05000285/FIN-2010004-02
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Failure to Submit a Required Licensee Event Report |
| Description | The inspectors identified a Severity Level IV noncited violation for the failure to submit a licensee event report within 60 days as required by 10 CFR 50.73. Specifically, the diesel fuel oil storage system was inoperable for approximately 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> from January 6, 2010, until January 7, 2010. On January 6, 2010, fuel oil transfer pump FO-37 was inoperable due to a fire main rupture submerging the pump for approximately 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. With no other means to transfer fuel from storage tank FO-10 to FO-1, the fuel oil storage system was inoperable, and the fuel volume in FO-10 was unavailable. This was reportable condition required by 10 CFR 50.73(a)(2)(i)(B) as a condition prohibited by technical specifications. The licensee performed a reportability evaluation, and the violation was entered into the corrective action program as Condition Report 2010-3865.
The inspectors determined that the licensees failure to submit a licensee event report was a performance deficiency. The inspectors reviewed this issue in accordance with NRC Inspection Manual Chapter 0612 and the NRC Enforcement Manual. Through this review, the inspectors determined that traditional enforcement was applicable to this issue because the NRC\'s regulatory ability was potentially affected. Specifically, the NRC relies on licensees to identify and report conditions or events meeting the criteria specified in regulations in order to perform its regulatory function, and when this is not done the regulatory function is impacted, and is therefore more than minor. The inspectors determined that this finding was not suitable for evaluation using the significance determination process, and as such, was evaluated for traditional enforcement only in accordance with the NRC Enforcement Policy. This is a Severity Level IV violation as defined in Section 2.2.1.c of the NRC Enforcement Policy (Section 1R15). |
| Site: | Fort Calhoun |
|---|---|
| Report | IR 05000285/2010004 Section 1R15 |
| Date counted | Sep 30, 2010 (2010Q3) |
| Type: | NCV: |
| cornerstone | Miscellaneous |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.15 |
| Inspectors (proximate) | L Ricketson J Kirkland D Stearns G George J Clark D Graves I Anchondo W Schaup T Buchanan R Hickok N Greene J Wingebach |
| INPO aspect | |
| ' | |