Browse wiki

Jump to navigation Jump to search
The NRC inspectors identified a NCV of 10 The NRC inspectors identified a NCV of 10 CFR Part 50, Appendix B, Criterion V, Instructions, Procedures, and Drawings, for the failure to adequately accomplish engineering services procedure, ES-0419, Equal To/Better Than (ETBT) Evaluation Process, Revision 9, for new fire hoses located in the reactor building. The issue was entered into the licensees CAP as condition report CR-12-05730. The inspectors determined that the failure to adequately accomplish ES-0419 for new fire hoses in the reactor building was a PD. The inspectors reviewed IMC 0612 and determined that the PD is more than minor and therefore a finding because if left uncorrected it would have the potential to lead to a more significant safety concern in that degradation of the fire hoses in post loss of coolant accident (LOCA) conditions would adversely impact the emergency core cooling system (ECCS) containment sump screens. The inspectors reviewed IMC 0609, Attachment 4, and Appendix A Exhibit 2, and determined the finding was of very low safety significance or Green because the finding was not a design deficiency or represented a loss of function. Specifically, the inspectors identified the problem prior to the licensee incurring actual risk exposure time. The inspectors reviewed IMC 0310 and determined the cause of the finding involved the cross-cutting area of human performance, the component of resources, and the aspect of adequate emergency equipment, H.2(d), because the licensee failed to ensure the new fire hoses would not impact safety-related components such as ECCS sump screens during post-LOCA conditions. sump screens during post-LOCA conditions.  +
23:59:59, 30 September 2013  +
05000395  +
23:59:59, 30 September 2013  +
Has query"Has query" is a predefined property that represents meta information (in form of a <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Subobject">subobject</a>) about individual queries and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
Modification date"Modification date" is a predefined property that corresponds to the date of the last modification of a subject and is provided by <a rel="nofollow" class="external text" href="https://www.semantic-mediawiki.org/wiki/Help:Special_properties">Semantic MediaWiki</a>.
03:48:00, 28 September 2017  +
23:59:59, 30 September 2013  +
Failure to Adequately Evaluate New Fire Hoses for Post-Loss of Coolant Accident Conditions  +