ENS Event | |
|---|---|
20:29 Aug 25, 2016 | |
| Title | Mechanical Draft Cooling Tower Declared Inoperable |
| Event Description | At 1629 EDT on August 25, 2016, it was determined that a Mechanical Draft Cooling Tower (MDCT) fan should be declared inoperable if its associated fan brake is nonfunctional. The MDCT fan brake is required to prevent fan over speed from a design basis tornado. The MDCT fans are required to support the operability of the Ultimate Heat Sink (UHS). Currently, the MDCT fans and fan brakes are operable. A past operability evaluation is being performed and has initially identified that from 0855 EDT to 1738 EDT on April 6, 2016, the Division 1 'A' fan brake was nonfunctional due to a nitrogen bottle being below the required pressure. Additionally, from 0856 EDT on April 6, 2016, to 1641 EDT on April 7, 2016, the Division 1 'C' fan brake was also nonfunctional due to a nitrogen bottle being below the required pressure. Therefore, the Division 1 UHS and associated Emergency Diesel Generators (EDGs) would have been inoperable. During this time, at 1347 EDT on April 6, 2016, the Division 2 EDG 14 was inoperable for 22 seconds for a planned testing.
This resulted in an unanalyzed condition because the plant configuration during the 22 seconds when EDG 14 was inoperable would not support safe shutdown capability in the event of a tornado. A past operability review is in progress to determine if declaring a MDCT fan inoperable due to a fan brake being nonfunctional results in any additional instances of unanalyzed condition within the past three years. This condition is reportable under 10 CFR 50.72(b)(3)(ii)(B), as an event or condition that results in an unanalyzed condition that significantly degrades plant safety. There was no adverse impact to public health and safety or to plant employees. The NRC Resident Inspector has been notified. |
| Where | |
|---|---|
| Fermi Michigan (NRC Region 3) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition | |
| LER: | 05000341/LER-2016-006 Regarding Inadequate Interpretation of Technical Specifications Related to Mechanical Draft Cooling Tower Fan Brake System Leads to Condition Prohibited by Technical Specifications Loss of Safety Function and Unanalyzed |
| Time - Person (Reporting Time:+1.17 h0.0488 days <br />0.00696 weeks <br />0.0016 months <br />) | |
| Opened: | Brett Jebbia 21:39 Aug 25, 2016 |
| NRC Officer: | Dong Park |
| Last Updated: | Aug 25, 2016 |
| 52202 - NRC Website
Loading map... | |
Unit 2 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (53 %) |
| After | Power Operation (53 %) |
WEEKMONTHYEARENS 552312021-05-03T13:30:0003 May 2021 13:30:00
[Table view]10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition ENS 537122018-11-01T04:00:0001 November 2018 04:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition En Revision Imported Date 12/31/2018 ENS 536742018-10-19T04:00:00019 October 2018 04:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Low Pressure Core Injection Pumps Incapable of Automatic Startup ENS 527242017-05-02T21:00:0002 May 2017 21:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition for Combustion Turbine Generator Configuration ENS 523422016-11-02T14:34:0002 November 2016 14:34:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition for Control Rod Drop Accident at Low Power ENS 522142016-08-31T23:50:00031 August 2016 23:50:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition with a Potential Tornado ENS 522022016-08-25T20:29:00025 August 2016 20:29:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Mechanical Draft Cooling Tower Declared Inoperable ENS 514402015-10-02T12:25:0002 October 2015 12:25:00 10 CFR 50.72(b)(3)(v)(A), Loss of Safety Function - Shutdown the Reactor, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Loose Safety Relief Valve Discharge Flange Bolts ENS 422242005-12-23T03:25:00023 December 2005 03:25:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Eecw Temperature Control Valve Not Fully Open ENS 418472005-07-18T02:31:00018 July 2005 02:31:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition of Maintenance Bus Tie Breakers ENS 418162005-06-30T23:31:00030 June 2005 23:31:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition Related to the Standby Feedwater Pumps and Control Circuits ENS 417142005-05-18T22:50:00018 May 2005 22:50:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Identification of Design and Operating Procedure Deficiencies Related to Appendix R Events ENS 415512005-03-30T21:00:00030 March 2005 21:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Identification of Design and Operating Procedure Deficiencies 2021-05-03T13:30:00 | |