Finding | |
|---|---|
| Title | Failure to Control Combustible Gas Cylinders in Accordance with Fire Protection Program |
| Description | The inspectors identified a finding of very low safety significance with an associated Non-Cited Violation of the Clinton Power Station Unit 1 Operating License (NPF-62, Section 2.F). The licensee failed to implement the Fire Protection Program in accordance with program requirements by failing to follow approved Fire Protection Program procedures for the control of combustible gas cylinders in the plant. As a corrective action, the licensee promptly removed the combustible gas cylinders found by the inspectors. The inspectors concluded that this finding was associated with the Protection Against External Factors attribute of the Initiating Events Cornerstone and affected the cornerstone objective to limit the likelihood of those events that upset plant stability and challenge critical safety functions during shutdown as well as power operations. Specifically, the fire hazard for the affected area was increased by the uncontrolled presence of the compressed gas cylinders. In addition, based on review of Example 4k in IMC 0612, Power Reactor Inspection Reports, Appendix E, Examples of Minor Issues, the issue would not be considered to be of minor significance because a credible fire scenario involving the identified transient combustibles could affect equipment important to safety. The finding was determined to be of very low safety significance during a Phase 3 Significance Determination Process review since the delta core damage frequency was determined to be negligible. Because a postulated fire in the area where the combustible gas cylinders were found could affect only one train of safe shutdown equipment, the safe shutdown path was not affected by the finding. The inspectors concluded that this finding affected the cross-cutting area of human performance. Specifically, the licensee did not adequately ensure that supervisory and management oversight of work activities involving contractors supported nuclear safety. (IMC 0310 H.4(c) |
| Site: | Clinton |
|---|---|
| Report | IR 05000461/2010002 Section 1R05 |
| Date counted | Mar 31, 2010 (2010Q1) |
| Type: | NCV: Green |
| cornerstone | Initiating Events |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.05 |
| Inspectors (proximate) | M Holmberg R Jickling R Langstaff J Cassidy B Metrow B Kemker M Ring S Mischke D Lords E Coffman J Draper A Scarbeary D Sand |
| CCA | H.2, Field Presence |
| INPO aspect | LA.2 |
| ' | |