05000440/FIN-2012008-05
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Failure to Provide Full Area Detection |
| Description | The inspectors identified a finding of very low safety significance (Green) and associated Non-Cited Violation of License Condition 2.C(6) for the failure to provide detection throughout Fire Area 1CC-4a. Specifically, Fire Area 1CC-4a was described by the USAR as having an early warning detection system. However, the corridor area of Fire Area 1CC-4a lacked detection. The licensee entered the issue into their corrective action program and planned to evaluate a change to their detection system. The inspectors determined that the finding was more than minor because the lack of detection in the corridor area of Fire Area 1CC-4a could result in delayed detection of a fire which, if unmitigated, could affect safety-related cables above the corridor area. The finding was of very low safety significance because the portion of Fire Area 1CC-4a which contained safety-related cables did have smoke detectors and a sprinkler/spray system. This finding has a cross-cutting aspect in the area of Problem Identification and Resolution, Self-Assessments, because the licensee did not conduct a self-assessment of sufficient depth. Specifically, a self-assessment reviewed Fire Area 1CC-4a, but did not assess the design of systems in terms of the licensing basis. |
| Site: | Perry |
|---|---|
| Report | IR 05000440/2012008 Section 1R05 |
| Date counted | Jun 30, 2012 (2012Q2) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.05 |
| Inspectors (proximate) | M Munir R Langstaff R Winter H Peterson |
| CCA | P.6, Self-Assessment |
| INPO aspect | CL.2 |
| ' | |
Finding - Perry - IR 05000440/2012008 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Perry) @ 2012Q2
Self-Identified List (Perry)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||