05000387/LER-2011-002, Regarding Manual Scram Due to Unisolable Extraction Steam System Leak

From kanterella
Jump to navigation Jump to search
Regarding Manual Scram Due to Unisolable Extraction Steam System Leak
ML110950062
Person / Time
Site: Susquehanna 
Issue date: 03/28/2011
From: Rausch T
Susquehanna
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
LER 11-002-00
Download: ML110950062 (5)


LER-2011-002, Regarding Manual Scram Due to Unisolable Extraction Steam System Leak
Event date:
Report date:
Reporting criterion: 10 CFR 50.73(a)(2)(iv), System Actuation

10 CFR 50.73(a)(2)(i)

10 CFR 50.73(a)(2)(vii), Common Cause Inoperability

10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded

10 CFR 50.73(a)(2)(viii)(A)

10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition

10 CFR 50.73(a)(2)(viii)(B)

10 CFR 50.73(a)(2)(iii)

10 CFR 50.73(a)(2)(ix)(A)

10 CFR 50.73(a)(2)(iv)(A), System Actuation

10 CFR 50.73(a)(2)(x)

10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor

10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat

10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown

10 CFR 50.73(a)(2)(v), Loss of Safety Function

10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications
3872011002R00 - NRC Website

text

Timothy S. Rausch Sr. Vice President & Chief Nuclear Officer PPL Susquehanna, LLC 769 Salem Boulevard Berwick, PA 18603 Tel. 570.542.3445 Fax 570.542.1504 tsrausch@pplweb.com I

J MAR 2 8 2011 U. S. Nuclear Regulatory Commission Attn: Document Control Desk Mail Stop OP 1 -17 Washington, DC 20555 PP SUSQUEHANNA STEAM ELECTRIC STATION LICENSEE EVENT REPORT 50-387/2011-002-00 LICENSE NO. NPF-14 PLA-6703 Docket No 50-387 Attached is Licensee Event Report (LER) 50-387/2011-002-00. This event was determined to be a System Actuation and reportable under 10 CFR 50.73(a)(2)(iv) in that Unit 1 was manually scrammed due to an unisolable extraction steam leak. All systems functioned as required.

There were no actual consequences to the health and safety of the public as a result of this event.

No regulatory commitments are associated with this LER.

Attachment Copy:

NRC Region I Mr. P. W. Finney, NRC Sr. Resident Inspector Mr. R. R. Janati, DEP/BRP Mr. B. K. Vaidya, NRC Project Manager

NRC FORM 366 U.S. NUCLEAR REGULATORY COMMISSION APPROVED BY OMB: NO. 3150-0104 EXPIRES:10/31/2013 (10-2010)

, the NRC digits/characters for each block) may not conduct or sponsor, and a person is not required to respond to, the information collection.

l3. PAGE Susquehanna Steam Electric Station Unit 1 05000387 1 OF 4

4. TITLE Unit 1 Manual Scram due to Unisolable Extraction Steam System Leak
5. EVENT DATE
6. LER NUMBER
7. REPORT DATE
8. OTHER FACILITIES INVOLVED SEQUENTIAL REV FACILITY NAME DOCKET NUMBER MONTH DAY YEAR YEAR NUMBER NO.

MONTH DAY YEAR 05000 FACILITY NAME DOCKET NUMBER 01 25 2011 2011 - 002 -

00 03 28 2011 05000

9. OPERATING MODE
11. THIS REPORT IS SUBMITTED PURSUANT TO THE REQUIREMENTS OF 10 CFR§: (Check all that apply)

E] 20.2201(b)

[I 20.2203(a)(3)(i)

[l 50.73(a)(2)(i)(C)

E-50.73(a)(2)(vii)

El 20.2201(d)

[E 20.2203(a)(3)(ii)

El 50.73(a)(2)(ii)(A)

[3 50.73(a)(2)(viii)(A)

[E 20.2203(a)(1)

El 20.2203(a)(4)

El 50.73(a)(2)(ii)(B)

El 50.73(a)(2)(viii)(B)

El 20.2203(a)(2)(i)

El 50.36(c)(1)(i)(A)

El 50.73(a)(2)(iii)

El 50.73(a)(2)(ix)(A)

10. POWER LEVEL E] 20.2203(a)(2)(ii)

E] 50.36(c)(1)(ii)(A) 0 50.73(a)(2)(iv)(A)

El 50.73(a)(2)(x)

El 20.2203(a)(2)(iii)

[] 50.36(c)(2)

El 50.73(a)(2)(v)(A)

[1 73.71(a)(4)

El 20.2203(a)(2)(iv)

El 50.46(a)(3)(ii)

El 50.73(a)(2)(v)(B)

El 73.71(a)(5) 65%

[E 20.2203(a)(2)(v)

[E 50.73(a)(2)(i)(A)

[E 50.73(a)(2)(v)(C)

[E OTHER El 20.2203(a)(2)(vi)

El 50.73(a)(2)(i)(B)

[E 50.73(a)(2)(v)(D)

Specify in Abstract below or in

CORRECTIVE ACTIONS

The following corrective actions have been completed:

Valves in both units with a plugged pressure boundary penetration similar to BIV1 0245C have been identified.

The bleeder trip valve cover plug for BIV1 02450 was replaced and seal welded in-place.

The cover plugs for 12 other bleeder trip valves in Unit 1 were seal welded in-place.

The Crane, Hoist and Rigging Program was revised in 2003 after the last major overhaul of the valves to include a pre-lift checklist, which includes an inspection of attachment points.

Standards, expectations and importance of procedure use and adherence were discussed during the March 2011 All Hands meetings.

" Reviewed the procedure use and adherence performance gap as part of a separate evaluation of station procedure use and adherence.

The following corrective actions are planned:

Seal weld the Unit 2 valves with a plugged pressure boundary penetration.

Seal weld the remaining Unit 1 valves with a plugged pressure boundary penetration.

Revise controlled planning procedure which describes assembly and acceptance criteria for threaded pipe assemblies. The procedure will also include critical information on application and limitations of thread sealant.

Review Lessons Learned fact sheet with appropriate groups as an interim measure.

Evaluate knowledge gap via performance analysis in the Maintenance Curriculum Committee. Knowledge gap issue has been entered into the Corrective Action Program.

Implement corrective actions from the procedure use and adherence evaluation as follows:

Revise plant procedure to incorporate additional management expectations on procedure ownership, procedure quality, and use of Knowledge Based Decision Making.

Develop and implement a Dynamic Learning Activity for station personnel to demonstrate how procedure use and compliance expectations are to be met.

Create coaching card with enhanced criteria for what is to be observed regarding procedure use and adherence when performing direct and paired observations by supervisors and managers.

No regulatory commitments are associated with this report.

NRC Form 366 (10-2010)

ADDITIONAL INFORMATION

Failed Component Information:

Component:

BTV1 0245C; 16 inch Bleeder Trip (Check) Valve Manufacturer:

Atwood & Morrill Co.

Previous Similar Events

0 LER 2010-003-01, Docket No. 387/License No. NPF-14 LER 1993-009-00, Docket No. 388/License No. NPF-22 NRC Form 366 (10-2010)