05000440/FIN-2011008-03
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Failure to Test Safety-Related Contactors at Degraded Voltage Conditions |
| Description | The inspectors identified a finding of very low safety significance and associated Non-Cited Violation of 10 CFR Part 50, Appendix B, Criterion III, Design Control, for failure to test safety-related motor starter contactors at design basis conditions. Specifically, the licensee failed to demonstrate the ability of ESW Pump A discharge valve 1P45F0130A motor starter contactor to operate at minimum pickup voltage during design basis degraded voltage conditions. This finding was entered into the licensees corrective action program. The performance deficiency was determined to be more than minor because if left uncorrected it would have the potential to lead to a more significant safety concern. The finding screened as of very low safety significance (Green) because the finding involved a design or qualification deficiency that did not result in a loss of operability. Specifically, after further evaluation, the licensees engineering staff concluded the issue did not impact current operability because periodic testing for other type of contactors provided validation the valve motor contactor would operate when required for the postulated degraded voltage conditions. This finding has a cross-cutting aspect in the area of Problem Identification and Resolution Corrective Action Program for failure to take appropriate corrective actions to address safety issues and adverse trends in a timely manner, commensurate with their safety significance and complexity. |
| Site: | Perry |
|---|---|
| Report | IR 05000440/2011008 Section 1R21 |
| Date counted | Dec 31, 2011 (2011Q4) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.21 |
| Inspectors (proximate) | R Langstaff B Jose C Baron S Kobylarz M Jones A Stone C Tilton I Hafeez |
| CCA | P.3, Resolution |
| INPO aspect | PI.3 |
| ' | |
Finding - Perry - IR 05000440/2011008 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Perry) @ 2011Q4
Self-Identified List (Perry)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||