IR 05000338/2023011
| ML23267A001 | |
| Person / Time | |
|---|---|
| Site: | North Anna |
| Issue date: | 09/26/2023 |
| From: | James Baptist Division of Reactor Safety II |
| To: | Carr E Dominion Nuclear |
| References | |
| IR 2023011 | |
| Download: ML23267A001 (1) | |
Text
SUBJECT:
NORTH ANNA POWER STATION, UNITS 1 & 2 - QUADRENNIAL FOCUSED ENGINEERING INSPECTION (FEI) COMMERCIAL GRADE DEDICATION REPORT 05000338/2023011 AND 05000339/2023011
Dear Eric S. Carr:
On August 17, 2023, the U.S. Nuclear Regulatory Commission (NRC) completed an inspection at North Anna Power Station, Units 1 & 2 and discussed the results of this inspection with Mr.
Jim Jenkins, Plant Manager, and other members of your staff. The results of this inspection are documented in the enclosed report.
One finding of very low safety significance (Green) is documented in this report. This finding involved a violation of NRC requirements. We are treating this violation as a non-cited violation (NCV) consistent with Section 2.3.2 of the Enforcement Policy.
If you contest the violation or the significance or severity of the violation documented in this inspection report, you should provide a response within 30 days of the date of this inspection report, with the basis for your denial, to the U.S. Nuclear Regulatory Commission, ATTN:
Document Control Desk, Washington, DC 20555-0001; with copies to the Regional Administrator, Region II; the Director, Office of Enforcement; and the NRC Resident Inspector at North Anna Power Station, Units 1 & 2.
If you disagree with a cross-cutting aspect assignment in this report, you should provide a response within 30 days of the date of this inspection report, with the basis for your disagreement, to the U.S. Nuclear Regulatory Commission, ATTN: Document Control Desk, Washington, DC 20555-0001; with copies to the Regional Administrator, Region II; and the NRC Resident Inspector at North Anna Power Station, Units 1 & 2.
September 26, 2023
This letter, its enclosure, and your response (if any) will be made available for public inspection and copying at http://www.nrc.gov/reading-rm/adams.html and at the NRC Public Document Room in accordance with Title 10 of the Code of Federal Regulations 2.390, Public Inspections, Exemptions, Requests for Withholding.
Sincerely, James B. Baptist, Chief Engineering Branch 1 Division of Reactor Safety Docket Nos. 05000338 and 05000339 License Nos. NPF-4 and NPF-7
Enclosure:
As stated
Inspection Report
Docket Numbers:
05000338 and 05000339
License Numbers:
Report Numbers:
05000338/2023011 and 05000339/2023011
Enterprise Identifier:
I-2023-011-0029
Licensee:
Dominion Nuclear Company
Facility:
North Anna Power Station, Units 1 & 2
Location:
Mineral, VA
Inspection Dates:
July 24, 2023, to August 11, 2023
Inspectors:
P. Braxton, Reactor Inspector
S. Campbell, Senior Reactor Systems Engineer
R. Fanner, Reactor Inspector
Approved By:
James B. Baptist, Chief
Engineering Branch 1, Division of Reactor Safety
SUMMARY
The U.S. Nuclear Regulatory Commission (NRC) continued monitoring the licensees performance by conducting a Quadrennial Focused Engineering Inspection (FEI) Commercial Grade Dedication at North Anna Power Station, Units 1 & 2, in accordance with the Reactor Oversight Process. The Reactor Oversight Process is the NRCs program for overseeing the safe operation of commercial nuclear power reactors. Refer to https://www.nrc.gov/reactors/operating/oversight.html for more information.
List of Findings and Violations
Corrective actions to verify material characteristics of item procured not consistent with procurement technical evaluation (PTE)
Cornerstone Significance Cross-Cutting Aspect Report Section Mitigating Systems Green NCV 05000338,05000339/2023011-01 Open/Closed
[P.3] -
Resolution 71111.21N.
