05000255/FIN-2008002-01
From kanterella
Jump to navigation
Jump to search
Finding | |
|---|---|
| Title | Failure to Ensure Fire Door Was Closed (Section 1R05) |
| Description | The inspectors identified a Green NCV of License Condition 2.C.(3), Fire Protection, for failure to ensure a fire door between an emergency diesel generator room and a vital switchgear room was closed. This partially open door degraded the fire containment capability assumed in the fire hazards analysis. The fire door was closed and this issue was entered into the licensee\'s corrective action program as CR-PLP-2008-00075. The finding is more than minor because it is associated with the protection against external factors (fires) attribute of the mitigating system cornerstone and affected the objective to maintain the reliability and capability of systems that respond to events to prevent undesirable consequences. In accordance with Inspection Manual Chapter 0609, Appendix F, Fire Protection SDP, the inspectors conducted a Phase I SDP screening. The inspectors determined the finding is of very low safety significance (Green), because the fire areas had fully functional, automatic waterbased fire suppression which provided adequate coverage in both rooms and no transient combustible loads were present in either room. The finding includes a cross-cutting aspect in the area of human performance in that human error prevention techniques (H.4(a)), in this case adequate self checking, were not effective in ensuring this door was closed after use. (Section 1R05 |
| Site: | Palisades |
|---|---|
| Report | IR 05000255/2008002 Section 1R05 |
| Date counted | Mar 31, 2008 (2008Q1) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.05 |
| Inspectors (proximate) | D Mcneil J Cassidy S Orth J Ellegood S Bakhsh R Walton P Lee J Giessner C Lipa M Learn |
| CCA | H.12, Avoid Complacency |
| INPO aspect | QA.4 |
| ' | |
Finding - Palisades - IR 05000255/2008002 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Palisades) @ 2008Q1
Self-Identified List (Palisades)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||