Finding | |
---|---|
Title | Fire Protection Compensatory Measures Did Not Cover All Fire Protection Features |
Description | The team identified a finding because the licensee did not include fire protection features in Procedure 1000.120, ANO Fire Impairment Program, Revision 20. The approved fire protection program required implementing compensatory measures for degraded fire protection systems and features, but the fire impairment implementing procedure addressed only action to identify, document and apply compensatory measures for specific fire protection systems. The team identified that the licensee did not implement compensatory measures for periods when the Appendix R emergency lighting units were placed out of service for maintenance and testing. This finding has been entered into the corrective action program as CR-ANO-C-2010-02205. Failure to ensure that all of the applicable elements of the approved fire protection program were included in the fire impairment implementing procedure is a performance deficiency. The finding is more than minor because it is associated with the Protection Against External Events attribute of the Mitigating Systems cornerstone since it affected the availability, reliability, and capability of systems that respond to fire events to prevent undesirable consequences. Because this issue relates to fire protection, the team used the guidance of Manual Chapter 0609, Appendix F, Attachment 2, to determine that this fire prevention and administrative control deficiency had a low degradation rating in that it minimally impacted the fire protection program. Based on this, the finding screened as having very low safety significance (Green) during a Phase 1 significance determination. This finding is identified as FIN 05000313;05000368/2010006-01, Inadequate Compensatory Measures for Out-Of-Service Appendix R Emergency Lights. No cross cutting aspect was associated with this finding because the team determined that this deficiency is not indicative of current performance because this practice existed for longer than three year |
Site: | Arkansas Nuclear |
---|---|
Report | IR 05000313/2010006 Section 1R05 |
Date counted | Sep 30, 2010 (2010Q3) |
Type: | Finding: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.05 |
Inspectors (proximate) | J Mateychick S Alferink S Graves E Uribe J Everett |
INPO aspect | |
' | |
Finding - Arkansas Nuclear - IR 05000313/2010006 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Arkansas Nuclear) @ 2010Q3
Self-Identified List (Arkansas Nuclear)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||