The
NRC-Identified
a Green finding associated with a Non-cited violation of Title 10 CFR Part 50 Appendix B Criterion XVI, Corrective Action, for failure to verify material characteristics of an item procured were consistent with the procurement technical evaluation (PTE).
Specifically, the material properties were not verified consistent with the PTE methodology which directed verification of material characteristics to mitigate previous deficiencies in accordance with the instructions contained in MS-AA-MVL-101, Receipt Inspection, Rev 9 and the criteria added in PTE 10000012272, Rev. 11.
Additional Tracking Items
None.
INSPECTION SCOPES
Inspections were conducted using the appropriate portions of the inspection procedures (IPs) in effect at the beginning of the inspection unless otherwise noted. Currently approved IPs with their attached revision histories are located on the public website at http://www.nrc.gov/reading-rm/doc-collections/insp-manual/inspection-procedure/index.html. Samples were declared complete when the IP requirements most appropriate to the inspection activity were met consistent with Inspection Manual Chapter (IMC) 2515, Light-Water Reactor Inspection Program - Operations Phase. The inspectors reviewed selected procedures and records, observed activities, and interviewed personnel to assess licensee performance and compliance with Commission rules and regulations, license conditions, site procedures, and standards.
REACTOR SAFETY
71111.21N.03 - Commercial Grade Dedication Commercial Grade Dedication (section 03.01)
- (1) SCR, 42291078
- (2) Transmitter, 42488999
- (3) Belts, 37094110
- (4) Valve, 42019703
- (5) Bearings, 42091523
- (6) Oil 42137857
- (7) Oil, 37696340
- (8) Circuit Breaker 480 V, 16455490
- (9) Time delay relay, 03421330
- (10) Control Relay 125 V DC, 06130460
- (11) Printed Circuit Board, Amplifier,
INSPECTION RESULTS
Corrective actions to verify material characteristics of item procured not consistent with procurement technical evaluation (PTE)
Cornerstone Significance Cross-Cutting Aspect Report Section Mitigating Systems Green NCV 05000338,05000339/2023011-01 Open/Closed
[P.3] -
Resolution 71111.21N.0 The NRC-Identified a Green finding associated with a Non-cited violation of Title 10 CFR Part 50 Appendix B Criterion XVI, Corrective Action, for failure to verify material characteristics of an item procured were consistent with the PTE. Specifically, the material properties were not verified consistent with the PTE methodology which directed verification of material characteristics to mitigate previously deficiencies in accordance with the instructions contained in MS-AA-MVL-101, Receipt Inspection, Rev 9 and the criteria added in PTE 10000012272, Rev. 11.
Description:
The team identified an issue of concern related to the failure to adequately use the Fourier Transform Infrared Report (FTIR) test methodology (Method 1) to support the destructive testing criteria to verify the critical characteristics of Material ID, 37094110. FTIR is a common form of infrared spectroscopy. This methodology was based on review of corrective actions from condition report, SU-CR-000-CR1208021. This report identified a failure of similar belts at the Surry facility on or around September 18, 2022, where belts failed on multiple instances. In review of the condition report, one of the contributing causes for the failures were related to vendor quality issues. As a result, in support of Material ID 37094110, North Anna modified the acceptance criteria for the destructive testing of belts to utilize the FTIR methodology. Specifically, in PTE 10000012272, Rev. 11, the licensee specified the performance of FTIR testing to validate that belts were comprised of Ethylene Propylene Diene Terpolymer (EPDM) rubber, the inner cords were made of polyester, and the outer fabric sleeve was made of polyester fabric. Based on information reviewed, the licensee appeared to have missed this attribute and accepted the belts into stock. Based on the review of UD Lot Results With Parts Used WO Data - 6-13-2023, UD Data tab, two different belts associated with the PTE were received on April 17, 2023, for Material ID 37094110 and April 13, 2023, for Material ID 37094130.
