Title | Failure to Implement Timely Corrective Actions Resulted in a Plant Trip |
Description | A self-revealing finding was identified for the licensees failure to implement timely corrective actions. Specifically, after the overheating and failure of a Circulating Water Pump (CWP) motor resulted in an unplanned reactor down power, the licensee failed to implement timely corrective actions to monitor and trend motor stator temperatures using the installed RTDs. Consequently, a second CWP motor failed due to overheating that resulted in a reactor trip. No violations of NRC requirements were identified because the performance deficiency involved non-safely related equipment. The licensee entered this issue in the corrective action program as condition report 1697977. Corrective actions included immediately taking the motor stator RTD temperatures on both Units and using that data to monitor the CWP motors thermal performance for degradation. The finding was more than minor because it affected the equipment reliability attribute of the Initiating Events Cornerstone and affected the cornerstone objective to limit the likelihood of those events that upset plant stability and challenge critical safety functions during shutdown as well as power operations. Using NRC manual Chapter 0609.04, SDP Phase 1 screening, the finding was determined to be of very low safety significance (Green) because it was a transient initiator, but did not contribute to both the likelihood of a reactor trip and the likelihood that mitigation equipment or functions will not be available. The finding involved the cross-cutting area of Problem Identification and Resolution with a corrective action program aspect. Specifically, the licensee did not take appropriate corrective actions to address safety issues and adverse trends in a timely manner, commensurate with their safety significance and complexity. |
Site: | Saint Lucie |
---|---|
Report | IR 05000335/2012007 Section 4OA2 |
Date counted | Jun 30, 2012 (2012Q2) |
Type: | Finding: Green |
cornerstone | Initiating Events |
Identified by: | Self-revealing |
Inspection Procedure: | IP 71152 |
Inspectors (proximate) | G Hopper J Reyes J Sowa R Ng R Taylor T Chandler T Morrissey |
CCA | P.3, Resolution |
INPO aspect | PI.3 |
' | |
Finding - Saint Lucie - IR 05000335/2012007 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Saint Lucie) @ 2012Q2