05000410/LER-2004-001, Re Inoperability of a Control Room Envelope Filtration System Train Due to a Locked Closed Damper

From kanterella
(Redirected from 05000410/LER-2004-001)
Jump to navigation Jump to search
Re Inoperability of a Control Room Envelope Filtration System Train Due to a Locked Closed Damper
ML040690740
Person / Time
Site: Nine Mile Point 
Issue date: 02/27/2004
From: Godley R
Constellation Energy Group
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
NMP2L 2111 LER 04-001-00
Download: ML040690740 (6)


LER-2004-001, Re Inoperability of a Control Room Envelope Filtration System Train Due to a Locked Closed Damper
Event date:
Report date:
Reporting criterion: 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications

10 CFR 50.73(a)(2)(v), Loss of Safety Function

10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition

10 CFR 50.73(a)(2)

10 CFR 50.73(a)(2)(iii)

10 CFR 50.73(a)(2)(x)

10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor

10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat

10 CFR 50.73(a)(2)()(A)

10 CFR 50.73(a)(2)(vi)(A)
4102004001R00 - NRC Website

text

P.O. Box 63 Lycoming, New York 13093 Constellation Energy Group Nine Mile Point Nuclear Station February 27, 2004 NMP2L 2111 United States Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555

SUBJECT:

Nine Mile Point Unit 2 Docket No. 50^410 Facility Operating License No. NPF-69 Licensee Event Report 04-001, "Inoperability of a Control Room Envelope Filtration System Train Due to a Locked Closed Damper" Gentlemen:

In accordance with 10 CFR 50.73(a)(2)(i)(B) and 10 CFR 50.73(a)(2)(v)(D), we are submitting Licensee Event Report 04-001, "Inoperability of a Control Room Envelope Filtration System Train Due to a Locked Closed Damper."

Very truly yours, Robert C. Godley Manager Operations RCG/DEV/bjh Attachment cc:

Mr. H. J. Miller, NRC Regional Administrator, Region I Mr. G. K. Hunegs, NRC Senior Resident Inspector

NRC FORM 366 U.S. NUCLEAR REGULATORY COMMISSION APPROVED BY OMB NO. 3160-0104 EXPIRES 731-2004 (1.2001)

(See reverse for required number of the NRC may not conduct or sponsor, and a person Is not required to respond to. the information digits/characters for each block) collection.

FACILITY NAME (1)

DOCKET NUMBER (2)

PAGE (3)

Nine Mile Point, Unit 2 05000410 1 OF 5

TITLE (4)

Inoperability of a Control Room Envelope Filtration System Train Due to a Locked Closed Damper EVENT DATE (5)

LER NUMBER (6)

REPORT DATE (7)

OTHER FACILUTtES INVOLVED (8)

MO DAY YEAR YEAR SEQUENTIAL REV MO DAY YEAR ACILITY NAME DOCKET NUMABER NUMBER NO 05000 01 28 2004 2004 -

001 -

00 02 27 2004 ACIlTY NAME DOCKET NUMBER 05000 OPERATING THIS REPORT IS SUBMITTED PURSUANTTO THE REQUIREMENTS OF 10 CFR j: (Checkall that apply) (11)

MODE (9)

_1_

POWER

_ 20.2201(b) 20.2203(a)(3)(li) 50.73(a)(2)(ii)(B) 50.73(a)(2)(tx)(A)

LEVEL (10) 98 20.2201 (d) 20.2203(a)(4) 50.73(a)(2)(iii) 50.73(a)(2)(x) 20.2203(a)(1)

_ 50.36(c)(1)(i)(A)

_ 50.73(a)(2)(Iv)(A) 73.71 (a)(4) 20.2203(a)(2)(I) 50.36(c)(1)(i)(A) 50.73(a)(2)(v)(A)

_ 73.71 (a)(5) 20.2203(a)(2)(ii) 50.36(c)(2) 50.73(a)(2)(v)(B)

OTHER 20.2203(a)(2)(iii) 50.46(a)(3)(ii) 50.73(a)(2)(v)(C) 20.2203(a)(2)Cv) 50.73(a)(2)()(A)

X 50.73(a)(2)(v)(D) 20.2203(a)(2)(v)

X 50.73(a)(2)(t)(B) 50.73(a)(2)(vli) 20.2203(a)(2)(v 50.73(a)(2)(t)(C) 50.73(a)(2)(vlii)(A) 20.2203(a)(3)(M) 50.73(a)(2)(vi)(A) 50 a2P'

