| Title | Low Pressure Core Injection Pumps Incapable of Automatic Startup |
| Event Description | On 10/19/2018, at approximately 0400 EDT, during an investigation into a failed surveillance test for a Loss of Offsite Power (LOP) coincident with a Loss of Coolant Accident (LOCA), it was identified that the Engineered Safety System Bus degraded voltage relay scheme contained a time delay setting that could inhibit all Low Pressure Core Injection (LPCI) pumps from automatically starting and operating during a LOP/LOCA, thus making LPCI incapable of meeting its functional requirement of automatic startup and operation regardless of the availability of offsite power supply (UFSAR Section 6.3.1.4 and Tech. Spec. Surveillance Requirement 3.8.1.17).
The condition was identified during the first-time performance of a revised surveillance procedure for a LOP coincident with a LOCA signal. Fermi is currently in Mode 4 (Cold Shutdown) and LPCI auto start on a LOP/LOCA signal is not required. However, the initial investigation identified the condition likely existed in the past during modes of operation where LPCI auto start on LOP/LOCA was required. Investigation into the cause and corrective actions is ongoing. Since LPCI auto start is not required at the time of discovery (Mode 4), this event is being reported pursuant to 50.72(b)(3)(ii)(b). The NRC Resident Inspector has been notified. |
| Where | |
|---|---|
| Fermi Michigan (NRC Region 3) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition | |
| LER: | 05000341/LER-2018-006 Emergency Diesel Generator Load Sequencer Inhibits Automatic Start of Residual Heat Removal Pumps Under Certain Scenarios Due to Unrecognized Original Design Defect |
| Time - Person (Reporting Time:+6 h0.25 days <br />0.0357 weeks <br />0.00822 months <br />) | |
| Opened: | Justin D. Wilhelm 10:00 Oct 19, 2018 |
| NRC Officer: | Ossy Font |
| Last Updated: | Oct 19, 2018 |
| 53674 - NRC Website
Loading map... | |
Unit 2 | |
|---|---|
| Reactor critical | Not Critical |
| Scram | No |
| Before | Cold Shutdown (0 %) |
| After | Cold Shutdown (0 %) |
WEEKMONTHYEARENS 552312021-05-03T13:30:0003 May 2021 13:30:00
[Table view]10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition ENS 537122018-11-01T04:00:0001 November 2018 04:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition En Revision Imported Date 12/31/2018 ENS 536742018-10-19T04:00:00019 October 2018 04:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Low Pressure Core Injection Pumps Incapable of Automatic Startup ENS 527242017-05-02T21:00:0002 May 2017 21:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition for Combustion Turbine Generator Configuration ENS 523422016-11-02T14:34:0002 November 2016 14:34:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition for Control Rod Drop Accident at Low Power ENS 522142016-08-31T23:50:00031 August 2016 23:50:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition with a Potential Tornado ENS 522022016-08-25T20:29:00025 August 2016 20:29:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Mechanical Draft Cooling Tower Declared Inoperable ENS 514402015-10-02T12:25:0002 October 2015 12:25:00 10 CFR 50.72(b)(3)(v)(A), Loss of Safety Function - Shutdown the Reactor, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Loose Safety Relief Valve Discharge Flange Bolts ENS 422242005-12-23T03:25:00023 December 2005 03:25:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Eecw Temperature Control Valve Not Fully Open ENS 418472005-07-18T02:31:00018 July 2005 02:31:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition of Maintenance Bus Tie Breakers ENS 418162005-06-30T23:31:00030 June 2005 23:31:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition Related to the Standby Feedwater Pumps and Control Circuits ENS 417142005-05-18T22:50:00018 May 2005 22:50:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Identification of Design and Operating Procedure Deficiencies Related to Appendix R Events ENS 415512005-03-30T21:00:00030 March 2005 21:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Identification of Design and Operating Procedure Deficiencies 2021-05-03T13:30:00 | |