consumers Power company General Offices: 212 West Michigan Avenue, Jackson, Michigan 49201
- Area Code 517 788-0550 September 22, 1976 Mr James G. Keppler Office of Inspection & Enforcement Region III' US Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, IL 60137 DOCKEI' 50-255, LICENSE DPR PALISADES PLANT ~ ER-76 RPS MATRIX RELAYS The attached event report relates to a failure of an RPS Matrix relay at the Palisades Plant.
This type of failure is reportable on a thirty-day basis but the report was inadvertently misplaced.
The discovery of this omission was the result of the recent emphasis being placed on event reports and an extensive search for this event report which was mislaid during the plant review process.
In an effort to resolve this problem, the plant staff has instituted a formal method of maintaining control of all Palisades Plant event report.s.
This method of control will be maintained until the Company computerized status system proves capable of performing this function.
As mentioned in the report, a testing program involving the selection of a re-placement relay is nearing completion.
We have performed a series of tests on five different relays that were ordered to specification equivalent to the ex-isting relays..
- These relays (all dry contact type) have been subjected to a series of tests including surge current, seismic, operating time, etc.
Pre-liminary results lead us to conclude that an acceptable replacement relay will be found.
David A. Bixel Assistant Nuclear Licensing Administrator SEP 2 7 1976
e LICENSEE EVENT REPORT
- Palisades CONTROL BLOCK:... I __.... I __.___..__.I [PLEASE PRINT ALL REQUIRED INFORMATION]
LICENSEE NAME 01 IMIIIPIAILlll 7
8 9 14 1
6 LICENSE NUMBER 10101-1°101°1°1°1-1°1°1 15 25 REPORT REPORT LICENSE TYPE 14111111111 26 30 EVENT TYPE I 0 I 3 I 31 32 REPORT OATE
@E]coN'T 1 I I 7
8 57 58 TYPE SOURCE w L1J DOCKl;T NUMBER lol51ol-101215151 EVENT OATE lo l5l 2IOl716 I 1°191 2 12 17161 59
.60 61 BB 69 74 75 80
EVENT DESCRIPTION
lol2l !During routine testing it was found that one of the twenty-four.RPS Matrix relays I
7 89 00 lolsj I failed to operate.
Light tapping of the relay case appears to have resolved the I
7 89 00 lol41 I problem.* Weekly testing of the relays has continued with no further problems I
7 8 9 80 lol51 I observed to date.
I 7 89 00 jol6I ~'------------------------------------------~(_ER_-~7_6-_1~7~) __________ ~1 7
8 9 PRME 80 SYSTEM
CAUSE
COMPONENT COMPONENT.
COOE COOE COMPONENT COOE SUPPLIER MANUFACTURER VIOLATIJN
@0 lrf Al lliJ IRfEILfA(Ylxl w
I A I 0 I 5 ( 5 I L!J 7
8 9 10 11 12 17 43 44 47 48 CA!JSE DESCRIPTION fol0I I The cause of this failure appears to be associat~d with the mercury wetted 7
8 9
- lolsl I contacts. (ADLAKE Mod MW-2621-609) and is similar to that reported previously
~
j (UE-74-1).
A selected group of replacement relays is currently being tested.
8 9 FACILITY (Contd Line 18)
METHOD OF STATUS
% POWER OTHER STATUS DISCOVERY DESCRIPTION DISCOVERY I
EEi illJ I 0 I 5 I 0 I -' __
NA __
7 El 9
10 12 13 FORM OF 44 ACTIVITY CONTENT RELEASED OF RELEASE AMOUNT OF ACTIVITY EEl
~ W
..... I ___
N_A ___
__, I 7
8 9
10 11 44 PERSONNEL EXPOSURES NUMBER TYPE
DESCRIPTION
[ill I ol o Io I * ~
7 8 9 11 12 13 PERS.ONNEL INJURIES NUMBER
DESCRIPTION
[EJ I 01 o I o I 7
8 9 11 12 l1LJ 45 I
45 NA NA 46 NA LOCATION OF RELEASE NA I
80 I
80 I
80 80 80 80 80 PROBABLE C-ONSEQUENCES EJfil I None.