The team concluded the procurements received specifying the FTIR methodology were also necessary since two commercial vendors were used to procure belts under this PTE based on Material ID 37094130. This material ID was not a part of the original inspection scope but revealed itself based on the use of PTE 10000012272, Rev. 11, which linked both material IDs. In addition, the linked material section of the PTE specified these material IDs and had an active status as of March 20,2023. The inspectors also reviewed SU-CR-000-CR1208021, written to address the Surry belt failures, and located the same material IDs referenced in PTE 10000012272, Rev. 11. This supported the basis for concluding the corrective actions were not adequate for the circumstances.
Corrective Actions: The licensee entered the issue into the corrective action program based on CR1235239 & CR1235267 and performed an operability determination.
Corrective Action References: CR-000-CR1208021 was initiated based on the Surry belt failures in 09/18/2022.
Performance Assessment:
Performance Deficiency: The licensee failed to adequately implement corrective actions to ensure the established requirements in MS-AA-MVL-101, Receipt Inspection, Rev 9 were implemented commensurate with circumstances for the performance and documentation of quality receipt inspection activities, to include Material Verification (MV) inspection activities.
Screening: The inspectors determined the performance deficiency was more than minor because if left uncorrected, it would have the potential to lead to a more significant safety concern. Specifically, the use of the FTIR methodology to verify material characteristics was listed in the PTE for 9 material IDs at North Anna and Surry. Absent NRCs intervention, the licenses failure to establish and perform appropriate acceptance testing for the specified material IDs used for replacements could lead to in-service component deterioration and resultant failures.
Significance: The inspectors assessed the significance of the finding using IMC 0609 Appendix A, The Significance Determination Process (SDP) for Findings At-Power. the team determined the deficiency affected the design or qualification of a mitigating SSC, which at the time of the inspection, maintained its operability or PRA functionality. (Screened against IMC 0609, Appendix A, Exhibit 2, Step A1a, Green.) The applicable belts were installed on safety related HVAC systems which were linked to High-risk components, Emergency Switchgear Rooms.
Cross-Cutting Aspect: P.3 - Resolution: The team assessed the issue for cross-cutting aspects and determined one existed using the criteria in IMC 0310, Aspects Within the Cross-cutting Areas. Specifically, the team determined the Problem Identification and Resolution Area, Resolution attribute was most appropriate because the organization did not take effective corrective actions to address issues commensurate with their safety significance (PI.3).
Enforcement:
Violation: Title 10 CFR Part 50 Appendix B Criterion XVI, Corrective Action states, measures shall be established to assure that conditions adverse to quality, such as failures, malfunctions, deficiencies, deviations, defective material, and equipment, and non-conformances are promptly identified and corrected.
CR-000-CR1208021 was initiated to document the V-belt failures which was adverse to quality. PI-AA-200, Corrective Action was used, in part, to establish measures to be taken to assure that conditions adverse to quality are promptly identified and corrected. PTE 10000012272, Rev. 11 was updated based on the PI-AA-200 procedure and specified the requirements for destructive testing based on corrective actions listed from CR-000-CR1208021.
Section 1, Purpose of MS-AA-MVL-101, Receipt Inspection, Rev 9 requires the specific instruction for ensuring material verification (MV) inspection activities were conducted.
Contrary to the above, the licensee did not accomplish the activity adequately to support correcting the condition documented above by not implementing the instructions contained in MS-AA-MVL-101, Receipt Inspection, Rev 9 and the criteria added in PTE 10000012272, Rev. 11 to support material verification using FTIR. Specifically, the material properties were not verified consistent with the PTE methodology which directed verification of material characteristics to mitigate previously deficiencies within the Dominion Energy fleet.
Enforcement Action: This violation is being treated as a non-cited violation, consistent with Section 2.3.2 of the Enforcement Policy.
EXIT MEETINGS AND DEBRIEFS
The inspectors verified no proprietary information was retained or documented in this report.
