Finding | |
---|---|
Title | Failure to Identify and Correct CCW Pipe Corrosion |
Description | An NRC-identified NCV of 10 CFR Part 50, Appendix B, Criterion XVI, Corrective Action, was identified for the licensees failure to promptly identify and correct component cooling water (CCW) external pipe corrosion that led to a through-wall flaw and leak on the Unit 3 CCW surge tank makeup line. FPL performed an immediate operability screening and determined the condition was operable but degraded considering previous prompt operability determinations for more significant CCW system leaks that bounded the leak rate and with similarly characterized structural flaws. Plant operators later isolated the through wall leak and established an alternate makeup path. This issue has been entered into the licensees corrective action program as AR 2223132.The failure to identify and correct the significant external corrosion that occurred on the Unit 3 CCW surge tank makeup line was a performance deficiency. The performance deficiency was more than minor because it was associated with the equipment performance attribute of the mitigating systems cornerstone and adversely affected the cornerstone objective of ensuring the reliability of systems that respond to initiating events to prevent undesirable consequences. Specifically, through wall corrosion affects the reliability of the CCW system. The inspectors determined the finding to be of very low safety significance because it did not represent an actual loss of function of one or more non-technical specification trains of equipment designated as high safety-significant in accordance with the licensees maintenance rule program for greater than 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. The finding had a cross-cutting aspect in the area of Problem Identification and Resolution, Identification, because the licensee failed to identify the significant external corrosion and apparent metal pipe wastage. Prior opportunities for FPL to identify the significant external corrosion and pipe wastage occurred through maintenance activities on the same pipe section and system engineer quarterly systems walkdowns [P.1]. |
Site: | Turkey Point |
---|---|
Report | IR 05000250/2017003 Section 1R04 |
Date counted | Sep 30, 2017 (2017Q3) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.04 |
Inspectors (proximate) | J Orr J Reyes R Carrion D Hardage J Nadel P Capehart L Suggs |
Violation of: | 10 CFR 50 Appendix B 10 CFR 50 Appendix B Criterion XVI |
CCA | P.1, Identification |
INPO aspect | PI.1 |
' | |
Finding - Turkey Point - IR 05000250/2017003 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Turkey Point) @ 2017Q3
Self-Identified List (Turkey Point)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||