The system is 7
8 9 designed to perform its function with a failure of this type. I 80 LOSS OR DAMAGE TO FACILITY TYPE
DESCRIPTION
ITfil uJ NA 7
8 9 10 80 PUBLICITY ADDITIONAL FACTORS I A report on the results of these tests will be completed within the next few weeks. I 7
89 00 ITJfil I Resolution of the problem is expected to begin following review of the report.
7 89 80
|
|---|
|
|
| | | Reporting criterion |
|---|
| 05000255/LER-2076-001, Licensee Event Report ER-76-01 - Sirw Vent Plugged | Licensee Event Report ER-76-01 - Sirw Vent Plugged | | | 05000255/LER-2076-002, Licensee Event Report ER-76-02 - Rps/Sis - Ps Out of Calibration | Licensee Event Report ER-76-02 - Rps/Sis - Ps Out of Calibration | | | 05000255/LER-2076-003, Licensee Event Report ER-76-03 - CCW P52-C Inboard Bearing Failed While Preventative Maintenance Was Being Performed on CCW Pump P52-A | Licensee Event Report ER-76-03 - CCW P52-C Inboard Bearing Failed While Preventative Maintenance Was Being Performed on CCW Pump P52-A | | | 05000255/LER-2076-004, Licensee Event Report ER-76-04 - MSIV Closure Set Point Was Found Below Tech Spec Limit of Greater than 500 Psia on Two Instruments | Licensee Event Report ER-76-04 - MSIV Closure Set Point Was Found Below Tech Spec Limit of Greater than 500 Psia on Two Instruments | | | 05000255/LER-2076-006, Licensee Event Report ER-76-06 - Several CRDM Inner Bearing of Clutches Would Not Rotate When Turned by Hand or a Number of Others Did Not Rotate Freely | Licensee Event Report ER-76-06 - Several CRDM Inner Bearing of Clutches Would Not Rotate When Turned by Hand or a Number of Others Did Not Rotate Freely | | | 05000255/LER-2076-007, Licensee Event Report ER-76-0087: Reactor Protective System, Main Steam Flow Transmitter Was Found Out of Tolerance During Surveillance Testing, & Transmitter Could Not Be Recalibrated | Licensee Event Report ER-76-0087: Reactor Protective System, Main Steam Flow Transmitter Was Found Out of Tolerance During Surveillance Testing, & Transmitter Could Not Be Recalibrated | | | 05000255/LER-2076-008, Licensee Event Report ER-76-008, Gaseous Release, Which Was Caused by Operational Error, Not Released Above Permissible Levels | Licensee Event Report ER-76-008, Gaseous Release, Which Was Caused by Operational Error, Not Released Above Permissible Levels | | | 05000255/LER-2076-009, Licensee Event Report ER-76-009, Containment Spray, a Condition Leading to Operation in a Degraded Mode | Licensee Event Report ER-76-009, Containment Spray, a Condition Leading to Operation in a Degraded Mode | | | 05000255/LER-2076-010, Licensee Event Report ER-76-010, During Testing, the Charging Pump, P55-A, Failed to Perform Properly | Licensee Event Report ER-76-010, During Testing, the Charging Pump, P55-A, Failed to Perform Properly | | | 05000255/LER-2076-012, Licensee Event Report ER-76-0102, for Long-Term Cooling Qualification, Two Valves, CV-2113 & CV-2115, Associated with Charging System, May Not Meet Code Requirement | Licensee Event Report ER-76-0102, for Long-Term Cooling Qualification, Two Valves, CV-2113 & CV-2115, Associated with Charging System, May Not Meet Code Requirement | | | 05000255/LER-2076-013, Licensee Event Report ER-76-013, Discharge of Cooling Water Above 5oF Limit | Licensee Event Report ER-76-013, Discharge of Cooling Water Above 5oF Limit | | | 05000255/LER-2076-014, Licensee Event Report ER-76-14, Relating to Removing Diesel Generator from Service, Advising, Corrective Action Will Be Completed About 8/1/1976, Not by 7/1/1976 as Transmitted on 5/25/1976 | Licensee Event Report ER-76-14, Relating to Removing Diesel Generator from Service, Advising, Corrective Action Will Be Completed About 8/1/1976, Not by 7/1/1976 as Transmitted on 5/25/1976 | | | 05000255/LER-2076-017, License Event Report 1976-017-00 Re Failure of RPS Matrix