| Title | Failure to Perform Validation for Safe Shutdown Manual Actions |
| Description | A finding of very low safety significance was identified by the inspectors for the failure to perform a validation of added safe shutdown manual actions. The failure to perform a validation resulted in less than adequate emergency lighting for the safe shutdown manual actions. The licensee subsequently entered the issue into their corrective action program and planned to relocate existing emergency lighting to provide adequate lighting at panel 1DC13J. The finding was determined to be more than minor because the failure to validate the safe shutdown manual actions adversely resulted in less than adequate emergency lighting for the actions. The less than adequate emergency lighting affected the reliability associated with performance of the manual action. The issue was of very low safety significance because the finding represented a low degradation because portable lighting was available. (Section 1R05.8.b(1) |
| Site: | Braidwood |
|---|---|
| Report | IR 05000456/2009006 Section 1R05 |
| Date counted | Mar 31, 2009 (2009Q1) |
| Type: | Finding: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.05 |