IE Insp Rept 50-213/82-05 on 820208-12.No Noncompliance Noted.Major Areas Inspected:Local Leak Rate Testing,Training Qualification,Control Room Activities & post-refueling Startup Testing
ML20050A735
Person / Time
Site: Haddam Neck File:Connecticut Yankee Atomic Power Co icon.png
Issue date: 03/12/1982
From: Bettenhausen L, Chung J, Petrone C
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To:
Shared Package
ML20050A733 List:
References
50-213-82-05, 50-213-82-5, NUDOCS 8204020207
Download: ML20050A735 (8)


Text

. _ _ _ _ _ _ _ _ _ _ _ _ _ _

-

,

.

.

U.S. NUCLEAR REGULATORY COMMISSION Region I Report No.

50-213/82-05 Docket No.

50-213 License No.

OPR-61 Priority Category C

--

Licensee:

Connecticut Yankee Atomic Power Company P. O. Box 270 Hartford, Connecticut 06101 Facility Name: Haddam Neck Plant Inspection at: Haddam, Connecticut Inspection conducted:

February 8-12, 1982 Inspectors:

y -[a b,/ / -Mp_

J['.2/f 2_

O C.' D. Petrone, Reactor Inspector dite signed dl L 4 / ffh~ /s 3hz /? L.

J. W. Chung, Ph.D., Re'ctor Inspector date' signed a

Approved by:

e.dr4 ~

3//7-/91 L. H. Bbttenhausen, Ph.D., Chief, Test Program date signed i

Section, Engineering Inspection Branch Ingection Summary:

l Inspection on February 8-12, 1982 (Report No. 50-213/82-05)

Areas Inspected:

Routine, unannounced inspection of local leak rate testing, training and qualification, control room activities, and post refueling startup testing including, control rod drops, control rod worth and baron worth, isothermal temperature coefficient measurement, shutdown margin, and core outlet thermocouple calibration.

The inspection involved 53 inspector-hours onsite by two region based NRC inspectors.

Results:

No items of noncompliance were identified.

l l

Region I Form 12 (Rev. April 77)

0204020207 820319 PDR ADOCK 05000213

PDR

_ _

_ _ _ _ _ _ _ _ - _

_ _ _ _ _ _ _

.

.

DETAILS 1.

Persons Contacted Principal Licensee Employees I

  • R. C. Beganski, Engineer
  • N. Burnett, Operating Assistant to Engineering
  • J. L. DeLawrence, Senior Engineer, ISI R. Eppinger, Reactor Engineer J. H. Ferguson, Unit Superintendent
  • R. H. Graves, Station Superintendent
  • D. J. Ray, Engineering Supervisor P. Shanley, Licensing Engineer, NUSCO
  • R. Test, Station Service Superintendent M. E. Turner, Assistant ISI Engineer USNRC
  • T. Smith, Resident Inspector The inspectors also interviewed other licensee employees including adminis-trative, operations, and I&C personnel.
  • denotes those present at the exit interview.

2.

Local Leak Rate Testing The inspector performed a review, on a sampling basis, of the Local Leak Rate Testing (LLRT) precedures and test results for conformance with Technical Specifications and 10 CFR 50, Appendix J, Type B and C require-ments to verify:

Technically adequate and approved procedures were used;

--

--

Test personnel were qualified; Special test equipment required by procedures was calibrated;

--

Post maintenance work was parformed for failed LLRT in accordance

--

with facility procedures; Post maintenance LLRT was performed for failed LLRT;

--

LER was issued on failed LLRT; and,

--

Test results were in accordance with the requirements specified in

--

Technical Specifications (TS).

l l

_ _ _ _ _ _ _ _ _ _ _

.

.

a.

LLRT Program The inspector determined by review of the LLRT program procedure, l

SUR 5.7-15-C, Original, February 28, 1980, and 1979-1980 test summary that the following penetrations were excluded from the 10 CFR 50, Appendix J, type B or C tests.

(1) N2 supply line penetration to PRT.

(2) Reactor Coolant Pump (RCP) seal water supply.

(3) Service water to and from the containment cooling coil.

(4) Residual Heat Removal System penetrations.

(5) Main steam line.

(6) Feedwater system.

l The inspector noted that exemptions to Appendix J tests were proposed to the NRC as documented in letters to the NRC dated March 14, 1975 and August 9, 1977, and in a letter from the NRC to the licensee dated March 11, 1977, requesting more information.

The proposed exemptions have yet to be approved by the NRC, and the tests were not performed during that period.

The inspector concurred with the licensee's contention that, even though the Feedwater Isolation Valves were isolated automatically by a Containment Isolation Signal is per TS, Feedwater and Main Steam Penetrations were not subjected to Type C test requirements of Appendix J, Paragraph II-H, 10 CFR 50.

