ENS 53712
ENS Event | |
|---|---|
04:00 Nov 1, 2018 | |
| Title | En Revision Imported Date 12/31/2018 |
| Event Description | EN Revision Text: UNANALYZED CONDITION DUE TO MODIFICATION NOT ADDED TO PROCEDURE
On November 1, 2018, at approximately 1300 EDT, Fermi 2 identified that a Station Blackout (SBO) procedure was deficient as a result of a modification installed during a recent refueling outage. A review identified that the performance of the SBO procedure could have resulted in a challenge to having an alternate AC source available within one hour as outlined in the Updated Final Safety Analysis Report (UFSAR) 8.4.2. The alternate AC source was always available to be manually aligned in accordance with other standard operating procedures. The modification did not affect the function for Appendix R alternative shutdown. Immediate actions are underway to revise the impacted procedure. The health and safety of the public was not affected as offsite power has remained available since the modification was installed. Investigation into the cause and corrective actions is ongoing. Fermi 2 is reporting this event as an unanalyzed condition pursuant to the requirements of 10 CFR 50.72(b)(3)(ii)(B). The licensee notified the NRC Resident Inspector.
The purpose of this notification is to retract a previous report made on November 1, 2018 (EN 53712) under 10 CFR 50.72(b)(3)(ii)(B). Subsequent to the initial notification, the event, site procedures, and the NRC guidance in NUREG-1022 pertaining to 10 CFR 50.72(b)(3)(ii)(B) were reviewed further. The evaluation determined that at the time of the event, there were multiple methods defined in existing station procedures to establish an available alternate AC source within one hour as outlined in the Updated Final Safety Analysis Report (UFSAR) 8.4.2. Under these circumstances, the event does not represent an unanalyzed condition under 10 CFR 50.72(b)(3)(ii)(B). Therefore, EN 53712 can be retracted and no Licensee Event Report (LER) under 10 CFR 50.73(a)(2)(ii)(B) is required to be submitted. The licensee has notified the NRC Resident Inspector. Notified R3DO (Riemer). |
| Where | |
|---|---|
| Fermi Michigan (NRC Region 3) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition | |
| Time - Person (Reporting Time:+16.17 h0.674 days <br />0.0962 weeks <br />0.0221 months <br />) | |
| Opened: | Jeffrey Myers 20:10 Nov 1, 2018 |
| NRC Officer: | Jeff Herrera |
| Last Updated: | Dec 28, 2018 |
| 53712 - NRC Website
Loading map... | |
Unit 2 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
WEEKMONTHYEARENS 552312021-05-03T13:30:0003 May 2021 13:30:00
[Table view]10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition ENS 537122018-11-01T04:00:0001 November 2018 04:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition En Revision Imported Date 12/31/2018 ENS 536742018-10-19T04:00:00019 October 2018 04:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Low Pressure Core Injection Pumps Incapable of Automatic Startup ENS 527242017-05-02T21:00:0002 May 2017 21:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition for Combustion Turbine Generator Configuration ENS 523422016-11-02T14:34:0002 November 2016 14:34:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition for Control Rod Drop Accident at Low Power ENS 522142016-08-31T23:50:00031 August 2016 23:50:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition with a Potential Tornado ENS 522022016-08-25T20:29:00025 August 2016 20:29:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Mechanical Draft Cooling Tower Declared Inoperable ENS 514402015-10-02T12:25:0002 October 2015 12:25:00 10 CFR 50.72(b)(3)(v)(A), Loss of Safety Function - Shutdown the Reactor, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Loose Safety Relief Valve Discharge Flange Bolts ENS 422242005-12-23T03:25:00023 December 2005 03:25:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Eecw Temperature Control Valve Not Fully Open ENS 418472005-07-18T02:31:00018 July 2005 02:31:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition of Maintenance Bus Tie Breakers ENS 418162005-06-30T23:31:00030 June 2005 23:31:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition Related to the Standby Feedwater Pumps and Control Circuits ENS 417142005-05-18T22:50:00018 May 2005 22:50:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Identification of Design and Operating Procedure Deficiencies Related to Appendix R Events ENS 415512005-03-30T21:00:00030 March 2005 21:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Identification of Design and Operating Procedure Deficiencies 2021-05-03T13:30:00 | |