On August 17, 2023, the inspectors presented the Quadrennial Focused Engineering Inspection (FEI) Commercial Grade Dedication results to Mr. Jim Jenkins, Plant Manager, and other members of the licensee staff.
DOCUMENTS REVIEWED
Inspection
Procedure
Type
Designation
Description or Title
Revision or
Date
71111.21N.03
Corrective Action
Documents
CR1208021
1-VS-AC-7 Belt Failure
9/18/2022
71111.21N.03
Corrective Action
Documents
Resulting from
Inspection
CR1234419
Procedure MS-AA-PTE-401-1001 Inconsistency Found
07/31/2023
71111.21N.03
Corrective Action
Documents
Resulting from
Inspection
CR1234428
Self-Identified Discrepancy during NRC Inspection for
07/31/2023
71111.21N.03
Corrective Action
Documents
Resulting from
Inspection
CR1234518
NRC Identified: PTE 10000013530 missing Active
Functional Mode for Isolation Safety Function
8/01/2023
71111.21N.03
Corrective Action
Documents
Resulting from
Inspection
CR1234721
NRC Identified: Procedures MS-AA-MNI-401 and MS-AA-
PTE-401 Require Administrative Changes
08/03/2023
71111.21N.03
Corrective Action
Documents
Resulting from
Inspection
CR1235026
NRC Identified: Purchase Order 4500382357 Receipt
Discrepancy
08/08/2023
71111.21N.03
Corrective Action
Documents
Resulting from
Inspection
CR1235136
NRC Identified: Purchase Order 4500377130
08/09/2023
71111.21N.03
Corrective Action
Documents
Resulting from
Inspection
CR1235145
NRC Observation: NRC Senior Resident Inspector
observed two access controlled doors not properly closed
08/09/2023
71111.21N.03
Corrective Action
Documents
CR1235204
NRC Identified: Shelf-life item in Warehouse has no
assigned shelf life
08/10/2023
Inspection
Procedure
Type
Designation
Description or Title
Revision or
Date
Resulting from
Inspection
71111.21N.03
Corrective Action
Documents
Resulting from
Inspection
CR1235233
NRC Identified Critical Characteristic not Verified for Valve
Seat Material
08/10/2023
71111.21N.03
Corrective Action
Documents
Resulting from
Inspection
CR1235237
NRC Identified Inadequate FMEA per procedure
08/10/2023
71111.21N.03
Corrective Action
Documents
Resulting from
Inspection
CR1235239
NRC Identified Material Verification not performed for SC
37094110
08/10/2023
71111.21N.03
Corrective Action
Documents
Resulting from
Inspection
CR1235267
NRC Identified Material Verification for 37094130 and
37094120
08/10/2023
71111.21N.03
Corrective Action
Documents
Resulting from
Inspection
CR1235278
NRC Identified Shelf Life Not Identified for 42488999,
Rosemount transmitter
08/10/2023
71111.21N.03
Drawings
215-FB-034F
Flow/Valve Operating Numbers Diagram Compressed Dry
Air Bottle System North Anna Power Station Units 1 & 2,
Sheet 1 of 5
Rev. 22
71111.21N.03
Drawings
11715-FB-034F
Flow/Valve Operating Numbers Diagram Compressed Dry
Air Bottle System North Anna Power Station Units 1 & 2,
Sheet 2 of 5
Rev. 22
71111.21N.03
Drawings
11715-FB-034F
Flow/Valve Operating Numbers Diagram Compressed Dry
Air Bottle System North Anna Power Station Units 1 & 2,
Sheet 4 of 5
Rev. 22
71111.21N.03
Engineering
Changes
NA-21-00077
1-SI-TK-2 Boron Injection Tk-Header Flow, 01-SI-FT-
1943-IXMITR and Charging Pumps Disch Hdr to Bit Flow
Transmitter, 02-SI-FT-2943-IXMITR
3/27/2022
Inspection
Procedure
Type
Designation
Description or Title
Revision or
Date
71111.21N.03
Engineering
Evaluations
10000009369
version 2
Oil, turbine, zinc-free, DTE 732 (Material Identification No.
