staff on Site Planned Dates Start End Inspection Activity Title Page 3 of 3 02/23/2017 11:47:57

7111108

- INSERVICE INSPECTION UNIT 1

10/15/2018 10/26/2018 IP 7111108P Inservice Inspection Activities - PWR Comments:

This report does not include INPO and OUTAGE activities.

This report shows only on-site and announced inspection procedures.