Finding | |
|---|---|
| Title | Reactor Trip On Unit Auxiliary Transformer 241-1 Sudden Pressure Relay Actuation Due To 2C Heater Drain Pump Motor Electrical Fault |
| Description | A Green finding was self-revealed on December 27, 2008, when excessively long motor leads caused a phase to phase overcurrent trip of the 2C heater drain pump and subsequent Unit 2 reactor trip. Specifically, adequate procedural guidance on re-terminating the 2C heater drain pump motor leads following refurbishment was not provided, which resulted in excessive motor lead length. This issue was entered into the licensees corrective action program as Issue Report (IR) 860458. Since the procedures that govern activities on equipment that is not used to prevent or mitigate the consequences of postulated accidents that could cause undue risk to the health and safety of the public, such as the heater drain pump, this finding does not represent a violation of regulatory requirements. The inspectors determined the finding was more than minor because it impacted the procedure quality attribute of the Initiating Events Cornerstone objective to limit the likelihood of those events that upset plant stability and challenge critical safety functions during shutdown as well as power operations. The inspectors determined the issue was of very low safety significance because it did not contribute to both the likelihood of a reactor trip and the likelihood that mitigation equipment or functions would not be available. There is no cross-cutting aspect associated with this finding because the development of the inadequate procedure did not reflect current performance |
| Site: | Braidwood |
|---|---|
| Report | IR 05000456/2009002 Section 4OA3 |
| Date counted | Mar 31, 2009 (2009Q1) |
| Type: | Finding: Green |
| cornerstone | Initiating Events |
| Identified by: | Self-revealing |
| Inspection Procedure: | IP 71153 |
| Inspectors (proximate) | B Dickson A Garmoe |
| INPO aspect | |
| ' | |
Finding - Braidwood - IR 05000456/2009002 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Braidwood) @ 2009Q1
Self-Identified List (Braidwood)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||