ENS 41800
ENS Event | |
---|---|
07:16 Jun 27, 2005 | |
Title | Declaration of an Unusual Event Due Transformer Fire >10 Minutes |
Event Description | UNUSUAL EVENT (EAL #16 - Fire) declared at 0327 on 6/27/05 due to uncontrolled fire in the Unit 4 Main Transformer lasting longer than 10 minutes. Unit 4 experienced an automatic reactor trip from 100% on a turbine trip due to a fire in the Main Transformer. The fire was extinguished after approximately 25 minutes. On-site fire brigade and Miami-Dade fire department responded. The cause of the fire is under investigation.
The reactor is stable in Mode 3. No safety systems were affected. All rods fully inserted, no ECCS actuations, no relief valves lifted and no personnel injuries occurred. Offsite power is still available and no emergency diesels auto started, however, there was an auxiliary feedwater actuation. Hazardous Material response is being implemented due to discharge of transformer oil. There may be a possible press release on this event. The NRC Resident Inspector was notified along with State and local agencies.
The NOUE was terminated at 05:00 due to the fire being extinguished and the emergency no longer existing. The NRC Resident Inspector was notified. Notified RDO 3 (Evans), EDO (Case), IRO (Frant), FEMA (Bagwell), DHS (Reed)
Received a call from a member of the Turkey Point Communications Group. The licensee does not plan on issuing a press release at this time. Notified R2DO (Evans). |
Where | |
---|---|
Turkey Point ![]() Florida (NRC Region 2) | |
Reporting | |
Emergency class: | Unusual Event |
10 CFR 50.72(a) (1) (i), Emergency Class Declaration 10 CFR 50.72(b)(2)(iv)(B), RPS Actuation 10 CFR 50.72(b)(3)(iv)(A), System Actuation 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release | |
Time - Person (Reporting Time:+-2.95 h-0.123 days <br />-0.0176 weeks <br />-0.00404 months <br />) | |
Opened: | Jim Speicher 04:19 Jun 27, 2005 |
NRC Officer: | Chauncey Gould |
Last Updated: | Jun 27, 2005 |
41800 - NRC Website
Loading map... {"minzoom":false,"maxzoom":false,"mappingservice":"leaflet","width":"350px","height":"250px","centre":false,"title":"","label":"","icon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"zoom":6,"defzoom":14,"layers":["OpenStreetMap"],"image layers":[],"overlays":[],"resizable":false,"fullscreen":false,"scrollwheelzoom":true,"cluster":false,"clustermaxzoom":20,"clusterzoomonclick":true,"clustermaxradius":80,"clusterspiderfy":true,"geojson":"","clicktarget":"","imageLayers":[],"locations":[{"text":"\u003Cb\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003E\u003Ca class=\"mw-selflink selflink\"\u003EENS 41800\u003C/a\u003E - \u003Ca href=\"/Turkey_Point\" title=\"Turkey Point\"\u003ETurkey Point\u003C/a\u003E\n\u003C/p\u003E\u003C/div\u003E\u003C/b\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003E[[Declaration of an Unusual Event Due Transformer Fire \u0026gt;10 Minutes]]\n\u003C/p\u003E\u003C/div\u003E","title":"ENS 41800 - Turkey Point\n","link":"","lat":25.435330555555556,"lon":-80.33125833333334,"icon":"/w/images/9/9b/NextEra_Energy_icon.png"}],"imageoverlays":null} | |
Unit 4 | |
---|---|
Reactor critical | Critical |
Scram | A/R |
Before | Power Operation (100 %) |
After | Hot Standby (0 %) |
Turkey Point ![]() | |
WEEKMONTHYEARENS 568132023-10-25T01:59:00025 October 2023 01:59:00
[Table view]10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip ENS 567552023-09-22T22:19:00022 September 2023 22:19:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip ENS 566582023-08-04T17:20:0004 August 2023 17:20:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip ENS 562642022-12-08T19:02:0008 December 2022 19:02:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Due to Excessive Reactor Coolant System Leakage ENS 555132021-10-09T07:00:0009 October 2021 07:00:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Auxiliary Feedwater System AUTO-STARTED on Feedwater Isolation Signal ENS 551532021-03-25T01:29:00025 March 2021 01:29:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notice of Unusual Event Declared Due to Fire Alarm in Containment ENS 551172021-03-01T16:12:0001 March 2021 16:12:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Automatic Reactor Trip Due to Reactor Protection System Actuation ENS 551092021-02-20T23:30:00020 February 2021 23:30:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Three Individuals in Distress Offshore of the Facility ENS 548472020-08-21T03:54:00021 August 2020 03:54:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Manual Reactor Trip Due to Steam Generator Water Level Control ENS 548442020-08-19T17:25:00019 August 2020 17:25:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Automatic Reactor Trip During Startup ENS 548392020-08-18T01:13:00018 August 2020 01:13:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Manual Reactor Trip Due to Rising Steam Generator Level ENS 547622020-07-06T01:09:0006 July 2020 01:09:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Reactor Trip Due to Turbine Trip ENS 544232019-12-05T17:20:0005 December 2019 17:20:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Deceased Manatee in Owner Controlled Area ENS 540722019-05-18T15:08:00018 May 2019 15:08:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip Due Grid Disturbance ENS 529602017-09-10T22:55:00010 September 2017 22:55:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip on Lowering Steam Generator Water Level ENS 529522017-09-08T03:14:0008 September 2017 03:14:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notification of Unusual Event - Hurricane Warning ENS 526212017-03-18T15:19:00018 March 2017 15:19:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Alert Declared for Indications of Fire in Safety Related Switchgear ENS 526232017-03-18T15:07:00018 March 2017 15:07:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(iv)(A), System