05000311/LER-1981-044, Forwards LER 81-044/04T-0.Detailed Event Analysis Encl

From kanterella
Jump to navigation Jump to search
Forwards LER 81-044/04T-0.Detailed Event Analysis Encl
ML20009E845
Person / Time
Site: Salem 
Issue date: 07/20/1981
From: Uderitz R
Public Service Enterprise Group
To: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML20009E846 List:
References
NUDOCS 8107280484
Download: ML20009E845 (3)


LER-1981-044, Forwards LER 81-044/04T-0.Detailed Event Analysis Encl
Event date:
Report date:
3111981044R00 - NRC Website

text

ver O PSEG Pubhc Service Electnc and Gas Company 80 Park Place Newark. N J. 07101 Phone 201430-7000 July 20, 1981 Mr. Boyce H. Grier Director of USNRC 5

g Office of Inspection and Enforcement S

XA Region 1 y

g 631 Park Avenue p

k

,h /

d Lu Q King of Prussia, Pennsylvania 19406 2

JUL 2 7 ;ggg,,(

Dear Mr. Grier:

tr

% g *sms# *//

enuna LICENSE NO. DP R-75 g

DOCKET NO. 50-311 f>

REPORTABLE OCCURRENCE 81-44/04T

'b Pursuant to the requirements of Salem Generating Station Unit No. 2 Technical Specifications, Section 5.6.2.2, we are submitting Licensee Event Report for Reportable Occurrence 81-44/04T.

This report is required within fourteen (14) days of the occurrence.

Sincerely yours,

[@

l l

R. A. UderitM l

General Manager -

I Nuclear Production CC:

Director, Office of Inspection and Enforcement (40) copies)

Director, Office of Management Information and Program Control (3 copies) l D'A$

l

>I

{

8107280484 10720 PDR ADOCK 05000311 S

PDR 95 2001 (300 % 1 79

Report Number:

81-44/04T Report Date:

July 20, 1981 Occurrence Date:

7-7-81 Facility:

Salem Generating Station, Unit 2 Public Service Electric & Gas Company Hancocks Bridge, New Jersey 08039 IDENTIFICATION OF OCCURRENCE:

Inadvertent Contamination Of On-Site Storage Area.

This report was initiated by Incident Report 81-235.

CONDITIONS PRIOR TO OCCURRENCE:

Mode 3 - Rx Power 0% - 0 MWe DESCRIPTION OF OCCURRENCE:

At 1800 hours0.0208 days <br />0.5 hours <br />0.00298 weeks <br />6.849e-4 months <br />, June 7, 1981, a routine radiation survey of the fenced in storage area outside No. 2 fuel handling building revealed contam-ination in excess of 10 times normal background.

The contamination was discovered in the area where the old No. 2 spent fuel storage racks had been stored after decontamination in preparation for shipment for disposal.

The area was roped off and further radiation surveys were undertaken.

DESIGNATION OF APPARENT CAUSE OF OCCURRENCE:

Personnel error.

Failure to properly protect the ground from possible contamination.

ANALYSIS OF OCCURRENCE:

When the spent fuel storage racks were removed from the Unit 2 spent fuel pool, they were decontaminated in accordance with station pro-cedures.

The resultant radiation levels were determined to be from previously fixed contamination.

The spent fuel storage racks were placed in the restricted fenced in yard next to the No. 2 fuel handling building awaiting disposal.

While awaiting disposal normal rainfall l

occurred.

The rinsing of the racks, with slightly acidic rain, along with the higher outside temperatures, apparently caused some contami-nation to wash off the racks on to the surface of the yard, i

l 1

i l

l l

l l

i

LER 81-44/04T July 20, 1981 s

3:

CORRECTIVE ACTION

.The contaminated area was surveyed to map out the exact locations of the contamination.

The contaminated dirt and stones have been re-moved and stored in sealed drums while awaiting shipment to a burial site.

The contamination was found not to have spread and the yard drains contained no trace of contamination.

Due to the uniqueness of this situation, no procedural changes are anticipated at this time.

Personnel have been counseled in the proper methods of radioactive material storage.

j FAILURE DATA:

Not Applicable 1

l, i.

Prepared By T.

J. Espey u

'6 Manager 4 Sdlem Generating Station SORC Meeting No.

81-63 i

l e

i i

I i