05000454/FIN-2016001-02
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Entry into Mode 3 with Turbine Trip Function of SSPS Disabled |
Description | A finding of very low safety significance and associated non-cited violation (NCV) of Technical Specification (TS) Limiting Condition for Operation (LCO) 3.0.4 was self-revealed when the licensee transitioned Unit 1 to Mode 3 with the turbine trip function of the Solid State Protection System (SSPS) disabled although the turbine trip function was required by TS LCO 3.3.2 to be operable in Mode 3. Upon identification, the licensee immediately manually tripped the turbine and restored the automatic turbine trip function. The licensee entered the issue into the corrective action program (CAP) and initiated actions to revise the mode change checklist and affected surveillance procedures. The inspectors determined that the finding was of more than minor safety significance because it was associated with the Configuration Control aspect of the Initiating Events Cornerstone and adversely affected the cornerstone objective of limiting the likelihood of events that upset plant stability and challenge critical safety functions. The finding was Green because the manual turbine trip and main steam isolation functions were not affected by the finding. The inspectors determined that the finding had a cross-cutting aspect of Work Management in the area of Human Performance (H.5) because the licensee failed to plan, control, and execute work activities such that nuclear safety was the overriding priority. |
Site: | Byron |
---|---|
Report | IR 05000454/2016001 Section 4OA3 |
Date counted | Mar 31, 2016 (2016Q1) |
Type: | NCV: Green |
cornerstone | Initiating Events |
Identified by: | Self-revealing |
Inspection Procedure: | IP 71153 |
Inspectors (proximate) | C Thompson E Duncan I Khan J Cassidy J Draper J Mcghee |
Violation of: | Technical Specification - Procedures Technical Specification |
CCA | H.5, Work Management |
INPO aspect | WP.1 |
' | |
Finding - Byron - IR 05000454/2016001 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Byron) @ 2016Q1
Self-Identified List (Byron)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||