Emergency Preparedness Biennial Exercise Inspection Report 05000336/2021501 and 05000423/2021501
ML21174A042
Person / Time
Site: Millstone  
(DPR-065, NPF-049)
Issue date: 06/23/2021
From: Fred Bower
Decommissioning, ISFSI, and Reactor Health Physics Branch
To: Stoddard D
Dominion Energy
Bower F
References
IR 2021501
Download: ML21174A042 (7)


Text

June 23, 2021

SUBJECT:

MILLSTONE POWER STATION, UNITS 2 AND 3 - EMERGENCY PREPAREDNESS BIENNIAL EXERCISE INSPECTION REPORT 05000336/2021501 AND 05000423/2021501

Dear Mr. Stoddard:

On June 10, 2021, the U.S. Nuclear Regulatory Commission (NRC) completed an inspection at Millstone Power Station, Units 2 and 3 and discussed the results of this inspection with Mr. Michael O'Connor, Plant Manager and other members of your staff. The results of this inspection are documented in the enclosed report.

No findings or violations of more than minor significance were identified during this inspection.

This letter, its enclosure, and your response (if any) will be made available for public inspection and copying at http://www.nrc.gov/reading-rm/adams.html and at the NRC Public Document Room in accordance with Title 10 of the Code of Federal Regulations 2.390, Public Inspections, Exemptions, Requests for Withholding.

Sincerely, Fred L. Bower, III, Chief Security, EP and Incident Response Branch Division of Radiological Safety and Security

Docket Nos. 05000336 and 05000423 License Nos. DPR-65 and NPF-49

Enclosure:

As stated

Inspection Report

Docket Numbers:

05000336 and 05000423

License Numbers:

DPR-65 and NPF-49

Report Numbers:

05000336/2021501 and 05000423/2021501

Enterprise Identifier: I-2021-501-0008

Licensee:

Dominion Energy Nuclear Connecticut, Inc.

Facility:

Millstone Power Station, Units 2 and 3

Location:

Waterford, CT 06385

Inspection Dates:

June 7, 2021 to June 11, 2021

Inspectors:

J. Ambrosini, Senior Emergency Preparedness Inspector

E. Andrews, Health Physicist

P. Boguszewski, Resident Inspector

J. Walker, Emergency Response Inspector, Region II

Approved By:

Fred L. Bower, III, Chief

Security, EP and Incident Response Branch

Division of Radiological Safety and Security

SUMMARY

The U.S. Nuclear Regulatory Commission (NRC) continued monitoring the licensees performance by conducting an emergency preparedness biennial exercise inspection at Millstone Power Station, Units 2 and 3, in accordance with the Reactor Oversight Process. The Reactor Oversight Process is the NRCs program for overseeing the safe operation of commercial nuclear power reactors. Refer to https://www.nrc.gov/reactors/operating/oversight.html for more information.

List of Findings and Violations

No findings or violations of more than minor significance were identified.

Additional Tracking Items

None.

INSPECTION SCOPES

Inspections were conducted using the appropriate portions of the inspection procedures (IPs) in effect at the beginning of the inspection unless otherwise noted. Currently approved IPs with their attached revision histories are located on the public website at http://www.nrc.gov/reading-rm/doc-collections/insp-manual/inspection-procedure/index.html. Samples were declared complete when the IP requirements most appropriate to the inspection activity were met consistent with Inspection Manual Chapter (IMC) 2515, Light-Water Reactor Inspection Program - Operations Phase. The inspectors reviewed selected procedures and records, observed activities, and interviewed personnel to assess licensee performance and compliance with Commission rules and regulations, license conditions, site procedures, and standards.

Starting on March 20, 2020, in response to the National Emergency declared by the President of the United States on the public health risks of the coronavirus (COVID-19), inspectors were directedto begin telework. In addition, regional baseline inspections were evaluated to determine if all or a portion of the objectives and requirements stated in the IPcould be performed remotely. If the inspections could be performed remotely, they were conducted per the applicableIP. In some cases, portions of an IP were completed remotely and onsite. The inspections documented below met the objectives and requirements for completion of the IPand, for this inspection, were completed onsite.

REACTOR SAFETY

71114.01 - Exercise Evaluation

Inspection Review (IP Section 02.01-02.11) (1 Sample)

(1) The inspectors evaluated the biennial emergency plan exercise at Millstone Unit 2. As a result of the 2020 COVID-19 Public Health Emergency, Dominion requested and received an exemption to reschedule their biennial emergency preparedness exercise from 2020 to 2021 (ML20287A273). The exercise scenario simulated fuel damage from a seismic event, a steam generator tube rupture, and a stuck open main steam line safety valve. After the conclusion of the combined onsite and offsite evaluated exercise, Millstone onsite emergency responders continued their participation to respond to a simulated large-scale fire which damaged the spent fuel pool in order to demonstrate the extensive damage mitigation guidelines described in 10 CFR 50.155(b)(2) as required by 10 CFR Part 50, Appendix E.IV.F.2.j on June 8, 2021. Additionally, Dominion completed the ingestion pathway exercise as required by 10 CFR Part 50, Appendix E.IV.F.2.d on June 9, 2021.

71114.04 - Emergency Action Level and Emergency Plan Changes

Inspection Review (IP Section 02.01-02.03) (1 Sample)

(1) The inspectors evaluated the following submitted Emergency Action Level and Emergency Plan changes.
  • Evaluation MP-20-18, EPI-FAP 10 Dose Assessment

This evaluation does not constitute NRC approval.

71114.08 - Exercise Evaluation Scenario Review

Inspection Review (IP Section 02.01 - 02.04) (1 Sample)

(1) The inspectors reviewed and evaluated the proposed scenario for biennial emergency plan exercise on May 6,

OTHER ACTIVITIES - BASELINE

===71151 - Performance Indicator Verification

The inspectors verified licensee performance indicators submittals listed below:

EP01: Drill/Exercise Performance (IP Section 03.12)===

(1) Unit 2 (July 1, 2020 through March 31, 2021)

Unit 3 (July 1, 2020 through March 31, 2021)

EP02: ERO Drill Participation (IP Section 03.13) (1 Sample)

(1) Unit 2 (July 1, 2020 through March 31, 2021) Unit 3 (July 1, 2020 through March 31, 2021)

EP03: Alert & Notification System Reliability (IP Section 03.14) (1 Sample)

(1) Unit 2 (July 1, 2020 through March 31, 2021) Unit 3 (July 1, 2020 through March 31, 2021)

INSPECTION RESULTS

No findings were identified.

EXIT MEETINGS AND DEBRIEFS

The inspectors verified no proprietary information was retained or documented in this report.

  • On June 10, 2021, the inspectors presented the emergency preparedness biennial exercise inspection results to Mr. Michael O'Connor, Plant Manager and other members of the licensee staff.

DOCUMENTS REVIEWED

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

71114.01

Corrective Action

Documents

CR 1174850

Miscellaneous

MJUN21BE

Millstone Unit 2 Biennial Exercise Scenario Package for

June 8, 2021

ML20261H597

Dominion Energy Nuclear Connecticut, Inc., Millstone Power

Station Units 1, 2, and 3, Request for Exemption From

Biennial Emergency Preparedness Exercise Requirements in

CFR 50, Appendix E, Sections IV.F.2.b and IV.F.2.c

09/17/2020

ML20287A273

Millstone Power Station, Unit Nos. 1, 2, and 3 - Temporary

Exemption From the Exercise Frequency Requirements of

CFR Part 50, Appendix E, Sections IV.F.2.B AND

IV.F.2.C (EPID L-2020-LLE-0145 [COVID-19])

11/20/2020