2137857)
05/23/2015
71111.21N.03
Engineering
Evaluations
10000036456
Procurement Technical Evaluation for Exxon Mobil
Teresstic 46 Turbine Oil (Material Identification No.
37696340)
7/21/2022
71111.21N.03
Engineering
Evaluations
10000037783
Rosemount Transmitter Model 3153N
8/11/2020
71111.21N.03
Engineering
Evaluations
10000054532
Molded Case Circuit Breakers, Thermal/Magnetc Fixed
Rev. 2
71111.21N.03
Engineering
Evaluations
10000069032
CGIE Inter Utility Rosemount PCB
Rev.0
71111.21N.03
Engineering
Evaluations
NA-SPEC-000-
NAS-0044
Specification for Recirculation Pumps
05/22/1972
71111.21N.03
Engineering
Evaluations
10000001048
Time Delay Relays
Rev.3
71111.21N.03
Engineering
Evaluations
10000009369,
Version 03
Oil, turbine, zinc-free, DTE 732 (Material Identification No.
2137857)
05/11/2023
71111.21N.03
Engineering
Evaluations
10000013530
Valve,CPV O-Seal System 1" MFR.: CPV Manufacturing
Inc.
11/07/2017
71111.21N.03
Engineering
Evaluations
10000018472,
Version 11
Procurement Technical Evaluation for Bearings, Ball &
Angular Contact, Single & Bearings, Ball & Angular
Contact, Single & Double Row
07/19/2016
71111.21N.03
Engineering
Evaluations
10000018472,
Version 14
Procurement Technical Evaluation for Bearings, Ball &
Angular Contact, Single & Bearings, Ball & Angular
Contact, Single & Double Row
11/17/2016
71111.21N.03
Engineering
Evaluations
10000073202,
Version 0
Oil, turbine, zinc-free, DTE 732 (Material Identification No.
2137857)
05/12/2023
71111.21N.03
Engineering
Evaluations
PTE 900395
Westinghouse Safeguards Panel Control Relays
Rev. 3
71111.21N.03
Miscellaneous
EPRI Report
1016272
Nuclear Maintenance Applications Center Turbine Oil
Compatibility
03/2008
Inspection
Procedure
Type
Designation
Description or Title
Revision or
Date
71111.21N.03
Miscellaneous
Report1019593
Nuclear Maintenance Applications Center Radiation
Stability of Modern Turbine Oils
09/2009
71111.21N.03
Miscellaneous
PO 4500468575-
00001-
000000275263
Tyco Electronics Corp
2/04/2018
71111.21N.03
Miscellaneous
PO 4500486204-
00001-
000000277058
Purchase Order for Oil, turbine, zinc-free, DTE 732
(Material Identification No. 42137857)
10/25/2018
71111.21N.03
Miscellaneous
PO 4500494854-
00001-
000000275740
Tiger Controls Inc.
