Finding | |
|---|---|
| Title | Non-Seismic Scaffolding Installed Over Service Water Equipment |
| Description | The inspectors identified a noncited violation of Technical Specification 5.4.1.a (Procedures), for the licensees failure to erect scaffolding over safety-related equipment with adequate seismic supports. As a result, the scaffolding would likely fail during a seismic event and impact the service water system. Contract personnel assembled the scaffolding and were under perceived time pressure to finish the work, which was their last task before departing the site. A licensee supervisor inspected the scaffolding and failed to identify the deficiency. The licensee entered the finding into their corrective action program as Smart Form SMF-2008-003683. The finding was more than minor because it was similar to non-minor Example 4.a from Manual Chapter 0612, Appendix E, Examples of Minor Issues, in that the scaffolding could adversely affect safety related equipment during a seismic event. Using the NRC Manual Chapter 0609, Attachment 4, Phase 1 - Initial Screening and Characterization of Findings, the finding was a qualification deficiency confirmed not to result in loss of operability or functionality. This finding had a Human Performance crosscutting aspect (work practices component) because the licensee failed to ensure adequate supervisory and management oversight of work activities, including contractors, such that nuclear safety was supporte |
| Site: | Comanche Peak |
|---|---|
| Report | IR 05000445/2008005 Section 1R04 |
| Date counted | Dec 31, 2008 (2008Q4) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.04 |
| Inspectors (proximate) | L Ricketson J Dixon K Clayton B Tharakan L Carson G Replogle B Tindell M Bloodgood D Reinert G Tutak J Kramer N Okonkwo N Hernandez |
| CCA | H.2, Field Presence |
| INPO aspect | LA.2 |
| ' | |
Finding - Comanche Peak - IR 05000445/2008005 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Comanche Peak) @ 2008Q4
Self-Identified List (Comanche Peak)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||