05000483/LER-2021-001, Manual Actuation of Essential Service Water System

From kanterella
Jump to navigation Jump to search
Manual Actuation of Essential Service Water System
ML21098A254
Person / Time
Site: Callaway 
Issue date: 04/08/2021
From: Bianco F
Ameren Missouri, Union Electric Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
ULNRC-06640 LER 2021-001-00
Download: ML21098A254 (7)


LER-2021-001, Manual Actuation of Essential Service Water System
Event date:
Report date:
Reporting criterion: 10 CFR 50.73(a)(2)(iv)(A), System Actuation

10 CFR 50.73(a)(2)(x)

10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor

10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat

10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown

10 CFR 50.73(a)(2)(v), Loss of Safety Function

10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications

10 CFR 50.73(a)(2)(i)

10 CFR 50.73(a)(2)(vii), Common Cause Inoperability

10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded

10 CFR 50.73(a)(2)(viii)(A)

10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition

10 CFR 50.73(a)(2)(viii)(B)

10 CFR 50.73(a)(2)(iii)

10 CFR 50.73(a)(2)
4832021001R00 - NRC Website

text

Callaway Plant MISSOURI April 08, 2021 ULNRC-06640 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555-0001 10 CFR 50.73 Ladies and Gentlemen:

DOCKET NUMBER 50-483 CALLAWAY PLANT UNIT 1 UNION ELECTRIC COMPANY RENEWED FACILITY OPERATING LICENSE NPF-30 LICENSEE EVENT REPORT 2021-001-00 MANUAL ACTUATION OF ESSENTIAL SERVICE WATER SYSTEM The enclosed licensee event report is submitted in accordance with 10 CFR 50.73(a)(2)(iv)(A) to report an event or condition that resulted in a manual actuation ofthe essential service water system.

This letter does not contain any new commitments.

Frederick Bianco Senior Director, Nuclear Operations

Enclosure:

LER 202 1-001-00 8315 County Road 459 Steedman, MO 65077 AmerenMissouri.com

ULNRC-06640 April 08, 2021 Page 2 of 3 cc:

Mr. Scoff A. Morris Regional Administrator U. S. Nuclear Regulatory Commission Region IV 1600 East Lamar Boulevard Arlington, TX 76011-4511 Senior Resident Inspector Callaway Resident Office U.S. Nuclear Regulatory Commission 8201 NRC Road Steedman, MO 65077 Mr. M. Chawla Project Manager, Callaway Plant Office ofNuclear Reactor Regulation U. S. Nuclear Regulatory Commission Mail Stop O8B1A Washington, DC 20555-0001

ULNRC-06640 April 08, 2021 Page 3 of 3 Index and send hardcopy to QA File A160.0761 Hardcopy:

Certrec Corporation 6500 West Freeway, Suite 400 fort Worth, TX 76116 (Certrec receives ALL attachments as long as they are non-safeguards and may be publicly disclosed.)

Electronic distribution for the following can be made via Tech Spec ULNRC Distribution:

F. M. Diya B. L. Cox F. J. Bianco S. P. Banker S. J. Meyer T. B. Elwood Corporate Oversight N$RB Secretary Performance Improvement Coordinator STARS Regulatory Affairs Mr. Jay Silberg (Pillsbury Winthrop Shaw Pittman LLP)

Missouri Public Service Commission

NRC FORM 366 U.S. NUCLEAR REGULATORY COMMISSION APPROVED BY 0MB: NO. 3150-0104 EXPIRES: 0813112023 (08-2020)

Esmated burden per response to comply with this mandatory collection request 80 hours9.259259e-4 days <br />0.0222 hours <br />1.322751e-4 weeks <br />3.044e-5 months <br />. Reported LIC E N S E E EVE NT REP0RT LE R learned are incorporated into the licensing process and fed back to industry. Send comments I

t I

regarding burden esbmate to the FOPA, Library, and Information Collections Branch (T-6 A1OM), U.S.

(See Page 3 for required number of digitslchamcters for each block)

Nuclear Regulatori Commission, Washington, DC 20555-0001, or by e-mail to lntscollects.Resourcenrc.gov, and the 0MB reviewer at 0MB Office of Informabon and Regulatory (See NUREG-1022, R.3 for instruction and guidance for completing this form

Affairs, (3150-0104),

AUn:

Desk au: oira_submission(ffiomb.eon.gov.