03/19/2019
71111.21N.03
Miscellaneous
PO 4500494854-
00001-
000000275983
Tiger Controls Inc
03/28/2019
71111.21N.03
Miscellaneous
Admiral Valve Trip Report
2/22/2017
71111.21N.03
Miscellaneous
10000021748
Rosemount 1154 B and D Series Amplifier and Calibration
Rev. 2
71111.21N.03
Miscellaneous
4500754346-
00001-
000000315232
03/09/2022
71111.21N.03
Miscellaneous
59-A086-00001
Agastat 7000 Series Timing Relays, Models 7012, 7022,
& 7032
Rev.4
71111.21N.03
Miscellaneous
59-A086-00003
Agastat E7000 Series Timing Relay ( Double Pole Model)
Rev.3
71111.21N.03
Miscellaneous
59-R711-00006
Model 1153 Series Alphaline Pressure Transmitters for
Nuclear Service
Rev.5
71111.21N.03
Miscellaneous
59-R711-00007
Model 1153 Series D Alphaline Nuclear Pressure
Transmitters
Rev.8
71111.21N.03
Miscellaneous
D2013004
IEEE Qualification Report of Rosemount 3153N
Rev. B
71111.21N.03
Miscellaneous
DOM-QA-1
Nuclear Facility Quality Assurance Program Description
Rev. 35
71111.21N.03
Miscellaneous
DOM-QA-1
Nuclear Facility Quality Assurance Program Description
Rev. 19
71111.21N.03
Miscellaneous
DS-21-008
ExxonMobil Lubricants & Grease Commercial Grade
Survey Report
07/29/2021
71111.21N.03
Miscellaneous
ET-S-09-0112
Issuance of QDR-S-4.2 & N-4.2, Revision 13, OSRS
Pump Motors
Rev. 0
71111.21N.03
Miscellaneous
MMSR
Master Material Stock Request
10/15/2011
Inspection
Procedure
Type
Designation
Description or Title
Revision or
Date
0000044656
71111.21N.03
Miscellaneous
MMSR 00071303
Master Material Stock Request
10/07/2020
71111.21N.03
Miscellaneous
Notification
200195900
Oil Fails Testing
2/20/2019
71111.21N.03
Miscellaneous
Notification
200229847
Missing Documentation for 55 gallons Teresstic 46, Batch
Nos. 70241883-01 and 702418238-01
09/08/2022
71111.21N.03
Miscellaneous
NQC 4733
Measuring and Test Equipment History Card
08/08/1990
71111.21N.03
Miscellaneous
PO 4500241653-
00001-
000000234469
Purchase Order for (Material Identification No. 42137857)
Oil, turbine, zinc-free, DTE 732
09/17/2015
71111.21N.03
Miscellaneous
PO 4500302377-
00003-
000000251492
Purchase Order for OM-Bearings, Ball & Angular Contact,
No.2 (Material Identification No. 42091523)
10/31/2016
71111.21N.03
Miscellaneous
PO 4500319699-
00001-
000000250412
Purchase Order for OM-Bearings, Ball & Angular Contact,
No.2 (Material Identification No. 42091523)
09/08/2016
71111.21N.03
Miscellaneous
PO 4500413591-
00002-
000000265163
Purchase Order for Valve, globe, 1", body material
aluminum (Material Identification No. 42019703)
11/17/2017
71111.21N.03
Miscellaneous
PO 4500486204-
00001-
000000275110
Purchase Order for Oil, turbine, zinc-free, DTE 732
(Material Identification No. 42137857)
10/25/2018
71111.21N.03
Miscellaneous
PO 4500506904-
00001-
000000276484
Purchase Order for Oil, turbine, zinc-free, DTE 732
(Material Identification No. 42137857)
2/08/2019
71111.21N.03
Miscellaneous
PO 4500506904-
00001-
000000277057
Purchase Order for Oil, turbine, zinc-free, DTE 732
(Material Identification No. 42137857)
2/08/2019
71111.21N.03
Miscellaneous
PO 4500603001-
00001-
000000297124
Westinghouse Repair & Replacement
09/10/2020
71111.21N.03
Miscellaneous
PO 4500754346-
00001-
000000315325
Paragon Energy Solution LLC
03/15/2022
Inspection
Procedure
Type
Designation
Description or Title
Revision or
Date
71111.21N.03
Miscellaneous
PO 4500786701-
00001-
000000321856
Purchase Order for Oil, lubricating, grade Teresstic 46, 55
gallons
09/08/2022
71111.21N.03
Miscellaneous
PO 4500786701-
00001-
000000321857
Purchase Order for Oil, lubricating, grade Teresstic 46, 55
gallons
09/08/2022
71111.21N.03
Miscellaneous
PO 4500788281-
00001-
000000320652
Purchase Order for Bearing, thrust (Material Identification
No. 42091523)
08/02/2022
71111.21N.03
Miscellaneous
PO 4500797806-
00001-
000000326373
Purchase Order for Oil, lubricating, grade Teresstic 46, 55
gallons
2/23/2023
71111.21N.03
Miscellaneous
PO 4500838815-
00001-
000000329385
Applied Industrial Technologies
94/17/2023
71111.21N.03
Miscellaneous
QDR-N-4.2/QDR-
S-4.2
Review Package of Electrical Equipment for North Anna
Power Station Units 1 & 2 and Surry Power Station Units
& 2
04/24/2014
71111.21N.03
Miscellaneous
QM1
Applied Technical Services, Inc. (ATS) Quality Manual
10/01/2018
71111.21N.03
Miscellaneous
Record Indexing
Data No.
