Finding | |
|---|---|
| Title | Unrecognized Inoperable Reactor Protection System Instrument Channel |
| Description | A self-revealing NCV of Technical Specification (TS) Limiting Condition for Operation (LCO) 3.3.1 was identified for the licensees failure to input the correct Eagle 21 resistance temperature detector (RTD) coefficients into the Eagle 21 reactor protection system (RPS) which resulted in channels being inoperable for longer than their allowed outage times. Immediate corrective actions to restore compliance included inputting the correct RTD coefficients into the Eagle 21 RPS. Planned corrective actions to prevent recurrence included revising engineering procedures to include validation that the RTD coefficients were derived via the correct methodology. This issue was entered into the licensees corrective action program as action request (AR) 02129632. The licensees failure to input the correct RTD coefficients into the Eagle 21 RPS was a performance deficiency. The performance deficiency was more than minor because it was associated with the equipment performance attribute of the mitigating systems cornerstone and adversely affected the cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences (i.e., core damage) because the specified safety function of each functional unit was not met. The inspectors evaluated the significance of this finding and determined the finding was of very low safety significance (Green) because the finding did not affect the function of other redundant or diverse methods of reactor shutdown. The NRC assigned a cross cutting aspect associated with the Resources element of the Human Performance area because the licensee failed to ensure that procedures related to RTD replacement contained adequate information for verifying and inputting correct RTD coefficients [H.1]. |
| Site: | Turkey Point |
|---|---|
| Report | IR 05000250/2016004 Section 4OA3 |
| Date counted | Dec 31, 2016 (2016Q4) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | Self-revealing |
| Inspection Procedure: | IP 71153 |
| Inspectors (proximate) | A Sengupta D Orr J Reyes J Rivera L Suggs M Thomas P Capehart W Loo |
| Violation of: | Technical Specification |
| CCA | H.1, Resources |
| INPO aspect | LA.1 |
| ' | |
Finding - Turkey Point - IR 05000250/2016004 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Turkey Point) @ 2016Q4
Self-Identified List (Turkey Point)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||