05000483/FIN-2009004-01
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Inadequate Corrective Actions for Essential Service Water Pump Cable Underground Electrical Vault Seals |
Description | The inspectors identified a noncited violation of 10 CFR Part 50, Appendix B, Criterion XVI, Corrective Action, associated with the licensees failure to take prompt corrective actions prevent continuous submergence of essential service water pump kerite insulated power cables. The continuously submerged environment for these cables existed because the two vaults containing these cables (MH-01N and MH-01S) had inadequate seals needed to protect the vaults from incoming surface water. Callaway Action Request 200201916 stated that all medium voltage cables of concern were located more than 4 feet above the basemat of the vault and thus were not in a submerged condition. The Callaway action request noted that the seals at the top lid were the source of water intrusion and that the seal design was inadequate. On July 9 and 22, 2009, the resident inspectors, along with Callaway plant engineers, inspected the two essential service water underground vaults. The north vault (train A) was found to have water covering the two safety related upper cable trays. Contrary to the Callaway Action Request 200201916 evaluation, the cable trays were about 2.5 feet and 3.5 feet from the basemat of the vault floor. During these 2009 inspections it was noted that the same lid design deficiency identified in Callaway Action Request 200201916 still existed. This led to the discovery that the Callaway Action Request actions from 2002 had not been completely performed. The only significant corrective action had been to increase the inspection frequency to once every three years. The licensee has subsequently taken measures to improve the seals and written Callaway Action Request/Request for Resolution 200905838 to further evaluate this issue. This finding is more than minor because it affected the Mitigating Systems Cornerstone attribute of design control for ensuring the availability, reliability, and capability of safety systems. Using Manual Chapter 0609.04, Phase 1 Initial screening and Characterization of Findings, this finding was determined to be of very low safety significance because the degraded seals were a design or qualification deficiency confirmed not to result in loss of operability. The inspectors determined that the finding has no crosscutting aspect as the performance deficiencies were not - 3 - Enclosure reflective of current performance. The licensee entered this item into their corrective action program as Callaway Action Request 20090885 |
Site: | Callaway |
---|---|
Report | IR 05000483/2009004 Section 1R06 |
Date counted | Sep 30, 2009 (2009Q3) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.06 |
Inspectors (proximate) | D Dumbacher C Osterholtz V Gaddy J Groom M Vasquez C Steely |
INPO aspect | |
' | |
Finding - Callaway - IR 05000483/2009004 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Callaway) @ 2009Q3
Self-Identified List (Callaway)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||