Actuation, 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Reactor Trip and Loss of Ability for Unit 4 to Supply Power to Unit 3 ENS 521362016-07-30T07:33:00030 July 2016 07:33:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Turkey Point Unit 3 Shutdown Due to Water Hammer ENS 515182015-11-06T16:38:0006 November 2015 16:38:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Deceased American Crocodile ENS 511472015-06-11T12:22:00011 June 2015 12:22:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Inadvertent Emergency Plan Siren Actuation ENS 510652015-05-12T08:30:00012 May 2015 08:30:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Reactor Trip Due to Main Generator Differential Trip ENS 509212015-03-25T19:25:00025 March 2015 19:25:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Sheepshead Minnow Mortality in Cooling Canal System ENS 506452014-11-30T18:54:00030 November 2014 18:54:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Auxiliary Feedwater Actuation Due to Planned Reactor Trip ENS 506242014-11-17T11:08:00017 November 2014 11:08:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Emergency Siren Malfunction ENS 503542014-08-11T14:20:00011 August 2014 14:20:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip on Loss of Instrument Air Followed by Safety Injection ENS 503062014-07-24T20:04:00024 July 2014 20:04:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Deceased American Crocodile ENS 501402014-05-25T09:36:00025 May 2014 09:36:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Automatic Reactor Trip Due to Turbine Trip on Loss of Condenser Vacuum ENS 500542014-04-23T17:02:00023 April 2014 17:02:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Specified System Actuation During Rod Testing ENS 490212013-05-10T15:08:00010 May 2013 15:08:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Unit 3 Manual Reactor Trip Due to Malfunction of Turbine Valves ENS 489482013-04-19T21:20:00019 April 2013 21:20:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unusual Event Due to Loss of Offsite Power Greater than 15 Minutes ENS 488212013-03-13T15:20:00013 March 2013 15:20:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Afw Actuation Due to Trip of 3B Feedwater Pump ENS 488172013-03-12T18:31:00012 March 2013 18:31:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Automatic Reactor Trip Due to Turbine Inlet Pressure Perturbation ENS 487642013-02-18T06:31:00018 February 2013 06:31:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip Due to High Seal Leakoff on Reactor Coolant Pump 3A ENS 487442013-02-12T03:36:00012 February 2013 03:36:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip Due to Turbine Trip on Loss of Condenser Vacuum ENS 485472012-11-30T08:10:00030 November 2012 08:10:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification - 40 Gallons of Diesel Fuel Spilled in Oca ENS 481542012-08-02T13:00:0002 August 2012 13:00:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Non-Work Related Onsite Fatality ENS 477972012-04-02T23:33:0002 April 2012 23:33:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event - Fire from Hydrogen Supply to Volume Control Tank ENS 473492011-10-18T04:56:00018 October 2011 04:56:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Waste Water Spill ENS 467672011-04-19T14:45:00019 April 2011 14:45:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Fatality of a Contract Employee ENS 466602011-03-06T21:44:0006 March 2011 21:44:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Manual Reactor Trip Due to Secondary Sodium Concentrations Exceeding Chemistry Limits ENS 464712010-12-10T03:58:00010 December 2010 03:58:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Manual Reactor Trip After Indications of a Condenser Tube Leak ENS 464192010-11-15T11:03:00015 November 2010 11:03:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip Due to Loss of a Circulating Water Pump with Another Pump Out of Service for Maintenance ENS 462742010-09-23T21:14:00023 September 2010 21:14:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Reactor Trip Due to Inadvertent Energization Generator Trip ENS 462652010-09-22T00:17:00022 September 2010 00:17:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip ENS 462462010-09-09T19:34:0009 September 2010 19:34:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip During Startup Due to a Control Bank Step Counter Failure ENS 462352010-09-08T17:45:0008 September 2010 17:45:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip During Maintenance on a Reactor Protection System Relay ENS 456192010-01-11T15:55:00011 January 2010 15:55:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip Initiated Due to High Steam Generator Level ENS 455222009-11-27T04:40:00027 November 2009 04:40:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Two Shutdown Bank Rods Were Dropped from Fully Withdrawn Position ENS 455212009-11-26T18:28:00026 November 2009 18:28:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Cuban Nationals Landing on Owners Controlled Area ENS 451982009-07-12T11:20:00012 July 2009 11:20:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Law Enforcement Notified of Discovery of Firearm During X-Ray Screening ENS 449082009-03-16T14:45:00016 March 2009 14:45:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to 1 Gallon Oil Spill at Fossil Units ENS 447512009-01-03T16:55:0003 January 2009 16:55:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification to State Agency Due to Minor Diesel Fuel Oil Spill ENS 447022008-12-07T19:05:0007 December 2008 19:05:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Spill of Fuel Oil ENS 447012008-12-06T16:26:0006 December 2008 16:26:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Waste Water Discharge ENS 446962008-12-04T20:15:0004 December 2008 