The NRC may not conduct or hftps:llwww.nrc.qovlreading-rrnldoc-collections/nureqslstafflsrl022/r3/)

alorn unless the document

3. Page Callawav Plant. Unit No. I 05000483 1 OF 4
4. Title Manual Actuation of Essential Service Water System
5. Event Date
6. LER Number
7. Report Date
8. Other Facilities Involved Facility Name Docket Number Month Day Year Year SIUfltI5I Revision Month Day Year 5000

Facility Name Docket Number 02 09 2021 2021

- 001 00 04 08 2021 osooo L Operafing Mode
10. Power Level MODE3 000
11. This RepOrtiS Submitted Pursuanttothe Requiremenis oflO CFR:

(Check all that apply)

I 0 CFR Part 20 D

20.2203(a)(2)(vi)

E 50.36(c)(2) 50.73(a)(2)(iv)(A) 50.73(a)(2)(x)

LI 20.2201 (b) 20.2203(a)(3)(i)

U 50.46(a)(3)(ii) 50.73(a)(2)(v)(A)

I 0 CFR Part 73 El 20.2201(d)

E 20.2203(a)(3)(ii)

El 50.69(g) fl 50.73(a)(2)(v)(B)

El 73.71(a)(4)

D 20.2203(a)(1)

LI 20.2203(a)(4) 50.73(a)(2)(i)(A) 50.73(a)(2)(v)(C) 73.71(a)(5)

El 20.2203(a)(2)(i) 10 CFR Part 21 El 50.73(a)(2)(i)(B)

El 50.73(a)(2)(v)(D)

E 73.77(a)(1)Q)

El 20.2203(a)(2)(H) fl 21.2(c)

E 50.73(a)(2)(i)(C) fl 50.73(a)(2)(vii)

El 73.77(a)(2)(i) 20.2203(a)(2)(iii) 10 CFR Part 50 E

50.73(a)(2)(ii)(A)

E 50.73(a)(2)(viii)(A)

E1 73.77(a)(2)(ii)

LI 20.2203(a)(2)(iv) 50.36(c)(1)(i)(A)

El 50.73(a)(2)(ii)(B)

El 50.73(a)(2)(viii)(B)

El 20.2203(a)(2)(v) 50.36(c)(1)(ii)(A) 50.73(a)(2)(iii)

E 50.73(a)(2)Qx)(A)

LI Other (Specify here, in Abstract, or in NRC 366A).

12. Licensee Contactforthis LER icensee Contact hone Number (Indude Area Code) r. B. Elwood, Supervising Engineer, Regulatory Affairs and LiCensing 314-225-1 905
13. Complete One lineforeach ComionentFaiIure Descdbed inthis Repoit

Cause

System Component Manufacturer Reportable To IRIS

Cause

System Component Manufacturer Reportable To IRIS

14. Supplemental Report Expected Month Day Year
15. Expected Submission Date No D Yes (lfyes, complete 15. Expected Submission Date)
16. Absfract(Umftto 1560 spaces, i.e., approximately 15 single-spaced typewritten lines)

On February 9, 2021

, at 0838 operators commenced placing both trains of Essential ServiCe Water (ESW) in manual alignments in accordance with annunciator response procedure OTA-RK-00014, Addendum 12A, ServiCe Water Pump Lockout. The manual actuation of ESW was in response to a condition where two non-safety Service Water (SW) pumps ripped and locked out due to low lubrication (lube) water pressure.

the cause of the trips and subsequent lockouts of the A and B SW pumps was attributed to low lube water pressure caused by fouling of the lube water Y-strainers. The fouling occurred since the normal weekly backflush of the Y-strainers could not be performed while a temporary alteration in support of maintenance (TASM) was installed in order to repair a leak in the permanent lube water piping. Preventive Maintenance (PM) tasks had not been initiated prior to the event to periodically clean the Y-strainers in order to compensate for the inability to backflush.

rhe initial corrective action taken in response to the event was cleaning of the Y-strainers in the lube water piping.

In addition, PM tasks were created to clean the Y-strainers on a weekly basis for the remaining time that the TASM was installed.

