Finding | |
|---|---|
| Title | Missed Inspections on Automatic Voltage Regulator Cards Results in Emergency Diesel Generator Failure to Run |
| Description | The inspectors identified a self-revealing Green NCV of 10 CFR 50, Appendix B, Criterion XVI, Corrective Actions, because between 2012 and 2016, Entergy did not perform vendor specified inspections of the 23 emergency diesel generator (EDG) automatic voltage regulator (AVR) cards. As a result, on March 7, 2016, and March 10, 2016, the 23 EDG failed to run due to poor voltage regulation caused by degraded connections on the AVR card. Entergy replaced the AVR card in the 23 EDG, repaired similarly degraded solder joints on the AVR cards for the 21 and 22 EDGs, and wrote CR-IP2-2016-1260 and CR-IP3-2016-1370. The inspectors determined that this performance deficiency was more than minor because it is associated with the Equipment Performance attribute of the Mitigating Systems cornerstone and adversely affected its objective to ensure the reliability of systems that respond to initiating events to prevent undesirable consequences. Specifically, the 23 EDG failed to run on March 7, 2016, and March 10, 2016. The inspectors evaluated the finding in accordance with IMC 0609, Appendix A and concluded it required a detailed risk evaluation (DRE). The DRE was performed by a Region I SRA and concluded the performance deficiency resulted in a change in core damage frequency of low E-8/year or very low safety significance (Green). The inspectors determined that this violation was not indicative of current performance because the last time Entergy would reasonably have been prompted to create corrective actions to perform periodic inspections was during the initial inspections in 2010. Therefore, no cross-cutting aspect was assigned. |
| Site: | Indian Point |
|---|---|
| Report | IR 05000247/2016003 Section 1R15 |
| Date counted | Sep 30, 2016 (2016Q3) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | Self-revealing |
| Inspection Procedure: | IP 71111.15 |
| Inspectors (proximate) | B Haagensen E Dipaolo F Arner G Newman J Amberosini J Furia S Elkhiamy S Rich |
| Violation of: | 10 CFR 50 Appendix B 10 CFR 50 Appendix B Criterion XVI |
| INPO aspect | |
| ' | |