05000440/FIN-2014003-01
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Failure to Promptly Correct a Condition Adverse to Quality on Division 2 EDG |
| Description | A self-revealed finding of very low safety significance and associated non-cited violation (NCV) of 10 CFR, Part 50, Appendix B, Criterion XVI, Corrective Action, was identified on May 7, 2014, for the failure to correct a condition adverse to quality. Specifically, the licensee failed to correct a lube oil leak, identified by operations personnel on April 12, 2014, during the monthly run of the Division 2 Emergency Diesel Generator (EDG). As discussed in Condition Report (CR) 2014-06755, the leak was from a Swagelok fitting on the turbocharger supply line and at a rate of less than an ounce per hour. The CR was closed to a work order to complete repairs. On May 7, the next scheduled surveillance run of the Division 2 EDG occurred. The leak had not been repaired and, during the run, became progressively worse resulting in an unplanned (emergency) shutdown of the diesel and the diesel being declared inoperable. The leak was quantified as approximately a gallon per hour at the time of the shutdown (CR 2014-08487). The line was repaired and the diesel was returned to operable status on May 8. The licensee promptly evaluated the other EDGs and determined that a common cause condition did not exist. The failure was caused by fatigue cracking of the Swagelok fitting due to misalignment during installation. A root cause evaluation was conducted by the licensee. The finding was determined to be more than minor because it was associated with the Mitigating Systems Cornerstone attribute of equipment performance and adversely affected the cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. The finding was determined to be of very low safety significance because there was no design deficiency, no actual loss of safety function, and no single train loss of safety function for greater than the Technical Specification (TS)-allowed outage time. This finding has a cross-cutting aspect in the area of problem identification and resolution evaluation, for the failure to thoroughly evaluate the issue and ensure that the resolution addressed the cause and extent of condition when identified in April 2014. |
| Site: | Perry |
|---|---|
| Report | IR 05000440/2014003 Section 1R19 |
| Date counted | Jun 30, 2014 (2014Q2) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | Self-revealing |
| Inspection Procedure: | IP 71111.19 |
| Inspectors (proximate) | J Beavers J Jandovitz J Nance M Kunowski M Marshfield M Phalen |
| Violation of: | 10 CFR 50 Appendix B Criterion XVI Technical Specification |
| CCA | P.2, Evaluation |
| INPO aspect | PI.2 |
| ' | |