05000395/FIN-2013004-03
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Failure to Adequately Evaluate New Fire Hoses for Post-Loss of Coolant Accident Conditions |
Description | The NRC inspectors identified a NCV of 10 CFR Part 50, Appendix B, Criterion V, Instructions, Procedures, and Drawings, for the failure to adequately accomplish engineering services procedure, ES-0419, Equal To/Better Than (ETBT) Evaluation Process, Revision 9, for new fire hoses located in the reactor building. The issue was entered into the licensees CAP as condition report CR-12-05730. The inspectors determined that the failure to adequately accomplish ES-0419 for new fire hoses in the reactor building was a PD. The inspectors reviewed IMC 0612 and determined that the PD is more than minor and therefore a finding because if left uncorrected it would have the potential to lead to a more significant safety concern in that degradation of the fire hoses in post loss of coolant accident (LOCA) conditions would adversely impact the emergency core cooling system (ECCS) containment sump screens. The inspectors reviewed IMC 0609, Attachment 4, and Appendix A Exhibit 2, and determined the finding was of very low safety significance or Green because the finding was not a design deficiency or represented a loss of function. Specifically, the inspectors identified the problem prior to the licensee incurring actual risk exposure time. The inspectors reviewed IMC 0310 and determined the cause of the finding involved the cross-cutting area of human performance, the component of resources, and the aspect of adequate emergency equipment, H.2(d), because the licensee failed to ensure the new fire hoses would not impact safety-related components such as ECCS sump screens during post-LOCA conditions. |
Site: | Summer ![]() |
---|---|
Report | IR 05000395/2013004 Section 4OA5 |
Date counted | Sep 30, 2013 (2013Q3) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | |
Inspectors (proximate) | E Coffman J Reece R Hamilton R Kellner W Pursley |
Violation of: | 10 CFR 50 Appendix B Criterion V |
CCA | H.1, Resources |
INPO aspect | LA.1 |
' | |
Finding - Summer - IR 05000395/2013004 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Summer) @ 2013Q3
Self-Identified List (Summer)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||