The permanent corrective action was to complete a modification to replace the section of the common lube vater piping where the leak occurred.

Both trains of ESW were returned to standby alignments on February 9, 2021 at I 140.

Jo 068d (oo-9o) 99 dOd OdN (spunoj oeedo eP!SflO 6uunp siseq API99M e uo pewioj.ied AiiewJou SI bU!qSfl3Eq svieq4Q) p9U!BU!Ew eqou PInOD eJnss3Jd pue MOD JM qn j SJU!84S-A ]8M eqn 9q uep O qo[ e 94B!1!U! O SM eoupin6 eq 6uqsnppeq 40 PB1SUI pewjopd eq ou pinoo 6uqsnj3eq Bq qons 6uidid ]9BM aqn MS 94O uo!Jn6uoo pei svi +/- peqsnjoeq q TOU pflOt.S S]9U!B]S-A J98M eqn dwnd MS 11TTL1 s.ioBJdo o suo!43flJ4su! 6U!A!6 svi e qiiv 6uoiE penss! S8M po q6u y Aiddns J9TBM eqnj [>j :5iiJ dwnd (MD) J8M 6ueIno]!o 1V WOJ4 sdwnd MS eq OTJBM eqn pe!Iddns qot.pv PeIIEsu! SBM (yjJ oueueuiew jo ioddns U! Uo!e]Ie Meodwe e ei ; 91e1os! O))O UI sdwnd MS 1T OJTM eqn 6U!Alddns ]9pe9q UOWWOO q UO p9Up! SeM iEI edid e

MeflUBf UO U9A3 Gq O]OUd eJnss9Jd ]9M eqn MOl 04 9fl flO PNOOI PU pedduT sdwnd MS A44BS-UOU oivv eeqv UOEIJPUOO B O 9SUOUS9] U! SM MS 40 UO!1fl IEflUEW eq flO)jDO7 dwnd J9eM 3!M9S WflPU9PPV [OOO-i-V1O enpood esUods3] ]oTe!OUnUUB qv 3UEPJOO3 U! SU9WU6!Ie IflU8W U! SU!84 MS3 qoq 6U!oBId pUeWWOO s.io;edo e

6 Memqe UQ

NOI1dIdDSg 1NA O!M8S JO flO 0J9M SW9SAS P91219] A4eJeS iolew ON iUA9 S!t4 JO 9W14 eq B enssed PUE eneedwe 6U!eJedo IWJOU 4e JQ U! SM TUEIU ABM2IIED 9LU
5NQIJjQNQD +/-NV1d 7VI+/-INI
  • MOL JM eqn io wd6 g. pue einssaid JOBM qfl io 6!sd L jo sU!odT9s du dwnd MS o!ewoTne e MO J94EM eqn MOl o

)SBO 9144 U! s6uueeq dwnd MS R oooid oiapo u (wd6) enu!w ied sUoIIe6 9 o s! MO JOJ 36ueJ IeLwoU aq PU8 (6!sd) 6ne6 qOU! JBnbs SpUflOd gg o g. S! onssed 6UeJ IEWJOU 31J ainssejd pUB MO J9eM eqn JO P9P!AOJd S! UO!eU3WnJSUI s5Uueeq dwnd eq 6U!]9Ue ! o4Jopd JTM eq UBI3 o 6U!d!d ieeiv qn, eq U! pIIeTsU! SUOe]OjJ9d q3U!-/. 1!M SJ9U!4S-A qsew aie ajeqi S6U!JB3q dwnd eq e4opqn o dwnd MS o pp!Aod s!

(eqn) UOi4eouqfl7 dA4 ie6n.pweo flIOA-IflP peds-4UesUoo IB3IJA Uo!ons-eIqnop e6e;s9I6U!s ]E sdwnd MS A1!DBd3 wesAs UoJed O ei UO!18J3d0 IBw.OU 6Upnp STU9UOd WOO wesAs MS Lfl ON2M 6U!I003 Se!IddflS ose wsAs MS LI+/-

UBId P!SU! 9U!I wriiej W94sAs J948M 6U!eIno!o eq ai ! SWfl1aJ PUe U9Wd!flb 6UEqOX9 ME!I!Xfle 4UId U!8W SflOUA OJ4EM 6U!I003 Se!Iddfls W9SAS MS cUOe]dO TUEId IBWJOU 6UUflQ

