Title | Failure to Adequately Implement Flooding EALs |
Description | The inspectors identified an NCV associated with emergency preparedness (EP) planning standard 10 CFR 50.47(b)(4), and the requirements of Sections IV.B and IV.C of Appendix E to 10 CFR Part 50. Specifically, Dominion did not maintain in effect the Millstone Units 2 and 3 emergency action level (EAL) schemes by failing to provide an effective measuring instrument for determining flooding water levels. These deficiencies adversely affected the ability of the licensee to properly classify events involving a major flood condition. Dominion entered the issue into their corrective action system (CR501482) and provided additional means to determine flood water levels. The finding is more than minor because it is associated with the Facilities and Equipment attribute of the EP Cornerstone and affected the cornerstone objective to ensure that the licensee is capable of implementing adequate measures to protect the health and safety of the public in the event of a radiological emergency. The inspectors determined the finding to be of very low safety significance (Green) because an EAL has been rendered ineffective such that a Notification of Unusual Event (NOUE) would not be declared for a flooding event, but because of other EALs, an appropriate declaration could be made in a degraded manner. The finding has a cross-cutting aspect in the area of Human Performance, Resources, in that Dominion personnel did not take provide appropriate procedures to address a Risk-Significant Planning Standard (RSPS) issue completely, accurately, and in a timely manner commensurate with the safety significance because Dominion did not provide a means of reliably and accurately assessing flooding levels that could reach 19 feet above mean sea level. |
Site: | Millstone ![]() |
---|---|
Report | IR 05000336/2012005 Section 1R01 |
Date counted | Dec 31, 2012 (2012Q4) |
Type: | NCV: Green |
cornerstone | Emergency Prep |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.01 |
Inspectors (proximate) | B Haagensen D Orr E Keighley J Ambrosini J Caruso J Deboer J Krafty M Modes R Bellamy R Rolph |
CCA | H.1, Resources |
INPO aspect | LA.1 |
' | |
Finding - Millstone - IR 05000336/2012005 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Millstone) @ 2012Q4
Self-Identified List (Millstone)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||