4500302377
ProLog and Shipment Information for Material
Identification No. 42091523
10/31/2016
71111.21N.03
Miscellaneous
Record Indexing
Data No.
4500319699
ProLog and Shipment Information for Material
Identification No. 42091523
09/08/2016
71111.21N.03
Miscellaneous
SDBD-NAPS-QS
System Design Basis Document For Quench Spray
System
Rev. 24
71111.21N.03
Miscellaneous
TE Number
CGIVP03
EPRI CGI Joint Utility Task Group Commercial Grade
Item Evaluation For Valve Diaphragms And Seats
Rev. 1A
71111.21N.03
Procedures
MS-AA-PTE-
401-1001
Issuance and Control of Procurement TQAR Notes
Rev. 1
71111.21N.03
Procedures
0-OP-21.9A
Valve Checkoff - Control Room Bottled Air Pressurization
System
Rev. 11
71111.21N.03
Procedures
Preparation and Processing of Administrative Procedures
Rev. 16
Inspection
Procedure
Type
Designation
Description or Title
Revision or
Date
and Guidance and Reference Documents
71111.21N.03
Procedures
CFR 50.59 and 10 CFR 72.48 - Changes, Tests, and
Experiments
Rev. 17
71111.21N.03
Procedures
CM-AA-ETE-101
Engineering Technical Evaluation (ETE)
Rev. 16
71111.21N.03
Procedures
CM-AA-ETE-101
Engineering Technical Evaluation (ETE)
Rev. 5
71111.21N.03
Procedures
DNES-AA-GN-
1005
Failure Modes and Effects Analysis (FMEA)
Rev. 3
71111.21N.03
Procedures
DNES-AA-MEL-
4001
The Safety Classification of Structures, Systems, And
Components
Rev. 1
71111.21N.03
Procedures
DNES-AA-MEL-
4001
The Safety Classification of Structures, Systems, And
Components
Rev. 2
71111.21N.03
Procedures
DNES-AA-MEL-
4001
Determining the Safety Classification of Structures,
Systems, and Components
Rev. 4
71111.21N.03
Procedures
DNES-VA-GN-
0038
Seismic Qualification of Equipment
Rev. 0
71111.21N.03
Procedures
Inspection Plan
00001122
VL-C333 STD PKG, DMG, CLN, QC, CGEI FOR 3/4"
VALVE TRIM PARTS
03/07/2002
71111.21N.03
Procedures
Inspection Plan for OM-Bearings, Ball & Angular Contact
No. 2
2/06/2000
71111.21N.03
Procedures
Inspection Plan for Oil, Mobil, Grade DTE 797 & 732
04/25/2001
71111.21N.03
Procedures
Inspection Plan for Lubricant, Exxon, E2S, QG, QH
07/01/2022
71111.21N.03
Procedures
Measuring and Test Equipment
Revision 13
71111.21N.03
Procedures
Supply Chain Management Process
Rev. 1
71111.21N.03
Procedures
MS-AA-IEE-301
Item Equivalency Evaluation
Rev. 13
71111.21N.03
Procedures
MS-AA-MNI-401
Material Request and Material Requirements Planning
(MRP)
Rev. 16
71111.21N.03
Procedures
MS-AA-MVL-101
Quality Receipt Inspection
Rev. 9
71111.21N.03
Procedures
MS-AA-MVL-101
Quality Receipt Inspection
Rev. 4
71111.21N.03
Procedures
MS-AA-MVL-101