  • wesAs MS eqO (sd5) SUW9]!flb9d OUEII!9Mfl5 PU SUO!1OV P]!flb8d (037) UO!TJdQ JOJ UOE!pUOQ 6UE!W!7 Sep!AO]d (MS) WSA5 J9BM O!AJ9S IB!USSa 2.Lt (aD UO!OI!Od5 BO!UqOe SU!84 wsAs MS WOJJ WSAS MS SLIT PUE SPEOI P84EI9J-19JSUOU eeIOS! [ASI :5119] S9AIA UO!4EIOS! PeeI9J-i191ES PUE Pe4nDe eje SU!8J WeSAS M53 qoq UO!EO!pU! [Ia :51131 ønssed UO!40flS MOI wv [at :511)) (Svdv) IeU6!S UO!Efl4Oe J348MP94

&iH!XflB JO 1BU6!S (dccl) J9MOU esjjo 40 SSOI [sr :5IIJ (515) IeU6!S UO!4091U! A44BS B O 4d!oe] UOdfl SUO!pUflJ Aees P9J!flbeJ SW9SAS eqW O U!3j4flS 9]B SU!J WeTSAS MS U! MOD PUE nssd eq 9JflSU MO4UeAU! SHfl o SSOI UA9]d o; iepio u SU!BJ W9SIS MS3 LI ai O4O9UUOO-SSOJO s! 11O!LIM WeSAS MS P9EI9]-14e1eSUOU W04 P9!IddflS q AEW SUIJT wesAs MS qoq ]O ]qi*e U! SPEOI UOEJ9dO IWJOU 6UunG SU!EJ4 4UEPUflP8J PUE TU9PU9U9PU! 0M4 40 S4S!SUOO W9SAS MS3 1 W94SAS [v

5113] J91MP9d Me!I!XflV io Alddns p9TeIe-Ae4Es paIJe4e]d-UOU 8 PU [va :5113] lOOd 96e]05 ini Ued5 1flJO UneNeW o OJflOs PeBl9]-A91Bs paueJ3Jd-U0U e Sep!AO]d OSIE wsAs MS eqi [ :SII] (SHn) U!5 EW!Ifl 11 O SU9UOUWOO W0J4 489q pUe eq IBflP!S9J J94SUE4 OJ9BM 6U!I000 O MOD PeTBI9]-A1BS e Sep!AOJU We;SAS MSi.[o>i :5113] WeSAS (\\f5) J9EM O!M9S P9eI9J-A91ESUOU eq UB [19 :5113] wesAs (M53) JEM eo!AJ9S IB!1U9SS 9L4 S3AIOAUI d37 S!q U! ppode TUA 1 GNV (S)VJ3ISAS c(S)dfl+/-Dfld1S dO NOI+/-dIdDSG ALLVNWN 00-

[00-ON N38VflN

£2OOO9O L.

ON !Ufl UEId AEMeIIED A3N 7VliN3fltS UV3A N3BV(1NN31 t U3SWflN 1313Oa Z 3IAIVN AJJ7IDVJ

  • ]aqwnu iouoo svo P!IBA AUJJfl3 2 SABidsp uooeoo eq 6U!]!flbeJ o u!isenbe iiO TU8WflOOP em sseiun uoflwJoJu! JO UO!3eIIO3 e o puodsej o penbei ou s! uosjed e pue josuods wjoj s!q 6u!jeldwoo oj eouep!n6 pu uo!pnJlsu! io çj VDdflN eec)

Jo 3flPUO3 Ou Aew DdN 81J AoDaoeqwoJuoss!wqns JO B )fSe :uy (frOO-O9C) s!BV AJoeIn6ed U2 UOIWJOU JO GDV1O 9JO :ie ]8M3!A8] SIAJO elB pu A063]U@eOJflOSedSTDeII030JUI o

ew-e Aq

.10 OOO-999O DC UO6U!qSBM UO!SS!WWOD JO2fl6j

]B3flN I

I i

I

.s.n (vgov 9-i) qoui suooeo uowjoui pue Meq VIOd 81fl O eewse uepinq 6upJe6eJ 7

SIU8WWO3 Plies AJISflPU! O oeq pe pue sseood 6u!sue3!I eLfl OU! peeJodio3u! 8J peuie suosse peJoded SJflOL4 02 :senbei UO39IOD kiopuew SR1 411M AidwoD O esuodsei ]ed uepjnq peews (oo-9o) coII4:I9o oo-og ON 2W0 AS 3AONddV NOISSIWIIJOD ANOLV1flO3N NV37DflN Sfl V99 WN0i ONN