Relays | License Event Report 1976-017-00 Re Failure of RPS Matrix Relays | | | 05000255/LER-2076-021, Licensee Event Report ER-76-21 - Containment Purge Supply Valve, a Condition Leading to Operation on a Degraded Mode | Licensee Event Report ER-76-21 - Containment Purge Supply Valve, a Condition Leading to Operation on a Degraded Mode | | | 05000255/LER-2076-023, Corrected Licensee Event Report ER-76-23: Changing Typographical Error of Event Report No. ER-76-03 to ER-76-23 - Dealing with CCW Pump P-52-C, Inboard Bearing Failure | Corrected Licensee Event Report ER-76-23: Changing Typographical Error of Event Report No. ER-76-03 to ER-76-23 - Dealing with CCW Pump P-52-C, Inboard Bearing Failure | | | 05000255/LER-2076-024, Licensee Event Report ER-76-24 - Exceeding Pdil Limits, Which Will Be Resolved Through Clarification of Present Plant Technical Specification | Licensee Event Report ER-76-24 - Exceeding Pdil Limits, Which Will Be Resolved Through Clarification of Present Plant Technical Specification | | | 05000255/LER-2076-025, Licensee Event Report ER-76-25 - Hydrogen Recombiner, a Condition Leading to Operation on a Degraded Mode | Licensee Event Report ER-76-25 - Hydrogen Recombiner, a Condition Leading to Operation on a Degraded Mode | | | 05000255/LER-2076-026, Licensee Event Report ER-76-26 - Plant Discharge Temperature Increased More Rapidly than Expected | Licensee Event Report ER-76-26 - Plant Discharge Temperature Increased More Rapidly than Expected | | | 05000255/LER-2076-027, Licensee Event Report ER-76-27 - Containment Purge Supply Valve | Licensee Event Report ER-76-27 - Containment Purge Supply Valve | | | 05000255/LER-2076-028, License Event Report 1976-028-00 Re Rod Sequencer Operation | License Event Report 1976-028-00 Re Rod Sequencer Operation | | | 05000255/LER-2076-029, License Event Reports 1976-029-00, 1976-030-00, & 1976-031-00 Re Control Rod Drives | License Event Reports 1976-029-00, 1976-030-00, & 1976-031-00 Re Control Rod Drives | | | 05000255/LER-2076-033-01, Low D-C Voltage | Low D-C Voltage | | | 05000255/LER-2076-034, License Event Reports 1976-034-00 & 1976-035-00 Re Discharge Cooling Water Above 5oF Limit | License Event Reports 1976-034-00 & 1976-035-00 Re Discharge Cooling Water Above 5oF Limit | | | 05000255/LER-2076-036, License Event Report 1976-036-00 Re Containment Air Locks | License Event Report 1976-036-00 Re Containment Air Locks | | | 05000255/LER-2076-037, License Event Report 1976-037-00 Re Out-of-Spec Point of Neutron Monitor Channel C | License Event Report 1976-037-00 Re Out-of-Spec Point of Neutron Monitor Channel C | | | 05000255/LER-2076-038, License Event Reports 1976-038-00, 1976-039-00, 1976-040-00, & 1976-042-00 Re Discharge Cooling Water Above 5oF Limit | License Event Reports 1976-038-00, 1976-039-00, 1976-040-00, & 1976-042-00 Re Discharge Cooling Water Above 5oF Limit | | | 05000255/LER-2076-041, License Event Report 1976-041-00 Re Chlorine Discharge Limit Exceeded | License Event Report 1976-041-00 Re Chlorine Discharge Limit Exceeded | | | 05000255/LER-2076-043, License Event Report 1976-043-00 Re Leak in Charging Pump Suction Line | License Event Report 1976-043-00 Re Leak in Charging Pump Suction Line | | | 05000255/LER-2076-044, License Event Report 1976-044-00 Re Drift of Reactor Protection System Steam Generator Low Level Trip Set Point | License Event Report 1976-044-00 Re Drift of Reactor Protection System Steam Generator Low Level Trip Set Point | | | 05000255/LER-2076-045, License Event Report E1976-045-00 Re Failure of DBA Sequencer to Operate | License Event Report E1976-045-00 Re Failure of DBA Sequencer to Operate | | | 05000255/LER-2076-046, Re Chemicals Passed Through Neutralizer Tank Into Plant Discharge Structure | Re Chemicals Passed Through Neutralizer Tank Into Plant Discharge Structure | |
|