Quality Receipt Inspection
Rev. 9
71111.21N.03
Procedures
MS-AA-PRO-401
Procurement Control
Rev. 12
71111.21N.03
Procedures
MS-AA-PRO-402
Purchase Orders
Rev. 8
71111.21N.03
Procedures
MS-AA-PTE-401
Procurement Technical Evaluation Determination
Rev. 16
71111.21N.03
Procedures
MS-AA-PTE-401
Procurement Technical Evaluation Determination
Rev. 21
Inspection
Procedure
Type
Designation
Description or Title
Revision or
Date
71111.21N.03
Procedures
MS-AA-PTE-401
Procurement Technical Evaluation Determination
Rev. 8
71111.21N.03
Procedures
MS-AA-PTE-401
Procurement Technical Evaluation Determination
Rev. 10
71111.21N.03
Procedures
MS-AA-PTE-401
Procurement Technical Evaluation Determination
Rev. 17
71111.21N.03
Procedures
MS-AA-PTE-401-
1001
Rev. 10
71111.21N.03
Procedures
MS-AA-PTE-401-
1002
Sampling Methodology for Material Acceptance
Rev. 1
71111.21N.03
Procedures
MS-AA-PTE-401-
1004
Rev. 10
71111.21N.03
Procedures
MS-AA-PTE-401-
1004
Rev. 3
71111.21N.03
Procedures
MS-AA-PTE-401-
1004
Rev. 6
71111.21N.03
Procedures
MS-AA-SCE-301
Subcomponent Classification Evaluation
Rev. 3
71111.21N.03
Procedures
MS-AA-SLD-701
Shelf Life Evaluation and Control
Rev. 5
71111.21N.03
Procedures
MS-AA-SLD-701
Shelf Life Evaluation and Control
Rev. 2
71111.21N.03
Procedures
MS-AA-SLD-701
Shelf Life Evaluation and Control
Rev. 3
71111.21N.03
Procedures
MS-AA-TRN-202
Procurement Engineering Services Qualification and
Certification Program
Rev. 6
71111.21N.03
Procedures
MS-AA-VEN-101
Vendor Surveillance
Rev. 3
71111.21N.03
Procedures
MS-AA-WHS-131
In-Storage Maintenance of Items
Rev. 8
71111.21N.03
Procedures
MS-AA-WHS-132
Control of Shelf Life Material
Rev. 1
71111.21N.03
Procedures
MS-AA-WHS-133
In-Storage Maintenance of Items
Rev. 3
71111.21N.03
Procedures
MSS SP-61-2013
Pressure Testing of Valves
71111.21N.03
Procedures
NO-AA-VEN-210
Safety-Related and Commercial Grade Vendors Lists
Rev. 1
71111.21N.03
Procedures
Corrective Action
Rev. 41
71111.21N.03
Procedures
VPAP-0704
Shelf Life Evaluation and Control
Rev.6
71111.21N.03
Procedures
VPAP-0812
Station Lubrication Program
Rev. 18
71111.21N.03
Procedures
VPAP-0812
Station Lubrication Program
Rev. 19
71111.21N.03
Procedures
VPAP-704
Shelf Life Evaluation and Control
Rev.11
71111.21N.03
Procedures
Work Management
Rev. 25
71111.21N.03
Radiation
Surveys
MS-AA-WHR-401
Receiving
Rev. 8
Inspection
Procedure
Type
Designation
Description or Title
Revision or
Date
71111.21N.03
Self-
Assessments
PIR1218044
Assessment of Commercial Grade Dedication Process in
Preparation for 2023 NRC CGD Inspection
7/10/2023
71111.21N.03
Work Orders