Jo 868d t9o-go) V99E Od DdN (6)ts)(A!)()(e)Log I3 0 [ U! p91JPdS wsAs o UO!jBflDe Aq (y)(A!)()(e)eLog ddD 0 1-40 U9WGJ!flb9J 6Upode]

SIIWfl1 S!q+/-

2C20 E 6 Memq UO pEfl3E A8flUW SeM wesAs MSi SNU!S 31 9BW!Ifl S8 8M9S E1 pe Urn AII8W]OU 40U op 4E( SW9SAS J8M 93!M9S A3U8JeW (6)

S! S9!IddB UO!D3S S!qO (v)(A!)()(E) qds6esd o TU3W3J!flbeJ q; 3M O} WD4SAS eqj

()

. UO!4395 SNT 0 (g)(A!)()(e) qde6eed U! PtS!I SW9SAS eqjo AUS o UO!8fl3e oewons ]O EflUEW U!

L4 UO!4!pUOO JO TU9A9 AUy (y)

pode iieqs eeSUe!I QLI pd U! SB4S (v)(A!)()(e)ELog ddD 0 1. AIIEDUIO9dS WSAS MS JO UO!Sfl38 IEflUSW S jod9J o (y)(A!)()(e)Log o 4UEflS]fld pwqns ! eIi S!1 I91N]3dIflOd DNI1dOdd 9

9O!M9S O JO4SO] 9J9M sdwnd MS TI91 UO!ipUO3 AqpUeS eq o pewn;e SBM WO4SAS MS eq U8 P9U6!S9P e P9UO!pUfl4 SUeUOdWO3 AeJBS y SUep!3OE o SODU9flbeSUOO 9Lf 6U!jB6!!W PUS S9 IP!S 6UIAow9J UMOpfl1S 4ES 6U!U!eU!8w PUS 6UAqoE JOJ p9J!flbe] SUO!pUfl4 PI]-AeJBS auojd o S! /J9 S)fU!S eeq ewn SB eiues eq; pus urn A,iewiou ou op eq SWaSAS ]9BM OAJS Aoue6iawe 6U!6UeSqo oToedseJ qv AeBS JBPflU UO SEM pedw Ie!W9Od eqj TUAG S!q IfIIM PSPOSSE S4OedW! S IUUOSJed jo Ie3!6010!PSJ ]B9PflU BflOE OU 9]9M a191fl IS3NflQSNQ3 AJ3dVS dO 1NViSS3SSV t

peje,dwoo SSM ]!Sde]

994E

[ qo]evj UO P9AOWJ SBM VJSV+/-

JP1 UOWWOO ]98M eqn MS 3L1T UO Peeidwoo SBM J!ede ed!d eq I!Wn S!Sq APiM S UO S]U!B]TS-A 11 USI3 O p9e]9Ue6 U9qT 9M (vja) e3UBUeU!S 9A!W9A9]d 6 IJemqe UO sdwnd MS JLI lie 104 SJU!EJTS-A MS eq Usep o peeidwoo 9JM sqor peie eq o dwnd MS 9 o 8JAO39J AU!3J4flS peq MOD UB Jnss9Jd J98M eqn 6 MEmqe UO ovu Aq SUewU6!Ie AqpUeS o pwne 9]M MS o SU!eJ qo OU!UUflJ ale sdwnd MS 0M4 UEq SSI UL4M flO)DO dwnd MS ]OJ enpood SUodS]

JOE!3UflUU8 9q4 LWM 9OUSPJ003S U! P1JTS MISflUEW J9M MS O SU!E] q;oq SUodSe] UI (S)U!od4S flO)I3OI eq Ueq4]E]6 nq pepEJ63p nssd J4BM eqn wv UW o penU!;Uoo dwnd MS 3 ei 9JnsseJd ]9EM eqn MOl UO ;no pjoo US peddu oss nq P1J4S o;ns dwnd MS.9 +/- jnssjd JTSM eqn MOl UO no UB pddii dwnd MS V 1

