05000311/LER-1981-021, Forwards LER 81-021/03L-0.Detailed Event Analysis Encl

From kanterella
Jump to navigation Jump to search
Forwards LER 81-021/03L-0.Detailed Event Analysis Encl
ML20063H708
Person / Time
Site: Salem PSEG icon.png
Issue date: 06/17/1981
From: Uderitz R
Public Service Enterprise Group
To: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML20063H711 List:
References
NUDOCS 8209020085
Download: ML20063H708 (2)


LER-1981-021, Forwards LER 81-021/03L-0.Detailed Event Analysis Encl
Event date:
Report date:
3111981021R00 - NRC Website

text

.

[

O PSEG Pai.c Sar ice E!e:tric and Gas Company 80 Park Plata Newar k, N.J. 07101 Phone 201/430-7000 v

QeTT)R N $ -

fp 8, 6 TC-June 17, 1981 Mr. Boyce H. Grier Director of USNRC Office of Inspection and Enforcement Region 1 631 Park Avenue King of Prussia, Pennsylvania 19406

Dear Mr. Grier:

LICENSE NO. DPR-75 DOCKET NO. 50-311 REPORTABLE OCCURRENCE 81-21/03L Pursuant to the requirements of Salem Generating Station Unit No. 2 Technical Specifications, Section 6.9.1, we are submitting Licensee Event Report for Reportable Occurrence 81-21/03L.

This report is required within thirty (30) days of the occurrence.

Sincerely yours, k ; U erl R.

A.

General Manager -

Nuclear Production

[ CC:

Director, Office of Inspection i

l 1

and Enforcement (30 copies) l Director, Office of Management Information and Program Control (3 copies) 1 1

I

[

8209020085 810617 PDR ADOCK 05000311 S

PDR The Energy People 95 200? :3$3*/. 4 E

Rap,dtt-Number:

81-21/03L R port Dato:

June 17, 1981

' Occurrence Date:

5/19/81 Facility:

Salem Generating Station, Unit 2 Public Service Electric & Gas Company Hancocks Bridge, New Jersey 08038 IDENTIFICATION OF OCCURRENCE:

Auxiliary Feedwater Storage Tank (AFWST) < 200,000 Gallons CONDITIONS PRIOR TO OCCURRENCE:

Mode 2 - Rx Power 3% - Unit Load OMW DESCRIPTION OF OCCURRENCE:

During a routine surveillance of the console, it was determined the level in the AFWST was below the minimum level (200,000 gallons).

Action Statement 3.7.1.3 was entered at 1036 hours0.012 days <br />0.288 hours <br />0.00171 weeks <br />3.94198e-4 months <br /> on May 19, 1981.

This occurrence constituted operation in a degraded mode IAW Technical Specification 6.9.1.9b.

DESIGNATICN OF APPARENT CAUSE OF OCCURRENCE:

Personnel error.

In the process of using the AFWST as a water supply for steam line heatup, the supply valve to the AFWST was throttled too far to compensate for the water removed.

ANALYSIS OF OCCURRENCE:

Technical Specification 3.7.1.3a requires that with the auxiliary feed storage tank inoperable, within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> restore the AFST to operable status or be in hot standby within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

CORRECTIVE ACTION

The AFWST was filled to > 200,000 gallons of stored water.

DCR-1-EC763 and DCR-2-EC762 have been issued to provide an additional level alarm that can be acted upon prior to the AFWST level decreasing to 200,000 gallons.

Action Statement 3.7.1.3a was terminated at 1050 hours0.0122 days <br />0.292 hours <br />0.00174 weeks <br />3.99525e-4 months <br /> on May 19. 1981.

FAILURE DATA:

Not Applicable

'A Prepared By J. J.

Espey

/

Manager - Salem 7enerating Station SORC Meeting No.

81-50