| Title | Loss of High Pressure Coolant Injection |
| Event Description | On Tuesday, January 27, 2015, at 0948 EST, with the Reactor Mode Select Switch (RMSS) in the Shutdown position and Pilgrim Nuclear Power Station (PNPS) at 0% core thermal power, the High Pressure Coolant Injection (HPCI) system was isolated by the main control room operating crew and declared INOPERABLE. HPCI had been in service for reactor pressure control following the automatic reactor scram experienced during winter storm 'Juno' reported in EN 50769. It appears there was a malfunction of the HPCI turbine gland seal condenser blower or associated condensate pump. Reactor pressure control was transitioned to the safety relief valves and the reactor cooldown was continued. The plant is stable. The Emergency Diesel Generators are powering the safety related 4KV buses and reactor water level is being maintained by the Reactor Core Isolation Cooling (RCIC) system. HPCI is required to be OPERABLE in accordance with Technical Specification 3.5.C.1. Since HPCI is a single train system, the INOPERABILITY is reportable in accordance with 10CFR50.72(b)(3)(v)(D). The cause of the HPCI malfunction is not known at this time and troubleshooting continues.
This event had no impact on the health and/or safety of the public. The USNRC Senior Resident Inspector has been notified. Shutdown cooling is in service. |
| Where | |
|---|---|
| Pilgrim Massachusetts (NRC Region 1) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident | |
| LER: | 05000293/LER-2015-001 Regarding Loss of 345KV Power Resulting in Automatic Reactor Scram During Winter Storm Juno |
| Time - Person (Reporting Time:+2.13 h0.0888 days <br />0.0127 weeks <br />0.00292 months <br />) | |
| Opened: | John Whalley 16:56 Jan 27, 2015 |
| NRC Officer: | John Shoemaker |
| Last Updated: | Jan 27, 2015 |