6 Memqe UO

.TeSe] SBM flO)f3O -1T UE W!flBLflTB S]U!e]4S-A LI4 UBeID 0 P9E!1!U! SEM qoly wd6 9LI6!Sd o: SBM ! dwnd MS 3

]04 UB wd6 9/6!Sd SBM MOW9]flSSeJd J98M eqn dwnd MS a dwnd MS v io wd6 6!Sd oi-JeM MOD UB enssed J9EM qn nopo dwnd eq pee6!s9AU! ioedo P!STflO 8 UeqM 9w! ei U! TOU SSM dwnd eqj MOW9]flSSaJd JEM qn MOl UO ;no pejoo q o p9U!wJaep SEM dwnd MS v e 6 MSmq UO v

sdwnd MS L% O ]SM eqn 40 MOD UE enssed peonp U! 6U!TInS S]3U!eJTSA eqT U! Un pinq OUeW!peS IBUO!!PPE peSneo UO!flIOA S!11 ssedde i U!SEq eq; o osq MO wn 6U!U6!IBeJ peUedo-e] eJeM SAIBA sssdAq eqT JTEI noq US AI8TBW!XOJddV *III J9MO 6U!I000 o6 o U!Seq J9MO 6U!I000 eq WO4 MO Wfl9] MD -1 6U!U6!Ie S9!I!A!D8 9OUBUeU!EW Jo UO!4flOeXe eq 6Upnp PSOID eJeM [3)1 :5113] S9AIB1 ssedAq JMO 6U!I003 2 Memq9 40 UOOW4S 9L4 UQ

  • S4fl0)I3OI dwnd epni3ejd 04 U!6]BW 34nb9pB eABq o p9Jeedde senssed J9BM eqn eq 90U!S [O 6 MenJq9 oTJoud P9Efl1U! Ueeq 40U pEL S]U!e]4S-A 3114 U5813 04 sqol J9A9MOH SL1SnIPi3Bq APiM w.iopd o I!I!qeU! 1T O 9flj PIflO 6UIwoDeq SJ9U!EJ1S-A J948M eqn 04 pnque SSM PU9JT 6UIpe]69p qi sdwnd MS 9O4 9JnSS9JU J9TEM eqn U! U94 6U!p8J63p B PeWUeP! SPUflOJ oeedo [O 9 MeflUet UO UO!S4U9W9IdW! LAJSV+/-

w 00-

[.00-ON U38VflN

£2OOO9O I-ON !Ufl U81d ASMSIIED A3N 7VLLN3flO3S NV3A N38I1flNN31 t N3SINflN I3NDOa 3WVN ALI1IDVi L

  • ieqwnu o.uoo SNO P!IeA Ajuejjno 2 sAeidsp uooeo eq 6U1]!flbe] io 6usenbe]

(icJio uewn3op eq sseun uoewJoJu! O UODGO O puodsa o p8]!flbeJ ou s! uosed e pu osuods wjoj S!q 6u,ieidwoo ioj eOUep!fl6 pue UOflOflJ1SU! JOJ VOdflN 989)

Jo T3flPUOD IOU Aew DdN +/- Aobaoeqwo)uosswqns e]!O :B S9 :19V Uoo-oc) SJ!ejJV MoBIned pu uoiewjoui jo 83J4Q Q :e J9M8AJ Q elfl pu Ao6oJu@eoJnosedsoeIIoooJuI o

I!eW-e Aq Jo [OOO-999O DC UO6U!qS8M UO!SS!WWOD MO8fl6e JBeIDflN I

II s.n (vow 9-i) q3UeJS suoioeiioo UO!TBWJOJUI U2 AJJq!7 VIOd eq o eew!Tse uepinq 6u!p]86e]

(

SU3WWO3 pueS *kiisnpu! o oeq pej pue sseood 6usueoi e olu! pBTB]odJoou! e peue suosse

peJoded S]flOLj 09 :isenboj uopeoo Mopuew S!Lfl IffiM AidwoD o esuodse ed uepjnq pew!s (oo-9o) oIicI8o 53N1dX3 VOO-O9 0N :swo AS 3AOUddV NOISSIWWOO ANOLVTflD3U UV37OflN Sfl V995 WNOJ ONN

Jo : 6d (go-o) V99C JdOd DaN

  • MS 40 UOiTBfl4Oe ienuw qT U! P9IflS8]

SjU8A ]9O OU PUflOJ AEMBIIBO io sieeA 9A!4 4sd wosj jo Me!AeJ y

S1N9A dV1WdIS SflOIA3dd 2

P9II1SU!

