05000277/LER-2012-001, Regarding Laboratory Analysis Identities Safety Relief Valves and Safety Valve Set Point Deficiencies

From kanterella
(Redirected from 05000277/LER-2012-001)
Jump to navigation Jump to search
Regarding Laboratory Analysis Identities Safety Relief Valves and Safety Valve Set Point Deficiencies
ML12311A021
Person / Time
Site: Peach Bottom 
Issue date: 11/02/2012
From: Pat Navin
Exelon Generation Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
LER-12-001-00
Download: ML12311A021 (6)


LER-2012-001, Regarding Laboratory Analysis Identities Safety Relief Valves and Safety Valve Set Point Deficiencies
Event date:
Report date:
Reporting criterion: 10 CFR 50.73(a)(2)(i)

10 CFR 50.73(a)(2)(vii), Common Cause Inoperability

10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded

10 CFR 50.73(a)(2)(viii)(A)

10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition

10 CFR 50.73(a)(2)(viii)(B)

10 CFR 50.73(a)(2)(iii)

10 CFR 50.73(a)(2)(ix)(A)

10 CFR 50.73(a)(2)(iv)(A), System Actuation

10 CFR 50.73(a)(2)(x)

10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor

10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat

10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown

10 CFR 50.73(a)(2)(v), Loss of Safety Function

10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications
2772012001R00 - NRC Website

text

A Exelon Generation.

10CFR 50.73 November 2, 2012 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 Peach Bottom Atomic Power Station (PBAPS) Units 2 Renewed Facility Operating License No. DPR-44 NRC Docket Nos. 50-277

Subject:

Licensee Event Report (LER) 2-12-001 Enclosed is a Licensee Event Report concerning a condition prohibited by Technical Specifications involving Safety Relief Valves (SRVs) and one Safety Valve (SV) that did not meet their Technical Specification + 1% set point tolerance when tested in the laboratory. In accordance with NEI 99-04, the regulatory commitment contained in this correspondence is to restore compliance with the regulations. The specific methods that are planned to restore and maintain compliance are discussed in the LER. If you have any questions or require additional information, please do not hesitate to contact us.

Sincerely, Patrick D. Navin Plant Manager Peach Bottom Atomic Power Station PDN/djf/IR 1418320 / 1417767 / R1181769 Attachment cc:

US NRC, Administrator, Region I US NRC, Senior Resident Inspector R. R. Janati, Commonwealth of Pennsylvania S. Grey, State of Maryland P. Steinhauer, PSE&G, Financial Controls and Co-owner Affairs INPO Records Center CCN: 12-70

NRC FORM 366 U.S. NUCLEAR REGULATORY COMMISSION APPROVED BY OMB: NO. 3150-0104 EXPIRES: 10/31/2013

',10-2010)

, the NRC may e for each bock) not conduct or sponsor, and a person is not required to respond to, the digits/characters finformation collection.

3. PAGE Peach Bottom Atomic Power Station (PBAPS) Unit 2 05000277 1 OF 5
4. TITLE Laboratory Analysis Identifies Safety Relief Valves and Safety Valve Set Point Deficiencies
5. EVENT DATE
6. LER NUMBER
7. REPORT DATE
8. OTHER FACILITIES INVOLVED FACILITY NAME DOCKET NUMBER MONTH DAY YEAR YEAR SUE REV MONTH DAY YEAR 05000 MONT DAY YEAR YEAR NUMBER NO.

FACILITY NAME DOCKET NUMBER 09 25 2012 12

- 001 -

00 11 02 2012 05000

9. OPERATING MODE
11. THIS REPORT IS SUBMITrED PURSUANT TO THE REQUIREMENTS OF 10 CFR §: (Check all that apply)

[] 20.2201(b)

El 20.2203(a)(3)(i)

[E 50.73(a)(2)(i)(C) 0 50.73(a)(2)(vii)

N El 20.2201(d)

El 20.2203(a)(3)(ii)

El 50.73(a)(2)(ii)(A)

[I 50.73(a)(2)(viii)(A)

El 20.2203(a)(1)

[E 20.2203(a)(4)

El 50.73(a)(2)(ii)(B)

[E 50.73(a)(2)(viii)(B)

El 20.2203(a)(2)(i)

El 50.36(c)(1)(i)(A)

El 50.73(a)(2)(iii)

[E 50.73(a)(2)(ix)(A)

10. POWER LEVEL [E

20.2203(a)(2)(ii)

El 50.36(c)(1)(ii)(A)

[I 50.73(a)(2)(iv)(A)

El 50.73(a)(2)(x)

El 20.2203(a)(2)(iii)

El 50.36(c)(2)

El 50.73(a)(2)(v)(A)

El 73.71 (a)(4) 0%

El 20.2203(a)(2)(iv)

El 50.46(a)(3)(ii)

[I 50.73(a)(2)(v)(B)

El 73.71(a)(5)

El 20.2203(a)(2)(v)

[E 50.73(a)(2)(i)(A)

[] 50.73(a)(2)(v)(C)

E] OTHER El 20.2203(a)(2)(vi) 0 50.73(a)(2)(i)(B)

El 50.73(a)(2)(v)(D)

Specify in Abstract below or in

Cause of the Event

The cause of the SRVs / SV being outside of their allowable as-found setpoints is due to setpoint drift.

