05000255/FIN-2011003-06
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Failure to Include The Steam Generator Mausoleum in the Groundwater Protection Risk Ranking Program, Problem Identification & Resolution |
| Description | The inspectors identified a finding of very low-safety-significance and an associated NCV of TS 5.4.1, Procedures, for the failure to implement procedures and include the steam generator mausoleum in the groundwater risk-ranking program for structures, systems, or components after a small amount of water was identified on the floor that contained Cs-137 and tritium with a credible mechanism to reach groundwater. Specifically, the licensee did not implement Station Procedure EN-CY-111, Radiological Groundwater Monitoring Program to evaluate and document this structure after it was determined to contain radioactive liquids with a single barrier before reaching groundwater. Completion of the groundwater risk-ranking process may have prescribed additional measures to enhance or reinstate leak detection methods for this structure that contains licensed material and for which there is a credible mechanism for licensed material to reach groundwater. The licensee entered the condition into the corrective action program. Corrective actions included creating a recurring action item AR 00107492 to inspect the mausoleum every 6 months and clean up any water. The finding was more than minor because it affected the Public Radiation Safety Cornerstone objective to ensure adequate protection of public health and safety from exposure to radioactive materials released into the public domain, in that these conditions could result in reduced capability to detect and correct leaks of radioactive material before there is an impact on public dose. It is associated with program and process attribute of this cornerstone. Using IMC 0609, Attachment D, for the Public Radiation Safety SDP, the inspectors determined the finding to be of very low-safety significance because there is no indication of a spill or release of radioactive material on site or to the offsite environs from this structure and therefore, this finding was not a failure to implement the effluent program and public dose remained less than 10 CFR Part 50, Appendix I, limits. The finding was previously entered in the licensees corrective action program. However, the licensee failed to take appropriate corrective actions to address issues. Consequently, this deficiency has a cross-cutting aspect in Problem Identification and Resolution (Corrective Action Program). |
| Site: | Palisades |
|---|---|
| Report | IR 05000255/2011003 Section 2RS7 |
| Date counted | Jun 30, 2011 (2011Q2) |
| Type: | NCV: Green |
| cornerstone | Pr Safety |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71124.07 |
| Inspectors (proximate) | M Holmberg J Cassidy J Ellegood R Walton T Taylor J Beavers |
| CCA | P.3, Resolution |
| INPO aspect | PI.3 |
| ' | |
Finding - Palisades - IR 05000255/2011003 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Palisades) @ 2011Q2
Self-Identified List (Palisades)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||