SBM OU!d!d JM eqn eq eoeide o Uoeo!pow TUeUewJd qevj UO P9AOW9] SeM L/JJ 1 pauno jeep 9q1 eieqii 6UId!d J9IBM eqn UOWWOO 9L4 40 UO!O9S 9L4 eid9J o UO!4B3!pOW e D4aidwoo o S2M uo!43B 9AE39JJO3 4U9UWJU ei P9IIESU! SEM VJSVI 911418(11 W! 6U!U!eWe] q;io siseq AINM e UO S]Ui&JS-A 91 U9I3 0 p9BaJ3 9J9M S)fSB lAid UO!4!ppB UI 6u!d!d evi eqn 94 U! sJ9U!e4S-A 9Lfl4O 6U!UB9I3 P9AIOAU! [O 6 AJenJq3 UO P9eIdWO3 S8M 113!L1M UO!438 9A!39JJOD IE!1!U! +/-

9[JQJ3N ALLD3ddOD qsnppEq O IqBU! eqio 1BSUedWO3 o po UI SJ9U!e4S-A U9I3 AIIE3!POUd o UAe ojoud p!iU!

eeq 40U p ss VId 6U!d!d IeeM qnI ;UeUewJd U! N891 J!ed oepo U! P9IIB1SU! SEM svi 9I!LIM pet.wojied eq 40U pifloD SJU!B4S-A eqilo qsnppq AIN9M IEWJOU 9q4 9OU!S peJJfl330 6UIInoJ 9QL S]U!EJS-A ]9BM eqn eq jo 6U!InoJ Aq pesneo 9JnssoJd J9EM eqn MOI O pnquE SEM sdwnd MS a pUe, eqo STflONOOI 4Uflb9SqflS PUE SdUT qjo eSneO 1

1N3A3 3H+/- dO SflVD 9

00-LOO ON N38VflN

£2i-OOO9O I

ON !Ufl UBId AEMBIIBD AU 7VIIN3flO3S UV3A i38VIflNN31 *t N3SWflN l3NDOa Z 3WVN AII7IOVi I

ieqwnu iouoo 9VJO PIIeA AIueJJn3 B sABIds!p UO38IO3 eq 6u!J!nbeJ JO 6u!Tsenbe]

(/]/o iuewnoop em sseiun uoewjoju o uooeoo o puodsei o pei!nbe ou s! uosd e pu iosuods uuoj S!qj 6uiieidwoo oj DUBp!fl6 pue UO!43fl]jSU! JOJI O [-D3dflN eec)

Jo PflPUO3 TOU Aew DdN AOboeqwop)uosswqns JO :e se :u4 (oo-oc) seiv Moin6e pue uoqwjoup o 3U1O 9O :e JeM8!A8] 9JQ eq pue AO63JU@e3JflOS8dS38I,O3OJUI o

I!Ew-e Aq Jo OOO-999O DG UOUqS8 UO!SS!WWOD MOEfl68 Jeon I

i

.s.n (vov 9-i) 3UJ9 SUO3eIIOD UOiBWJOJUI pue AJeJqfl VIOd 8Lfl O eiewse uepJnq 6up6e f

suewwo3 pueS kisnpu o oeq pej pue sseood 6usueo eq ou pee]odJo3u! e pewee suosse

peiJode sinoq OR :senbej uoipeo Ajoepuew S!1 M Aidwoo o esuodse ]9d uapinq pews (oo-9o) coM:I9o :3flJ)(3 IoIo-og: ON BWO A8 3AOUddV NOISSIVJWOO ANOIVTflO3N UV3TDflN Sfl V99 IAINOJ DNN