'ir' B-LICENSEE CONTACT FOR THIS LER (12)

NAME TELEPHONE NUMBER (Include Area Code)

Patrick K. Doran, General Supervisor System Engineering 315-349-4539 COMPLETE ONE LINE FOR EACH COMPONENT FAILURE DESCRIBED IN THIS REPORT (13)

CAUSE

SYSTEM COMPONENT MANU-REPORTABLE

CAUSE

SYSTEM COMPONENT MANU-REPORTABLE FACTURER TO EPK ij FACTURER TO EPK BVl UIDMP P014 Y

SUPPLEMENTAL REPORT EXPECTED (14)

EXPECTED MONTH DAY YEAR SUBMISSION DATE (15)

II lES (Ifyes comRpL-eEXPECTED SUBMISSION DATE).

IXINO I

I sBSTRACT (Umi to 1400 spaces, i.e., approximately 15 single-spaced typewrltten lines) (16)

On January 28, 2004, while performing surveillance testing on the Division 11 Control Room Outside Air Special Filter Train (CROASFT), the required flow to establish test conditions could not be achieved. Backdraft damper 2HVC*DMP93, on the inlet ductwork to the Division 11 CROASFT, was determined to be in the locked closed position, causing the Division 11 Control Room Envelope Filtration (CREF) subsystem to be inoperable. The plant entered Action A of Technical Specification 3.7.2, which requires restoration of the Inoperable CREF subsystem within 7 days. Further investigation determined that damper 2HVC*DMP93 had been locked closed for approximately 4.5 months, and that the other redundant CREF subsystem (Division I) had also been inoperable on several occasions during that 4.5 month period.

This event is reportable in accordance with 10 CFR 50.73(a)(2)(i)(B) as OAny operation or condition which was prohibited by the plant's Technical Specifications," and 10 CFR 50.73(a)(2)(v) as "Any event or condition that could have prevented the fulfillment of the safety function of structures or systems that are needed to: (D) Mitigate the consequences of an accident.,

The cause of the event was a deficiency in the blade lock for damper 2HVC*DMP93, whereby setscrews were not holding the blade lock securely in the disengaged position. A contributing cause was inadequate acceptance criteria in the CREF system monthly surveillance test procedure.

The corrective actions include modifying the blade lock to provide additional assurance that it will not inadvertently engage, and revising the CREF system monthly surveillance procedure to provide guide values for acceptable flow and differential pressure conditions.

NRC FORM 386 (1-2001)

(If more space Is required, use addonal copies of NRC Fom, 366AJ (17)

I. Description of Event

On January 28, 2004, while performing surveillance testing on the Division II Control Room Outside Air Special Filter Train (CROASFT), the required flow to establish test conditions could not be achieved. Initial Investigation revealed that backdraft damper 2HVC*DMP93, on the Inlet ductwork to the Division II CROASFT, was stuck shut and could not be opened by hand. This resulted in the Division II Control Room Envelope Filtration (CREF) subsystem being Inoperable. The plant entered Action A of Technical Specification 3.7.2, OControl Room Envelope Filtration (CREF)

System," which requires restoration of the Inoperable CREF subsystem within 7 days.

Damper 2HVC*DMP93, as installed, was determined to have a manual, door latch style, blade lock. The blade lock, when engaged, is designed to lock the damper In the closed position. To disengage the blade lock, the device is pulled down out of the way and secured by setscrews. To manually engage the blade lock, the setscrews are loosened, which allows the blade lock's internal spring to drive the lock into position. There is no automatic engagement of the blade lock. Further examination of damper 2HVC*DMP93 determined that the blade lock's setscrews were not holding the blade lock securely In the disengaged position. Based on a review of plant computer data and monthly surveillance test records for the Division II CREF subsystem, it was concluded that damper 2HVP*DMP93 had become locked In the closed position sometime between September 11, 2003 and October 11, 2003.

An inspection of the corresponding backdraft damper (2HVC*DMP94) in the redundant Division I CROASFT, and a review of the Division I CREF subsystem monthly surveillance test records, were performed. The inspection and review concluded that the blade lock associated with damper 2HVP*DMP94 was not interfering with the ability of the damper to open as designed. Therefore, the operability of the Division I CREF subsystem was confirmed.

The blade lock for damper 2HVP*DMP93 was restored to the disengaged position, and the damper was successfully tested and returned to service. The Division II CREF subsystem was declared operable on January 29, 2004 at approximately 1634 hours0.0189 days <br />0.454 hours <br />0.0027 weeks <br />6.21737e-4 months <br />, and Technical Specification 3.7.2, Action A was exited.