The check valve on the N2 supply penetration to PRT was leak-tested and incorporated into the LLRT programs during 1981 testing.

However, the inspector was concerned with one inboard check valve on the penetration which had no additional outboard isolation valve.

In a licensee letter to NRR dated August 8, 1977, the licensee proposed to install two additional check valves inside of containment and to seismically qualify the lines between the three check valves.

The inspector reviewed design modification packages, i'DCR Summary of January 1,1978 through February,1982, NUSCO Drawings, and CY 50.59 l

l

)

reports, and verified by onsite inspection that the N2 supply line I

was not modified to qualify the line seismically and the proposed check valves were not installed.

It is our understanding that the licensee would resolve this item with NRR.

A licensee representative stated that the items (2), (3) and (4)

listed p uviously would be implemented into the LLRT program prior to the next refueling outage and that these tests would be completed prior to restart. Tcis is an unresolved item pending NRC:RI inspection of additional test implementation into LLRT program (213/82-05-01).

.

.

,

i b.

LLRT Procedure Review I

The inspector verified by review of the station procedure review program and its computer printouts of February 10, 1982, that 29 of 49 LLRT procedures were overdue for review as required by TS 6.8.1 and ANSI N18.7-1976.

The inspector determined that Station Engineering which was reorganized recently recognized the inadequacy of LLRT procedures and their l

review.

The inspector understood that the procedure review would be completed by June 1, 1982.

This is an unresolved item pending NRC:RI inspection on LLRT procedures (213/82-05-02).

c.

Test Results - 1981 The inspector reviewed LLRT results performed between September 23, 1981 and November 14, 1981, and noted that total leak rate was 56,935 lb. of air / day. The acceptance requirement was 882 lb. of air / day at 40 psig. The inspector verified that 56,511 lb. of the total 56,935 lb. air / day leak rate was attributed to component cooling to the neutron shield tank cooler due to valve seat leaks on CC-CV-885.

Subsequently LER 81-18/3L was issued.

Corrective maintenance was performed on CC-CV-885, and LLRT was completed again on October 17, 1981. Total leak rate of 335.21 lb.

of air / day met the acceptance criteria of 882 lb. per day.

The inspectors had no further questions.

3.

Post Refueling Startup Testing a.

A review of the startup testing program was performed to verify conduct and completion of TS requirements.

This review encompassed the following:

--

In-house Startup Report;

--

Control rod drop times; Control rod worth and boron worth;

--

--

Isothermal temperature coefficient measurement;

--

Reactor shutdown margin; and

--

Core outlet thremocouple calibration.

b.

The inspector verified by review of facility records in the following areas that startup testing was conducted in accordance with technically adequate procedures and that the facility is being operated within license limits.

i

_

_.

__._ _

_ _ _. __.

_ _.

_

_ _. _. _ _

_ _ _ _

. - _ ~ _

_

_

,

.

.

t i

i

!

l (1) Post Refueling Startup Report Review i

The inspector and licensee representatives discussed the licensee's l

.

plans to submit a Starccp Report to the NRC.

The licensee

,

stated that a Startup Report would not be submitted because no

changes had taken place during the refueling which would require

,

f a report submittal as specified in the Technical Specifications.

-

.

The inspector verified the licensee's determination by review

'

of the following documents for the Cycle 11 refueling:

.

!

'

r

--

BAW-1680, Connecticut Yankee Cycle 11 Nuclear Design

!

Report, June, 1981.

!

--

BAW letter FPL-81-202, dated November 24, 1981, " Connecticut Yankee Reactor Effects of Cycle 10 Coastdown on Cycle 11".

,

The inspector noted that the licensee's Reactor Engineer is

!

preparing an in-house Startup Physics Test Report which discusses

the tests performed and summarizes the results obtained. The inspector reviewed a preliminary draft of this report.

,

j No items of noncompliance were identified.

(2) Control Rod Drop Times Control rod drop time tests were performed to verify conformance

.

with TS 4.2-2.

The inspector reviewed procedure SUR 5.3-2-C,

Hot Rod Drop Time Measurements, Revision 5, effective April 24,

,

1981, which was used for this verification.

The inspector independently reviewed Visicorder traces for selected rod drops

-

and compared his results to licensee analyses with no discrepancies.

'

l No items of noncompliances were identified.

(3) Control Rod Worth and Boron Worth The control rod reactivity worth and ejected rod worth are

determined in accordance with procedure SUR 5.3-6-C, Control

!