20:15:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Request for Law Enforcement Assistance Involving an Undentified Substance ENS 445022008-09-18T18:15:00018 September 2008 18:15:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification to Miami-Dade County Due to Spill ENS 443622008-07-23T21:08:00023 July 2008 21:08:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification of Oil Spill to Florida Dept. of Environmental Protection ENS 441282008-04-09T03:50:0009 April 2008 03:50:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification to Osha for Fatality Onsite Due to an Apparent Heart Attack ENS 441152008-04-01T15:26:0001 April 2008 15:26:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification to State of Florida Due to Chromate Spill ENS 441072008-03-29T14:00:00029 March 2008 14:00:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Oil Waste Discharge Into Storm Drain Onsite ENS 440162008-02-29T09:51:00029 February 2008 09:51:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Manual Reactor Trip Due to High Steam Generator Water Level ENS 440092008-02-26T18:09:00026 February 2008 18:09:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Units 3 and 4 Tripped Due to Grid Fluctuations ENS 432892007-04-06T20:00:0006 April 2007 20:00:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification - Spill of Molybdates from Ccw. ENS 427952006-08-23T13:40:00023 August 2006 13:40:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Potential News Worthy Event ENS 427662006-08-14T01:30:00014 August 2006 01:30:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Made Due to an Oil Spill at Turkey Point ENS 426172006-06-03T19:45:0003 June 2006 19:45:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification of a Fuel Oil Spill ENS 423992006-03-08T20:53:0008 March 2006 20:53:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Valid Actuation of Emergency Diesel Generators ENS 421372005-11-11T20:02:00011 November 2005 20:02:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip During Startup Following Failure of Rod Control Power Cabinet ENS 421042005-11-01T03:27:0001 November 2005 03:27:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unusual Event Declaration: Loss of Offsite Power Due to Loss of Startup Transformer ENS 420782005-10-26T01:40:00026 October 2005 01:40:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to a Small Fire at the Main Turbine Area ENS 420672005-10-23T02:54:00023 October 2005 02:54:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to Hurricane Wilma ENS 420562005-10-15T11:02:00015 October 2005 11:02:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Auxiliary Feedwater Actuation on a Manual Reactor Trip ENS 420012005-09-19T15:04:00019 September 2005 15:04:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to Hurricane Rita ENS 419432005-08-25T03:04:00025 August 2005 03:04:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to Hurricane Warning ENS 418002005-06-27T07:16:00027 June 2005 07:16:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Declaration of an Unusual Event Due Transformer Fire >10 Minutes ENS 417432005-06-03T04:33:0003 June 2005 04:33:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Declared Unusual Event Due to Rcs Leakage in Excess of Technical Specification Limit ENS 415162005-03-24T00:56:00024 March 2005 00:56:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Reactor Manually Tripped from 20% Power During Load Reduction. ENS 415112005-03-22T08:47:00022 March 2005 08:47:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Reactor Manually Tripped Following Loss of Main Feed Pump ENS 415082005-03-21T15:45:00021 March 2005 15:45:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification to Derm About Fuel Oil Spill ENS 415772005-03-12T15:00:00012 March 2005 15:00:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification of Inappropriately Marked Radioactive Material Packages ENS 412982004-12-29T03:46:00029 December 2004 03:46:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip Due to Generator Exciter Cooling Water Leak ENS 412922004-12-25T12:36:00025 December 2004 12:36:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Unit4 Manually Tripped Due to Lowering Condenser Vacuum ENS 412572004-12-14T16:45:00014 December 2004 16:45:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Reactor Manually Tripped Due to Fire on Unit 3 Hp Turbine ENS 412322004-11-30T13:50:00030 November 2004 13:50:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation, 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Technical Specification Required Shutdown Due to Dropped Control Rod ENS 412292004-11-29T05:09:00029 November 2004 05:09:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation, 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Technical Specifications Required Shutdown Due to Dropped Control Rod ENS 410832004-10-01T18:15:0001 October 2004 18:15:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Death of a Contract Employee from an Apparent Heart Attack ENS 410682004-09-24T21:00:00024 September 2004 21:00:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to Hurricane Warning ENS 410642004-09-22T20:00:00022 September 2004 20:00:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification to Miami-Dade County ENS 410452004-09-17T00:10:00017 September 2004 00:10:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Oil Spill and Fire ENS 410072004-09-02T14:56:0002 September 2004 14:56:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notification of Unusual Event Declared ENS 407522004-05-14T21:29:00014 May 2004 21:29:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Scram Due to Lowering Steam Generator Level ENS 402432003-10-13T21:00:00013 October 2003 21:00:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Injured Crocodile Found on Plant Access Road 2023-09-22T22:19:00 | |