II. Cause of Event

The apparent cause of this event was a deficiency In the manufacturing, installation and/or construction of the manual blade lock associated with damper 2HVC*DMP93. The original design drawing for the manual blade lock showed a release pin Installed through the blade lock's pull-down rod. However, the actual installed design uses two setscrews to maintain the device in the disengaged position. The first setscrew is tightened against the blade lock pull-down rod.

The second setscrew is used to jam the first setscrew to prevent it from loosening. No records were found indicating that the blade locks were replaced or ever used. As such, the blade lock appears to be original construction.

Although the installed design worked successfully for 18 years of operation, the friction connection between the pull-down rod and the first setscrew is not optimal due to system vibration caused by the damper closing and opening.

A contributing cause of this event was Inadequate acceptance criteria in the CREF system monthly surveillance test procedure. Although total flow and various differential pressure readings were taken during monthly flow tests for each CROASFT, the procedure did not state any expected ranges or values for the readings taken. The lack of an acceptable flow range resulted in the operators not recognizing that the low air flow through the Division II CROASFT was indicative of damper 2HVC*DMP93 being closed.

(Ef more space Is required, use addetonadcophMs of Ot more spXe Is required, use addtonal copies of NRC Foxn 366A) (1 7)

Ill. Analysis of Event (Cont'd)

The probability of a core damage event occurring during the 72 hour8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> period during which both CREF subsystems were inoperable was determined to be 4.4E-7. The damper position and CROASFT inoperability do not increase the probability of a core damage event.

In the event of a core damage event, the Division I CREF subsystem could have been returned to an operable status within a reasonable amount of time.

Even with damper 2HVP*DMP93 locked closed, approximately one half of the normal required flow was measured through the Division II CROASFT (the blade lock does not hold the damper tightly closed). With this intake flow rate, control room pressure was observed to remain positive relative to the outside atmosphere, but was less than the 1/8 inch water gauge required by Technical Specification Surveillance Requirement 3.7.2.4.

Assuming zero unfiltered leakage into the control room envelope, the reduced outside air intake flow rate would result in control room doses that would not exceed the limits of 10 CFR 50, Appendix A, General Design Criterion (GDC) 19. Any increase in post-accident control room dose due to unfiltered inleakage at the lower observed control room pressure would be at least partially offset by the reduction in dose due to the reduced outside air intake flow rate.

In the event of a core damage event, radiological conditions in the control room would be monitored. Actions described in emergency plan implementing procedures would be taken, as necessary, to limit the thyroid dose to control room personnel. These actions could include ingestion of potassium Iodide pills and the use of respiratory protection (e.g., self-contained breathing apparatus).

Based on the above considerations, the event is considered of low safety significance and did not pose a threat to the health and safety of the public or site personnel.

IV. Corrective Actions

1.

To provide additional assurance that the blade lock will not inadvertently engage, a dimple was drilled in the blade lock's pull-down rod for both dampers 2HVP*DMP93 (Division II CREF) and 2HVP*DMP94 (Division I CREF). With the blade lock in the disengaged position, the setscrews were installed with loctite and tightened into the dimple to secure the blade lock in the disengaged position. The dampers were subsequently tested and returned to service.

2. The CREF system damper drawing was reviewed, and a walkdown of the CREF system was conducted. Only dampers 2HVC*DMP93 and 2HVC*DMP94 were identified as having the manual blade lock.
3. The CREF system monthly flow surveillance test procedure has been revised to provide guide values for acceptable flow and differential pressure conditions.
4.

Other ventilation system surveillance test procedures that are similar to the CREF system monthly flow surveillance test procedure were reviewed, and the acceptance criteria associated with these procedures were determined to be adequate to prevent similar occurrences of this event.

(If more space Is required, use adddonal copies aNRC Forn 366A) (17)

V. Additional Information

1. Failed Components:

Backdraft damper, mark no. 2HVC*DMP93, manufactured by Pacific Air Products Co., Model SLI 00

Previous similar events

None Identification of components referred to in this Licensee Event Report:

2.

3.

Components Control Room Envelope Control Room Envelope Filtration System Control Room Outside Air Special Filter Train Damper Filter IEEE 805 System ID NA VI VI VI VI IEEE 803A Function N/A N/A N/A UDMP FLT NRC FORM 386A (1.2001)