Finding | |
|---|---|
| Title | Failure to Adequately Torque Fasteners on Emergency Diesel Generator Number 2 |
| Description | The team reviewed a self-revealing non-cited violation of 10 CFR Part 50, Appendix B, Criterion V, Instructions, Procedures, and Drawings, which occurred when the licensee failed to include specific instructions in work orders with respect to the use of lubrication during emergency diesel generator (EDG) fastener torquing. The failure to include specific lubrication instructions in work orders resulted in the inadequate torquing of bolting on the number 2 EDG and contributed to a lube oil leak during a surveillance run of the affected diesel. Procedures in effect during the time the fasteners were torqued required planners to include specific lubrication instructions in work orders for the EDGs. The licensee corrected the current issue by properly lubricating and torquing the fasteners for the right bank camshaft and restored the EDG 2 to operable status. The licensee entered this issue into the corrective action program as condition report CR-CNS-2014-06885. The failure to specify lubricants in EDG work order instructions involving fastener torquing, in violation of Procedure 7.2.53.12, Cooper Bessemer Bolting and Torque Program, is a performance deficiency. The performance deficiency was determined to be more than minor, and therefore a finding, because it was associated with the human performance attribute of the mitigating systems cornerstone and affects the associated cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events. Additionally, if left uncorrected, it has the potential to lead to a more significant safety concerns, in that the failure to include these instructions in work orders has resulted in, and could continue to result in loose fasteners on the emergency diesel generator. Using Inspection Manual Chapter 0609, Appendix A, issued June 19, 2012, the Significance Determination Process for Findings At Power; the inspectors determined the finding was of very low safety significance (Green) because the finding: (1) was not a deficiency affecting the design and qualification of a mitigating structure, system, or component, and did not result in a loss of operability or functionality; (2) did not represent a loss of system and/or function; (3) did not represent an actual loss of a function of a single train for greater than the technical specification (TS) allowed outage time, and (4) did not represent an actual loss of a function of one or more non-TS trains of equipment. The finding has a cross-cutting aspect in the problem identification and resolution area due to the organizations failure to take effective corrective actions to address the deficiency after it was identified in a 2010 root cause evaluation and failure to recognize the ineffectiveness of the previous corrective actions until after the lube oil leak in 2014 (P.3). |
| Site: | Cooper |
|---|---|
| Report | IR 05000298/2015008 Section 4OA2 |
| Date counted | Jun 30, 2015 (2015Q2) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | Self-revealing |
| Inspection Procedure: | IP 71152 |
| Inspectors (proximate) | C Henderson E Ruesch J Melfi P Jayroe |
| Violation of: | 10 CFR 50 Appendix B Criterion V Technical Specification Technical Specification - Procedures |
| CCA | P.3, Resolution |
| INPO aspect | PI.3 |
| ' | |