Finding | |
|---|---|
| Title | Failure to Account for Essential Service Water Strainer Debris Loading and Isolation Valve Gross Leakage |
| Description | The inspectors identified a finding of very-low safety significance, and associated NCV of Title 10 Code of Federal Regulations (CFR) Part 50, Appendix B, Criterion III, Design Control, for the failure to account for the effects of the maximum strainer debris loading, and isolation valve gross leakage in the emergency service water flow balance testing and hydraulic analysis. As a result, the hydraulic calculations and flow balance test acceptance criteria overestimated the system flow capacity and, thus, did not ensure the capability of the system to meet its flow demand. The licensee entered this finding into their Corrective Action Program (CAP) to evaluate and resolve, including revising the affected calculations and test procedures. The performance deficiency was determined to be more than minor because it was associated with the Mitigating Systems cornerstone attribute of design control, and affected the cornerstone objective of ensuring the availability, reliability, and capability of mitigating systems to respond to initiating events to prevent undesirable consequences. The finding screened as very-low safety significance (Green) because it did not result in the loss of operability or functionality. Specifically, the licensee reviewed the latest flow balance test results and determined sufficient margin existed between the as-found value and the minimum required flowrate value to account for the effects of the strainer maximum debris loading. In addition, the licensee performed a historical review which did not find instances of isolation valve leakage in excess of the remaining margin. The inspectors did not identify a cross-cutting aspect associated with this finding because it was not confirmed to reflect current performance due to the age of the performance deficiency. |
| Site: | Cook |
|---|---|
| Report | IR 05000315/2015001 Section 1R07 |
| Date counted | Mar 31, 2015 (2015Q1) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.07 |
| Inspectors (proximate) | J Ellegood J Mancuso K Riemer L Rodriguez M Mitchell N Feliz-Adorno R Walton T Taylor |
| Violation of: | 10 CFR 50 Appendix B Criterion III, Design Control |
| INPO aspect | |
| ' | |