'

Rod Group Reactivity Worth Combined with Boron Worth and Ejected

i Rod Worth, Revision 9, effective April 16, 1981, to meet the l

~

requirements of TS 3.10.

l Procedure SUR 5.3-6-C performed November 7 and 8, 1981, was

reviewed to determine technical adequacy. The measured data were compared with the predicted values for control rod worth.

i The following results were noted.

'

,

l

.

'

.

.

Control Rod Bank Measured Worth Predicted Worth

{%deltak/k)

(% delta k/k)

B

.83 0.78 + 15%*

A 1.99 1.81 I 15%

D 2.28 2.05 T 15%

C 1.78 1.76 7 15%

Total 6.88 6.40i15%

Ejected Control Rod Measured Worth Predicted Worth (% delta k/k)

(% delta k/k)

Bank B at 233 steps Bank A, D, C at 320 steps 8-11

.027

.029 + 20%

B-31

.015

.016120%

Bank A at 170 steps Bank B at 0 steps Bank C, 0 at 320 steps B-11 0.182 0.180 + 20%

B-31 0.112 0.139120%

The inspectors also reviewed reactimeter traces for selected rod worth determinations.

Boron worth determinations for seven critical boron concentrations with corresponding inserted rod worths were compared with predicted values from the Nuclear Design Report. A linear-least-squares-fit to experimental data resulted in an inverse boron worth of 135.5 ppm per % delta k/k.

This value agrees with the predicted values of 145 for all rods in and 149 for all rod out within the allowable tolerance of 112%.

No items of noncompliance were identified.

(4) Isothermal Temperature Coefficient Measurement The licensee measures isothermal temperature coefficient in accordance with procedure SUR 5.3-5-C, " Moderator Temperature Reactivity Coefficient Measurement", Revision 5, April 16, 1981 to comply with the requirements of TS 3.16.

SUR 5.3-5-C was reviewed and found to give satisfactory isothernal temperature coefficient data.

The moderator temperature coefficients (corrected to an equivalent hot, full power moderator coefficient)

averaged -6.88 E-5 delta k/k per 0F which is in close agreement with the predicted value in the Nuclear Design Report of -6.7 E-5 and less than the maximum value of +7.1 E-5 in TS 3.16.

No items of noncompliance were identifie...

.

_ -. ~ - _

- -

-. - - _

_.

- -

.

- - _...

.

.

,

(5) Shutdown Margin

The inspectors reviewed the manner in which the licensee met l

T.S. 3.10.F to demonstrate that a 3*I, delta k/k shutdown margin is maintained during subcritical operations, considering a

'

j stuck control rod.

The total measured worth of the control rods, 6.887 delta k, less 1.10% for stuck rod H2, less.5% for L

uncertainties demonstrates adequate shutdown margin at the

!

'

"

beginning of Cycle 11.

No items of noncompliance were identified.

1 l

(6) Core Outlet Thermocouple Calibration l

The licensee performs an intercomparison of incore thermocouple l

readings and reactor coolant loop resistance temperature devices

(RTD) at hot, isothermal conditions prior to initial criticality

using Procedure PM 9.3-2-C, Revision 2, April 16, 1981. An

offset is then computed and made part of the computer correction to the thermocouple reading.

The offset value is the difference

,

j between the actual thermocoulle reading and the average thermo-couple reading when all outlying values are removed from the

!

average.

The average thermocouple reading was 535.70F. The

'

maximum difference between each operable thermocouples reading

,

and the average isothermocouple temperature (measured by the j

incore thermocouples) was 1.7610F.

The offset for each operable

{

thermocouple was within the + 20F criterion specified in PM

.

'

9.3-2-C.

As a result of this test, nine of the forty-eight thermocouples were declared inoperable and the input from these thermocouples was eliminated from the computer program.

4.

Control Room Observation

,

The inspectors observed control room operations for shift turnover and i

facility operation in accordance with the administrative procedures and l

TS requirements. Documents reviewed included weekly surveillance, shift

-

turnover, shif t logs, and primary-side log sheets.

The inspectors noted two alarms on the Control Center Alarm Board, for which Maintenance Requests were issued to repair a noisy control rod drive

"B" MG set i

bearing and to calibrate on alarm board instrument setpoint.

'

No unacceptable conditions were identified.

'

5.

Unresolved Items f

Unresolved items are matters about which more information is required in

order to ascertain whether they are acceptable, an item of noncompliance, l

or a deviation. The unresolved items identified during the inspection

'

l were discussed in Paragraphs 2.a and 2.b.

!

l

,

.

..

.-

,

. -. -.

-

. -. -

-

- -

....

-. - _,

._-

.

o

.

6.

Exit Interview At the conclusion of this inspection, the inspection scope and findings were presented to the licensee's management (identified in paragraph 1)