Title | Failure to Timely Correct Conditions Adverse to Fire Protection |
Description | The team identified a violation of License Condition 2.E for the failure to correct a noncompliance. Procedure OPOP04-Z0-0001, "Control Room Evacuation;' Revision 35, was not consistent with the post-fire safe shutdown analysis in that it failed to ensure the actions met critical time requirements. The licensee failed to implement timely corrective actions to correct this deficiency. Inspection Report 05000498/2011006 and 05000499/2011006 documented a violation involving the failure to implement and maintain in effect all provisions of the approved fire protection program. During this inspection, the team identified that the licensee had failed to restore compliance with its license condition within a reasonable time. The licensee's failure to implement timely corrective actions to correct conditions adverse to fire protection as required by its Operations Quality Assurance Plan is a performance deficiency. This performance deficiency was of more than minor safety significance because it was associated with the mitigating systems cornerstone and adversely affected the cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events (such as fire) to prevent undesirable consequences. Specifically, the licensee failed to ensure reliability of its post-fire safe shutdown systems by demonstrating that it could achieve safe shutdown following a fire in the control room by using approved actions. The significance of this finding could not be evaluated using Inspection Manual Chapter 0609, Appendix F, Fire Protection Significance Determination Process, because the performance deficiency involved a control room fire that led to control room evacuation. A senior reactor analyst determined that the upper bound for the overall change in core damage frequency that resulted from this performance deficiency was 2. 702E-7/yr and was not significant with respect to large early release frequency. The analyst therefore determined that this performance deficiency was of very low risk significance (Green). The team determined that the performance deficiency had a cross-cutting aspect in the corrective action component of the problem identification and resolution cross-cutting area because the licensee did not thoroughly evaluate the problem such that resolutions addressed the cause. Specifically, the licensee failed to take adequate corrective actions to ensure that operators could perform all necessary manual actions as approved prior to exceeding the regulatory requirements |
Site: | South Texas |
---|---|
Report | IR 05000498/2012007 Section 4OA2 |
Date counted | Dec 31, 2012 (2012Q4) |
Type: | Violation: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71152 |
Inspectors (proximate) | A Rosebrook A Sanchez N Hernandez S Alferinkb Tharakanr Kellar M Hayes S Achen |
CCA | P.2, Evaluation |
INPO aspect | PI.2 |
' | |
Finding - South Texas - IR 05000498/2012007 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (South Texas) @ 2012Q4
Self-Identified List (South Texas)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||