Additional evaluations of the cause(s) of the SRVs / SV setpoint deficiencies are being performed in accordance with the site Corrective Action Program.

Analysis of the Event

There were no actual safety consequences associated with this event.

This report is being submitted pursuant to:

10CFR 50.73(a)(2)(i)(B) - Condition Prohibited by Technical Specifications -'Technical Specification Limiting Condition for Operation (LCO) 3.4.3 requires that 11 of the 13 SRVs / SVs be operable during operational Modes 1, 2, and 3.

Contrary to this requirement, six SRVs and one SV were found with setpoints outside of the Technical Specification setpoint requirements.

10CFR 50.73(a)(2)(vii) - Common Cause Failure of Multiple Trains being Inoperable -

Six SRVs and one SV were considered inoperable as a result of exceeding their allowable setpoint range based on laboratory testing.

Therefore, this occurrence is considered as a common cause failure of multiple independent trains being inoperable.

The ASME Boiler and Pressure Vessel Code requires that the Reactor Pressure Vessel (EIIS:

RCT) be protected from overpressure during upset conditions by self-actuated relief valves. As part of the nuclear pressure relief system, the size and number of SRVs and SVs are selected such that the peak pressure in the nuclear system will not exceed the ASME Code limits for the Reactor Coolant Pressure Boundary. There exists a total of 13 SRVs / SVs installed on the four Main Steam (EIIS: SB) Lines. The eleven installed SRVs exhaust steam through discharge lines to a point below the minimum water level in the Suppression Pool. The two installed SVs discharge steam directly to the Drywell. The SRVs and SVs are located on the four main steam lines (EIIS: SB) within Primary Containment. The SRVs are 'three-stage' valves consisting of a main valve disc and piston (third stage) operated by a second stage disc and piston displaced by either a first stage pressure-sensing pilot (for overpressure protection) or a pneumatically-operated mechanical push rod (for the ADS function or for remote-manual operation). The SVs are direct-acting, spring loaded relief valves.

Analysis of the Event

continued There were a total of seven SRVs and one SV initially removed for testing and replacement during the 1 9 th Refueling Outage. Technical Specification Limiting Condition for Operation 3.4.3 requires 11 of the 13 total SRVs / SVs to be operable to provide the reactor coolant system overpressure safety function. The safety function of any combination of 11 SRVs and SVs are required to satisfy the assumptions of the safety analyses.

During the Unit 2 Cycle 19 operations, there were no plant transients that required automatic or manual SRV / SV operation.

The as-found setpoints for the six SRVs that tested outside of their Technical Specification allowable range were low.

However, all six SRVs outside of their Technical Specification allowable setpoint range were within the ASME Code allowable +/- 3% tolerance.

Because the SRV as-found set points were on the low side, there was no loss of the TS 3.4.3 overpressure safety function for these valves. The one SV outside of its TS allowable range also exceeded the ASME Code allowable +/- 3% tolerance. Since only 11 of the 13 SRVs / SVs are required to be operable, the 70B SV did not impact the TS 3.4.3 safety function. Two of the six SRVs (SRV S/N 82 and S/N 24) were also Automatic Depressurization System (ADS) valves. The setpoint drift had no impact on the ADS or manual function of the valves.

The event is not considered to be risk significant.

Corrective Actions

The six SRVs and the one SV were replaced with refurbished SRVs / SV for the 2 0 th Unit 2 operating cycle. Since the 70B SV exceeded the + 3% SV tolerance, the other SV (70A) was removed and sent for laboratory testing in accordance with the ASME code. The 70A SV was replaced with a refurbished SV for the 2 0 th Unit 2 operating cycle.

A licensing change to revise the SRV / SV set point tolerance to + 3% is planned to be submitted to the NRC in 2013.

Other actions will be pursued, as necessary, to address causes determined in accordance with the site Corrective Action Program.

Previous Similar Occurrences There were four previous LERs identified involving SRVs / SVs exceeding their Technical Specification +/- 1% setpoint requirement. LER 2-10-03 reported two SRVs and one SV having their as-found setpoints in excess of the TS allowable + 1% tolerance. LER 3-07-01 reported two SRVs and one SV having their as-found setpoints in excess of the TS allowable +/- 1%

tolerance.

LER 2-06-02 reported one SV having its as-found setpoints in excess of the TS allowable +/- 1% tolerance. LER 3-05-04 reported a situation involving four SRVs having their as-found setpoints in excess of the TS allowable +/- 1% tolerance.

Previous Similar Occurrences, continued The previous SRV / SV as-found setpoints were all within the +/- 3% ASME code allowable setpoint tolerance. Completed corrective actions addressing setpoint drift for these previous events involved replacement of the previous SRVs with different SRVs and therefore, would not have been expected to prevent this event. The corrective action discussed in LER 2-10-03 to revise the TS to change the SRV/SV tolerance from + 1% to + 3% is not yet complete. The TS change request is expected to be submitted in 2013.